8
6219 Brittmoore Road - Houston, Texas 77041-5114 USA Tel: 1-713-849-3366 - Fax: 1-713-849-3654 URL: www.aaatech.com - E-Mail: [email protected] AAA Technology & Specialties Co., Inc. CORROSION RESISTANT PIPE SUPPORT SYSTEM Serving Industry with Quality Pipe Supports Since 1971 TRI*BOLT U-BOLT WITH TRI*COAT TRI*BOLT WITH TRI*COAT WITH TRI*GUARD THERMOPLASTIC BAR TRI*GUARD THERMOPLASTIC BAR TRI*CLIP THERMOPLASTIC CLAMP BAR

CORROSION RESISTANT PIPE SUPPORT SYSTEM · Technology’s sister company) for assistance in calculating pipe support loads In the event that the load to be carried at any location

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

6219 Brittmoore Road - Houston, Texas 77041-5114 USA

Tel: 1-713-849-3366 - Fax: 1-713-849-3654

URL: www.aaatech.com - E-Mail: [email protected]

AAA Technology & Specialties Co., Inc.

C O R R O S I O N R E S I S T A N T P I P E S U P P O R T S Y S T E M

Serving Industry with Quality Pipe Supports Since 1971

T R I * B O L T ™

U - B O L T W I T H

T R I * C O A T ™

T R I * B O L T ™ W I T H

T R I * C O A T ™ W I T H

T R I * G U A R D ™

T H E R M O P L A S T I C

B A R

T R I * G U A R D ™

T H E R M O P L A S T I C B A R

T R I * C L I P ™

T H E R M O P L A S T I C

C L A M P B A R

AAA Technology & Specialties Co., Inc. Page 2

CORROSION RESISTANT PRODUCTS

Corrosion between pipe supports and pipe at metal to met-al contact points is a common problem in the process and offshore industries. When TRI•GUARD™ thermoplastic bars are placed under pipes, they eliminate metal to metal contact and the resultant corrosion. With TRI•GUARD™, water drains away from the pipe and the TRI•GUARD™ contact point due to the TRI•GUARD™ shape and no long-er pools on the bottom side of the pipe. TRI•GUARD™ also prevents electrical conductivity between the pipe and the pipe support member. TRI•GUARD™ is UV resistant which translates to longer product life. TRI•GUARD™ (standard either black or white) can be used at operating temperatures up to 180°F (82°C) and under all diameter pipes. For higher temperature applica-tions, TRI•GUARD-AM™ can be used at operating temper-atures up to 340°F (171°C) and TRI•GUARD-PE™ can be used at operating temperatures up to 482°F (250°C). For pipe supports requiring lateral restraint (i.e. a guide), please see our TRI•BOLT™ product line of coated U-bolts.

TRI*GUARD™ DURABLE THERMOPLASTIC SUPPORTS

Nominal Pipe Dia.

(in)

Bar Length "L" (in)

Bar Hole Dia.

"G" (in)

Bar Size "D" (in)

Bar Height "H" (in)

Hole C-C Length "B" (in)

U-Bolt Rod Dia.

(in)

1/2 2 1/2 1 3/16 3/8 3/4 5/16 1/4

3/4 3 3/8 3/4 5/16 1 3/8 1/4

1 3 3/8 3/4 5/16 1 5/8 1/4

1/2 2 1/2 1/2 1 7/16 1 3/16 3/8

3/4 3 1 1/2 1/2 1 7/16 3/8

1 3 1 3/4 1/2 1 7/16 3/8

1 1/4 3 1/2 2 1/8 1/2 1 7/16 3/8

1 1/2 4 2 3/8 1/2 1 7/16 3/8

2 4 1/2 1/2 1 7/16 2 13/16 3/8

2 1/2 5 3 7/16 5/8 1 7/16 1/2

3 6 5/8 1 7/16 4 1/16 1/2

4 7 5/8 1 7/16 5 1/16 1/2

5 1/2 8 6 1/8 5/8 1 7/16

6 9 11/16 1 7/16 7 3/8 5/8

8 11 11/16 1 7/16 9 3/8 5/8

10 13 1/2 7/8 1 1/2 11/16 11 5/8 3/4

12 16 1 1 1/2 11/16 13 3/4 7/8

14 17 1 1 1/2 11/16 15 7/8

16 19 1 1 1/2 11/16 17 7/8

18 21 1/2 1 1/8 1 1/2 11/16 19 1/8 1

20 23 1/2 1 1/8 1 1/2 11/16 21 1/8 1

24 27 1/2 1 1/8 1 1/2 11/16 25 1/8 1

30 33 1/2 1 1/8 1 1/2 11/16 31 1/8 1

36 39 1/2 1 1/8 1 1/2 11/16 37 1/8 1

42 45 1/2 1 1/8 2 15/16 43 1/8 1

48 51 1/2 1 1/8 2 15/16 49 1/8 1

54 57 1/2 1 1/8 2 15/16 55 1/8 1

60 63 1/2 1 1/8 2 15/16 61 1/8 1

Nominal Pipe Dia.

(mm)

Bar Length

"L" (mm)

Bar Hole Dia.

"G" (mm)

Bar Size "D"

(mm)

Bar Height

"H" (mm)

Hole C-C Length

"B" (mm)

U-Bolt Rod Dia.

(mm)

15 63 30 10 20 8 6

20 75 35 10 20 8 6

25 75 41 10 20 8 6

15 63 30 12 25 11 10

20 75 12 25 11 38 10

25 75 12 25 11 44 10

32 10 87 54 12 25 11

40 102 12 25 11 60 10

50 114 12 25 11 71 10

65 12 126 87 15 25 11

80 152 15 25 11 103 12

100 178 15 25 11 129 12

125 12 203 156 15 25 11

150 229 17 25 11 187 15

200 279 17 25 11 238 15

250 343 22 38 18 295 20

300 406 25 38 18 349 22

350 432 25 38 18 381 22

400 483 25 38 18 432 22

450 546 28 38 18 486 25

500 597 28 38 18 537 25

600 699 28 38 18 638 25

750 851 28 38 18 791 25

900 1003 28 38 18 943 25

1050 1156 28 50 24 1095 25

1200 1308 28 50 24 1248 25

1350 1461 28 50 24 1400 25

1500 1613 28 50 24 1553 25

713-849-3366 | www.aaatech.com | [email protected] Page 3

CORROSION RESISTANT PRODUCTS

PIPE DIAMETER - The diameter of the TRI•GUARD™ thermoplastic bars is based upon the diameter of the pipe and the diameter of the stand-ard u-bolts available for the specific pipe diameter. For 1/2”, 3/4” and 1” pipe diameters, u-bolts are manufactured in 1/4” rod diameter as well as 3/8” rod diameter. For the pipe diameter, the u-bolt rod diameter and the TRI*GUARD bar diameter relationship, please see the table below:

From the tables above, identify the TRI•GUARD™ bar diameter that will be provided. Then calculate the load to be carried by the TRI•GUARD™ bar at this particular location and compare the load with the allowable load per bar below: LOAD LIMITATIONS - TRI•GUARD™ bar load capacity is limited as follows: 3/4” Dia. - 4,000 Lbs. (1814 Kg. or 17.79 kN), 1” Dia. - 8,000 Lbs. (3628 Kg. or 35.58 kN), 1 1/2” Dia. - 10,000 Lbs. (4535 Kg. or 44.48 kN), 2” Dia. - 12,500 Lbs. (5669 Kg. or 55.6 kN). Please be aware that loads may be from the weight of the piping, valves and flanges and may also be from thermal growth and from occasional loads such as wave, earthquake or wind loads, etc. Consult your piping stress engineer for guidance or contact PipingSolutions, Inc. (AAA Technology’s sister company) for assistance in calculating pipe support loads In the event that the load to be carried at any location exceeds these loads per TRI•GUARD™ bar load capacity, then use multiple TRI•GUARD™ bars at the specific location until the number of bars times the capacity for one bar exceeds the load to be carried. In the event that multiple bars are required, be certain to verify that the bars will fit on top of the support member and they must also be the same size bars. For pipe supports requiring lateral restraint (i.e. a guide), please see our TRI•BOLT™ product line of coated U-bolts. If the lateral loads are larg-er than can be resisted by a U-Bolt, contact AAA Technology for other guide options. TEMPERATURE - TRI•GUARD™ (standard either black or white) can be used at operating temperatures up to 180°F (82°C) and under pipes of virtually all diameters. For higher temperature applications, TRI•GUARD-AM™ can be used at operating temperatures up to 340°F (171°C) and TRI•GUARD-PE™ can be used at operating temperatures up to 482°F (250°C). For TRI•GUARD™ and TRI•BOLT™ applications, the pol-yshrink coating that is used to coat the U-Bolts to make them TRI-BOLTs can only be used at operating temperatures up to 230°F (110°C).

TRI•BOLT™ FINISH - Carbon steel U-Bolts can be coated with the following finish: Hot Dip Galvanized, Xylan Blue, Xylan Black, Polyurea or Sermagard. Alternatively, the U-Bolts can be manufactured of 304 SS, 316 SS or another appropriate alloy. TRI•GUARD™ with Base Plate - TRI•GUARD™ with a Base Plate bonded to the bottom of the TRI•GUARD™ eliminates the necessity of in-stalling a base plate or epoxying the TRI•GUARD™ to the structural steel beneath it. The base plates are 1” larger in width and length than the TRI•GUARD™ bar and come with the holes drilled and the TRI•GUARD™ bars epoxied to the steel. Steel can be ordered in the following finish-es: Plain, Hot Dip Galvanized, Painted, Xylan Blue, Xylan Black, Polyurea or Sermagard.

TRI*GUARD™ SELECTION CRITERIA

Nom. Pipe Dia. 1/2 3/4 1 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4 5 6 8 10 12 14 16 18

U-Bolt Rod Dia. 1/4 1/4 1/4 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 1/2 5/8 5/8 3/4 7/8 7/8 7/8 1

TRI•GUARD Dia. 3/4 3/4 3/4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2

Nom. Pipe Dia. 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 54 56 60

U-Bolt Rod Dia. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

TRI•GUARD Dia. 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 2 2 2 2 2 2

TRI*GUARD™ Standard (White)

Maximum Operating Temperature:180⁰F (82⁰C)

TRI*GUARD™ Standard (Black) (UV) Maximum Operating

Temperature:180⁰F (82⁰C)

TRI*GUARD-AM™ (Amber)

Maximum Operating Temperature:340⁰F (171⁰C)

TRI*GUARD-PE™ (PEEK)

Maximum Operating Temperature:482⁰F (250⁰C)

AAA Technology & Specialties Co., Inc. Page 4

CORROSION RESISTANT PRODUCTS

TRI•BOLT™ corrosion resistant restraints prevent the pipe from moving upwards as well as laterally. When it is necessary to limit lateral movement of a pipe, TRI•BOLT™ is the right selection for loads that are not excessive. For higher lateral load capacities, use pairs of TRI•BOLTs™ as shown in the illustration at the bottom of this page. The TRI•COAT™ protective layer is bonded to the U-bolt sur-face thermally. The TRI•COAT™ protective layer prevents electrical conductivity between the pipe and the u-bolt member. TRI•COAT™ is UV resistant which translates to longer product life. TRI•BOLTs™ can be used at operating temperatures up to 230°F (110°C). and can be provided in carbon steel with a HDG finish, 304 SS or 316 SS.

TRI*BOLT™ with TRI*COAT™ U-BOLTS FOR SERVICE IN CORROSIVE ENVIRONMENTS

Nominal Pipe

Dia. (IN)

U-Bolt Bar Diam "A" (IN)

U-Bolt Inside

"B" (IN)

U-Bolt Leg C-C "C" (IN)

Tangent Length "D" (IN)

Thread Length "E" (IN)

1/2 1/4 15/16 1 3/16 2 3/4 2 1/8

3/4 1/4 1 1/8 1 3/8 2 3/4 2 1/8

1 1/4 1 3/8 1 5/8 2 3/4 2 1/8

1/2 3/8 15/16 1 5/16 2 19/32 2 1/8

3/4 3/8 1 1/8 1 1/2 2 3/4 2 1/8

1 3/8 1 3/8 1 3//4 2 3/4 2 1/8

1 1/4 3/8 1 11/16 2 1/16 2 7/8 2 1/8

1 1/2 3/8 2 2 3/8 3 2 1/2

2 3/8 2 7/16 2 13/16 3 1/4 2 1/2

2 1/2 1/2 2 15/16 3 7/16 3 3/4 3

3 1/2 3 9/16 4 9/16 4 3

4 1/2 4 9/16 5 1/16 4 1/2 3

5 1/2 5 5/8 6 1/2 5 3

6 5/8 6 3/4 7 3/8 6 1/8 3 3/4

8 5/8 8 3/4 9 3/8 7 1/8 3 3/4

10 3/4 10 7/8 11 5/8 8 3/8 4

12 7/8 12 7/8 13 3/4 9 5/8 4 1/4

14 7/8 14 1/8 15 10 1/4 4 1/4

16 7/8 16 1/8 17 11 1/4 4 1/4

18 1 18 1/8 19 1/8 12 5/8 4 3/4

20 1 20 1/8 21 1/8 13 5/8 4 3/4

24 1 24 1/8 25 1/8 15 5/8 4 3/4

30 1 30 1/8 31 1/8 18 5/8 4 3/4

36 1 36 1/8 37 1/8 21 5/8 4 3/4

42 1 42 1/8 43 1/8 24 5/8 4 3/4

48 1 48 1/8 49 1/8 27 5/8 4 3/4

54 1 54 1/8 55 1/8 30 5/8 4 3/4

60 1 60 1/8 61 1/8 33 5/8 4 3/4

Nominal Pipe Dia.

(mm)

U-Bolt Bar Diam "A" (mm)

U-Bolt Inside

"B" (mm)

U-Bolt Leg C-C

"C" (mm)

Tangent Length

"D" (mm)

Thread Length

"E" (mm)

15 6 24 30 70 54

20 6 29 35 70 54

25 6 35 41 70 54

15 10 24 34 66 54

20 10 28 38 70 54

25 10 35 45 70 54

32 10 43 53 74 54

40 10 50 60 77 64

50 10 62 71 83 64

65 12 75 87 96 77

80 12 91 103 102 77

100 12 117 129 115 77

125 12 143 155 127 77

150 15 172 187 156 95

200 15 223 238 181 95

250 20 275 295 213 102

300 22 327 349 244 108

350 22 359 381 260 108

400 22 410 432 286 108

450 25 461 486 321 121

500 25 512 537 346 121

600 25 613 638 397 121

750 25 766 791 473 121

900 25 918 943 549 121

1050 25 1070 1095 625 121

1200 25 1223 1248 702 121

1350 25 1375 1400 778 121

1500 25 1528 1553 854 121

Page 5

CORROSION RESISTANT PRODUCTS

As previously stated, corrosion between pipe supports and pipe commonly occurs at metal to metal contact points in the process and offshore industries. TRI•CLIP™ Isolators, made of thermoplastic bars just like the TRI•GUARD™ bars, clip on pipe clamps, cradles and saddles to pre-vent metal to metal contact between the pipe and the pipe clamp, cradle or saddle. TRI•CLIP™ Isolators are bonded to the pipe clamp, cradle or saddle member with 2 sided tape. AAA Technology supplies the TRI*CLIP™ isolators along with the pipe clamps, cradles and saddles already bonded to the steel members. Alternatively, the TRI*CLIP™ Isolators can be supplied in bags tied to each pipe clamp, cradle or saddle for field installation at a later time. With TRI•CLIP™ Isolator bars like with the TRI•GUARD™ bars, water drains away from the pipe and the TRI•CLIP™ contact point due to the TRI•CLIP™ cylindrical shape. Moisture will no longer collect at contact points between the pipe and the support. TRI•CLIP™ Isolators also prevent electrical conductivity between the pipe and the pipe support member. TRI•CLIP™ Isolators can be used at operating temperatures up to 180°F (82°C) and on clamps, cradles and saddles for virtually all pipe and duct diameters. TRI•CLIP™ Isolators are also available UV resistant material which translates to longer product life. For higher temperature applications, TRI•CLIP™ Isolators are available in the following options:

Amber—TRI*GUARD-AM™ for temperatures to 340 ⁰F

PEEK—TRI*GUARD-PE™ for temperatures to 482 ⁰F TRI•CLIP™ Isolator bars are manufactured by AAA Technology from 1 1/2” diameter TRI•GUARD™ bars. They are cut and machined to fit the clamp dimensions that our customer provides to us for each application.

TRI*CLIP™ ISOLATORS ISOLATES PIPES FROM CLAMPS, CRADLES & SADDLES

TRI*CLIP™ ISOLATORS for Pipe Clamps

Nominal Pipe Dia.

(in)

Nominal Pipe Dia.

(mm)

Clamp Width (in)

Clamp Width (mm)

Number of TRI•CLIPs per Clamp

3 80 1 25 4

4 100 1 1/4 31 4

5 125 1 3/8 34 4

6 150 1 1/2 37 6

8 200 1 1/2 37 8

10 250 2 50 8

12 300 2 50 8

14 350 2 1/2 63 8

16 400 2 1/2 63 10

18 450 2 1/2 63 10

20 500 2 1/2 63 10

24 600 3 75 12

26 650 3 75 14

28 700 3 75 14

30 750 4 100 16

32 800 4 100 16

34 850 4 100 16

36 900 4 100 16

TRI*CLIP™ ISOLATORS for Pipe Cradles

Nominal Pipe Dia.

(in)

Nominal Pipe Dia.

(mm)

Cradle Width (in)

Cradle Width (mm)

Number of TRI•CLIPs per Cradle

3 80 4 100 2

4 100 4 100 2

5 125 4 100 4

6 150 4 100 4

8 200 4 100 4

10 250 4 100 4

12 300 6 150 4

14 350 6 150 4

16 400 6 150 6

18 450 6 150 6

20 500 6 150 6

24 600 8 200 6

26 650 8 200 8

28 700 8 200 8

30 750 8 200 8

32 800 8 200 8

34 850 8 200 8

36 900 8 200 8

How to order TRI*CLIP™ ISOLATORS

Specify Fields where “X” is entered

Pipe Dia. Clamp or Cradle

Width Cradle Angle

Bar Material (White, Black, Amber or Peek) or Maximum Pipe Temperature

Pipe Clamps X X X

Pipe Cradles X X X X

713-849-3366 | www.aaatech.com | [email protected]

AAA Technology & Specialties Co., Inc.

SPECIFICATIONS for TRI*CLIP™, TRI*GUARD™ & TRI*COAT™ for use with TRI*BOLT™

TRI*GUARD™ & TRI*CLIP™ White & Black Properties

Value in Metric Units

Value in Imperial Units

Applicable ASTM

Physical Properties

Density 1.42 g/cc 0.0513 lb/in³ D792

Water Absorption 0.25% 0.25% D570

Moisture Absorption at Equilibrium 0.22% 0.22% D570

Water Absorption at Saturation 0.9% 0.9% D570 / ISO 62

Melt Flow 1 g/10 min 1 g/10 min 1.05kg/190⁰C

Mechanical Properties

Hardness, Rockwell M 94 94 D785

Hardness, Rockwell R 120 120 D785

Tensile Strength, Ultimate 69 MPa 10000 psi D638

Elongation at Break 75% 75% D638

Tensile Modulus 2.8 GPa 406 ksi D638

Flexure Modulus 2.9 GPa 421 ksi D790

Flexural Yield Strength 99 MPa 14400 psi D790

Compressive Yield Strength 124 MPa 18000 psi D695

Poisson’s Ratio 0.35 0.35

Fatigue Strength 32 MPa 4640 psi D672

Shear Strength 66 MPa 9570 psi D732

Izod Impact, Notched 1.23 J/cm 2.3 ft-lb/in D256

Izod Impact, Unotched NB NB D256

Izod Impact, Notched Low Temperature 0.96 J/cm 1.8 ft-lb/in D256

Tensile Impact Strength 358 kJ/m² 170 ft-lb/in² D1822

Coefficient of Friction 0.35 0.35 50 mm/s (2 in/s)

Electrical Properties

Electrical Resistivity 1e+015 ohm-cm 1e+015 ohm-cm D257

Dielectric Constant 3.7 3.7 D150

Dielectric Strength 19.7 kV/mm 500kV/in D149

Dissipation Factor 0.005 0.005 D150

Arc Resistance 220 sec 220 sec D495

Thermal Properties

CTE, Linear 20⁰C 122 µm/m-ºC 67.8 µin/in-⁰F

CTE, Linear 100⁰C 149 µm/m-ºC 82.8 µin/in-⁰F

Thermal Conductivity 0.4 W/m-K 2.78 BTU-in/hr-ft²

Melting Point 175 ⁰C 347 ⁰F D3418

Maximum Service Temperature, Air 82 ºC 180 ºF At 1.8 MPa

Deflection Temperature at 0.46 MPa (66 psi) 169 ⁰C 336 ºF D648

Deflection Temperature at 1.8 MPa (264 psi) 125 ⁰C 257 ⁰F D648

Flammability, UL94 HB HB

TRI*COAT™ UV Resistant Metric Units Imperial Units Applicable

ASTM

Hardness (Shore A) 80 +/- 5 80 +/- 5 D2240

Tensile 12.27 +/- 1.3 MPa 1779 +/- 177 psi D412

Elongation (%) 330 +/- 33 330 +/- 33 D412

Tear Strength 48.2 +/- 5 N/mm 275 +/- 28 lb/in D412

Low Service Temperature -29 ºC -20 ºF

High Service Temperature 82 ºC 180 ºF

Electrical Property Insulation Excellent Excellent

Page 6

SPECIFICATIONS for TRI*CLIP™, TRI*GUARD™ & TRI*COAT™ for use with TRI*BOLT™

TRI*GUARD™ & TRI*CLIP™ Properties TRI*GUARD

AM TRI*GUARD

AM TRI*GUARD

PE Applicable

ASTM TRI*GUARD

PE

Metric Units Imperial Units Imperial Units Metric Units

Physical Properties

Density 1.27 g/cc 0.046 lb/in³ 0.047 lb/in³ D792 1.30 g/cc

Water Absorption 0.25% 0.25% 0.10% D570 0.10%

Moisture Absorption at Equilibrium 0.22% 0.22% 0.22% D570 0.22%

Water Absorption at Saturation 1.25% 1.25% 0.9% D570 / ISO 62 0.9%

Mechanical Properties

Hardness, Rockwell M 112 112 100 D785 100

Hardness, Rockwell R 125 125 126 D785 126

Tensile Strength, Ultimate 114 MPa 16500 psi 16000 psi D638 110 MPa

Elongation at Break 80% 80% 20% D638 20%

Tensile Modulus 3.45 GPa 500 ksi 500 ksi D638 3.45 GPa

Flexure Modulus 3.45 GPa 500 ksi 600 ksi D790 4.13 GPa

Flexural Yield Strength 137.5 MPa 20000 psi 25000 psi D790 171.9 MPa

Compressive Yield Strength 151.3 MPa 22000 psi 20000 psi D695 137.5 MPa

Poisson’s Ratio 0.35 0.35 0.35 - 0.35

Shear Strength 103.45 MPa 15000 psi 13800 psi D732 95.2 MPa

Izod Impact, Notched .267 J/cm .5 ft-lb/in 1.55 ft-lb/in D256 .829 J/cm

Coefficient of Friction 0.40 0.40 0.40 50 mm/s (2 in/s) 0.40

Electrical Properties

Electrical Resistivity 1e+017 ohm-cm 1e+017 ohm-cm 4.9e+016 ohm-cm D257 4.9e+016 ohm-cm

Dielectric Constant 3.15 3.15 3.7 D150 3.7

Dielectric Strength 32.7 kV/mm 830kV/in 480kV/in D149 19.91 kV/mm

Dissipation Factor 0.0013 0.0013 .003 D150 .003

Thermal Properties

CTE, Linear 20⁰C 122 µm/m-ºC 67.8 µin/in-⁰F 67.8 µin/in-⁰F 122 µm/m-ºC

CTE, Linear 100⁰C 149 µm/m-ºC 82.8 µin/in-⁰F 82.8 µin/in-⁰F 149 µm/m-ºC

Thermal Conductivity 0.4 W/m-K 2.78 BTU-in/hr-ft² 1.7 BTU-in/hr-ft² 0.245 W/m-K

Melting Point 210 ºC 410 ⁰F 633 ⁰F D3418 334 ºC

Maximum Service Temperature, Air 171 ºC 340 ºF 482 ⁰F At 1.8 MPa 250 ºC

Deflection Temp @ 1.8 MPa (264 psi) 204 ºC 400 ⁰F 320 ⁰F D648 160 ºC

Flammability, UL94 V-0 V-0 V-0 UL94 V-0

TRI*COAT™ UV Resistant Metric Units Imperial Units Applicable

ASTM

Hardness (Shore A) 80 +/- 5 80 +/- 5 D2240

Tensile 12.27 +/- 1.3 MPa 1779 +/- 177 psi D412

Elongation (%) 330 +/- 33 330 +/- 33 D412

Tear Strength 48.2 +/- 5 N/mm 275 +/- 28 lb/in D412

Low Service Temperature -29 ºC -20 ºF

High Service Temperature 107 ºC 225 ºF

Electrical Property Insulation Excellent Excellent

Page 7 713-849-3366 | www.aaatech.com | [email protected]

AAA TECHNOLOGY & SPECIALTIES CO., INC. 6219 Brittmoore Road, Houston, Texas 77041-5114, U.S.A.

Telephone: 713-849-3366 ▪ FAX: 713-849-3654 E-mail: [email protected]; Website: http://www.aaatech.com

Fig. 51201-TC Fig. 5110-WP-TB Pipe Cradle

TRI-STAND OPTIONS