Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
HIGH
CRAN
KING
AGM
FULL
THRO
TTLE
SERI
ES|
BATTERY & TERMINAL DIMENSIONS (All units shown in mm)
Terminal: AP
DISCHARGE PROFILE (Constant Current)12-Volt Battery Temperature: 77°F (25°C)
173A49.0A 36.0A
10.4A 5.8A 3.2A
- All listed ratings are @ 100% SoC, T=77°F (25°C), 1.75VPC unless otherwise specified.- Specifications listed are for estimation purposes only. Battery performance can vary depending on application. Battery design subject to change.
DISCHARGE TABLE (Constant Current)Time20hr
10hr
8hr
5hr
3hr
2hr
1hr
Amps3.2
5.8
7.0
10.4
16.5
21.5
36.0
Rate0.05 CA
0.10 CA
0.13 CA
0.25 CA
0.33 CA
0.50 CA
1.00 CA
35
ABS Plastic - Flame Res. Rating UL94-HB
MECHANICAL SPECIFICATIONSGroup Size
Terminal Type
8.64”Height (w/ terminal)
7.95”Height (case only)
6.84”Width
9.46”Length
49.2 lbsWeight
See reverse sideAP
220 mm202 mm173 mm240 mm22.3 kg
Terminal Torque
Case Type
240
186
202 22
0
169
53
12 Volt
ELECTRICAL SPECIFICATIONSNominal Voltage
70 AHC100
64 AHC20
52 AHC5
2480 AmpsShort Circuit Current
750 AmpsCCA900 AmpsCA or MCA
1400 AmpsPHCA
5.0 mΩ Internal Resistance
1:9
19.517
1:9
POSITIVE17.2
19.517
16NEGATIVENEGATIVE
19.1 17.9
RESERVE CAPACITYReserve @25 AMPS Reserve @75 AMPS120 Minutes 21 Minutes64 Amp Hours20 Hour Rate
CYCLING CAPACITY
fullriv
erbatt
ery.co
m
FT750-35
RESERVE CAPACITY
FT750-35FT750-35
9001:2008 Quality Management System14001:2004 Environmental Management System18001:2007 Occupational Health & Safety Management System
DELIVERY APPROVED!
LAND, SEA& AIR
Fullriver batteries are sealed lead acid batteries made with Absorbed Glass Mat (AGM) technology. The electrolyte is absorbed into the fiberglass separator material rather than in a free-flowing liquid form. Fullriver batteries are non-spillable electric storage batteries. They are excepted from the requirements of DOT’s hazardous materials regulations, since they adhere to the requirements of code 49 CFR Section 173.159(D) - (CLASSIFIED APPROVED: DOT, CFR, HMR49, IATA, ICAO67, IMDG27)
CERTIFIED
AP, DT (AP), M6, M6M (Stud), TP07 (AP) ,TP08 (AP)
FR45
M8
TERMINAL TORQUE SPECS
5.6 - 7.9
7.9 - 10.1
9.6 - 10.7
DT (Stud), M10M (Stud) 12.2 - 14
50-70
Nmin-lbsTerminal Type
70-90
85-95
110-125
4.2 - 6.0
ft-lbs
6.0 - 7.5
7.1 - 8.0
9.2 - 10.4
Bulk
Absorption
Float
CHARGE VOLTAGES
14.4 - 14.7V
12V
TC Factor: (-2mV°F/cell) or (-4mV°C/cell)
Charge Stage
Battery Voltages
14.4 - 14.7V
13.6V
28.8 - 29.4V
24V
28.8 - 29.4V
27.2V
43.2 - 44.1V
36V
43.2 - 44.1V
40.8V
57.6 - 58.8V
48V
57.6 - 58.8V
54.6V
Storage
Operation
Charge with TC
TEMPERATURE RANGE SPECIFICATIONS
Charge w/o TC*TC= Temperature Compensation
5°F to 122°F
RecommendedCondition
5°F to 104°F
5°F to 122°F
32°F to 104°F
-40°F to 160°F
Maximum
-40°F to 160°F
-40°F to 160°F
5°F to 122°F
-15°C to 50°C
Recommended
-15°C to 40°C
-15°C to 50°C
0°C to 40°C
-40°C to 71°C
Maximum
-40°C to 71°C
-40°C to 71°C
-15°C to 50°C
SELF DISCHARGE vs TIME/TEMPERATURE100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%0 2 4 6 8 10 12 14 16 18 20 22 24STORAGE PERIOD (MONTHS) Note: “Boost Charge” required @ 75% SoC, Max 50% Soc
Stat
e of
Cha
rge
(SoC
)
104°F (40°C) 86°F (30°C) 77°F (25°C)
CYCLE LIFE vs DEPTH of DISCHARGE (DOD)100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
DO
D
0 500LIFE CYCLES (per BCI)
1000 1500 2000 2500 3000
*(Based on BCI Testing @ 2-hr Rate)
STATE of CHARGE (SOC) vs OPEN CIRCUIT VOLTAGE (OCV)26.00
25.50
25.00
24.50
24.00
23.50
23.00
13.00
12.75
12.50
12.25
12.00
11.75
11.5010 20
State of Charge (SOC)
OCV
(12V
Bat
tery
) OCV (24V Battery)
30 40 50 60 70 90 10080
TEMPERATURE vs CAPACITY110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
TEMPERATURE °C (°F)
CAPA
CITY
%
-40 -20 0 20 40 60(-40) (-4) (32) (68) (104) (140)