12-20 Molded Case Circuit Breakers 10-225 Amperes F-Frame .. f-i -i Cutler-Hammer January 2001 Vol. 1, Ref. No. [0486J Dimensions/Weights Table 12-30. Dimensions in Inches (mm) Number of Poles 1 2 3 4 Width 1.375(35) 2.75 (70) 4.125(105) 5.5(140) Height 6(152) 6(152) 6(152) 6(152) Depth 3.375 (86) 3.375 (86) 3.375 (86) 3.375 (86) Table 12-31. Approximate Shipping Weight, Lbs. (Kg) Breaker Type ED, EDH, EDC EHD, FOB, FD, HFD, FDC Number of Poles 1 2 (.907) 2 3 3(1.361) 3(1.361) 4.5(2.041) 4.5(2.041) 4 6(2.721) Product Selection This information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbers for circuit breakers or trip units. Table 12-32. Circuit Breaker Catalog Numbering System FDC 3 100 L Circuit Breaker Type EHD FOB FD HFD FDC Number of Poles 1 = 1 Pole 2 = 2 Poles 3 = 3 Poles 4 = 4 Poles Trip Ar 010 015 020 025 030 035 J 045 050 060 070 080 090 100 110 125 150 175 (FD, 200 (FD, 225 (FD, HFD, FDC, 2-, 3-, 4-Pole Only) HFD, FDC, 2-, 3-, 4-Pole Only) HFD, FDC, 2-, 3-, 4-Pole Only) Circuit Breaker Type ED EDH EDC Number of Poles 2 = 2-Pole 3 = 3-Pole 200 Suffix E = 100% Protected (4-Pole only) Neutral Pole EH = 50% Protected (4-Pole only) K = High Magnetic Molded Case Switch L = Line and Load Terminals S = Stainless Steel Terminals V = 50°C Calibration W = Without Terminals Y = Line Terminals Only Z = Aluminum Terminals (< 100 Amperes) Suffix L = Line and Load Terminals W = Without Terminals Y = Line Terminals Only Z = Aluminum Terminals (100 Amperes) X E:T*M For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

Cutler-Hammer - Amazon S3...Cutler-Hammer January 2001 Vol. 1, Ref. No. [0485] Molded Case Circuit Breakers 10-225 Amperes F-Frame 12-19 Contents Description Product Description Technical

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Cutler-Hammer - Amazon S3...Cutler-Hammer January 2001 Vol. 1, Ref. No. [0485] Molded Case Circuit Breakers 10-225 Amperes F-Frame 12-19 Contents Description Product Description Technical

12-20 Molded Case Circuit Breakers10-225 AmperesF-Frame .. f-i -i

Cutler-HammerJanuary 2001

Vol. 1, Ref. No. [0486J

Dimensions/WeightsTable 12-30. Dimensions in Inches (mm)Numberof Poles

12

34

Width

1.375(35)2.75 (70)

4.125(105)5.5(140)

Height

6(152)6(152)

6(152)6(152)

Depth

3.375 (86)3.375 (86)

3.375 (86)3.375 (86)

Table 12-31. Approximate Shipping Weight, Lbs. (Kg)Breaker Type

ED, EDH, EDC

EHD, FOB, FD, HFD, FDC

Number of Poles1

—2 (.907)

2 3

3(1.361)

3(1.361)

4.5(2.041)

4.5(2.041)

4

6(2.721)

Product SelectionThis information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbersfor circuit breakers or trip units.

Table 12-32. Circuit Breaker Catalog Numbering System

FDC 3 100 L

Circuit BreakerType

EHDFOBFDHFDFDC

Numberof Poles

1 = 1 Pole2 = 2 Poles3 = 3 Poles4 = 4 Poles

Trip Ar

010015020025030035

J

0450500600700800901001 1 0125150175 (FD,200 (FD,225 (FD,

HFD, FDC, 2-, 3-, 4-Pole Only)HFD, FDC, 2-, 3-, 4-Pole Only)HFD, FDC, 2-, 3-, 4-Pole Only)

Circuit BreakerType

EDEDHEDC

Numberof Poles

2 = 2-Pole3 = 3-Pole

200

SuffixE = 100% Protected (4-Pole only) Neutral PoleEH = 50% Protected (4-Pole only)K = High Magnetic Molded Case SwitchL = Line and Load TerminalsS = Stainless Steel TerminalsV = 50°C CalibrationW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (< 100 Amperes)

SuffixL = Line and Load TerminalsW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (100 Amperes)

X

E:T*M For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

Page 2: Cutler-Hammer - Amazon S3...Cutler-Hammer January 2001 Vol. 1, Ref. No. [0485] Molded Case Circuit Breakers 10-225 Amperes F-Frame 12-19 Contents Description Product Description Technical

Cutler-HammerJanuary 2001Vol. 1, Ref. No. [0485]

Molded Case Circuit Breakers10-225 AmperesF-Frame

12-19

ContentsDescription

Product Description

Technical Dataand Specifications

Dimension/Weights

Product Selection ..

F-FramePage

12-19

12-1912-2012-20

Product Description• All F-Frame Circuit Breakers are

HACR rated.• All circuit breakers 10 through

50 amperes are suitable for HID(high intensity discharge) use.

• All F-Frame circuit breakers aresuitable for reverse feed use.

Typical F-Frame Breaker

Technical Data and SpecificationsTable 12-28. UL489 Interrupting Capacity RatingsCircuitBreakerType

EDEDHEDCEHD

FOBFD

HFD

FDC

Numberof Poles

2,32,32,312,32,3,412,3,412,3,42,3,4

Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)240

65100200

1818

65

100200

277

14

—25

65

480

1414

25

65100

600

_

14

18

2535

Volts DC &125

10101 01 0

—10

10

250 @®

1 010

1 0

2222

© DC ratings apply to substantially non-inductive circuits.® 2-pole circuit breaker, or two poles of 3-pole circuit breaker.® Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.

Table 12-29. IEC 157-1 (PI) Interrupting Capacity Ratings (P1)

CircuitBreakerType

EDEDHEDCFOBFD

HFD

FDC

Number ofPoles

2,32,32,32,3,4

12,3,412,3,4

2,3,4

Interrupting Capacity (Symmetrical Amperes) (kA)Volts AC (50/60 Hz)220, 240

65100200

18

2565

65100

200

380,415

14

35

65

100

440

14

35

65

100

500

14

18

25

35

Volts DC A125

101010

—10

10

250 @®

10

10

22

22

® DC ratings apply to substantially non-inductive circuits.® 2-pole circuit breaker, or two poles of 3-pole circuit breaker.© Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.

CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T.N

Page 3: Cutler-Hammer - Amazon S3...Cutler-Hammer January 2001 Vol. 1, Ref. No. [0485] Molded Case Circuit Breakers 10-225 Amperes F-Frame 12-19 Contents Description Product Description Technical

12-22 Molded Case Circuit Breakers10-225 AmperesF-Frame

Cutler-HammerJanuary 2001

Vol. 1,Ref. No. [0488]

Table 12-35. Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip UnitsMax.Cont.AmpereRating@40°C

1 0 ®152025303540455060708090

1001 1 0125150175200225

600V AC Maximum, 250V DC

14 kAIC <g> 600V ACType FOB (Includes Terminals on Load End Only)2-PoleCatalogNumber

FDB2010FDB2015FOB2020FDB2025FDB2030FDB2035FDB2040FDB2045FDB2050FDB2060FDB2070FDB2080FDB2090FDB2100FDB2110FDB2125FDB2150———

PriceU.S. $

435.435.435.435.435.435.435.393.435.435.565.565.565.565.

1,260.1,260.1,260.

———

3-PoleCatalogNumber

FDB3010FDB3015FDB3020FDB3025FDB3030FDB3035FDB3040FDB3045FDB3050FDB3060FDB3070FDB3080FDB3090FDB3100FDB3110FDB3125FDB3150———

PriceU.S. $

570.570.570.570.570.570.570.570.570.570.695.695.695.695.

1,565.1,565.1,565.

———

4-PoleCatalogNumber

FDB4010FDB4015FDB4020FOB4025FDB4030FDB4035FDB4040FDB4045FDB4050FDB4060FDB4070FDB4080FDB4090FDB4100FDB4110FDB4125FDB4150———

PriceU.S. S

910.910.910.910.910.910.910.910.910.

1 , 1 1 0 .1 , 1 1 0 .1 , 1 1 0 .1 , 1 1 0 .1 , 1 1 0 .2,495.2,495.2,495.

———

277V AC Maximum,125V DC25 kAIC @ 277V AC

600V AC Maximum, 250V DC

25 kAIC @ 480V ACType FD (Includes Terminals on Load End Only)1-PoleCatalogNumber

FD1010FD1015SFD1020*FD1025FD1030FD1035FD1040FD1045FD1050FD1060FD1070FD1080FD1090FD1100FD1110FD1125FD1150———

PriceU.S. S

299.299.299.299.299.299.299.299.299.299.335.335.335.335.760.760.760.

———

2-PoleCatalogNumber

—FD2015F02020FD2025FD2030FD2035FD2040FD2045FD2050FD2060FD2070FD2080FD2090FD2100FD2110FD2125FD2150FD2175FD2200FD2225

PriceU.S. S

735.735.735.735.735.735.735.735.735.855.855.855.855.

1,915.1 ,915 .1 ,915.1,920.1,920.1,920.

3-PoleCatalogNumber

—FD3015FD3020FD3025FD3030FD3035FD3040FD3045FD3050FD3060FD3070FD3080FD3090FD3100FD3110FD3125FD3150FD3175FD3200FD3225

PriceU.S.S

865.865.865.865.865.865.865.865.865.975.975.975.975.

2,205.2,205.2,205.2,205.2,205.2,205.

4-PoleCatalogNumber

—FD4015FD4020FD4025FD4030FD4035FD4040FD4045FD4050FD4060FD4070FD4080FD4090FD4100FD4110FD4125FD4150FD4175FD4200FD4225

PriceU.S.S

1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,495.1,495.1,495.1,495.3,080.3,080.3,080.3,080.3,080.3,080.

CO Not UL listed. 5 kAIC interrupting rating.<& UL listed for SWD applications, see NEC Article 240-83 (d).Note: Instruction Leaflet/FRED Number 29C101

Table 12-36. Types HFD and FDC Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip UnitsMax.Cont.AmpereRating@40°C

15 •2025303540455060708090

1001 1 0125150175200225

277V AC Maximum,125V DC65 kAIC @ 277V AC

600V AC Maximum, 250V DC

65 kAIC @ 480V ACType HFD(Includes Terminals on Load End Only)1-PoleCatalogNumber

HFD1015 A1

HFD1020®HFD1025HFD1030HFD1035HFD1040HFD1045HFD1050HFD1060HFD1070HFD1080HFD1090HFD1100HFD1110HFD1125HFD1150———

PriceU.S.S

366.366.366.366.366.366.366.366.366.427.427.428.427.

1,001.1,001.1,005.

———

2-PoleCatalogNumber

HFD2015HFD2020HFD2025HFD2030HFD2035HFD2040HFD2045HFD2050HFD2060HFD2070HFD2080HFD2090HFD2100HFD2110HFD2125HFD2150HFD2175HFD2200HFD2225

PriceU.S.S

885.885.885.885.885.885.885.885.885.

1,130 .1,130.1,130.1 ,130 .2,510.2,510.2,510.2,720.2,720.2,720.

3-PoleCatalogNumber

HFD3015HFD3020HFD3025HFD3030HFD3035HFD3040HFD3045HFD3050HFD3060HFD3070HFD3080HFD3090HFD3100HFD3110HFD3125HFD3150HFD3175HFD3200HFD3225

PriceU.S/S

1,140 .1,140.1,140.1,140.1 ,140 .1 ,140 .1 ,140 .1,140.1 ,140 .1,140.1,140.1,140.1 ,140.3,120.3,120.3,120.3,120.3,120.3,120.

4-PoleCatalogNumber

HFD4015HFD4020HFD4025HFD4030HFD4035HFD4040HFD4045HFD4050HFD4060HFD4070HFD4080HFD4090HFD4100HFD4110HFD4125HFD4150HFD4175HFD4200HFD4225

PriceU.S. S

1,940.1,940.1,940.1,940.1,940.1,940.1,940.1,940.1,940.2,445.2,445.2,445.2,445.4,405.4,405.4,405.4,370.4,370.4,370.

600V AC Maximum, 250V DC

100 kAIC @ 480V ACType FDC Current Limiting(Includes Terminals on Load End Only)2-PoleCatalogNumber

FDC2015FDC2020FDC2025FDC2030FDC2035FDC2040FDC2045FDC2050FDC2060FDC2070FDC2080FDC2090FDC2100FDC2110FDC2125FDC2150FDC2175FDC2200FDC2225

PriceU.S.S

1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,690.1,690.1,690.1,690.3,780.3,780.3,780.3,780.3,780.3,780.

3-PoleCatalogNumber

FDC3015FDC3020FDC3025FDC3030FDC3035FDC3040FDC3045FDC3050FDC3060FDC3070FDC3080FDC3090FDC3100FDC3110FDC3125FDC3150FDC3175FDC3200FDC3225

PriceU.S.S

1,710.1 ,710 .1 ,710 .1,710.1 ,710 .1 ,710 .1 ,710 .1 , 7 1 0 .1 , 7 1 0 .2,095.2,095.2,095.2,095.4,685.4,685.4,685.4,685.4,685.4,685.

4-PoleCatalogNumber

FDC4015FDC4020FDC4025FDC4030FDC4035FDC4040FDC4045FDC4050FDC4060FDC4070FDC4080FDC4090FDC4100FDC4110FDC4125FDC4150FDC4175FDC4200FDC4225

PriceU.S.S

2,910.2,910.2,910.2,910.2,910.2,910.2,910.2,910.2,910.3,600.3,600.3,600.3,600.6,610.6,610.6,610.6,610.6,610.6,610.

® UL listed for SWD applications, see NEC Article 240-83(d).Note: Instruction Leaflet/FRED Number 29C101

Discount Symbol. CB-2

E:T*M For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

Page 4: Cutler-Hammer - Amazon S3...Cutler-Hammer January 2001 Vol. 1, Ref. No. [0485] Molded Case Circuit Breakers 10-225 Amperes F-Frame 12-19 Contents Description Product Description Technical

12-166 Molded Case Circuit BreakersInternal AccessoriesAuxiliary Switch and Alarm Switch Combination

Cutler-HammerJanuary 2001

Vol. 1, Ref. No. [0632]

Table 12-322. E125 Auxiliary Switch and Alarm Switch CombinationElectrical RatingsVolts

600125250

Frequency Hz

50/60DCDC

Amperes

60.50.25

ContactArrangement

1 A - 1 B a n d1M-1B

CatalogNumber

AUXALRMEPK

PriceU.S.S

400.

Table 12-323, F-Frame Auxiliary Switch and Alarm Switch CombinationMountingLocation(Pole)

Left®Right

Factory MountedConnection Type and Location18-Inch (457 mm) Pigtail LeadsSame SideSuffixNumber

C01C04

AdderU.S.S

400.400.

Rear ?SuffixNumber

C02COS

AdderU.S. $

400.400.

Terminal BlockSame SideSuffixNumber

C03C06

AdderU.S.S

400.400.

Field MountedField Installation Kits :

Pigtail Leads

CatalogNumber

AAL1LPKAAL1RPK

PriceU.S.S

400.400.

Terminal Block

CatalogNumber

AAL1LTKAAL1RTK »

PriceU.S.S

400.400.

W Not listed with Underwriters Laboratories for field installation.@ Standard mounting location.® Not for use on 4-pole circuit breakers.Note: Instruction Leaflet/FRED Number 29C180

Table 12-324. J250 Auxiliary Switch and Alarm Switch CombinationElectrical RatingsVolts

600125250

Frequency Hz

50/60DCDC

Amperes

60.50.25

ContactArrangement

1 A - 1 B a n d1 M - 1 B

CatalogNumber

AUXALRMEPK

PriceU.S.S

400.

Table 12-325. J-Frame Auxiliary Switch and Alarm Switch CombinationNumber ofSets ofContacts(laandlbandIMandlB)

1

MountingLocation(Pole)

LeftRight *

Factory MountedConnection Type and Location18-Inch (457 mm) Pigtail LeadsSame SideSuffixNumber

C01C04

AdderU.S.S

400.400.

Rear*SuffixNumber

C02COS

AdderU.S.S

400.400.

Opposite SideSuffixNumber

AdderU.S.S

Terminal BlockSame SideSuffixNumber

COSC06

AdderU.S.S

400.400.

Field MountedField Installation Kits ®Pigtail Leads

CatalogNumber

AAL2LPKAAL2RPK

PriceU.S.S

400.400.

Terminal Block

CatalogNumber

AAL2LTKAAL2RTK s

PriceU.S.S

400.400,

® Listed with Underwriters Laboratories for field installation of interchangeable trip unit breakers under E64983.® Standard mounting location — leads exit rear of breaker.® Not for use on 4-pole circuit breakers.Note: Instruction Leaflet/FRED Number 29C181

Table 12-326. K-Frame Auxiliary Switch and Alarm Switch CombinationNumber ofSets ofContactsdaandlbandIMand 1B)

1

MountingLocation(Pole)

LeftRight d)

Factory MountedConnection Type and Location18-Inch (457 mm) Pigtail LeadsSame SideSuffixNumber

C01C04

AdderU.S.S

400.400.

Rear ?SuffixNumber

C02COS

AdderU.S.S

400.400.

Opposite SideSuffixNumber

AdderU.S.S

Terminal BlockSame SideSuffixNumber

C03C06

AdderU.S.S

400.400.

Field MountedField Installation KitsPigtail Leads

CatalogNumber

AAL3LPKAAL3RPK

PriceU.S.S

400.400.

?>

Terminal Block

CatalogNumber

AAL3LTKAAL3RTK

PriceU.S.S

400.400.

® Listed with Underwriters Laboratories for field installation of interchangeable trip unit breakers under E64983.® Standard mounting location — leads exit rear of breaker.Note: Instruction Leaflet/FRED Number 29C182

Discount Symbol, CB-2

F:T*N For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

Page 5: Cutler-Hammer - Amazon S3...Cutler-Hammer January 2001 Vol. 1, Ref. No. [0485] Molded Case Circuit Breakers 10-225 Amperes F-Frame 12-19 Contents Description Product Description Technical

12-170 Molded Case Circuit BreakersInternal AccessoriesShunt Trip

Cutler-HammerJanuary 2001

Vol. 1, Fief. No. [0636]

Table 12-335. G-Frame Shunt Trip (LH 3-Pole only)Electrical RatingsVolts

120240122424

Frequency

50/60 Hz50/60 HzDCDC60 Hz

Amp

1.12.12.85.7-

CatalogNumber

1373D62G011373D62G021373D62G151373D62G161373D62G20

PriceU.S.S

489.489.489.489.489.

SuffixNumber

SIS2S3S4S7

AdderU.S.S

489.489.489.489.489.

Note: G-Frame circuit breakers are factory sealed. UnderwritersLaboratories requires that internal accessories be installed atthe factory.Internal accessories are UL listed for factory installationunderE7819.Where local codes and standards permit and UL listing is notrequired, internal accessories can be field installed. Accessoryinstallation should be done before the circuit breaker is mountedand connected.

Note: Instruction Leaflet/FRED Number 15550

Table 12-336. E125 Shunt TripElectrical RatingsVolts | Frequency Hz

12-60110-240'!380 - 600

50/60. DC50/60, DC50/60

CatalogNumber

SNT060CPKSNT120CPKSNT480CPK

PriceU.S.S

489.489.489.

•>'-•' Suitable for use in ground fault applications.Note: Instruction Leaflet/FRED Number 29C152

Table 12*337. F-Frame Shunt TripVottage Rating(AC Frequency = 50/60 Hz)

Factory MountedConnection Type and Location18-Inch (457.2 mm) Pigtail LeadsSame SideSuffixNumber

AdderU.S.S

RearSuffixNumber

AdderU.S.S

Opposite SideSuffixNumber

AdderU.S.S

Terminal BlockSame SideSuffixNumber

AdderU.S.S

Field MountedField Installation Kits:?Pigtail Leads

CatalogNumber

PriceU.S.S

Terminal Block

CatalogNumber

PriceU.S.S

Left-Pole Mounting AC/DC Ratings12-24VACorDC4S-127VACor48-60VDC'^208 - 380V AC or 1 10 - 127V DC415 - 600V AC or 220 - 250V DC

SOISOSS09S13

489.489.489.489.

S02S06S10S14

489.489.489.489.

S03S07S11S15

489.489.489.489.

S04SOBS12S16

489.489.489.489.

SNT1LP03KSNT1LPOSKSNT1LP12KSNT1LP18K

489.483.489.489.

SNT1LT03KSNT1LT08KSNT1LT12KSNT1LT18K

489.489.489.489.

Right- or Neutral-Pole Mounting AC/DC Ratings12-24VACorDC48 - 127V AC or 48 -60V DC '208 - 380V AC or 1 1 0 - 127V DC415 - 600V AC or 220 - 250V DC

S17S21S25S29

489.489.489.489.

S18S22S26S30

489.489.489.489.

S19S23S27S31

489.489.489.489.

S20S24S28S32

489.439.489.489.

SNT1RP03KSNT1RP08KSNT1RP12KSNT1RP18K

489.489.489.489.

SNTIflTOSK^SNT1RT08K '-SNT1RT12K 'fSNT1RT18K '

489.489.489.489.

&! Not listed with Underwriters Laboratories, for field installation.® Pigtail wire size: 18 AWG (0.82 mm2).® Standard pigtail lead exit location.& 120V AC marked suitable for ground fault protection devices.® Standard mounting location.<? Not for use on 4-pole circuit breakers.Note: Instruction Leaflet/FRED Number 29C140

Table 12-338. J250 Shunt TripElectrical RatingsVolts

12-60110-240 '*380-600

Frequency Hz

50/60, DC50/60, DC50/60

CatalogNumber

SNT060CPKSNT120CPKSNT480CPK

PriceU.S.S

489.489.489.

* Suitable for use in ground fault applications.Note: Instruction Leaflet/FRED Number 29C152

Discount Symbol CB-2

F.T-N Far more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalag CAT.200.Q1.T.E