TapSwitch Airfield SignsInstallation and Owner’s Manual
Pg 1
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
D
D-Lux Catalog / Item Numbers
Product Code
Sign BrandD ~ DLUX
Sign Size1 ~ Size 12 ~ Size 23 ~ Size 35 ~ Size 5
Sign Style2U ~ Style 23U ~ Style 3UL ~ Style UL (unlit)
Lamp TypeA ~ D13 T10 45W incandescent
Modules1 to 4 in length
Sign FacesSF ~ Single FaceDF ~ Double Face
All signs are Class 2, Mode 2
D X X A X X F
DPg 2
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
AGM Sign VA Loads and L830 Specifications
These ratings are subject to change without notice.
* - Use Y connecter to add wattages of two L830s to achieve correct power
Sign Size Style
Sign No.
of
Modules
L830
Transformer
Power
Factor VA Load
1 2 1 100 1.0 73
1 2 2 100 1.0 100
1 2 3 100 1.0 128
1 2 4 200 1.0 155
2 2 1 100 1.0 100
2 2 2 200 1.0 155
2 2 3 300 1.0 210
2 2 4 300 1.0 261
3 2 1 100 1.0 128
3 2 2 300 1.0 210
3 2 3 300 1.0 273
3 2 4 500 1.0 368
1 3 1 100 1.0 73
1 3 2 200 1.0 102
1 3 3 300 1.0 129
1 3 4 300 1.0 157
2 3 1 200 1.0 102
2 3 2 300 1.0 157
2 3 3 500 1.0 210
2 3 4 600 1.0 293
3 3 1 300 1.0 129
3 3 2 500 1.0 210
3 3 3 600* 1.0 312
3 3 4 1000* 1.0 390
DPg 3
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
D-Lux T-10 & TapSwitch
AGM signs are designed to provide years of trouble-free service. Prior to the performance of any work on the signs, power should be disconnected either at the vault or through use of the sign’s power switch (available option). An annual inspection and cleaning of the sign interior is recommended to maintain bright and even light output. Inspection of the signs should also include removal of any excess dirt, snow, or other detritus to maintain proper visibility of the sign legend.
Maintenance
1. Place the sign on the pad with the floor flanges perpendicular to the length of the sign.2. Mark mounting locations.3. Move the sign out of the way. 4. Drill mounting holes for anchor bolts.5. Install L-830 transformer into the base can.
Ÿ Check technical data sheet to make sure correct wattage is used.6. Secure cable clamp to transformer secondary lead or secondary extension cord.7. Reposition the sign on the pad and hold at an angle.8. Pull the power cord out of the leg of the sign, plug it into the transformer secondary lead or extension
cord.9. Rotate the sign to the upright position over the anchor holes being careful to not pinch the power cord. 10.Loosely clamp flanges to the pad.11.Loosen the pinch bolts in the slip flanges.12.Tighten the anchors on the floor flanges.13.Tighten the pinch bolts in the slip flanges against the couplings.14. Remove the protective plastic on the panels, being careful not to create FOD.15. When work is done on circuit verify operation between dusk and dawn.
If the signs are to be stored before installation and kept in the original cardboard for protection, they must be stored in a dry location. If the corrugated material becomes wet it should be removed and recycled as storage of the signs wrapped in wet cardboard can cause damage as a result of aggravated humidity. If the cardboard is removed keep the protective plastic on the legend panels until installation. This provides the last layer of protection in the absence of the corrugated packaging. Resulting damage from improper storage is not covered by warranty.
Storage
Installation
AGM D-Lux LED signs are shipped in a corrugated wrapping to protect against abrasion during shipping. The packaged signs are meant to be hand carried, (sling straps are effective), or placed on dolly carts. The packaged sign is NOT designed to be handled by forklifts. Installation issues are almost always traced back to an incorrect isolation transformer or potential damage occurring in shipping or storage
. **Make sure to note any damage that occurred in shipping when receiving the signs and be sure to document it with the carrier. When installing the sign make sure that the correct L830 isolation transformer is connected.
Handling
DPg 4
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
D-Lux Warranty
AGM L858(L) Airfield Guidance Signs are warranted against mechanical and physical defects in design or manufacture for a period of 2 years from date of shipment or installation per FAA AC 150/5345-44(applicable edition) and will correct such by repair or replacement, at its option, provided the signs have been properly handled and stored prior to installation, properly installed and operated after installation, and provided further that the Buyer has notified AGM in writing within the warranty period and a reasonable time after notice of such defects. Refer to handling, storage, installation and operational instructions for proper procedural guidance that must be followed to maintain warranty provisions. This warranty is in effect for the specified term as long as the L-858(L) equipment: has not been, in AGM's judgment, altered in such a way as to affect the equipment adversely, subject to accident, negligence, improper storage, and has been operated and maintained in accordance with accepted FAA guidelines as describe in AC 150/5340-26(applicable edition) and AGM's published operational guidelines.
AGM reserves the right to examine signs on which a claim has been made. Equipment must be presented in the same condition as when the defect was discovered. AGM also reserves the right to require the return of equipment to establish any claim.
Disclaimer:AGM's obligation under this warranty is limited to repair or replacement of defective equipment sold by AGM at no cost to Buyer. This does not include any other costs such as the cost of removal, shipping, or installation of the defective part or repaired product, including labor or any consequential damages of any kind. Warranty services provided under this agreement does not assure uninterrupted operations of L-858(L) equipment. AGM shall not be liable for any indirect or consequential damages.
AGM's liability under no circumstances will exceed its sales price of the signs claimed to be defective. All transportation costs under this warranty are the responsibility of the purchaser. Replacement parts and or equipment provided under this warranty are covered under the same terms until the expiration of the original warranty period that began upon the first installation of the equipment.
This is AGM's sole and exclusive warranty with respect to the L-858(L) equipment sold to the Buyer. There are no express or implied warranties of fitness for any particular purpose or any implied warranties other than those made expressly herein.
AGM shall not be liable to the purchaser of this product or third parties for indirect or consequential damages, or for damages arising from the use of any options or parts other than those designated by AGM as approved products. Damage caused by lightning, flood and other natural or man made causes are outside the scope of this warranty.
Warranty
DPg 5
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
D-Lux Dimensions
X
Y
Z
H
DC
BA
Size 1 Size 2 Size 3 Size 5
A 30 37.5 41.88 41.88
B 59 73.75 83.75 NA
C 88 110 125.6 NA
D 117 146.3 167.5 NA
X 7.75 9.125 10.5 10.5
Y 14.63 18.5 21 21
Z 13 14.63 15.88 15.88
H 26.5 32.75 38.5 38.5
Length Size 1 Size 2 Size 3 Size 5
A 45 60 90 90
B 90 120 180 NA
C 135 180 270 NA
D 180 240 360 NA
Dimension(in inches)
A: Length of one moduleB: Length of two modulesC: Length of three modulesD: Length of four modules
X: Length from end of sign tofirst frangible leg
Y: Length between frangible legsZ: Sign maximum widthH: Sign maximum height
SHIPPING WEIGHTS & DIMENSIONS
Add 1.5” to outer dimensions from the table above to generate carton size.
Weights to the left are in pounds. Signs are boxed and expected to be moved by hand from truck on dollies or hand carried preferably with slings.
DO NOT USE FORKLIFT TO LIFT SIGNS FROM BELOW!
DPg 6
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
D-Lux Floor Flange
DPg 7
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
AGM Tap Switch Board
Last Lamp
1st Lamp 5V System (Up to 12 x T10 Lamps) **LED Indicator located next to 6.6A is illuminated with all other steps. If the CCR is set to 6.6A step, no LEDs will be visible except operational status indicator D106.
February 13, 2013www.AGMsigns.com315.682.6707
DPg 8
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
Power Connection Pin - 2 Pin - 4
J8 Not usedAlways open
Failsafe In - Closed when used in single board designs- Used as communicationlink in multiple board signs.
LED indicator plugPins 1 & 2 - LED indicator* *(optional)
LampConnection Pins - 1 & 3
CCR Steps Jumper Setting
2 - 3 = 5 Step Open = 3 Step
J9Jumped or shorted underneath
Operational Status IndicatorFlashing LED indicates board isenergized and operational.
Coil Connection
CCR Tap RelaysLEDs next to each relay indicatewhat CCR step is selected**
J2 SCR Noise Adjustment Jumper Setting
2 - 3 = Optional Open = Normal
RESET OperationPins 3 & 4
Not Used
REVISIONS oftware or Hardware
Revision Ref. #
AGM Tap Switch Board (Prior to 9/14/12)
Last Lamp
1st Lamp 5V System (Up to 12 x T10 Lamps) **LED Indicator located next to 6.6A is illuminated with all other steps. If the CCR is set to 6.6A step, no LEDs will be visible except operational status indicator D106.
Power Connection Pin - 2 Pin - 4
J8Always open.
Failsafe In - Closed when used in single board designs- Used as communicationlink in multiple board signs.
LED indicator plugPins 1 & 2 - LED indicator* *(optional)
LampConnection Pins - 1 & 3
CCR Steps Jumper Setting
2 - 3 = 5 Step Open = 3 Step
Operational Status IndicatorFlashing LED indicates board isenergized and operational.
Coil Connection
CCR Tap RelaysLEDs next to each relay indicatewhat CCR step is selected**
DPg 9
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
COIL
Lampsout
common
sensetap out
in
6.6A5.5A5.2A4.8A4.1A3.4A2.8A
DPg 10
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
The 9 14 12 version of the TapSwitch is a trouble free component. That being said SCR CCR circuits can have electrical noise that can affect the operation of the TapSwitch. If a jumper is placed between pins 2 & 3 on J2, (”SCR Noise Adjustment, shown on page 8), this can in most cases correct that operation.
If the jumper solution above does not provide resolution, and for TapSwitch versions earlier than the 9 14 12, (7 7 09, 3 20 10, etc.) follow the procedure below;
If the TapSwitch continues not functioning properly you can disconnect the sense wire from the coil, cap it off with a wire nut, and try a jumper between the terminal where it used to connect and a less sensitive winding. This would be a winding that is beyond where the original sense wire connected to the coil usually up into the 4.8A to 6.6A winding connections.
Operational Adjustment
February 13, 2013www.AGMsigns.com315.682.6707
Face Components:
2. ç) Panel Joint4. D8-D#4*P Panel
* = Legend or BlankElectrical Components
C7-24A TapSwitch Control Board C7-CCA Transformer Coil D7-T10S Lamp Socket D7-T10L T-10 Lamp
D6-S#R (
(Not Pictured)
Body Components:1. D6-S Modular Connector3. D6-S#TP Top5. D6-S#EC End6. D6-S#LB Lamp Mounting Bar7. D6-S#B Bottom9. D6-DC# Frangible Coupling
D6-DTS Thumbscrew Fastener C9-DNP Name Plate
#TC
↓(Not Pictured)↓
Universal Components:8. C6-SF5 Slip Flange10. C6-FF235 Floor Flange C6-THR Sign Tether(Not Pictured)
1
2
3
4
5
6
7
8
9
10
D-Lux Sign Parts
To complete part number, replace ‘#’ with sign size (1,2,3 or 5), and ‘ç’ with color (Y,R,B)
DPg 11
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707
AGM Isolating Safety Switch with Cover(Optional Item C7-SWC)
The switch is a DPDT (double pole double throw) style switch. Two terminals are for power to the PCM, two terminals are power from the isolation transformer, and two are the short circuit path.
Isolation Transformer
short
Power Supplyfrom
Isolation Transformer
Power to Sign PCM
Catalog # C7-SWC
Catalog # C7-SWC
The AGM isolating safety switch allows the guidance sign power control & circuitry to be isolated from the airfield CCR circuit, providing a greater measure of safety when performing maintenance. This allows the rest of the airfield circuitry to remain illuminated to maintain necessary communication to pilots. The isolating safety switch is weatherproof with an IP67 rating and also includes a weatherproof cover that provides additional protection against mechanical damage.
DPg 12
AGMAirfield GuidancesignManufacturers, Inc.
108 Fairgrounds Drive • Suite 8 Manlius, NY 13104
Phone: 315-682-6707 Fax: 315-682-6758
www.agmsigns.com
•
•
Revision 2.2
February 13, 2013www.AGMsigns.com315.682.6707