Schöck Isokorb® Type CPAFor parapet connections bearing moment, shear and axial forces in a vertical or horizontal orientation
Schöck Isokorb® Type CPA
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
2
Parapet
Interior slab
1: Schöck Isokorb® Type CPA parapet connection with vertical orientati-onFig.
Parapet
Interior slab
2: Schöck Isokorb® Type CPA parapet connection with horizontal orien-tationFig.
Assembly Section Details
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
3
Parapet
Interior slab
Type CPA Type CPAType CPA
Type ZXT Type ZXTType ZXT Type ZXT
3: Schöck Isokorb® Type CPA vertical orientation: plan view of parapet connectionFig.
Parapet
Interior slab
Type ZXT Type ZXT
Type CPA Type CPA Type CPA
4: Schöck Isokorb® Type CPA horizontal orientation: plan view of para-pet connectionFig.
Parapet
Interior slab
Type ZXT
Type CPA
Type ZXT
Type CPAType CPA
5: Schöck Isokorb® Type CPA vertical orientation: section view of para-pet connectionFig.
Parapet
Interior slab
Type CPA Type CPAType CPA
Type ZXT Type ZXTType ZXT Type ZXT
6: Schöck Isokorb® Type CPA horizontal orientation: section view of pa-rapet connectionFig.
Position of Schöck Isokorb®For optimal thermal performance the Schöck Isokorb® should be aligned with the insulation layer.
Orientation of Schöck Isokorb® ▶ Ensure proper installation orientation as shown in the cross-section view on the design drawings.
5 Note ▶ For insulation between the Schöck Isokorb® Type CPA elements, Schöck Isokorb® Type ZXT insulation spacers with � re protec-
tion plates are available.
Element Arrangement
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
4
Schöck Isokorb® Type CPA
Concrete cover withCC [mm]
[mm]
Isokorb® Height
180 40
190 45
200 50
210 55
220 40
230 45
240 50
250 55
260 60
270 65
280 70
290 70
300 65
Schöck Isokorb® Type CPA
Concrete cover withCC [in]
[in] [mm]
Isokorb®Height
7" 180 1 5/8"
7 1/2" 190 1 3/4"
7 7/8" 200 2"
8 1/4" 210 2 1/8"
8 5/8" 220 1 5/8"
9" 230 1 3/4"
9 1/2" 240 2"
9 7/8" 250 2 1/8"
10 1/4" 260 2 3/8"
10 5/8" 270 2 1/2"
11" 280 2 3/4"
11 3/8" 290 2 3/4"
11 3/4" 300 2 1/2"
Concrete cover (CC)The concrete cover (CC) of the Schöck Isokorb® Type CPA varies depending on the width of the parapet wall for the vertical appli-cation or the thickness of the roof slab in the horizontal application. As stainless, ribbed steel is used exclusively for the reinforce-ment at the parapet connection there is limited risk of corrosion.
Concrete Cover
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
5
Schöck Isokorb® Type CPA variantsThe Schöck Isokorb® Type CPA can be con� gured as follows:
▶ Isokorb®-height:H = 180 - 300 mm [7" - 11 3/4"]
▶ Parapet wall width:B = 180 - 300 mm [7" - 11 3/4"]
TypeIsokorb® Height
Fire resistance
CPA-H200- R120
▶ Fire resistance class: R120
Type designation in design documents
5 Special designsPlease contact the design support department if you have connections that are not possible with the standard product variants shown in this technical information manual ([email protected]).
Product Variants | Type Designation | Special Designs
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
6
⌀ Mn,y
x
y
z
Nn,z
⌀ Vn,x
7: Schöck Isokorb® Type CPA: Sign convention for structural system with a vertical connection at the parapetFig.
x
y
z
⌀ Mn,y
⌀ Vn,z
⌀ Nn,x
8: Schöck Isokorb® Type CPA: Sign convention for structural system with a horizontal connection at the parapetFig.
Parapet
Interior slab
b
h
h B
9: Schöck Isokorb® Type CPA: vertical connection parapet height hAFig.
Parapet
Interior slab
lk
b
H
h B
10: Schöck Isokorb® Type CPA: horizontal connection parapet height hBFig.
Sign convention for structural system
Sign Convention
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
7
Parapet
Interior slab≤ e
Type ZXT Type ZXT Type ZXT Type ZXT
Expansion joint 2 × Schöck Dorn LD
Type CPA Type CPA Type CPA Type CPA Type CPAType ZXT
11: Schöck Isokorb® Type CPA: Expansion joint spacing requirementsFig.
Schöck Isokorb® Type CPA
Joint Spacing e [m]
Insulation Thickness [mm] 120 23.0
Schöck Isokorb® Type CPA
Joint Spacing e [ft in]
Insulation Thickness [in] 4 3/4" 75’-5 1/2"
Maximum expansion joint spacingExpansion joints may be required along the length of the exterior parapet structure due to temperature changes that are isolated from the interior structure. To protect from temperature cracking, the limit of continuous parapet length is a distance ‘e’ between the outermost Schöck Isokorb® elements. A continuous parapet should extend beyond the Schöck Isokorb® with the expansion joint occurring between Isokorb® units.Schöck Expansion Joint Spacer boards can be used to build the expansion joints, and Schöck Dorn® (dowels) can be used for trans-mission of shear forces through the joint.
5 Notes ▶ The maximum expansion joint spacing must be veri� ed by the Engineer of Record (EOR). ▶ The joint must be free to contract or expand in the longitudinal direction. Schöck Dorn LD in stainless steel A4 would be a sui-
table dowel connector for the expansion joint with the Schöck expansion joint former board. ▶ The Schöck expansion joint former board is available from Schöck USA Inc.
Expansion Joint Spacing
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
8
≥ 16
0 m
m12
0 m
m
250 mm≥ 75 mm
≥ 50 mm[1 15/16"]
≥ 100 mm[3 15/16"]
[2 15/16"] [9 13/16"]
[4 3
/4"]
[6 5
/16"
]
Parapet
Interior slab
12: Schöck Isokorb® Type CPA vertical connection: edge distance section viewFig.
[9 13/16"]250 mm≥ 75 mm
[2 15/16"]
≥ 100 mm[3 15/16"]
[1 15/16"]≥ 50 mm
≥ 18
0 m
m[7
1/1
6"]
Parapet
Interior slab
13: Schöck Isokorb® Type CPA horizontal connection: edge distance sec-tion viewFig.
5 Edge distancesThe Schöck Isokorb® Type CPA layout must maintain the following conditions:
▶ The distance of the connection stirrup from the parapet edge or parapet expansion joint must be at least: eR ≥ 50 mm [2"]. ▶ The distance of the insulation from the edge of the � oor slab must be at least: eR ≥ 75 mm [3"]. ▶ The distance of the connection stirrup from the edge of the � oor slab must be at least: eR ≥ 100 mm [4"]. ▶ Note that the required distances to the � oor slab edge and to the parapet edge are not necessarily the same.
Edge distances
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
9
610
mm
180 - 300 mm37
0 m
m[1
4 9/
16"]
[7 3/32"] - [11 13/16"][2
4 1/
64"]
CCCC
14: Schöck Isokorb® Type CPA: side cross-section viewFig.61
0 m
m
370
mm
120
mm
120
mm
44 46 44
250 mm
3535 46
[4 3
/4"]
[14
9/16
"]
[24
1/64
'']
[4 3
/4"]
[9 13/16"]35 mm = [1 3/8"]44 mm = [1 3/4"]46 mm = [1 13/16"]
15: Schöck Isokorb® Type CPA: front cross-section viewFig.
Schöck Isokorb® Type CPA [mm] CPA [in]
Isokorb®-Length 250 9 7/8"
Tension/Compression Loops 2 × 3 ⌀ 8 –
Shear Resistance Bars 2 ⌀ 6 + 2 ⌀ 6 –
5 Product information ▶ Minimum width of parapet bmin = 180 mm [7"] note that minimum roof slab height hmin = 180 mm [7"] ▶ Download further product plans and cross-sections at www.schock-na.com/download
Schöck Isokorb® length and configuration
5 Notes ▶ The Schöck Isokorb® consists of metric components. ▶ Reinforcement bars ⌀6 correspond to 1/4" diameter ▶ Reinforcement bars ⌀8 correspond to 5/16" diameter
Product Dimensioning
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
10
8 4 20 21 01 6 11 9 7 51 3
CPA (B = 220 - 300 mm)[B = 8 5/8" - 11 3/4"]
CPA (B = 180 - 210 mm)[B = 7" - 8 1/4"]
|φVn|, |φNn| [kips/Unit]
φM
n [kN
m/U
nit]
φM
n [ki
p-ft/
Unit]
|φVn|, |φNn| [kN/Unit]
±0.0
±2.0
±1.0
±5.0
±3.0
±4.0
±0.0
±1.0
±2.0
±3.0
±4.0
±5.0
±6.0
±7.0
0.0 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.4 2.7
Product capacity diagram
Schöck Isokorb® Type CPA (B = 180 - 210) CPA (B = 220 - 300)
Design Values withConcrete Strength ≥ 27,5 MPa
φMn [kNm/Unit]
|φVn|, |φNn|[kN/Unit]
12.1 ±3.89 ±5.58
10.0 ±3.98 ±5.72
8.0 ±4.08 ±5.85
6.0 ±4.17 ±5.98
4.0 ±4.26 ±6.11
2.0 ±4.35 ±6.24
0.0 ±4.44 ±6.38
Interaction Table
Strength Capacity
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
11
Schöck Isokorb® Type CPA (B = 7" - 8 1/4") CPA (B = 8 5/8" - 11 3/4")
Design Values withConcrete Strength ≥ 4.000 psi
φMn [kip-ft/Unit]
|φVn|, |φNn|[kips/Unit]
2.72 ±2.87 ±4.12
2.25 ±2.94 ±4.22
1.80 ±3.01 ±4.31
1.35 ±3.08 ±4.41
0.90 ±3.14 ±4.51
0.45 ±3.21 ±4.60
0.0 ±3.27 ±4.71
5 Notes ▶ If any concrete on the interior or exterior of the Schöck Isokorb® is less than 27.5 MPa [4,000 psi] contact Schöck Design De-
partment. ▶ The Engineer of Record (EOR) must con� rm strength of the slabs attached to the Schöck Isokorb®. ▶ The values shown in the design capacity tables are ultimate (factored) values. ▶ For Sl: 1 inch = 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa. For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf,
1 MPa = 145.0 psi.
Strength Capacity
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
12
[4 3/4"]
≥ 18
0 m
m
≥ 160 mm[6 3/8"]
[7 1
/16"
]
120 mm
[1 9
/16"
]30
mm
Pos. ①
Pos. ①
Pos. ④
Pos. ④
Pos. ①
Pos. ②
Pos. ①
Pos. ③
Pos. ②
Pos. ⑤
Pos. ④
Pos. ③
Pos. ④
Pos. ⑤ Pos. ⑤
Pos. ②
Pos. ②
≥ l 0
≥ l 0
16: Schöck Isokorb® Type CPA horizontal connection: on-site reinforcementFig.
Schöck Isokorb® Type CPA
On Site Reinforcement Location Concrete Strength ≥ 27,5 MPa (4.000 psi)
Pos. 1 Slab Reinforcement
Pos. 1Roof Slab Side
201 mm2/Unit [0.311 in2/Unit]
Splice Length l0 340 mm [13 3/8"]
Pos. 2 Longitudinal Bars Parallel to Insulation
Pos. 2 Roof Slab Side and Parapet Side 4 × #3
Pos. 3 Connecting Edge Bars
Pos. 3 Parapet Side 3 × #3
Pos. 4 Constructive Edge Reinforcement
Pos. 4 Roof Slab Side and Parapet Side #3 @ 250 mm [#3 @ 10"]
Pos. 5 Parapet Reinforcement
Pos. 5
Parapet Side
214 mm2/Unit [0.332 in2/Unit]
Pos. 5 Recommendation 3 × #3
Splice Length l0 580 mm [22 7/8"]
At the table below are suggestions for cast-in-place connective reinforcement for 100 % section strength with minimum concrete strength of 27.5 MPa [4,000 psi]. The existing slab reinforcement can be taken into account for the required reinforcement of connections with Schöck Isokorb®.
5 Notes ▶ Pos. 3 bars are critical to transfer the load from the parapet to the structural slab. ▶ All free edges must be sti� ened using structural U-bars as per Engineer of Record (EOR) speci� cations.
On Site Reinforcement
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
13
120
mm
180 - 300 mm[7 1/16"] - [11 13/16"]
[4 3
/4"]
[6 5
/16"
] ≥
160
mm
≥ l0
Pos. ④
Pos. ③ Pos. ①
Pos. ②
Pos. ⑤
Pos. ②
Pos. ①≥ l0
Pos. ③
Pos. ④
Pos. ①
Pos. ④
Pos. ⑤
Pos. ②
Pos. ②Pos. ④
Pos. ⑤
17: Schöck Isokorb® Type CPA vertical connection: on-site reinforcementFig.
Schöck Isokorb® Type CPA
On Site Reinforcement Location Concrete Strength ≥ 27,5 MPa (4.000 psi)
Pos. 1 Slab Reinforcement
Pos. 1
Roof Slab Side
253 mm2/Unit [0.392 in2/Unit]
Pos. 1 Recommendation 2 × #4
Splice Length l0 776 mm [30 1/2"]
Pos. 2 Longitudinal Bars Parallel to Insulation
Pos. 2 Roof Slab Side and Parapet Side 4 × #3
Pos. 3 Connecting Edge Bars
Pos. 3 Roof Slab Side 2 × #4
Pos. 4 Constructive Edge Reinforcement
Pos. 4 Roof Slab Side and Parapet Side #3 @ 250 mm [#3 @ 10"]
Pos. 5 Parapet Reinforcement
Pos. 5Parapet Side
201 mm2/Unit [0.311 in2/Unit]
Splice Length l0 340 mm [13 3/8"]
5 Notes ▶ Pos. 3 bars are critical to transfer the load from the parapet to the structural slab. ▶ All free edges must be sti� ened using structural U-bars as per Engineer of Record (EOR) speci� cations.
On Site Reinforcement
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
14
� Have the factored member forces on the Schöck Isokorb® connection been determined at design level?
� Has the maximum permissible continuous parapet length between Isokorb® units been maintained?
� Have the requirements for on-site reinforcement of the Isokorb® connections been veri� ed?
� Are the requirements with regard to � re protection con� rmed?
� Has the maximum permissible expansion gap spacing been taken into consideration for the speci� c parapet con� gurati-on?
3 Check List
Schöck Isokorb® Type CPA
TH Schöck Isokorb®/US-en/2018.1/January
CPA
Prod
ucts
Installation instructions
I 0
TH Schock lsokorb® /US-en/2019.12/December
Refer to Shop Drawings for reinforcement details.
lo
Schock lsokorb® Type CPA
� -- - - - ----- - - ---------\,_10
15
CPA
::::,
"C
CPA
� u
:::,
"'O
e c..
Schock lsokorb® Type CPA
Installation instructions
16
�--------®
Refer to Shop Drawings for reinforcement details.
TH Schock lsokorb®/US-en/2019.12/December