CPVC Sprinkler Piping

Embed Size (px)

Citation preview

  • 7/30/2019 CPVC Sprinkler Piping

    1/11

    TATA HOUSING DEVELOPMENT COMPANY LTD.

    Innovation in MEP

    CPVC Sprinkler PipingPRM 25th-26th ,28th June 2013

  • 7/30/2019 CPVC Sprinkler Piping

    2/11

    TATA HOUSING DEVELOPMENT COMPANY LTD.

    Introduction

    CPVC pipes have replaced steel pipes for sprinklers across world

    successfully rendering trouble free service since 1986

    Use in horizontal grid sprinkler piping in residential floors

    Product is recommended by NFPA & approved by International codes

    Bureau of Indian Standards has published code IS 16088Standard for CPVC pipe in fire extinguishing systems

  • 7/30/2019 CPVC Sprinkler Piping

    3/11

    TATA HOUSING DEVELOPMENT COMPANY LTD.

    Fire Test as per UL 1821

    Fire reaches 760C (1,400F)

    After approximately 1

    minute, sprinkler head

    activates

    Pipe is in direct contact with

    fire plume at 370C - 480C

    (700F900F) for a total of

    10 minutes

  • 7/30/2019 CPVC Sprinkler Piping

    4/11

    TATA HOUSING DEVELOPMENT COMPANY LTD.

    Fire Test

    System inspected - no damageother than charring on the outside

    surface

    Inside Pipe Properties remain

    unchanged

    System then tested at 1,207 kPa

    (175 psi) (12 Bar) for 5 minutes

  • 7/30/2019 CPVC Sprinkler Piping

    5/11TATA HOUSING DEVELOPMENT COMPANY LTD.

    Fire Endurance Test

    IMO test requirements were :

    pipe: 1 SR 13.5 (PN 16) Temperature from 900C to 1200C

    flow rate ca. 32 l/min test was run for 30 min. without

    leakage

    stagnant water pressure for 30 min.

    followed by hydrostatic pressure test of 4.2 bar for 5 min.

  • 7/30/2019 CPVC Sprinkler Piping

    6/11TATA HOUSING DEVELOPMENT COMPANY LTD.

    Listing & Approvals

    IS :16088 Specification for CPVC pipes for Automatic Fire Sprinkler Systems.

    NSF potable water certification in USA

    NFPA 13, NFPA 13D, NFPA 13R, NFPA 90A, NFPA 24

    UL Listed (Specially Listed Product)

    UL-C and C-UL Listed

    Factory Mutual FM Approved

    LPCB approved

    VdS Approved for LH, OH I, OH II, OH III and OH IV (for exhibition and concert

    halls, cinemas, theaters only)

  • 7/30/2019 CPVC Sprinkler Piping

    7/11TATA HOUSING DEVELOPMENT COMPANY LTD.

    Advantages

    Corrosion and Scale Resistance

    Faster completion than metal pipes.

    CPVC systems may be field fabricated and this requires lessupfront engineering

    Quiet, clean and light weight means easy fabrication

    Easy installation and easily transported to other floors

    No Maintenance required- 50 year life expectancy

    Have better Hydraulic characteristics than metal pipes

  • 7/30/2019 CPVC Sprinkler Piping

    8/11TATA HOUSING DEVELOPMENT COMPANY LTD.

    Limitations

    Not suitable for basement

    Cannot be used in risers

    Upto 3 maximum diameter

    Not LISTED for outdoor applications

    Used in sprinkler heads rated at 107C or lower

  • 7/30/2019 CPVC Sprinkler Piping

    9/11TATA HOUSING DEVELOPMENT COMPANY LTD.

    8

    Pipe & Fittings Standards

    Pipe produced in SDR 13.5 dimensions

    Pipe manufactured per ASTM F442/ IS:16088

    Fittings are Schedule 40 for to 1 and Schedule 80 for 1 to 3

    Fittings manufactured per ASTM F437, F438, F439 or F1970 Pipe and fittings are available from 3/4 to 3 (20 mm to 80 mm) in size

    A full line of solvent weld fittings and transitions fittings

  • 7/30/2019 CPVC Sprinkler Piping

    10/11

    TATA HOUSING DEVELOPMENT COMPANY LTD.

    9

    Costing

    Drawings to be forwarded for cost benefit analysis

    Material cost savings generate 5 % on material costs

    when compared with MS or GI

    Real savings achieved in time

  • 7/30/2019 CPVC Sprinkler Piping

    11/11

    TATA HOUSING DEVELOPMENT COMPANY LTD.

    10

    Way Forward

    Acceptance by various CFOs but cannot provide blanket approval

    Developer has to propose upon which it will be studied by CFO

    Ideal for projects where sprinklers are required in high rise

    Residential floors

    Brand name is Blazemaster marketed in India by M/s Astral

    Vellore Institute of Technology in Chennai- 4,000 sprinklers