4
CLIENT - CONSULTANT - CONTRACTOR - PROJECT: PACKAGE-II : DOC. NAME : DESIGN CALCULATION SHEET 51NS CORE FOR NEUTRAL CT OF Converter duty TRANSFORMER OF SS2 DOCUMENT NO. - REV.-00 Dated : 03 /07/2014 System basic Input Data Transformer rating = 630 KVA C T ratios = 600/1A Design = 3 PH 4 WIRE Voltage = 690 V AC Frequency = 50 Hz Basic Input Data of Current Transformer: Ratio = 300 1 A Accuracy class for Core‐II ( 51NS) = 5P 15 Accuracy class for Core‐I = PS Selected Burden ( VA ) for core‐I (PS) = 10 VA Basic Input Data of Distribution Transformer: Primary Voltage (v) = 11 kV Secondary Voltage ( V ) = 690 V Transformer rating = 0.630 MVA Impedence of transformer = 4 % % impedance variation on negative side = 0 ( no negative tolerance‐ for calculation purpose) Distribution System Fault Current: Full load current,I FL = 6 = (0.63x 10) (1.7322x690) = A Min Transformer Impedance, Z M = (% impedance x (100‐% tolerance))/100 = 4 x ( 100‐0))/100 = 4 % = (I F  x 100)/ Z M = (527.17 x 100) /4) I F = 13179.3 Amp = = 43.94 Amp 1.2 1.1 1.4 I / CTR Max.through Fault current at CT Secondary Side I fs Maximum through fault current on LV side of transfromer , MVA, I F 527.17 (√ 3 X Sec. Voltage) (MVA X 10 6 ) 1.3 1 of 4

CT Sizing for 51NS for 0.63 MVA Conveter.trafo_Rev-00_03.07.14

Embed Size (px)

DESCRIPTION

CT Sizing Calculation for HT/LV Transformer Feeder

Citation preview

  • CLIENT -

    CONSULTANT -

    CONTRACTOR -

    PROJECT:

    PACKAGE-II :

    DOC. NAME : DESIGN CALCULATION SHEET 51NS CORE FOR NEUTRAL CT OF Converter duty TRANSFORMER OF SS2

    DOCUMENT NO. - REV.-00 Dated:03/07/2014

    SystembasicInputDataTransformerrating = 630KVA

    CTratios = 600/1ADesign = 3PH4WIREVoltage = 690 VACFrequency = 50 HzBasicInputDataofCurrentTransformer:Ratio = 300 / 1 AAccuracyclassforCoreII(51NS) = 5P 15AccuracyclassforCoreI = PSSelectedBurden(VA)forcoreI(PS) = 10 VA

    BasicInputDataofDistributionTransformer:PrimaryVoltage(v) = 11 kVSecondaryVoltage(V) = 690 VTransformerrating = 0.630 MVAImpedenceoftransformer = 4 %%impedancevariationonnegativeside = 0 (nonegativetolerance

    forcalculationpurpose)DistributionSystemFaultCurrent:

    Fullloadcurrent,IFL =

    6= (0.63x10)

    (1.7322x690)= A

    MinTransformerImpedance,ZM = (%impedancex(100%tolerance))/100= 4x(1000))/100= 4 %= (IFx100)/ZM= (527.17x100)/4)

    IF = 13179.3 Amp

    == 43.94 Amp

    1.2

    1.1

    1.4

    IF/CTRMax.throughFaultcurrentatCTSecondarySideIfs

    MaximumthroughfaultcurrentonLVsideoftransfromer,MVA,IF

    527.17

    (3XSec.Voltage)(MVAX106)

    1.3

    1 of 4

  • CTsizingcalculationforIDMTEarthFaultprotectionRelay(51NS)NumberofIdenticalCTS = 1 NOSLocationofCTS = Core_1ofNCTonTrafoorseperateCT

    IDMTEarthFaultprotectionRelay(51NS)InputdataRelayModule =E/FSetting = 10 %CurrentI/Pburden,VA = 0.1 VARelatyoperatingCurrent,IR = 0.1 AmpCoreICTInputdataRatio = 300 /1ASelectedBurden(VA) = 10 VAAccuracyClass = 5P 15CalculatedofCTBurdens:CableLengthl(m) = mLeadresistanceat70Cfor2.5mm2copper(/km) = /kmLeadResistance(RL)() = ()LeadBurden(VA) = VATotalMeterBurden(VA) = VATotalBurdenonCT(VA) = VACTSecondaryresistanceat750C(Rct)(DuetoDesignlimitationofCTmanufacturer,Rct) = 4

    Selectedburdenismorethanrequired. HENCESAFE.WhenCT,CoreIisusedwithratio600/1A,Incaseofphasetophasefaultmaximumprimarycurrenttobemeasuredbytherelayforoperation = 20%IfFaultcurrentatSecondary If = 13.2 kA

    VoltagedevelopedbyCTVct = If X(Rct+Rl)Pri.CTRatio

    = 13.2X1000X(4+0.887)/300)

    CTVct = 215.03 V

    AccordinglyminimumVAburdenofconsideredCTRatingwithALF15

    ALF = 15= ((Vct/ALF)xCTseccurrent)(RctxCTsecCurrent)

    = ((215.03/15)X1)(4X1)= 14.34 4= 10.34

    Hence10VACThaving5P15accuracyisadequateHenceNCTcore1orseperateCTon0.63MVAConvertertrafoCT300/1A,5P15,10VA,RCT=

  • 3 of 4

  • 4 of 4