Dallas County Community College District Purchasing Department 4343 IH-30 Mesquite, Texas 75150
August 23, 2017 ADDENDUM NO. 1 Bid No. 12407 Chiller Addition Brookhaven College Opening Date: August 29, 2017
2:00 p.m. Please take note that the above referenced Request for Bid is amended as follows: 1. Clarifications from the consultant are attached. There are no further changes/additions at this time. If there are any questions concerning this request for bid, please contact the Purchasing Department at 972/860-7771. END OF ADDENDUM
1616 Corporate Court, Suite 100 Irving, TX 75038 Phone 972-929-1199
ADDENDUM #1 NARRATIVE
Project Name: Brookhaven College Chiller AdditionProject No.: 16030Revision Date: 08/22/2017
Revision items: ME000, G101, DM200, M200
The specifications and drawings have been revised as follows:
SPECIFICATIONS:
Specification Section 23 64 16 – Centrifugal Chillers Deleted paragraph 2.14.B.2.c requiring factory performance testing at varying entering condenser water
temperatures. Deleted paragraph 2.14.B.2.d requiring Owner selected part load factory performance testing conditions. Deleted paragraph 2.14.B.3 requiring Owner and engineer access to factory performance testing.
DRAWINGS
ME000: Revised HVAC System Description to describe final system arrangement after completion of project. Removed Electrical section describing temporary electrical work.
DM200: Added Keyed Note 2 regarding temporary removal of existing standby generator exhaust flue. Added Keyed Note 3 regarding temporary removal of existing louver sections.
M200: Added Keyed Note 2 regarding re-installation of existing standby generator exhaust flue. Added Keyed Note 3 regarding re-installation of existing of louver sections. Added note regarding termination of new refrigerant relief piping (RR) above roof line.
END OF ADDENDUM #1
CENTRIFUGAL WATER CHILLERS 23 64 16 - 16BROOKHAVEN COLLEGE CHILLER ADDITION ADDEDNUM #1 08/22/17
a. Vane operated to actuate a double-pole, double-throw switch, with one pole field wired to the chiller control panel and the other pole field wired to the DDC system for HVAC.
b. Contacts: Platinum alloy, silver alloy, or gold-plated switch contacts with a rating of 10 A at 120-V ac.
c. Pressure rating equal to pressure rating of heat exchanger.d. Construct body and wetted parts of Type 316 stainless steel.e. House switch in a NEMA 250, Type 4 enclosure constructed of die-cast aluminum.f. Vane length to suit installation.
3. Pressure-Differential Switches:
a. Construction: Wetted parts of body and trim constructed of Type 316 stainless steel.
b. Performance: Switch shall withstand, without damage, the full-pressure rating of the heat exchanger applied to either port and exhibit zero set-point shift due to variation in working pressure.
c. Set Point: Screw type, field adjustable.d. Electrical Connections: Internally mounted screw-type terminal blocks.e. Switch Enclosure: NEMA 250, Type 4.f. Switch Action: Double-pole, double-throw switch, with one pole field wired to the
chiller control panel and the other pole field wired to the DDC system for HVAC.
B. Vibration Isolation:
1. Chiller manufacturer shall furnish vibration isolation for each chiller.2. Neoprene Pad:
a. Two layers of 0.375-inch-thick, ribbed- or waffle-pattern neoprene pads separated by a 16-gage, stainless-steel plate.
b. Fabricate pads from 40- to 50-durometer neoprene.c. Provide stainless-steel square bearing plate to load the pad uniformly between 20
and 40 psig with a 0.12- to 0.16-inch deflection.
2.14 SOURCE QUALITY CONTROL
A. Perform functional run tests of chillers before shipping.
B. Factory Performance Testing:
1. Factory performance test chillers, before shipping, according to AHRI 550/590.2. Test the following conditions:
a. Design conditions indicated.b. Reduction in capacity from design to minimum load in steps of 10 with condenser
fluid at design conditions.c. Reduction in capacity from design to minimum load in steps of 10 with varying
entering condenser-fluid temperature from design to minimum conditions in 5 deg F increments.
d. At five point(s) of varying part-load performance to be selected by Owner at time of test.
3. Allow Owner and Engineer access to place where chillers are being tested. Notify Owner in writing at least 14 days in advance of testing.
CODES:MECHANICAL: 2015 INTERNATIONAL MECHANICAL CODE*
ELECTRICAL: 2015 NATIONAL ELECTRIC CODE*PLUMBING: 2015 INTERNATIONAL PLUMBING CODE*
ENERGY: 2015 INTERNATIONAL ENERGY CONSERVATION CODE*
- WITH CITY OF FARMERS BRANCH AMENDMENTS
HVAC SYSTEM DESCRIPTION:AT THE COMPLETION OF THE PROJECT, THE CHILLED WATER SYSTEM WILL CONSIST OF THREE WATER-COOLED
CHILLERS (CH-1, CH-2, AND CH-3), THREE PRIMARY CHILLED WATER PUMPS (PCHP-1, PCHP-2, AND PCHP-3), AND TWO
SECONDARY CHILLED/HEATING WATER PUMPS. CH-1 IS A 700-TON CHILLER, CH-2 IS A 300-TON CHILLER, AND CH-3 IS A 400-TONCHILLER.
DOMESTIC COLD WATERPIPING
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATERRECIRCULATION PIPING
SANITARY VENT PIPING
COMPRESSED AIR PIPING
CONDENSATE DRAIN PIPING
CHEMICAL TREATMENT PIPING
CHILLED WATER RETURNPIPING
CHILLED WATER SUPPLYPIPING
CONDENSER WATER SUPPLYPIPING
CONDENSER WATER RETURNPIPING
DRINKING WATER PIPING
FIRE PROTECTION PIPING
FUEL OIL RETURN PIPING
FUEL OIL SUPPLY PIPING
FUEL OIL VENT PIPING
NATURAL GAS PIPING
GREASY WASTE PIPING
REFRIGERANT HOT GAS PIPING
HIGH PRESSURE STEAMCONDENSATE PIPING
HIGH PRESSURE STEAM PIPING
HEATING HOT WATER RETURNPIPING
HEATING HOT SUPPLY PIPING
LOW PRESSURE STEAMCONDENSATE PIPING
LOW PRESSURE STEAM PIPING
MAKE-UP WATER PIPING
OVERFLOW STORM DRAINPIPING
PUMPED COOLING COILCONDESATE DRAIN PIPING
PRIMARY CHILLED WATERRETURN PIPING
PRIMARY CHILLED WATERSUPPLY PIPING
PRIMARY HEATING HOT WATERRETURN PIPING
PRIMARY HEATING HOTSUPPLY WATER PIPING
REFRIGERANT LIQUID PIPING
REFRIGERANT RELIEF PIPING
REFRIGERANT SUCTION PIPING
SANITARY WASTE PIPING
SECONDARY CHILLED WATERRETURN PIPING
SECONDARY CHILLED WATERSUPPLY PIPING
SECONDARY HEATING HOTWATER RETURN PIPING
SECONDARY HEATING HOTWATER SUPPLY PIPING
STORM DRAIN PIPING
TEMPERED DOMESTIC WATERPIPING
CHANGE OF ELEVATION - RISE
(R) DROP (D)
EXISTING DUCT
EXISTING DUCT TO BEREMOVED
NEW DUCT
INDICATES DIRECTION OFAIRFLOW
DUCT TURNED UP, NEGATIVE
PRESSURE. FIRST FIGURE IS
TOP DIMENSION
DUCT TURNED UP, POSITIVE
PRESSURE. FIRST FIGURE IS
TOP DIMENSION
EXHAUST DUCT SECTION UP
RETURN DUCT SECTION UP
SUPPLY DUCT SECTION UP
EXHAUST DUCT SECTIONDOWN
RETURN DUCT SECTION DOWN
SUPPLY DUCT SECTION DOWN
BACKDRAFT DAMPER
HORIZONTAL FIRE DAMPER
VERTICAL FIRE DAMPER
HORIZONTAL FIRE/SMOKEDAMPER
VERTICAL FIRE/SMOKEDAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL SMOKE DAMPER
MANUAL VOLUME DAMPER
DUCT CAP
MOTORIZED DAMPER
CEILING DIFFUSER
CEILING EXHAUST/RETURNGRILLE
SIDEWALL GRILLE ORREGISTER
SLOT DIFFUSER OR GRILLE
CAP
PIPE TURNED DOWN
PIPE TURNED UP
PIPE ELBOW
PIPE CROSS
PIPE TEE
COMBINATION WYE ANDEIGHTH BEND
PIPE TEE BOTTOMCONNECTION
PIPE TEE UP
PIPE TEE TOP CONNECTON
PIPE FLANGE
PIPE UNION
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PIPE STRAINER
CLEANOUT PLUG
TRAP
AUTOMATIC BUTTERFLY VALVE
ANGLE VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
CALIBRATED BALANCINGVALVE
CHECK VALVE
GAS COCK
GATE VALVE
GLOBE VALVE
HOT TAP
NEEDLE VALVE
PLUG VALVE
PRESSURE REDUCING VALVE
PRESSURE REGULATOR
REGULATOR
PRESSURE RELIEF VALVE
SOLENOID VALVE
THERMOSTATIC MIXING VALVE
THREE WAY CONTROL VALVE
TWO WAY CONTROL VALVE
TAMPER SWITCH VAVLE
VALVE MOUNTED IN VERTICAL
TRAP PRIMER VALVE
WATER HAMMER ARRESTER
HOSE BIBB
P-TRAP
PENETRATION
CARBON DIOXIDE SENSOR
CONNECT NEW TO EXISTING
DIFFERENTIAL PRESSURESWITCH
FLOW METER
FLOW METER
FULL ENCIRCLEMENT TEE
HUMIDISTAT
HUMIDITY SENSOR
HYDROGEN SENSOR
PRESSURE GAUGE
PUMP
PUMP
ROUND
THERMOMETER
SPRINKLER HEAD
STATIC PRESSURE SENSOR
TEMPERATURE SENSOR
TEMPERATURE WELL
THERMOSTAT
VARIABLE FREQUENCY DRIVECONTROLLER
WATER HAMMER ARRESTER
DIFFUSER,
REGISTER,
GRILLE TAG
TERMINAL
UNIT TAG
CA
CD
CHEM
CHR
CHS
CR
CS
DW
F
FOR
FOS
FOV
GAS
GW
HG
HPC
HPS
HR
HS
LPC
LPS
MUW
OSD
PCD
PCHR
PCHS
PHR
PHS
RL
RR
RS
SAN
SCHR
SCHS
SHR
SHS
SD
TW
D
BDD
FD
FD
FSD
FSD
SD
SD
M
CO2
DPS
FM
H
HYD
SP
T
VFD
NECK SIZE20010"ØA
SCHEDULE DESIGNATION
AIR QUANTITY (CFM)
AIR QUANTITY (CFM)2000VAV-1 SCHEDULE DESIGNATION
REPRESENTS DEMO WORK
LOW VOLTAGE
CONDUIT
UNDERGROUND/UNDERFLOOR
CONDUIT
WIRE MOLD
HOMERUN
NEUTRAL CONDUCTOR
HOT CONDUCTOR
GROUND CONDUCTOR
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
ABOVE COUNTER DUPLEX
RECEPTACLE
QUADRAPLEX RECEPTACLE
MOUNT @ 44" A.F.F. U.N.O.
ABOVE COUNTER
QUADRAPLEX RECEPTACLEMOUNT @ 44" A.F.F. U.N.O.
SPECIAL PURPOSE
RECEPTACLE (VERIFY EXACTNEMA CONFIGURATION)
FLUSH FLOOR MOUNT DUPLEX
RECEPTACLE
CEILING MOUNTED DUPLEX
RECEPTACLE
FLOOR MOUNTEDQUADRAPLEX RECEPTACLE
CEILING MOUNTEDQUADRAPLEX RECEPTACLE
FLUSH FLOOR
DUPLEX/DATA/TELE OUTLET
FLUSH FLOORQUAD/DATA/TELE OUTLET
TRANSFORMER
208/120V ELECTRICAL PANEL
BOARD
480/277V ELECTRICAL PANEL
BOARD
I LINE PANEL BOARD
SWITCH BOARD
DATA COMMUNICATIONSOUTLET RUN 3/4" E.C. TO 6"
ABV. CLG.
TELEPHONE OUTLET RUN 3/4"
E.C. TO 6" ABV. CLG.
TELEPHONE / DATA OUTLET
RUN 3/4" E.C. TO 6" ABV. CLG.
FIREMAN'S TELEPHONE JACK
FLUSH FLOOR DATA OUTLET
FLUSH FLOOR TELEPHONE
OUTLET
FLUSH FLOOR TELE/DATA
OUTLET
CEILING MOUNTED DATA
OUTLET
CEILING MOUNTED TELEPHONE
OUTLET
CEILING MOUNTED TELE/DATA
OUTLET
PUSH-BUTTON
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION MOTOR
STARTER
VFD (VARIABLE FREQUENCY
DRIVE)
SPD (SURGE PROTECTIVE
DEVICE)
ENCLOSED CIRCUIT BREAKER
DISCONNECT
POWER POLE
MOTOR
JUNCTION BOX
WALL MOUNTED JUNCTION
BOX
J/BOX FOR VOICE/DATA
COMMUNICATIONS CABLE FORMODULAR FURNITURE SYSTEM.
RUN 1-1/4" E.C. W/PULL STRING
TO 6" ABOVE CEILING
J/BOX FOR POWER TO
MODULAR FURNITURE SYSTEM.
SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
MOTOR RATED SWITCH
TIMER SWITCH
DIMMER SWITCH
WALL MOUNTED OCCUPANCY
SENSOR
CEILING MOUNTED
OCCUPANCY SENSOR
BUZZER
GROUND ROD W/TEST WELL
SECURITY KEY PAD
KEY PAD
CARD READER SECURITY
SYSTEM CAM-LOCK DEVICE
DOOR CONTACT
MAGNETIC LOCK
MAGNETIC HOLD-OPEN DEVICE
PHOTOELECTRIC CELL
TIME CLOCK
INTERCOM
INTERCOM CALL MASTER
STATION
SQUARE D POWERLOGIC
CIRCUIT MONITOR
VESDA CONTROL PANEL
VEEDER ROOT
REMOTE FIRE ALARM
CONTROL PANEL
FIRE ALARM SYSTEM TAMPER
SWITCH
FIRE ALARM ANNUNCIATORPANEL
FIRE ALARM CONTROL PANEL
GENERATOR REMOTE ALARM
GENERATOR REMOTE
ANNUNCIATOR PANEL
GENERATOR
CLEAN AGENT RELEASE
CLEAN AGENT STORAGE
BOTTLE
AUDIO/VISUAL FIRE ALARM
DEVICE
CEILING FIRE ALARM DEVICE
FIRE STROBE
PULL STATION
METER
METER
KIRK-KEY INTERLOCK
VESDA
CEILING SPEAKER, NOTE: SUBSCRIPT 'F' DENOTES FIREALARM
WALL HUNG SPEAKER, NOTE:SUB SCRIPT 'F' DENOTES FIRE
ALARM SMOKE DETECTOR
UNDERFLOOR SMOKE
DETECTOR
DUCT MOUNTED SMOKE
DETECTOR
REMOTE PILOT LIGHT
HEAT DETECTOR
HEAT DETECTOR BELOW
FLOOR
FLAME DETECTOR
TELEVISION OUTLET MTD 96"
A.F.F. WITH 3/4" CONDUIT
CONNECTION TO OTHER
DEVICES, U.N.O.
2' X 4' FLUORESCENT -REFERENCE LIGHT FIXTURE
SCHEDULE
SAME AS 2' X 4' EXCEPT WITHEMERGENCY NICAD BATTERY
PACK
2' X 2' FLUORESCENT -REFERENCE LIGHT FIXTURE
SCHEDULE
SAME AS 2' X 2' EXCEPT WITHEMERGENCY NICAD BATTERY
PACK
FLUORESCENT STRIP -REFERENCE LIGHT FIXTURE
SCHEDULE
FLUORESCENT STRIP -EMERGENCY NICAD BATTERY
PACK
DOWNLIGHT - REFERENCE
LIGHT FIXTURE SCHEDULE
WALL WASHER - REFERENCE
LIGHT FIXTURE SCHEDULE
SAME AS DOWNLIGHT EXCEPTWITH EMERGENCY BATTERY
PACK
WALL MOUNTED LIGHTFIXTURE - REFERENCE LIGHT
FIXTURE SCHEDULE
LIGHT FIXTURE - REFERENCE
LIGHT FIXTURE SCHEDULE
LIGHT FIXTURE - REFERENCE
LIGHT FIXTURE SCHEDULE.
NOTE: REFERENCE PLANS FORNUMBER OF FIXTURE HEADS
SINGLE FACE EXIT SIGN -
SHADED AREA INDICATESILLUMINATED FACE -
REFERENCE LIGHT FIXTURE
SCHEDULE
DOUBLE FACE EXIT SIGN -
SHADED AREA INDICATESILLUMINATED FACE -
REFERENCE LIGHT FIXTURE
SCHEDULE
WALL MOUNTED EXIT SIGN -REFERENCE LIGHT FIXTURE
SCHEDULE
EMERGENCY LIGHTING
FIXTURE MK 'EM' U.N.O. -
REFERENCE LIGHT FIXTURESCHEDULE
DELTA CONNECTION
WYE-CONNECTION
CIRCUIT BREAKER
DISCONNECT/INTERRUPTER
SWITCH
FUSE
CAPACITOR
SERVICE WEATHERHEAD
GROUND CONNECTION
TRANSFORMER
CONTROL POWER
TRANSFORMER
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
CABLE POT HEAD
BUS DUCT
GROUND FAULT RELAY
FUSED CUTOUT
CONTACTOR, NORMALLY
CLOSED
CONTACTOR, NORMALLY OPEN
TRANSFER SWITCH
SWITCH
BATTERY
LIGHTNING ARRESTER
DRAWOUT CONNECTION
ELECTRIC RESISTANCEHEATER
GROUND BAR
CCTV CAMERA
VIA LIGHTING CONTACTOR
MEDIUM VOLTAGE CIRCUITBREAKER
TIME DELAY ANDINSTANTANEOUS
OVERCURRENT PROTECTIVERELAY
LV
F
3
4
M
T
D
OC
K
KP
CR
DC
ML
MH
PC
TC
IC
ICM
CM
VESDA
VR
RCP
TS
FAA
FACP
GEN
GAP
TV52
ABV ABOVE
ADAAMERICANS WITH DISABILITIES
ACT
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
AI ANALOG INPUT
AO ANALOG OUTPUT
APD AIR PRESSURE DROP
ASTABOVE GROUND STORAGETANK
BASBUILDING AUTOMATION
SYSTEM
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTER
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BOE BOTTOM OF EQUIPMENT
BTU BRITISH THERMAL UNIT
BTUHBRITISH THERMAL UNIT PER
HOUR
C CONDUIT
CA COMPRESSED AIR
CB CIRCUIT BREAKER
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CLG CEILING
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CO CLEANOUT
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CW DOMESTIC COLD WATER
CU COPPER
DB DRY BULB
DCO DOUBLE CLEANOUT
DI DIGITAL INPUT
DN DOWN
DO DIGITAL OUTPUT
DT DAY TANK
(E) EXISTING
EAGEXHAUST AIR
GRILLE/REGISTER
EAT ENTERING AIR TEMPERATURE
E.C. EMPTY CONDUIT
EFF EFFICIENCY
EPO EMERGENCY POWER OFF
ERVENERGY RECOVERY
VENTILATION
ESP EXTERNAL STATIC PRESSURE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWTENTERING WATERTEMPERATURE
EXH. EXHAUST
(F) FUTURE
ºF DEGREES FARENHEIT
FCO FLOOR CLEANOUT
FD FIRE DAMPER
FDCFIRE DEPARTMENT
CONNECTION
FDS FUSED DISCONNECT SWITCH
FLA FULL LOAD AMPS
FLD FLOOR DRAIN
FL FLOW LINE
FO FLAT OVAL DUCT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FP FIRE PROTECTION WATER
FPI FINS PER INCH
FPM FEET PER MINUTE
FSDCOMBINATION FIRE SMOKEDAMPER
FT FEET
FU FIXTURE UNITS
FV FACE VELOCITY
G GAS
GCO GRADE CLEANOUT
GE GENERAL EXHUAST
GFI GROUND FAULT INTERUPTER
GM GAS METER
GND GROUND
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRS GALVANIZED RIGID STEEL
GW GREASY WASTE
GWH GAS WATER HEATER
HB HOSE BIBB
HD HUB DRAIN
HG REFRIGERANT HOT GAS
HI HARDWIRE INTERLOCK
HP HORSEPOWER
HR HEATING HOT WATER RETURN
HS HEATING HOT WATER SUPPLY
HW DOMESTIC HOT WATER
HWCDOMESTIC HOT WATER
RECIRCULATION
HX HEAT EXCHANGER
IG ISOLATED GROUND
IWHINSTANTANEOUS WATERHEATER
IW INDIRECT WASTE
IWV INDIRECT WASTE VENT
KW KILOWATT
L LAVATORY
LAT LEAVING AIR TEMPERATURE
LE LAB EXHAUST
LBS POUNDS
MATVMASTER ANTENNA TELEVISION
SYSTEM
MB MOP BASIN
MBHTHOUSANDS OF BTUS PER
HOUR
MCA MINIMUM CIRCUIT AMPS
MFG MANUFACTURER
MOCPMAXIMUM OVERCURRENT
PROTECTION
MTD MOUNTED
(N) NEW
NC NOISE CRITERIA
NIC NOT IN CONTRACT
N3R NEMA 3R
O OXYGEN
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OCD OVERFLOW CONDENSATION
OCPDOVERCURRENT PROTECTIVE
DEVICE
OFCIOWNER FURNISHED
CONTRACTOR INSTALLED
OFD OVERFLOW ROOF DRAIN
OSD OVERFLOW STORM DRAIN
PBD PARALLEL BLADE DAMPER
PH PHASE
PP POWER POLE
PSI POUNDS PER SQUARE INCH
PSIGPOUNDS PER SQUARE INCH
(GAGE)
PVC POLYVINYL CHLORIDE PIPE
(R) RELOCATED
RA RETURN AIR
RABL RETURN AIR BOOT (L-SHAPED)
RABU RETURN AIR BOOT (U-SHAPED)
RAG RETURN AIR GRILLE/REGISTER
RD ROOF DRAIN
RL REFRIGERANT LIQUID
RPM REVOLUTIONS PER MINUTE
RPZ REDUCED PRESSURE ZONE
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
S SINK
SA SUPPLY AIR
SAG SUPPLY AIR GRILLE/REGISTER
SAN SANITARY SEWER
SD STORM DRAIN
SF SQUARE FEET
SMD SMOKE DAMPER
SP STATIC PRESSURE
SPD STATIC PRESSURE DROP
TPV TRAP PRIMER VALVE
TPD TOTAL PRESSURE DROP
TP TOTAL PRESSURE
TW DOMESTIC TEMPERED WATER
U URINAL
UF UNDERFLOOR
UG UNDERGROUND
U.N.O UNLESS NOTED OTHERWISE
V VENT
VAC VACUUM
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
W SANITARY WASTE
WB WET BULB
WC WATER CLOSET
WCO WALL CLEANOUT
WP WEATHER PROOF
WPD WATER PRESSURE DROP
WSHP WATER-SOURCE HEAT PUMP
" WC INCHES WATER COLUMN
" WG INCHES WATER GAUGE
WM WALL MOUNTED
XFMR TRANSFORMER
ABBREVIATIONS
MECHANICAL AND PLUMBING SYMBOLS
ELECTRICAL AND LIGHTING SYMBOLS
BASIS OF DESIGN
Sheet Title:
Sheet No.:
Issue Date:
Project Number:
DC
CC
D M
AIN
TE
NA
NC
E P
RO
JE
CT
S
FA
RM
ER
S B
RA
NC
H, T
EX
AS
BR
OO
KH
AV
EN
CO
LLE
GE
CH
ILLE
R A
DD
ITIO
N3939 V
ALLE
Y V
IEW
LA
NE
Date
08/22/17
Description
SUBMISSION LOG
16030
ME000
MECHANICAL/ELECTRICAL
ABBREVIATIONS AND
SYMBOLS
05/08/17
1
1
(E)34/16 SA
(E)2
6/14
SA
(E)1
4/14
SA
(E)AHU-NO. A-5
(E)CHP-1
(E)CHP-2
(E)24" CS
(E)12" CR
(E)12" CR
(E)1
0" B
YP
AS
S
(E)8
" C
R
(E)1
2" C
R
(E)1
6" C
S
(E)8" CS
(E)8" CS & CR
(E)CWP-3
(E)CWP-1
(E)10" CS & CR
(E)CWP-2
(E)8
" C
R
(E)8
" C
HR
/HR
(E)1
0" C
HR
/HR
(E)BOILER #2
(E)6" PCHR DN
TO (E)PCHP-3
(E)8
" C
HR
/HR
(E)6" DN TO
(E)PCHP-1
(E)8" CS
(E)8
" C
S
(E)1
0" C
HS
/HS
(E)8
" B
YP
AS
S
(E)CS SUMP
(E)8" CS
(E)1
0" C
HS
/HS
(E)1
0" C
HS
/HS
(E)8" CHS/HS
(E)BOILER #1
(E)8" PCHR DN
TO (E)PCHP-2
(E)6" PCHR
TO BOILERS FROM BOILERS
(E)10" CHR
(E)1
0" C
HR
/HR
(E)SEPARATOR
(E)8" BYPASS
(E)PCHP-1
(E)PCHP-2
(E)PCHP-3
(E)10" CHS/HS
(E)6" PCHS
(E)8
" C
HS
/HS
(E)16/14 EXH DN
(E)8" CHS/HS
(E)10" PCHR
(E)10" PCHS
(E)16/14 EXH
(E)10" HS
(E)1
0" C
HS
/HS
(E)18/24 EXH
(E)16/14 EXH
(E)10" CHS/HS
(E)10"
(E)EQUIPMENT PAD (TYPICAL)
FD
(E)26/20 EXH(E)26/20 EXH
(E)16/14 EXH DN
(E)EFCP-1
(E)1
4/14
SA
(E)SIDEWALL GRILLE
(E)14/6 SA
(E)14/14 SA
(E)6" CHR/HR
(E)6" CHS/HS
(E)6" PCHR
(E)GENERATOR
(E)CH-3
(400 TON)
(E)CH-1
(700 TON)
(E)CONTROL VALVE
(E)CONTROL
VALVE
1
(E)REFRIGERANT SENSOR
(E)REFRIGERANT SENSOR
(E)REFRIGERANT MONITORING PANEL
CENTRAL MECH PLANTA101
CORRIDORA103
TELEPHONE
EQUIP. RM.
A102
OFFICE
AREAWAY
TOILET
(E)8" CR
(E) 3" REFRIGERANT
RELIEF PIPING
HR
HS
(E)FM
2
3
3
Sheet Title:
Sheet No.:
Issue Date:
Project Number:
DC
CC
D M
AIN
TE
NA
NC
E P
RO
JE
CT
S
FA
RM
ER
S B
RA
NC
H, T
EX
AS
BR
OO
KH
AV
EN
CO
LLE
GE
CH
ILLE
R A
DD
ITIO
N3939 V
ALLE
Y V
IEW
LA
NE
Date
08/22/17
Description
SUBMISSION LOG
16030
KEY PLAN
RT
QMP
S
X
J K
CF
D
H
S
B AU
E
AREA OF WORK
DM200
PARTIAL BASEMENT
MECHANICAL DEMOLITION
PLAN
05/08/17SCALE: 1/4" = 1'-0"N
NORTH
01PARTIAL BASEMENT MECHANICAL DEMOLITION PLAN
KEY PLAN
RT
QMP
S
X
J K
CF
D
H
S
B AU
E
AREA OF WORK
REMOVE EXISTING PRIMARY CHILLED WATER PUMP
AND ASSOCIATED SUCTION AND DISCHARGE PIPING
BETWEEN ISOLATION VALVES AND PUMP.
PRIOR TO INSTALLATION OF NEW CHILLER ,
TEMPORARILY REMOVE EXISTING STANDBY
GENERATOR EXHAUST FLUE.
TEMPORARILY REMOVE NORTH AND CENTER SECTIONS
OF EXISTING LOUVER TO FACILITATE INSTALLATION OF
NEW CHILLER.
KEYED NOTES BY SYMBOL " "
11111
2
33333
1
1
1
8" CS 8" CR
6" PCHR
6" PCHS
CH-2
(300 TON)
02
M200
(E)34/16 SA
(E)2
6/14
SA
(E)1
4/14
SA
(E)AHU-NO. A-5
(E)CHP-1
(E)CHP-2
(E)24" CS
(E)12" CR
(E)12" CR
(E)1
0" B
YP
AS
S
(E)8
" C
R
(E)1
2" C
R
(E)1
6" C
S
(E)8" CS(E)CWP-3
(E)CWP-1
(E)10" CS & CR
(E)CWP-2
(E)8
" C
R
(E)8
" P
CH
R(E
)10"
PC
HR
(E)BOILER #2
(E)6" PCHR DN
TO (E)PCHP-3
(E)8
" P
CH
R
(E)6" DN TO
(N)PCHP-2
(E)8" CS
(E)8
" C
S
(E)1
0" P
CH
S
(E)CS SUMP
(E)8" CS
(E)8" PCHS
(E)BOILER #1
(E)8" PCHR DN
TO (E)PCHP-2
(E)6" PCHR
(E)SEPARATOR
(N)PCHP-2
(E)PCHP-1
(FORMERLY (E)PCHP-2)
(E)PCHP-3
(E)10" PCHS
(E)6" PCHS
(E)8
" P
CH
S
(E)16/14 EXH DN
(E)8" PCHS
(E)10" PCHR
(E)16/14 EXH
(E)10" HS
(E)18/24 EXH
(E)10"
(E)EQUIPMENT PAD (TYPICAL)
FD
(E)26/20 EXH(E)26/20 EXH
(E)16/14 EXH DN
(E)EFCP-1
(E)1
4/14
SA
(E)SIDEWALL GRILLE
(E)14/6 SA
(E)14/14 SA
(E)6" PCHR
(E)6" PCHS
(E)6" PCHR
(E)GENERATOR
(E)CH-3
(400 TON)
(E)CH-1
(700 TON)
(E)CONTROL VALVE
(E)CONTROL
VALVE
(E)REFRIGERANT SENSOR
(E)REFRIGERANT SENSOR
(E)REFRIGERANT MONITORING PANEL
CENTRAL MECH PLANTA101
CORRIDORA103
TELEPHONE
EQUIP. RM.
A102
OFFICE
AREAWAY
TOILET
(E)8" CR
(E)16/14 EXH
(E)3"
(E)3"
(E)3"
RR
RR
RR
RR
RR
RR
RR
3"(E)3"
(E)FM
(E)8
" B
YP
AS
S(E)1
0" C
HS
/HS
(E)1
0" C
HS
/HS
TO BOILERS FROM BOILERS
(E)10" CHR
(E)1
0" C
HR
/HR
(E)8" BYPASS
(E)10" PCHS
(E)10" HS
(E)1
0" C
HS
/HS
(E)10" CHS/HS
HR
HS
1
3" RR UP. TERMINATE
ABOVE ROOF LEVEL.
2
3
3
(E)8
" C
S
(E)8
" C
R
(E)6" CHR
(E)6" CHS
8" C
S
8" C
R
THERMOMETER (TYP.)
PRESSURE GAUGE (TYP.)
6" PCHS & PCHR
70" AFF CHR CONNECTION
78" AFF CHS CONNECTIONCHS & CHR CONNECTIONS
@ 77" AFF
CONTROL VALVE
(E)4" HOUSEKEEPING PADBASEMENT FLOOR SLAB
CH-2
NEOPRENE PAD (TYP.)
Sheet Title:
Sheet No.:
Issue Date:
Project Number:
DC
CC
D M
AIN
TE
NA
NC
E P
RO
JE
CT
S
FA
RM
ER
S B
RA
NC
H, T
EX
AS
BR
OO
KH
AV
EN
CO
LLE
GE
CH
ILLE
R A
DD
ITIO
N3939 V
ALLE
Y V
IEW
LA
NE
Date
08/22/17
Description
SUBMISSION LOG
16030
KEY PLAN
RT
QMP
S
X
J K
CF
D
H
S
B AU
E
AREA OF WORK
M200
PARTIAL BASEMENT
MECHANICAL PLAN
05/08/17SCALE: 1/4" = 1'-0"N
NORTH
01PARTIAL BASEMENT MECHANICAL PLAN
02SECTION AT CH-2SCALE: NONE
RENAME EXISTING PRIMARY CHILLED WATER PUMP
(FORMERLY PCHP-2) TO PCHP-1.
RE-INSTALL EXISTING GENERATOR EXHAUST FLUE
AFTER NEW CHILLER CH-2 HAS BEEN SET IN PLACE.
RE-INSTALL EXISTING LOUVER SECTION AFTER NEW
CHILLER CH-2 HAS BEEN SET IN PLACE.
KEYED NOTES BY SYMBOL " "
1
2
3
1
1
1