Upload
andrew
View
225
Download
0
Embed Size (px)
Citation preview
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 1/12
Cutler-Hammer VacClad-W Arc Resistant Switchgear
The Result of Innovative Technology
Hugo Sulzer
Switchgear Application Specialist
April 1996
ml Cutler-Hammer
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 2/12
TRADITIONAL METALCLAD SWITCHGEAR CONCEPTS
Developments in Technology for medium voltage metalclad
switchgear in recent years have greatly improved the reliability of the
distribution systems from 2.4KV to 38KV. Vacuum breakers have
fewer moving parts with lower inertia mechanisms resulting from
smaller contact gap requirements. The net result has increased the
reliability factors two fold. Improved insulation materials on breakers
along with bed fluidized epoxy insulation bonded to bus bars have not
only increased the performance reliability but has extended the lifeexpectancy of current designed metalclad switchgear to 40 plus years.
Distribution systems have also moved to higher interrupting ratings
such as 750,1000,1500MVA.
With the trend to higher interrupting ratings, the metalclad switchgear
design is recommended rather than metal enclosed and is the first
choice design of most consultants and utilities. The metalclad design
concentrates on a structure design which reduces the possibility of
arcing faults within the enclosure. For instance, all primary elements
such as breakers, voltage transformers and control power transform-
ers have disconnect means with isolating shutters establishing
isolation from the high voltage source. The enclosures containing
primary elements have been compartmentalized and grounded for
maximum isolation and confinement such as the breaker compart-
ment, main bus compartment and cable compartment. Within these
compartments all live parts where possible are fully insulated reducing
the possibility of an arcing fault to occur. This primary directive to
attempt to eliminate the possibility of an arcing fault has driven the
design development to metalclad switchgear construction for many
years. The design has proven itself to be a reliable switchgear design
in most applications. Structural containment due to arcing faults were
never considered by the traditional standards such as ANSI, IEEE,
NEMA, UL, CSA because of the design criteria established to prevent
arcing faults within the switchgear structure design.
Although arcing faults are rare, injuries from arcing faults in
switchgear have continued. When it does occur, the results can be
very destructive because of the energy levels reached within a
confined compartment. The structural containment proves inadequate
to prevent arcing products and hot gases escaping the faulted
compartment. Burns could result if operating personnel are in close
proximity to the faulted switchgear. Present regulatory organizations
such as NEC, OSHA recognize the hazards of electric arc propagation
and stipulates the use of protective clothing for operating personnel.
REASONS FOR DEVELOPMENT OF AN ARC RESISTANT
SWITCHGEAR
ARCING FAULT PHENOMENA
Arcing faults can occur within a compartment as a result of insulation
failure or human error. The pressure from an electric arc is developed
from two sources: the expansion of the metal in boiling, and the
heating of air by the arc energy. Copper expands by a factor of 67,000
times in vaporizing. This accounts for the expulsion of near-vaporized
droplets of molten metal from the arc; one of the tests showed that
droplets could be propelled up to 10 feet. The pressure also generates
plasma outward from the arc for distances proportional to the arc
energy. One cubic inch of copper vaporizes into 1.44 cubic yards of
vapor. The air in the arc stream expands in warming up from its
ambient temperature to that of the arc temperature (approx. 35,000
degrees F). All this happens within the first half cycle of the fault and
results in a sudden, large rise in pressure inside of the compartment.
The structure of the switchgear offers some containment but may not
be enough to prevent personal injury.
HISTORY OF ARC RESISTANTSWITCHGEAR IN EUROPE
In Europe, concern for internal arcing within the enclosure of
switchgears had existed for a number of years and in April 1969, work
in Germany led to the publication of “Pehla Recommendation no. 2”
which described the method for testing switchgear under conditions of
internal arcing and gave the criteria for accepting an arc resistant
construction. Some years later an IEC working group was formed to
study a German proposal for amending the switchgear specification
publication 298 to include a section on non-mandatory internal arc test
and in December 1978, Amendment no. 2 to IEC publication 298 was
adopted.[l] This Amendment and subsequent updates are considered
as the basis for arc resistant testing of metalclad switchgear in
Europe. It gives the locations where internal faults are more likely to
occur, types of accessibility for a switchgear, test arrangements, test
current and voltage to be applied, test procedure and the criteria for
assessing the test results. This IEC standard was also used as the
base standard in the development of the EEMAC Standard G14-1
1987 in Canada.
CANADIAN DEVELOPMENT OF ARC RESISTANT SWITCHGEAR
To provide some background in Canada as to how the EEMAC
Standard was developed, the following events took place before the
Standard was written. A failure took place in a substation in the City of
Toronto. The racking mechanism for the incoming circuit breaker was
designed such that the circuit breaker could pivot slightly out of
alignment and still satisfy interlocking requirements. This resulted in a
poor connection in one of the outer phases at the circuit breaker upper
primary disconnect.
The disconnect overheated, resulting eventually in thermal breakdown
of the circuit breaker bushing, and a flashover to the wall of the circuit
breaker cubicle. The resulting explosion in the circuit breaker
compartment caused the front door to bow, fractured its upper and
lower fastenings, and swung the door open, ejecting hot arc products
into the station building. Nobody was close to the equipment at the
time and there were no injuries.
In another event in Ontario’s Niagara Region, due to changes in
metering requirements in the Region, some current transformers were
removed from a circuit breaker cell and replaced by epoxy insulated
copper bars. One of the bolted connections was not properly torqued
and in the course of about a week, the heat generated at the poor
connection caused the insulation to deteriorate to the point of failure.
Page 2
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 3/12
e flashover resulted in a cable compartment cover being blown off,
aring eleven fastening bolts. Again, nobody was close to the
ipment and there were no injuries,
e third event had two explosive failures in adjacent cable compart-
nts in a metalclad switchgear in a Hamilton transformer station.
e primary cause of both failures was attributed to snow blowing into
cubicles via a ventilation louvre under the building eaves, resulting
he eventual failure of two cable potheads.
e first fault was interrupted by the feeder breaker but resulted in the
ors of the cable compartment being blown open. Five workmen
uding supervisors were dispatched from Ontario Hydro and
milton Hydro to examine the failed equipment and to start the repair
cedures. As they gathered around the failed cell, the second fault
he adjacent compartment took place. Because of a faulty feeder
uit breaker, the second fault persisted for a longer period of time,
h the result that the doors were completely torn off and the hot arc
ducts spilled into the aisleway. Four of the workmen were seriously
lowing this last failure, it was decided future metalclad bought by
tario Hydro must be able to withstand the explosive forcesnerated by faults inside metalclad cells i.e., the design must be arc
istant. Prior to these failures, Ontario Hydro had been made aware
European developments in this area, particularly in Germany. At the
e of Ontario Hydro’s decision, the International Electrotechnical
mmisssions (IEC) were in the process of establishing criteria for
cessful type testing of an arc resistant design. These were later
blished in Amendment No. 2 to IEC Standard 298 as previously
ted.
tario Hydro directed the members of the Electronic & Electrical
nufacturers Association (EEMAC) to form a working group to write
imilar Canadian specification to deal with the proper procedure for
ing a switchgear design which would prevent explosive forces from
caping due to the failure of the structure containment during the
ere overpressure phase of a fault.
e specification was completed in 1987 heavily influenced by Ontario
dro. The basis for the EEMAC G14-1 test procedure has similar
eria as established by IEC but strengthened in areas where Ontario
dro felt the procedure for testing needed improvement from the
ropean design criteria at the time it was written. To date, IEC has
de modifications to their specifications to improve the safety of
ntrol gear manufactured in Europe.
SIGN LEVELS FOR ARC RESISTANT SWITCHGEAR
e EEMAC G14-1 although a test procedure, does define three
inct levels of arc resistant design corresponding to the test
nditions stipulated within the test procedure.
Accessibility Type A: Switchgear with arc resistant
construction at the front only.
Accessibility Type B:
‘\
Accessibility Type C:
(Utility Requirement)
Note to Type C:
Switchgear with arc resistant
construction at front, back and sides.
Switchgear with arc resistant ’construction at front, back andsides
and between compartments within the
same cell or adjacent cells.
The only exception is that a fault in a
bus bar compartment of a feeder cell isallowed to break into the bus bar
compartment of an adjacent feeder cell.
(This recognizes the fact that most bus
compartments have very little volume
for gas expansion and that the pressure
relief in breaking into the adjacent main
bus compartment is acceptable,
according to EEMAC G14-1 1987.)
EVALUATION CRITERIA OF A SUCCESSFUL TEST
The test procedure outlines the following stipulations which must be
met for evaluating an acceptable arc resistant design.
Criteria No. 1
That properly secured doors, covers, etc., do not open.
Criteria No. 2
That parts which may cause a hazard do not fly off. This includes large
parts or those with sharp edges, for example, inspection windows,
doors, pressure relief flaps, cover plates, etc. made of metal or plastic.
Criteria No. 3
Accessibility Type B:
Accessibility Type C:
That arcing does not cause holes to
develop in the accessible front of the
switchgear.
That arcing does not cause holes in the
freely accessible front, sides and rear
of the enclosure.
That arcing does not cause holes in the
freely accessible front sides and rear of
the enclosure or in the walls separating
the cells in an assembly (except for
main bus bar barriers) or between
compartments of a cell. ’Criteria No. 4
That the cotton indicators fitted as per test specification do not ignite.
Indicators ignited as a result of the burning of paint, labels, etc. are
excluded from this assessment.
Page 3
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 4/12
EEMAC standard requires the cotton indicators to be 150g per square
meter density and must be 10.2 cm from the test surface.
IEC standard requires 150g per square meter density and must be
30 cm from test surface.
Criteria No. 5
That all the grounding connections remain effective.[3]
With the above five criteria having been tested and assessed by an
independent high voltage test station, a manufacturer is deemed to
have an arc resistant design.
At this point in time, it must be emphasized that failure within the
switchgear enclosure due either to a defect, an exceptional service
condition as an example, corrosive atmosphere or mal-operation may
initiate an internal arc.
There is little probability of such an event occurring in equipment
meeting the requirements of ANSI, IEEE, EEMAC but it cannot be
completely disregarded. Such an event may lead to the risk of injury,
if persons are present in the vicinity of the equipment.
It is desirable that system designers and purchasers provide the highest
appropriate degree of protection to persons. The principal objective is to
avoid internal arcs or to limit their duration and consequences.
Experience has shown that faults are more likely to occur in some
locations inside an enclosure than in others. Special attention should
be paid in such areas. For guidance, a list of such locations and
causes is given in Columns 1 and 2 of Table 1 of EEMAC G14-1.
Measures to decrease the probability of internal faults or to reduce therisk are recommended but not limited to examples in column 3.
If the measures described above are considered to be insufficient, then,
to cover the case of an arc occurring entirely in air within the switchgear
enclosure, a test in accordance with EEMAC G14-1, 1987 may be
agreed between the manufacturer and user. The tests required make
allowance for internal overpressure acting on covers, doors, inspection
windows, etc. and also takes into consideration the thermal effects of the
arc or its roots on the enclosure and of ejected hot gases directly from
the switchgear and damage to partitions which would endanger
operating personnel doing maintenance inside adjacent compartments.
It does not cover all effects which may constitute a risk, such as toxic
gas nor the location of the equipment within a building.
Table 1 Locations, causes and examples of measures decreasing the probability of internal faults or reducing the risk [3]
Locations where internal faultsare more likely to occur Possible causes of internal faults Examples of Measures
1 2 3
Cable Termination Inadequate design Selection of adequate
Compartments dimensions
Faulty installation Avoidance of crossed cable connections.Checking of workmanship on site.
Disconnectors SwitchesGrounding Switches
Failure of solid or liquid insulation (defectiveor missing)
Mal-operation
Check of workmanship and/or dielectric teston site. Regular checking of liquid levels.
Interlocks. Delays re-opening. Independentmanual operation. Making capacity forswitches and grounding switches.Instructions to personnel
Bolted Connectionsand Contacts
Instrument Transformers
Corrosion
Faulty assembly
Ferroresonance
Use of corrosion inhibiting coatings and/orgreases. Encapsulation where possible.
Checking of workmanship by suitable means.
Avoidance of these electrical influencesby suitable design of the circuit.
Circuit Breakers Insufficient maintenance Regular programmed maintenance.Instructions to personnel.
All Locations Error by personnel Limitation of access by compartmentation.Insulation embedded live parts.Instructions to personnel.
Aging under electric stresses
Pollution, moisture,dust vermin etc.
Partial discharge routine tests.
Measures to ensure that the ingressspecified service conditions are achieved.
Page 4
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 5/12
TLER-HAMMER VacClad-W ARC RESISTANT SWITCHGEAR
VELOPMENT
new Cutler-Hammer using the Westinghouse VacClad-W medium
age arc resistant switchgear design provides more advanced
hnology and more flexibility by incorporating into the basic steel
cture all requirements of containment during an arcing fault,
ing the many studies and tests conducted by Cutler-Hammer, its found that the internal arcing phenomenon consists of two stages
ally, the dynamic phase and a thermal phase. See Figure 1.
E DYNAMIC PHASE
The overpressure and the magnitude of arcing current and the volume
of the compartment are all interrelated. There are many differential
equations which have been developed but the geometry of each
switchgear compartment are subtly different making actual testing the
only ultimate way to prove an arc resistant design. The issue here is
to design a pressure relief vent into the switchgear compartment
design to allow the dynamic phase to dissipate without losing the
integrity of the fastening devices.[4]
THE THERMAL PHASE
While the arc is burning and expanding, part of the compartment bus bars
will vaporize, insulation will melt and disintegrate and burning of paint
results in smoke and fumes. The longer the fault is allowed to persist
beyond 30 cycles, the arc could burn through steel. This is why relay
coordination settings are very important to clear the fault before burn
through during the thermal phase takes place. Understanding the
dynamics of an arc fault and energy levels attained allowed Cutler-
Hammer to achieve the design goals required for arc resistant switchgear.
he start of arc initiation within 10 milliseconds, the absolute
ssure inside a switchgear enclosure could reach a pressure level
232 Ibs/square foot in some instances but this value is a function
he fault current magnitude. With such a rate of rise of pressure,
tainment cannot be accomplished within the compartment.
ure 1 Pressure in a cell/compartment during arc.
** *
I I I i
16 36 48 64 80 96 112 128 144 160I I I I I I I I I I
Time (ms)
Illustration of a three-phase internal arc fault
A) Short circuit current B) Arc Voltage C) Dynamic pressure inside the cell
* Compression
* Expansion
* Emission
* Thermal
Page 5
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 6/12
ESTING PROGRAM above the switchgear must be considered since the arc energy is now
being focused through the tops of the switchgear. Compartment to
utler-Hammer designed pressure relief vents in sufficient cross compartment as defined by EEMAC G14-1 had to be tested so that
ection areas on the roof of each metalclad compartment to effectively ( the design levels A, B and C were proven to be safe. The pressure
elieve the stresses within each compartment. The critical design of relief vents on top of the switchgear had to be of suitable thickness to
ourse are the hinges and latches which must hold together while ensure a walkable roof. During the installation of the switchgear,
ressure relief is accomplished. The overlaps of steel flanges had to construction crews quite often walk on top of enclosures during
eal off hot gases so that the cotton indicators outside the switchgear offloading and placing into final position on the switchgear floor.
ould not ignite. Cotton indicators representing bare skin in close
roximity to switchgear compartments in a typical test are shown in The Cutler-Hammer design not only has a walkable roof but theigure 3. The squares represent cotton indicators strategically placed unique raised flange provides automatic dripproof construction with
vulnerable areas of the switchgear design. Establishing a clear area every arc resistant design,
igure 3
FRONT VIEW REAR VIEW
age 6
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 7/12
test shown in Figure 4 shows the set up of cotton indicator
ions. The main bus compartment will be shorted with a copper
having 0.5mm diameter sufficient to initiate the arc. These test
ences were performed with type c arc resistant construction.
re 4
3
F R O N T 0
“IEWA_A
RWIRE 0
r’A B.5 mm
NOTES:?-TEST TO BE CARRIED OUT WITH ALL DOORS ON CELL NO. 3 OPEN
ItI
“a
LEFT SIDE VIEW REAR VIEW
Page 7
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 8/12
The design in Figure 5 is an internal bus duct rated 3000A. Bus duct
connections will be necessary in some form and testing to validate the
arc resistant design is necessary. Outside the compartment bus duct
location of cotton indicators to detect any leakage of hot gases is
critical even to extend beyond the roof line where the pressure vents
are located.
Figure 5
PLAN VIEWroof
NOTES:1. TEST TO BE CARRIEDOUT WITH DRESS PANELSREMOVED.2. CATU GROUNDING STUDSNO LONGER REQUIRED ININTERCELL BUS DUCT.
FRONT VIEW SIDE VIEW REAR VIEW
Page 8
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 9/12
LT LEVELS AVAILABLE
procedure for testing as written in EEMAC G14-1 states that the
levels tested must be agreed between the manufacturer and end
. The actual fault level is not stipulated. To provide improved
ator safety, the Cutler-Hammer design was tested to match the
rupting rating of the breaker. This ensures a coordinated design
e 2
between arc resistant ratings and breaker ratings for the life of the
switchgear design. It is common practice to add more feeder load on
distribution switchgear including motor feeders. Motor contribution will
increase the fault capacity of the distribution system. The allowed
increase of course must not exceed the interrupting capacity of the
breaker and for this reason, arc resistant tests were performed
matching the breaker ratings. See Table 2.
Nominal Rated Rated Rated Short Maximum Arc Resistant
cuit Breaker Nominal 3-Phase Rated Voltage Continuous Circuit at Rated Symmetrical Short Circuitpe and Impulse Voltage MVA Maximum Range Current at Maximum Interrupting Current Levelvel Class Class Voltage Factor K 60 Hz Voltage Capacity at 60 Hz
VCP-W250 4.16 250 4.76 1.24 1200 29 36 36kV B.I.L. 2000
3000
VCP-w350 4.16 350 4.76 1.19 1200 41 49 49kV B.I.L. 2000
3000
VCP-w500 7.2 500 8.25 1.25 1200 33 41 41
kV B.I.L. 20003000
0 VCP-w500 13.8 500 15 1.3 1200 18 23 23kV B.I.L. 2000
3000
0 VCP-w750 13.8 750 15 1.3 1200 28 36 36kV B.I.L. 2000
3000
0 VCP-WlOOO 13.8 1000 15 1.3 1200 37 48 48kV B.I.L. 2000
3000
0 VCP-W25 27 1170 28.5 1 630 25 25 255kV B.I.L. 1200
2000
Page 9
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 10/12
CONSTRUCTION DETAIL HIGHLIGHTS AND DIMENSIONS
All operations performed on breakers, potential transformers and
control power transformers, engagement/isolation/test are with the
compartment doors closed for operator safety. The front door is
nterlocked with the shutter assembly to reduce the chance of
accidental opening of the front door during even partial levering-in of
he breaker/potential transformer/control power transformer drawout
element. Viewing windows are provided so that the operator is able to
see at all times what position the drawout element has reached such
as the connected position or test/isolated position. In any breakerposition, the status indicators on the breaker can be seen through the
viewing windows which include breaker open and closed indicator
lag, stored energy mechanism charged or discharged flag. All
charging of stored energy mechanisms are done with the front door
closed in full view through the Lexan viewing windows, For typical
dimensions. see Table 3.
A cautionary note must be made that all doors and panels must be
properly closed and fastened for the arc resistant feature of the
switchgear to be operative.
The rear cable compartment has two designs available; an all bolted
back panel or a rear door with an 8 point latching handle mechanism
which requires no bolting.
The walkable roof combined with the inherent dripproof construction
provides the highest degree of equipment protection during installation
unctions such as levering-in, manual trip, manual close, manual and commissioning
Table 3 Typical Dimensions Indoor and Outdoor VacClad-W Arc Resistant Switchgear
I I I
Circuit BreakerType and ImpulseLevel
50 VCP-W25060kV B.I.L.
50 VCP-w35060kV B.I.L.
NominalVoltageClass
4.16
Nominal Rated3-Phase ContinuousMVA Current atClass 60 Hz
75 VCP-w500 7.2 500 120095kV B.I.L. 20001 I I 3ooo
\ L
150 VCP-w500 13.8 500 1200
150VCP-w750 13.8 750 120095kV B.I.L. 2000
3000
92.38”96.38”96.38”
150 VCP-WI000 13.8 1000 120095kV B.I.L. 2000
3000
92.38”96.38”96.38”
270 VCP-W25 27 1170 630 92.38”125kV B.I.L. 1200 96.38”
2000 96.38”
I I I
T
Height
92.38”96.38”96.38”
92.38”96.38”96.38”
92.38”96.38”96.38”
92.38”
96.38”96.38”
J
Indoor
Bottom
- - l - -
EntryWidth Depth
36” 97”97”
109”
36” 97”97”
109”
36” 97”97”
109”
36” 97”
97”109”
36” 97”97”
109”
36” 97”97”
109”
I
42” 109”
r Outdoor 1TopEntryDepth
Add 3”plus TopCableSpace
Add 3”plus TopCableSpace
Add 3”
plus TopCableSpace
Add 3”
plus TopCableSpace
Add 3”plus TopCableSpace
Add 3”plus TopCableSpace
Add 3”plus Top
CableSpace
Height Width
128” Add 4”per Cellto IndoorDimension
128” Add 4”per Cellto IndoorDimension
128” Add 4”per Cellto IndoorDimension
128” Add 4”
per Cellto IndoorDimension
128” Add 4”per Cellto IndoorDimension
128” Add 4”per Cellto IndoorDimension
128” Add 4”per Cell
to IndoorDimension
Bottom TopEntry EntryDepth Depth
Add 10” Add 70”to IndoorDimension
Add 10” Add 70”to IndoorDimension
Add lo” Add 70”to IndoorDimension
Add 10” Add 70”
to IndoorDimension
Add 10” Add 70”to IndoorDimension
Add 10” Add 70”to IndoorDimension
Add 10” Add 70”to Indoor
Dimension
Page 10
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 11/12
e 4 Section Views
Section view 5kVand 15kV; 1200A VacClad-WArc Resistant switchgear cubicle
Section view 27kV; 1200A VacClad-WArc
Resistant switchgear cubicle
Section view 5kVand 15kV; 2000A VacClad-WArc Resistant switchgear cubicle
Section view 27kV, 12OOA VacClad-WArc
Resistant switchgear cubic/e
Section view 5kVand 15kV; 3000A VacClad-WArc Resistant switchgear cubicle
Standard outdoor arrangements available in non walk-in, walk-in and common aisle (walk-in shown)
CLUSION
reliability of Westinghouse switchgear and circuit breakers, now
r-Hammer, has been proven by over 25 years of vacuum interrupter
n and manufacturing experience. The ongoing research and
opment program has resulted in many significant advances in
um interrupter technology. These advances have been incorporated
he Cutler-Hammer VacCiad-W Arc-Resistant Switchgear and VCP-W
it Breakers to provide enhanced dependability, reliability, and safety.
nsive design and development taking into account all critical mechani-
riteria of impact under overpressure makes the Cutler-Hammer
Arc Resistant switchgear the best design available in the
etplace. Cutler-Hammer provides VacClad-W Arc Resistant switchgearh meets most utility design requirements. Multiple bolting, reinforced
heavier gauge material does not provide a better design or longer life
ctancy; it only adds more weight to the switchgear assembly and more
plexity to servicing. The Cutler-Hammer VacClad-W Arc Resistant
n is not a retrofitted general purpose switchgear cubicle. Compartment
ed steel design achieves panel against panel interfacing, providing a
d joint under fault conditions which prevents smoke and gas escaping
her compartments, instead of conventional flat bolted panels which are
ecessarily smoke or gas tight.
The switchgear cubicle can be easily removed even after a major fault
occurrence without disturbing the adjacent cubicle, even in cases
which have inaccessible locations. The enclosure can be dismantled
inwardly with minimal unbolting.
Greater life expectancy is achievable with the Cutler-Hammer design
with minimum down time if replacement or repair is ever necessary.
REFERENCES
[l] L. Lam “Development and Testing of Arc-Proof Metal-Clad
Switchgear for 25kV and 34.5kV Application” presented at CEA
Fall meeting Sept 1982 Edmonton, Alberta.
[2] J.P. Meehan “Arc Proofing of Metal-Clad Switchgear-A Utility’s
Viewpoint” Ontario Hydro 1980-81.
[3] “Procedure for Testing the Resistance of Metal-Clad Switchgear Under
Conditions of Arcing due to an Internal Fault” EEMAC G14-1, 1987.
[4] Michel G. Drouet, Francois Nadeau “Pressure Waves due to
Arcing Faults in a Substation” IEEE transactions on power
apparatus and systems, Vol. PAS-98, No 5, Sept/Oct 1979.
Page 11
8/2/2019 Cutler Hammer MV Metal-Clad Arc-Resistant Switch Gear
http://slidepdf.com/reader/full/cutler-hammer-mv-metal-clad-arc-resistant-switch-gear 12/12
ABOUT THE AUTHOR
Hugo Sulzer received the Engineering Technologist degree in
Electrical/Electronics from the Hamilton Institute of Technology in
Hamilton, Ontario, Canada. He is a Switchgear Application Specialist
working in the Cutler-Hammer Sales Department in Canada. Hugo is
also a national resource for applications with vacuum devices in
Canada and is an associate member of IEEE. Hugo has been involved
with the development of Arc Resistant Switchgear for Cutler-Hammer,
Canada from its early design to the present.
Cutler-Hammer Westinghouse &
Cutler-Hammer ProductsFive Parkway CenterPittsburgh, PA 15220
(412) 937-6100
SA-233
Printed in U.S.A.