CPM/XPM - Condensor / Dry cooler

1

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Directions for use

61366/1

Page 2: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

2

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Declaration by the Manufacturer, Annex II B

As defined by the EC Machinery Directive (MD) 98/37/EC, the Low Voltage Directive (LVD)2006/95/EC and the EMC Directive 2004/108/EC.

Type of machinery Heat Exchangers supplied with direct cranking fans

Productdescription Unit Coolers Antarctic, EVFI, EVDL, DDXAir cooled Condensers CPS, CPM, DCPAir Coolers Antarctic, CBFI, CBDL, DDBDry Coolers XPS, XPM, XP, DXP

developed and designed in accordance with the MD 98/37/EC, LVD 2006/95/EC andEMC Directive 2004/108/EC on the own responsibility of:

Company Asarums Industri ABS. Industrivägen 2-4SE 374 50 ASARUMSweden

Harmonized Standards:

EN ISO 12100-1:2003 EN 61000-6-1EN ISO 12100-2:2003 EN 61000-6-2EN ISO 13857:2008 EN 61000-6-3EN 60204-1:2006 EN 61000-6-4EN ISO 4871

The product is not allowed to put in operation until the machine or system, which it is to beincorporated or which it is to be a part of, is in accordance with the Machinery Directive 98/37/EC.Thecompliance with EMC Directive 2004/95/EC is valid if the product is connected directly tothe main supply. If the product is integrated in a system or combined with other products (e.g. othercontrollers) the system manufacturer is responsible for compliance with EMC Directive 2004/95/ECfor the complete system.

Date : 2008-12-04

Signed by : Tord Engberg

Title: R&D Manager

Page 3: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

3

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

INDEX P

General description 4System of designation 5Receiving and mounting 6Installation 8Motor wiring diagram 11Tube installation 13Preventive maintenance 14

Page 4: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

4

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

General description

GeneralThis product is designed for outdoor location and is intended for refrigerants that arenot aggressive in contact with copper. The product is provided with axial fans and thecasing is made of aluzink AZ185 as standard.

Figure 1. Air cooled condenser / Dry cooler

ImportantDo not allow the product to be covered by foreign objects when in operation.Unobstructed circulation of air is necessary to achieve the highest cooling capacity.The coil surface area must be clean.

Item Designation Item Designation Item Designation1 Cooler element 4 Connection tube 7 Impeller2 Leg 5 Valve ( Schrader) 8 Fan guard3 * Drainplug 6 Motor 9 Safety switch

* = Applies to XPM only

9

14 2

6

7

8

5

3

Page 5: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

5

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

System of designations

Extras

Size

Fan type

Dry cooler / Air cooled condensers

XPM 80Q - 24 - 4 B1 - V - 900 - 36 - XCPM

Rows Deep

Circuits

Fan speed

V=Vertical airflowH=Horizontal airflow

Fin pitch

Page 6: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

6

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Receiving and mountingThe product has been checked and approved according to our quality system andfunctionality has been tested before leaving the factory. If damages due totransportation are detected on the product, please contact the sales office withoutdelay.

Assembly1. Move the product to the place ofinstallation before removing the packing.

2. The cooler is provided with lifting lugs.Lifting should be done according to theinstructions on the cooler.

3. The legs on XPM and CPM aremounted in the transport mode duringtransportation. They are to be fitted in thetwo upper pair of holes on the leg.

4. Bolt the product direct onto a firmbase, or with vibration pads, through thepre-drilled mounting holes.

Page 7: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

7

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Receiving and mountingFlatbed XPM/CPM which carriages upright.The product has been checked and approved according to our quality system andfunctionality has been tested before leaving the factory. If damages due totransportation are detected on the product, please contact the sales office withoutdelay.

Assembly1. Lift down the product on a stablesupport under each leg.N.B. The support is not includedThe support shall be at least 3500 mmlong, 100 mm thick and 200 mm widely.

2. Folding down cautious the product soit lays down plane to the support.

3. N:B: Watch out for the connections.

4. Lift the product right up.The legs are mounted in the transportmode during transportation. They are tobe fitted in the two upper pair of holeson the leg.Remove the protections of the pitch.

Page 8: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

8

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

InstallationInstallations may only be made byauthorised persons and in conformancewith national standards.

The cooler may not be connected toother voltage or frequency than itsrated data.

Connecting the fan

XPM/CPM is to be connected to thesafety switch as follows:Unscrew the screws (1) with ascrewdriver and remove the cover (2).Connect the cable through the screwfitting (3) on the side of the cover.

N.B. Ensure that the fan rotates in thedirection indicated by the arrow.

2

1

3

Setting the motor protectorThe maximum value of current at–30º C is indicated on the rating plate.Refer to the diagram for dimensioningof over-current protection at otherambient temperature. The over-currentprotection should have an adjustmentrange of ±20 %.

I

1.0

0.9

°C+10–10–300.8

–20 0

Page 9: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

9

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Y Y

>2xY

>2xY

Y

>Y

>Y

InstallationThe following instructions should be read together with the technical leaflet.

LocationPlace the product so that air can pass freely over the entire coil surface and ifpossible so that the wind direction won´t create recirculation of hot air.This applies particularly to models that have low fanspeed.The product is to be mounted on a firm base and secured with foundation bolts.The frame of the product has pre-drilled holes.

Page 10: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

10

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

0,7 x B

0,6 x Y

A

X

Y

B

B

A

0,8 x B

0,8 x B

0,7 x Y

0,7 x Y

0,8 x B

0,8 x B

>A / 4>B / 2

0,7 x Y

>x / 4>Y / 2

>x / 4>Y / 2

0,7 x Y

>x / 4>Y / 2

>x / 4>Y / 2

0,7 x B

0,6 x Y

>A / 4>B / 2

>A / 4>B / 2

>A / 4>B / 2

X

Y

Installation

Page 11: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

11

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

i nse rt. /$A F NS TR0 ,0

1

3

2

D

CPM/XPM900 / 700 / 450 / 300 min-1

L1 L2 L3

K1M

1 3 5

2 4 6

F2

97 95

98 962 4 6

PE

M3

SAFETY SWITCH

U

VW

W1 V2

V1

U1 W2

U2

380-420V

4G1,5

EMC classified 4G1,5 FOR FREQUENCY CONTROL23 THERMO PROTECTION with thermal contactor

220-240V

U1

W1

V1

W2

V2

U2

MOTOR PROTECTION(OVERLOAD)

* FUSE SIZE ACCORDING TO LABEL ON MOTOR PROTECTION RELAY F2.WITH ELECTRICAL FUSE AND MOTOR PROTECTION RELAY:

T

POS COMMENTDESCRIPTION

STANDARD

OPTION

OPTION

Motor wiring diagram 80X / 91X

Page 12: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

12

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

3/400V 4 POLES

3/400V 6 POLES3/400V 4 POLES

3/400V 6 POLES

L1 L2 L3 PE L1 L2 L3 PE

TK TK W2 U1 U2 V1 V2 W1 TK TK W2 U1 U2 V1 V2 W1

1/230V 4 POLES

1/230V 6 POLES

TK TKU1U2

L1

Z2 Z1

3/230V 4 POLES

L1 L2 L3 PE

TK TK W2 U1 U2 V1 V2 W1

N PE

Motor wiring diagram 80Q

Page 13: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

13

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

2

1Tube installation for CPM

The product is to be filled with the amountand type of refrigerant stated by theinstallation engineer. The connection tubesare located on the short side of the unit.

The hot-gas inlet is to be connectedto tube (1).The liquid outlet is to be connectedto tube (2).

Tube installation for XPM

The product is to be filled with the amountand type of brine stated by the installationengineer. The connection tubes are locatedon the short side of the unit.

The air vent is at the highest point of theheader (1).The tube inlet is to be connectedto tube (2).The tube outlet is to be connectedto tube (3).The drainplug (4) is located at the bottomof the header.

1

2

3

4

Page 14: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

14

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Preventive maintenance Warning. Make sure that the power supply is disconnected

Changing the fan / motor 80X / 91X1. Switch OFF the safety switchand lock it.

2. Unscrew the fastening screws of theprotective cover (1) and remove it.

3. Loosen the screw (2) and washer in thefan hub and pull off the impeller (3). Apuller must be used to do this.

4. Fit an eyebolt (4) in the top of the motorshaft.

5. Disconnect the electric cable from themotor terminal box (5). The motor weightsfrom 15 to 30 kg. Lifting tackle isrecommended.

6. Unscrew the screws (6) that holds themotor (7) to the motor shelf (8). Lift outthe motor.

Assemble in the reverse order.

StandstillDuring long periods when the unit is notin operation the fans should be run at leastfour times a month. They are to be rununtil the motor reaches normal workingtemperature, i.e., for about 15 minutes.

1

23

4

6

5

8

7

Page 15: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

15

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Preventive maintenance Warning. Make sure that the

power supply is disconnected

Changing the fan unit (80Q)

1. Switch OFF the safety switchand lock it.

2. Disconnect the electric cable from thefan unit terminal box (1). The fan unitweights is 35 kg. Lifting tackle isrecommended.

3. Unscrew the screws (2) that hold the fan.Lift out the fan unit by using stropsunder the fan brackets (3).

StandstillDuring long periods when the unit is notin operation the fans should be run atleast four times a month. They are to berun until the motor reaches normalworking temperature, i.e., for about 15minutes.

Assemble the fan unit (80Q)

1. Lift the fan unit back and fit the screws (2).

2. Connect the electric cable in the fan units terminal box. (1).

3. Unlock the safety switch and switch ON.

1

2

3

Page 16: CPM/XPM - Condensor / Dry cooler - AIAEN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system,

CPM/XPM - Condensor / Dry cooler

16

Asarums Industri AB Tel: +46 454 334 00Södra Industrivägen 2 – 4 Fax:+46 454 320 295SE – 374 50 AsarumSweden

Preventive maintenanceWarning. Make sure that the power supply is disconnected

Cleaning the coil surface

1. Coils that are lightly soiled can becleaned by carefully brushing andblowing with compressed air.

2. Then wash the coil battery with waterand environment-friendly detergent thatdoes not corrode aluminium or copper.Ammoniac may not be used.

3. Rinse and dry.

Caution

Always wear protective gloves whencleaning or in contact with the coilsurface.

2009-02-10