Technical Databook
Damper Actuators
Version 4
Belimo Asia Pacific
2 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Torque
General Damper Actuator40Nm G20Nm S10Nm N5Nm L2Nm C
General Damper Actuator M
Power Supply
AC/DC 24V 24AC 100...240V (AC 230 for Mechanical Fail-Safe Damper Actuator) 230
For customising types of Damper Actuators please contact your nearest Belimo sales representative.
New Generation General Damper Actuator for Asia Pacific
Damper Actuator standard type naming
Mechanical Fail-Safe Damper Actuator20Nm S10Nm N4Nm L2Nm T
Mechanical Fail-Safe Damper Actuator F
General Damper ActuatorOpen/Close, 3-point Open/Close (only for CMU230..)
Blank
Modulating DC 2(0)...10V Control -SR-RES
Auxiliary Switch -SForm fit -FTerminal Connection -T
Open/Close BlankModulating DC 2(0)...10V Control -SR
Auxiliary Switch -S, -S23-point -3
Mechanical Fail-Safe Damper Actuator
Product Naming L M U 24 -SR
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
3
Contents
The actuators listed in this catalogue are intended for theoperation of air dampers in HVAC systems. The Damper Actuator is not allowed to be used outside the specified field of application, especially in aircraft. The enclosure of the actuator equipment may only beopened by the manufacturer. It contains no componentswhich the user can replace or repair. The device contains electrical and electroniccomponents and is not allowed to be disposed of ashousehold refuse. All locally valid regulations andrequirements must be observed.
When calculating the torque required to operatedampers, it is essential to take into account all the datasupplied by the damper manufacturer concerning crosssectional area, design, mounting and air flow condition.
Note:
LMU24(-S/-F/-T)LMU24-SRLMU230(-S/-F)LMU230SR
NMU24(-S/-F/-T)NMU24-SRNMU230(-S/-F)NMU230SR
SMU24(-S/-F/-T)SMU24-SRSMU230(-S/-F)SMU230SR
GMU24GMU24-SRGMU230
Wiring diagramsAuxiliary switch adjustment
Mechanical accessories Replacement table (for Mechanical Fail-Safe Damper Actuators)
General Damper Actuator, 40Nm
LMQU24LMQU24-SR
Fast Running Damper Actuator, 4Nm
NMQU24NMQU24-SR
Fast Running Damper Actuator, 8Nm
SMQU24SMQU24-SR
Fast Running Damper Actuator, 16Nm
General Damper Actuator, 20Nm
General Damper Actuator, 10Nm
General Damper Actuator, 5Nm
Product overview
CMU24(-F8/-F10)(-T)CMU24-SR-RCMU230(-F8/-F10)CMU230(-F8/-F10)-RES
General Damper Actuator, 2Nm
Electrical accessories
Mechanical Fail-Safe Damper Actuator, 2Nm
Mechanical Fail-Safe Damper Actuator, 4Nm
Mechanical Fail-Safe Damper Actuator, 10Nm
TF24(-S)TF24-3TF24-SRTF230(-S)
LF24(-S)LF24-3LF24-SRLF230(-S)
NFUNFU-S2NFU24-SR
10111213
14151617
18192021
222324
56Mounting instructions 46
61
6365
2526
2728
2930
4
6789
62
31323334
TF230-SR 35
36373839
404142
Mechanical Fail-Safe Damper Actuator, 20Nm SFUSFU-S2SFU24-SR
434445
•
•
•
•
•
Using Belimo Damper Actuators:
Torque requirements:
4 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Damper Actuator product overview
General Damper Actuator
General Damper Actuator
Open/Close, 3-pointAC/DC 24V 50/60HzAuxiliary switch built-in 1 SPDT AC 100...240V 50/60HzAC 230V 50Hz (Open/Close)Auxiliary switch built-in 1 SPDT Modulating
AC/DC 24V 50/60HzControl signal DC 2(0)...10V, feedback DC 2...10V
AC 100...240V 50/60HzRunning time
Shaft diameterSound power level
Electrical connection Direction of rotationAngle of rotationPosition indicationDegree of protectionEMCAmbient temperatureNon-operation temperature
Cable 1m (-T: Terminal) Manual override Gear disengaging by pushbuttonGear disengaging by magnet
Selected by switchMax. 95°, can be limited at both ends with mechanical adjustable end stops
Mechanical, plug-onIP54 in any direction (-T: IP20)CE according to 89/336/EEC
-30...+50°C-40...+80°C
Humidity test 95% RH, non-condensing (to EN 60730-1)
* Only Open/Close, no 3-point.** CMU24-SR-R: Control signal 2(0)V at the right side, and the left side is available on request.
CMU..
2NmCMU24(-F8/-F10)(-T)
CMU230(-F8/-F10)CMU230(-F8/-F10)-RES*
CMU24-SR-R**
75s 150s6...12.7mmMax. 35dB(A)
LMU..
5NmLMU24(-F/-T)LMU24-S
LMU230
LMU230-S
LMU24-SR
LMU230SR
6...20mmMax. 35dB(A)
NMU..
10NmNMU24(-F/-T)NMU24-S
NMU230
NMU230-S
NMU24-SR
NMU230SR
8...26mmMax. 35dB(A)
SMU..
20NmSMU24(-F/-T)SMU24-S
SMU230
SMU230-S
SMU24-SR
SMU230SR
10...20mmMax. 48dB(A)
GMU..
40NmGMU24*
GMU230*
GMU24-SR
14...26mmMax. 48dB(A)
LMQU..
8…26.7mm
NMQU.. SMQU..
Open/Close
AC 24V 50/60Hz, DC 24V
Modulating
AC 24V 50/60Hz, DC 24V
Control signal DC 2(0)…10V, feedback signal DC 2…10V
Running time
Shaft diameter
Sound power level
Manual override
Electrical connection
Direction of rotation
Angle of rotation
Position indication
Degree of protection
EMC
Ambient temperature
Non-operation temperature
Humidity test
4Nm
LMQU24
LMQU24-SR
2.5s
8Nm
NMQU24
NMQU24-SR
4.0s
16Nm
SMQU24
SMQU24-SR
7.0s
12…25.5mmMax. 52dB(A)
Disengaging the gearing latch by means of a pushbutton, self-resetting
Cable 1m
Selected by switch
Max. 95°, can be limited at both ends with mechanical adjustable end stops
Mechanical, plug-on
IP54 in any direction
CE according to 2004/108/EC
-30…+40°C (without restrictions); +40…+50°C (with restrictions)
-40…+80°C
95% RH, non-condensing (to EN 60730-1)
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
5
Mechanical Fail-Safe Damper Actuator
Open/CloseAC/DC 24V 50/60HzAuxiliary switch built-in 1 SPDT
AC 230V 50/60HzAuxiliary switch built-in 1 SPDT 3-pointModulatingAC/DC 24V 50/60HzControl signal DC 2(0)...10V, feedback DC 2...10VRunning time -Motor -Spring return
Shaft diameterSound power level -Motor -Spring return
Electrical connection
Mechanical limiterPosition indicatorDegree of protectionEMCAmbient temperatureNon-operation temperature
Cable 1mSelected by mounting L/R
Max. 95°YESYES
IP54CE according to 89/336/EEC
* LF24-3 and all -SR types are 150s.
TF..
2NmTF24
TF24-STF230
TF230-S
TF24-3
TF24-SR
< 75s*< 25s
6...12mm
IP42
LF..4Nm
LF24-SLF24-SLF230
LF230-S
LF24-3*
LF24-SR
40-75s*~20s
8...16mmMax. 50dB(A)
62dB(A)
-30...+50°C
Humidity test 95% RH, non-condensing (to EN 60730-1)-40...+80°C
** TF24-3 nominal voltage is AC 24V, TF230 nominal voltage is AC 100...240V.
Damper Actuator product overview
Direction of rotationAngle of rotation
Machanical Fail-Safe Damper Actuator
Open/CloseAC 24...240V DC 24...125VAuxiliary switch built-in 2 SPDT
ModulatingAC/DC 24V 50/60HzControl signal DC 2(0)...10V, feedback DC 2...10VRunning time -Motor -Spring return
/Shaft diameter
Sound power level -Motor -Spring return
Electrical connection
Mechanical limiterPosition indicatorDegree of protectionEMCAmbient temperatureNon-operation temperature
Cable 1mSelected by mounting L/R
Max. 95°YESYESIP54
CE according to 2004/108/EEC
NFU..
10NmNFU
NFU-S2
NFU24-SR
Open/Close 75s; modulating 150s
10...12mm / 14...25.4mm
SFU..20NmSFU
SFU-S2
SFU24-SR
<20s
Open/Close Max. 50dB(A)/Modulating Max. 40dB(A) Open/Close Max. 50dB(A)/Modulating Max. 40dB(A)Max. 62dB(A)
-30...+50°C
Humidity test 95% RH, non-condensing (to EN 60730-1)-40...+80°C
Direction of rotationAngle of rotation
12 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
LMU230(-S/-F)
Technical data
Electrical data AC 100...240V 50/60HzNominal voltageNominal voltage rangePower consumptionWire/transformer sizingAuxiliary switch LMU230-S
Connection: MotorAuxiliary switch LMU230-S
TorqueDirection of rotationManual overrideAngle of rotationRunning timeSound power levelPosition indicationProtection classDegree of protection
EMCLow voltage directive
Mode of operationAmbient temperatureNon-operation temperatureHumidity testMaintenanceDimensions (LxWxH)
Shaft length: LMU230(-S)
Shaft : LMU230(-S)LMU230-F
Weight
AC 85...265V1.5W @ running / 0.5W @ holding
3.5VA
Cable 1m, 3x0.75mm2
Functional data 5NmSelectable by switch
Max. 95°, adjustable by mechanical stops150s for 95°Max. 35dB(A)Mechanical, remote visible
Working conditions II (totally insulated)IP54 in any direction
CE according to 89/336/EEC
Type 1 to EN 60730-1-30...+50°C
-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight See 'Dimensions'
8x8mm
Min. 37mmLMU230-F Min. 20mm
6...20mm
Approximately 550g
Dimensions [mm]
Cable 1m, 3x0.75mm2
1161620
74
16
8
22 94 41
28.5 100.5
0366
2.5
116
74
16
22 94 41
66
LMU230-FLMU230(-S)
1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
CE according to 73/23/EEC
Gearing latch disengaged by pushbutton, self-resetting
• For operation of air control dampers in HVAC system• Torque: 5Nm• Nominal voltage: AC 100...240V• Control: Open/Close or 3-point
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
13
LMU230SR
Technical data
Electrical data Nominal voltageNominal voltage rangePower consumption 2.0W @ running / 1W @ holdingWire/transformer sizing
Connection cable: Power supplyCable 1m, 4x0.75mm2
Functional data TorqueControl signalFeedback signalPosition accuracy Direction of rotation Selectable by switch
Angle of rotationRunning time 150s for 95°Sound power level Max. 35dB(A)Position indication
Working conditions Protection class II (totally insulated)Degree of protection
EMC CE according to 89/336/EEC
Mode of operationAmbient temperatureNon-operation temperatureHumidity test 95% RH, non-condensing (EN 60730-1)Maintenance
Dimensions / weight Dimensions (LxWxH) 179x66x60mmShaft lengthShaft 6...20mmWeight Approximately 700g
Signals
Low voltage directive CE according to 73/23/EEC
Dimensions [mm]
116
74
16
22 116 41
66
Gearing latch disengaged by pushbutton, self-resettingManual override
• For operation of air control dampers in HVAC system• Torque: 5Nm• Nominal voltage: AC 100...240V• Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
AC 100...240V 50/60HzAC 85...265V
4VA
Cable 1m, 2x0.75mm2
5Nm
DC 2(0)...10V (input impedance 100kΩ)DC 2...10V ±5%
Max. 95°, adjustable by mechanical stops
Mechanical, remote visible
IP54 in any direction
Type 1 to EN 60730-1
-30...+50°C-40...+80°C
Maintenance-free
Min. 37mm
14 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
NMU24(-S/-F/-T)
Technical data
Electrical data AC 24V 50/60Hz, DC 24V Nominal voltageNominal voltage rangePower consumptionWire/transformer sizingAuxiliary switch NMU24-S
Connection : Motor NMU24(-S/-F)Auxiliary switch NMU24-STerminals NMU24-TTorqueDirection of rotationManual overrideAngle of rotationRunning timeSound power levelPosition indicationProtection class
Degree of protection: NMU24(-S/-F)NMU24-T
Mode of operationEMC
Non-operation temperatureAmbient temperature
MaintenanceHumidity test
Shaft lengthDimensions (LxWxH)
NMU24-FWeight
Shaft: NMU24(-T/-S)
AC/DC 19.2...28.8V1.5W @ running / 0.2W @ holding3VA
Cable 1m, 3x0.75mm2
Functional data 10NmSelectable by switch
Max. 95°, adjustable by mechanical stops150s for 95°Max. 35dB(A)Mechanical, remote visible
Working conditions III (safety low voltage)
IP54 in any directionIP20
CE according to 89/336/EECType 1 to EN 60730-1-30...+50°C-40...+80°C
95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight See 'Dimensions'
8x8mm
Min. 40mm (20mm with K-NA for reverse mounting - optional)
8...26.7mm (8...20mm with K-NA)
Approximately 750g
Dimensions [mm]
Cable 1m, 3x0.75mm2
Max. 3x1.5mm2
1 SPDT, 1mA...3 (0.5)A, AC 250V , adjustable
124
06
26
25 99 41
08
NMU24(-S)
124
06
6.56
25 99
08
NMU24-T
12418 16
83
26
25 99 41
32 102
0308 2.5 8
NMU24-F
Gearing latch disengaged by pushbutton, self-resetting
• For operation of air control dampers in HVAC system• Torque: 10Nm• Nominal voltage: AC/DC 24V• Control: Open/Close or 3-point
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
15
Technical data
Nominal voltageNominal voltage rangePower consumptionWire/transformer sizingConnectionTorqueControl signal
Direction of rotation
Angle of rotation Max. 95°, adjustable by mechanical stopsRunning timeSound power levelPosition indicationProtection classDegree of protectionEMCMode of operationAmbient temperatureNon-operation temperatureHumidity testMaintenance
Electrical data
Functional data
Working conditions
Dimensions / weight Dimensions (LxWxH)Shaft lengthShaft 8...26.7mm (8...20mm with K-NA)Weight
Dimensions [mm]
124
06
26
25 99 41
08
Gearing latch disengaged by pushbutton, self-resettingManual override
NMU24-SR
• For operation of air control dampers in HVAC system• Torque: 10Nm• Nominal voltage: AC/DC 24V• Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
Feedback signal Position accuracy
AC 24V 50/60Hz, DC 24V AC/DC 19.2...28.8V2W @ running / 0.4W @ holding4VACable 1m, 4x0.75mm2
10NmDC 2(0)...10V (input impedance 100kΩ)
Selectable by switch
150s for 95°
Max. 35dB(A)Mechanical, remote visibleIII (safety low voltage)IP54 in any directionCE according to 89/336/EECType 1 to EN 60730-1
-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free165x80x62mmMin. 40mm (20mm with K-NA for reverse mounting - optional)
Approximately 800g
DC 2...10V ±5%
16 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
NMU230(-S/-F)
Technical data
Electrical data AC 100...240V 50/60Hz
AC 85...265V2.5W @ running / 0.6W @ holding
5.5VA
Cable 1m, 3x0.75mm2
Functional data 10Nm
Selectable by switch
Max. 95°, adjustable by mechanical stops
150s for 95°Max. 35dB(A)Mechanical, remote visible
Working conditionsIP54 in any directionCE according to 89/336/EEC
Type 1 to EN 60730-1-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight See 'Dimensions'
8x8mm
Min. 40mm (20mm with K-NA for reverse mounting - optional)8...26.7mm (8...20mm with K-NA)
Approximately 800g
Dimensions [mm]
Cable 1m, 3x0.75mm2
1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
124
06
26
25 99 41
08
NMU230(-S)
12418 16
83
26
25 99 41
32 102
0308 2.5 8
NMU230-F
II (totally insulated)
CE according to 73/23/EEC
Gearing latch disengaged by pushbutton, self-resetting
Nominal voltageNominal voltage range
Power consumption
Wire/transformer sizing
Auxiliary switch NMU230-S
Connection : Motor Auxiliary switch NMU230-S
Torque
Direction of rotationManual override
Angle of rotationRunning timeSound power levelPosition indicationProtection class
Degree of protection
Low voltage directiveEMC
Ambient temperatureMode of operation
Maintenance
Non-operation temperature
Humidity test
Shaft lengthDimensions (LxWxH)
NMU230-F
Weight
Shaft: NMU230(-S)
• For operation of air control dampers in HVAC system• Torque: 10Nm• Nominal voltage: AC 100...240V• Control: Open/Close or 3-point
DC2(0)...10V (input impedance 100kΩ)
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
17
NMU230SR
Technical data
Electrical data Nominal voltageNominal voltage rangePower consumptionWire/transformer sizing
Connection cable: Power supplyCable 1m, 4x0.75mm2
Functional data TorqueControl signal
Direction of rotation
Angle of rotationRunning timeSound power levelPosition indication
Working conditions Protection class II (totally insulated)Degree of protection
EMC
Mode of operationAmbient temperatureNon-operation temperatureHumidity testMaintenance
Dimensions / weight Dimensions (LxWxH)Shaft lengthShaft 8...26.7mm (8...20mm with K-NA)Weight Approximately 950g
For operation of air control dampers in HVAC systemTorque: 10NmNominal voltage: AC 100... 240VControl signal: DC 2(0)...10VPosition feedback: DC 2...10V
Signals
Low voltage directive
Dimensions [mm]
124
06
26
25 121 41
08
Gearing latch disengaged by pushbutton, self-resettingManual override
Feedback signalPosition accuracy
AC 100...240V 50/60HzAC 85...265V3.5W @ running / 1W @ holding6.5VA
Cable 1m, 2x0.75mm2
10Nm
Selectable by switch
Max. 95°, adjustable by mechanical stops150s for 95°Max. 35dB(A)Mechanical, remote visible
IP54 in any direction
CE according to 89/336/EEC
Type 1 to EN 60730-1-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)
Maintenance-free187x80x62mmMin. 40mm (20mm with K-NA for reverse mounting - optional)
CE according to 73/23/EEC
DC 2...10V ±5%
18 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
SMU24(-S/-F/-T)
Technical data
Electrical data AC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V2W @ running / 0.2W @ holding4VA
Cable 1m, 3x0.75mm2
Functional data 20NmSelectable by switch
Max. 95°, adjustable by mechanical stops
150s for 95°Max. 48dB(A)Mechanical, remote visible
Working conditions III (safety low voltage)
IP54 in any directionIP20CE according to 89/336/EEC
Type 1 to EN 60730-1-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight See 'Dimensions'
12x12mm
Min. 42mm (20mm for reverse mounting)
10...20mm
Approximately 1050g
Dimensions [mm]
Cable 1m, 3x0.75mm2
Terminals SMU24-T Max. 3x1.5mm2
1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
139
65
6.76
30 109
88
139
65
46
30 109 41
88
SMU24(-S) SMU24-TSMU24-F
10930
9723
4.28.8
57
Gearing latch disengaged by pushbutton, self-resetting
(10...26.7mm with K-ENSA - optional)
Nominal voltageNominal voltage rangePower consumption
Wire/transformer sizingAuxiliary switch SMU24-S
Connection : Motor Auxiliary switch SMU24-S
Direction of rotationTorque
Manual overrideAngle of rotationRunning timeSound power levelPosition indicationProtection class
Degree of protection: SMU24(-S/-F)SMU24-T
Ambient temperatureMode of operation
EMC
Maintenance
Weight
Non-operation temperatureHumidity test
Shaft lengthDimensions (LxWxH)
SMU24-F
Shaft: SMU24(-S)
• For operation of air control dampers in HVAC system• Torque: 20Nm• Nominal voltage: AC/DC 24V• Control: Open/Close or 3-point
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
19
SMU24-SR
Technical data
Electrical data Nominal voltageNominal voltage range
Power consumptionWire/transformer sizingConnection cable
Functional data TorqueControl signal
Direction of rotation
Angle of rotationRunning timeSound power levelPosition indication
Working conditions Protection classDegree of protectionEMCMode of operationAmbient temperatureNon-operation temperatureHumidity testMaintenance
Dimensions / weight Dimensions (LxWxH)Shaft lengthShaft
Weight
Dimensions [mm]
139
65
46
30 109 41
88
Manual override
• For operation of air control dampers in HVAC system• Torque: 20Nm• Nominal voltage: AC/DC 24V• Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
Feedback signalPosition accuracy
AC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V2W @ running / 0.4W @ holding4VACable 1m, 4x0.75mm2
20NmDC 2(0)...10V (input impedance 100kΩ)
Selectable by switch
Max. 95°, adjustable by mechanical stops
150s for 95°Max. 48dB(A)
Mechanical, remote visibleIII (safety low voltage)IP54 in any directionCE according to 89/336/EECType 1 to EN 60730-1-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free180x88x64mmMin. 42mm (20mm for reverse mounting)
10...20mm
Approximately 1050g
Gearing latch disengaged by pushbutton, self-resetting
(10...26.7mm with K-ENSA - optional)
DC 2...10V ±5%
20 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
SMU230(-S/-F)
Technical data
Electrical data AC 100...240V 50/60HzAC 85...265V2.5W @ running / 0.6W @ holding6VA
Cable 1m, 3x0.75mm2
Functional data 20NmSelectable by switch
Max. 95°, adjustable by mechanical stops150s for 95°Max. 48dB(A)Mechanical, remote visible
Working conditionsIP54 in any direction
CE according to 89/336/EEC
Type 1 to EN 60730-1-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight See ‘Dimensions’
12x12mm
Min. 42mm (20mm for reverse mounting)
10...20mm
Approximately 1050g
Dimensions [mm]
Cable 1m, 3x0.75mm2
139
65
46
30 109 41
88
1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
II (totally insulated)
CE according to 73/23/EEC
SMU230-F SMU230(-S)
10930
9723
4.28.8
57
Gearing latch disengaged by pushbutton, self-resetting
(10...26.7mm with K-ENSA - optional)
Nominal voltageNominal voltage rangePower consumptionWire/transformer sizingAuxiliary switch SMU230-SConnection : Motor
Auxiliary switch SMU230-S
TorqueDirection of rotationManual overrideAngle of rotationRunning timeSound power levelPosition indicationProtection classDegree of protection
EMCLow voltage directive
Ambient temperatureMode of operation
Maintenance
Non-operation temperatureHumidity test
Shaft lengthDimensions (LxWxH)
SMU230-F
Weight
Shaft: SMU230(-S)
• For operation of air control dampers in HVAC system• Torque: 20Nm• Nominal voltage: AC 100...240V• Control: Open/Close or 3-point
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
21
SMU230-SR
Technical data
Electrical data Nominal voltage
Nominal voltage range
Power consumptionWire/transformer sizingConnection cable: Power supply
Cable 1m, 4x0.75mm2
Functional data Torque20Nm
Control signal
Position accuracyDirection of rotation
Angle of rotationRunning timeSound power levelPosition indication
Working conditions Protection class II (totally insulated)Degree of protection
EMC
Mode of operationAmbient temperatureNon-operation temperatureHumidity testMaintenance
Dimensions / weight Dimensions (LxWxH)Shaft lengthShaft 10...20mm
Weight Approximately 1200g
Signals
Low voltage directive
Dimensions [mm]
139
65 46
30 131 41
88
Gearing latch disengaged by pushbutton, self-resettingManual override
(10...26.7mm with K-ENSA - optional)
• For operation of air control dampers in HVAC system• Torque: 20Nm• Nominal voltage: AC 100...240V• Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
Feedback signal
AC 100...240V 50/60HzAC 85...265V3.5W @ running / 1W @ holding6.5VA
Cable 1m, 2x0.75mm2
20NmDC 2(0)...10V (input impedance 100kΩ)
±5%Selectable by switch
Max. 95°, adjustable by mechanical stops 150s for 95°
Max. 48dB(A)Mechanical, remote visible
IP54 in any direction
CE according to 89/336/EEC
Type 1 to EN 60730-1
-30...+50°C-40...+80°C
95% RH, non-condensing (EN 60730-1)Maintenance-free202x88x64mm
Min. 42mm (20mm for reverse mounting)
CE according to 73/23/EEC
DC 2...10V
22 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
GMU24
Technical data
Electrical data AC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V4W @ running / 2W @ holding
6VACable 1m, 3x0.75mm2
Functional data 40NmSelectable by switch
Max. 95°, adjustable by mechanical stops
150s for 95°Max. 48dB(A)Mechanical, remote visible
Working conditions III (safety low voltage)
IP54 in any directionCE according to 89/336/EECType 1 to EN 60730-1-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight 220x116x70mmMin. 52mm (20mm for reverse mounting)
12...26.7mm/12...25.2mmApproximately 1700g
Dimensions [mm]
Gearing latch disengaged by pushbutton, self-resetting
Nominal voltageNominal voltage rangePower consumptionWire/transformer sizing
Connection cableTorque
Direction of rotationManual overrideAngle of rotationRunning timeSound power levelPosition indicationProtection classDegree of protection
EMC
Ambient temperatureMode of operation
Maintenance
Non-operation temperatureHumidity test
Shaft length
Dimensions (LxWxH)
WeightShaft
• For operation of air control dampers in HVAC system • Torque: 40Nm• Nominal voltage: AC/DC 24V• Control: Open/Close
6011
6
70
179
14336 41
Standard :
Length
>52>20
12...26.7 >12>1212...26.7 <25
<25
Damper spindle
12...22mm 12...18mm
22...26.7mm 12...18mm
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
23
GMU24-SR
Technical data
Electrical data Nominal voltageNominal voltage rangePower consumption 4.5W @ running / 2W @ holdingWire/transformer sizingConnection cable
Functional data TorqueControl signalFeedback signalPosition accuracyDirection of rotation
Angle of rotationRunning timeSound power levelPosition indication
Working conditions Protection classDegree of protectionEMCMode of operationAmbient temperature Non-operation temperatureHumidity testMaintenance
Dimensions / weight Dimensions (LxWxH)Shaft lengthShaft 12...26.7mm/12...25.2mmWeight
Dimensions [mm]
Gearing latch disengaged by pushbutton, self-resettingManual override
AC 24V 50/60Hz, DC 24VAC/DC 19.2...28.8V
6.5VA
Cable 1m, 4x0.75mm2
40Nm
DC 2(0)...10V (input impedance 100kΩ)DC 2...10V±5%Selectable by switch
Max. 95°, adjustable by mechanical stops150s for 95°
Max. 48dB(A)Mechanical, remote visibleIII (safety low voltage)IP54 in any directionCE according to 89/336/EEC
Type 1 to EN 60730-1-30...+50°C
-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free220x116x70mmMin. 52mm (20mm for reverse mounting)
Approximately 1700g
• For operation of air control dampers in HVAC system• Torque: 40Nm• Nominal voltage: AC/DC 24V• Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
6011
6
70
179
14336 41
Standard :
Length
>52>20
12...26.7 >12>1212...26.7 <25
<25
Damper spindle
12...22mm 12...18mm
22...26.7mm 12...18mm
24 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
GMU230
Technical data
Electrical data AC 100...240V 50/60HzAC 85...265V5W @ running / 2W @ holding
9VACable 1m, 3x0.75mm2
Functional data 40NmSelectable by switch
Max. 95°, adjustable by mechanical stops
150s for 95°
Max. 48dB(A)
Mechanical, remote visibleWorking conditions
IP54 in any direction
CE according to 89/336/EECCE according to 73/23/EEC
Type 1 to EN 60730-1-30...+50°C
-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight 220x116x70mmMin. 52mm (20mm for reverse mounting)
12...26.7mm/12...25.2mmApproximately 1700g
Dimensions [mm]
II (totally insulated)
Gearing latch disengaged by pushbutton, self-resetting
Nominal voltageNominal voltage rangePower consumptionWire/transformer sizingConnection cableTorqueDirection of rotationManual overrideAngle of rotationRunning timeSound power levelPosition indicationProtection classDegree of protection
EMCLow voltage directive
Ambient temperatureMode of operation
Maintenance
Non-operation temperatureHumidity test
Shaft lengthDimensions (LxWxH)
WeightShaft
• For operation of air control dampers in HVAC system• Torque: 40Nm• Nominal voltage: AC 100...240V• Control: Open/Close
6011
6
70
179
14336 41
Standard :
Length
>52>20
12...26.7 >12>1212...26.7 <25
<25
Damper spindle
12...22mm 12...18mm
22...26.7mm 12...18mm
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
25
LMQU24
Technical data
Electrical data AC 24V 50/60Hz, DC 24V
AC 19.2...28.8V / DC 21.6...28.8V
13W @ running / 1.5W @ holding
23VA (I max. 20A @ 5ms)
Cable 1m, 3x0.75mm2
Functional data Min. 4Nm @ nominal voltage
Reversible with switch 0 or 1
Gearing latch disengaged by pushbutton, self-resetting
Max. 95° adjustable mechanical end stops
2.5s for 90°
Manual triggering of the adaption by pressing the «Adaption» button
52dB(A)Mechanical, remote visible
! ≤ 50% from nominal torque (with restrictions)Working conditions III (safety extra-low voltage)
IP54 in any mounting position, UL/NEMA 2
CE according to 2004/108/EC
cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Type 1 (EN 60730-1)
–30...+40°C (without restrictions)! +40...+50°C (with restrictions)
–40...+80°C
95% RH, non-condensing (EN 60730-1)
Maintenance-free
Dimensions / weight
Nominal voltage
Nominal voltage range
Power consumption
Wire sizing
Connection
Torque (nominal torque)
Direction of rotation
Manual override
Angle of rotation
Running time
Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation
Sound power level
Position indication
Negative torque
Protection class
Degree of protection
EMC
Certification
Mode of operation
Ambient temperature
Non-operation temperature
Humidity test
Maintenance
Weight Approximately 850g
Dimensions [mm]
• For operation of air control dampers in HVAC system• Torque: 4Nm• Nominal voltage: AC/DC 24V• Control: Open/Close (not made for 3-point applications)
124
52
75
80
25 41121
Damper spindle Length
≥40 8...26.7 ≥8 ≤26.7
* ≥20 8...20 ≥8 ≤20
* Option (accessory K-NA)
Dimensions (LxWxH) 187x80x75mm
26 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
LMQU24-SR
Technical data
Electrical data Nominal voltageNominal voltage range AC 19.2...28.8V / DC 21.6...28.8VPower consumptionWire sizing
13W @ running / 1.5W @ holding23VA (I max. 20A @ 5ms)
Connection Cable 1m, 4x0.75mm2
Functional data Torque (nominal torque) Min. 4Nm @ nominal voltageControl signal DC 2(0)...10V, input impedance 100kΩFeedback signal DC 2...10V, max. 0.5mAPosition accuracy +5%Direction of rotation Reversible with switch 0/1
Manual override Gearing latch disengaged by pushbutton, self-resettingAngle of rotation Max. 95° adjustable mechanical stopsRunning time 2.5s for 90°Automatic adjustment of operatingrange and measuring signal U to matchthe mechanical angle of rotation
Manual triggering of the adaption by pressing the«Adaption» button
Override control MAX (maximum position)MIN (minimum position)ZS (intermediate position, only AC)
= 100%= 0%= 50%
Sound power level 52dB(A)Position indicationNegative torque
Mechanical, remote visible
! ≤50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage)
Degree of protection IP54 in any mounting position, UL/NEMA 2EMC CE according to 2004/108/ECMode of operation Type 1 to EN 60730-1
Certification cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Ambient temperature –30...+40°C (without restrictions)! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°CHumidity test 95% RH, non-condensing (EN 60730-1)Maintenance Maintenance-free
Dimensions / weightWeight Approximately 850g
Dimensions [mm]
• For operation of air control dampers in HVAC system• Torque: 4Nm• Nominal voltage: AC/DC 24V• Control modulating: DC 2(0)...10V• Position feedback: DC 2...10V
AC 24V 50/60Hz, DC 24V
124
52
75
80
25 41121
Damper spindle Length
≥40 8...26.7 ≥8 ≤26.7
* ≥20 8...20 ≥8 ≤20
* Option (accessory K-NA)
Direction of motion at Y = 0 V At switch position 0 resp. 1
Dimensions (LxWxH) 187x80x75mm
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
27
NMQU24
Technical data
Electrical data Nominal voltage
Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8VPower consumption
Wire sizing13W @ running /1.5W @ holding
23VA (I max. 20A @ 5ms)Connection Cable 1m, 3x0.75mm2
Functional data Torque (nominal torque) Min. 8Nm @ nominal voltage
Direction of rotation Reversible with switch 0 or 1
Manual override Gearing latch disengaged with pushbutton self-resetting
Angle of rotation Max. 95° adjustable mechanical end stops
Running time 4s for 90°
Automatic adjustment of operating range and measuring signal U to match the mechanical angle of rotation
Manual triggering of the adaption by pressing the «Adaption» button
Sound power level 52dB(A)
Position indication Mechanical, remote visible
Negative torque ! ≤ 50% from nominal torque (with restrictions)
Working conditions Protection class III Safety extra-low voltage
Degree of protection IP54 in any mounting position, UL/NEMA 2
EMC CE according to 2004/108/EC
Mode of operation Type 1 to EN 60730-1
Certification cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Ambient temperature –30...+40°C (without restrictions)! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weightWeight Approximately 970g
Dimensions [mm]
77
52
139
88
30 41131
Damper spindle Length
≥42 8...26.7 ≥8 ≤26.7
* ≥20 8...20 ≥8 ≤20
* Option (accessory K-SA)
• For operation of air control dampers in HVAC system• Torque: 8Nm• Nominal voltage: AC/DC 24V• Control: Open/Close (not made for 3-point applications)
AC 24V 50/60Hz, DC 24V
Dimensions (LxWxH) 202x88x77mm
28 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
NMQU24-SR
Technical data
Electrical data Nominal voltageNominal voltage range AC 19.2...28.8V / DC 21.6...28.8VPower consumptionWire sizing
13W @ running / 1.5W @ holding23VA (I max. 20A @ 5ms)
Connection Cable 1m, 4x0.75mm2
Functional data Torque (nominal torque) Min. 8Nm @ nominal voltageControl signal DC 2(0)...10V, input impedance 100kΩFeedback signal DC 2...10V, max. 0.5mA
Direction of rotation Reversible with switch 0/1Direction of motion at Y = 0 V At switch position 0 resp. 1 Manual override Gearing latch disengaged by pushbutton, self-resettingAngle of rotation Max. 95° adjustable mechanical stopsRunning time 4s for 90°Automatic adjustment of operating rangeand measuring signal U to match themechanical angle of rotation
Manual triggering of the adaption by pressing the«Adaption» button
Override control MAX (maximum position)MIN (minimum position)ZS (intermediate position, only AC)
= 100%= 0%= 50%
Sound power level 52dB(A)Position indication Mechanical, remote visibleNegative torque ! ≤50% from nominal torque (with restrictions)
Working conditions Protection class III (safety extra-low voltage)Degree of protection IP54 in any mounting position, UL/NEMA 2EMC CE according to 2004/108/ECMode of operation Type 1 to EN 60730-1
Certification cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Ambient temperature –30...+40°C (without restrictions)! +40...+50°C (with restrictions)
Non-operation temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)Maintenance Maintenance-free
Dimensions / weightWeight Approximately 970g
Position accuracy +5%
Dimensions [mm]
• For operation of air control dampers in HVAC system• Torque: 8Nm• Nominal voltage: AC/DC 24V• Control modulating: DC 2(0)...10V• Position feedback: DC 2...10V
AC 24V 50/60Hz, DC 24V
Dimensions (LxWxH) 202x88x77mm
77
52
139
88
30 41131
Damper spindle Length
≥42 8...26.7 ≥8 ≤26.7
* ≥20 8...20 ≥8 ≤20
* Option (accessory K-SA)
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
29
SMQU24
Technical data
Electrical data Nominal voltage
Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8VPower consumption
Wire sizing15W @ running /1.5W holding26VA (I max. 20A @ 5ms)
Connection Cable 1m, 3x0.75mm2
Functional data Torque (nominal torque) Min. 16Nm @ nominal voltageDirection of rotation Reversible with switch 0 resp. 1Manual override Gearing latch disengaged by pushbutton, self-resettingAngle of rotation Max. 95° adjustable mechanical end stopsRunning time 7s for 90°
Automatic adjustment of operating range to match the mechanical angle of rotation
Manual triggering of the adaption by pressing the «Adaption» button
Sound power level 52dB(A)Position indication Mechanical, remote visible
Negative torque ! ≤ 50% from nominal torque (with restrictions)Working conditions Protection class III (safety extra-low voltage / UL Class 2 supply)
Degree of protection IP54 in any mounting positionNEMA 2, UL Enclosure Type 2
EMC CE according to 2004/108/EC
Certification cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation Type 1 to EN 60730-1Ambient temperature –30...+40°C (without restrictions)
! +40...+50°C (with restrictions)
Non-operating temperature –40...+80°C
Humidity test 95% RH, non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 220x116x83mmWeight Approximately 1.7kg
Dimensions [mm]
83
62
179
116
36 41143
Damper spindle Length
≥52 12...26.7 ≥12 ≤25.5≥20 12...26.7 ≥12 ≤25.5
12...22mm 12...18mm
22...26.7mm 12...18mm
• For operation of air control dampers in HVAC system• Torque: 16Nm• Nominal voltage: AC/DC 24V• Control: Open/Close (not made for 3-point applications)
AC 24V 50/60Hz, DC 24V
Position feedback (Measuring voltage)
30 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
SMQU24-SR
Technical data
Electrical data Nominal voltageNominal voltage rangePower consumptionWire sizingConnection
Functional data Torque (nominal torque)Control signal Y
Direction of rotationDirection of motion at Y = 0 VManual overrideAngle of rotationRunning timeAutomatic adjustment of operating rangeand measuring signal U to match themechanical angle of rotation
Override control
Sound power levelPosition indicationNegative torque
Working conditions Protection classDegree of protection
EMCCertification
Mode of operationAmbient temperature
Non-operating temperatureHumidity testMaintenance
III
AC 24V 50/60Hz, DC 24VAC 19.2...28.8V / DC 21.6...28.8V15W @ running / 1.5W @ holding26VA (I max. 20A @ 5ms)Cable 1m, 4x0.75mm2
Min. 16Nm @ nominal voltageDC 2(0)...10V, input impedance 100kΩDC 2...10V, max. 0.5mA
Position accuracy +5%Reversible with switch 0/1At switch position 0 or 1Gearing latch disengaged by pushbutton, self-resettingMax. 95° adjustable mechanical end stops7s for 90°
Manual triggering of the adaption by pressing the«Adaption» button
MAX (maximum position)MIN (minimum position)ZS (intermediate position, only AC)
= 100%= 0%= 50%
52dB(A)Mechanical, remote visible
! ≤50% from nominal torque (with restrictions) (safety extra-low voltage / UL Class 2 supply)
IP54 in any mounting positionNEMA 2, UL Enclosure Type 2CE according to 2004/108/ECcULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14Type 1 (EN 60730-1)–30...+40°C (without restrictions)
! +50°C (with restrictions)–40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions [mm]
83
62
179
116
36 41143
Damper spindle Length
≥52 12...26.7 ≥12 ≤25.5≥20 12...26.7 ≥12 ≤25.5
12...22mm 12...18mm
22...26.7mm 12...18mm
• For operation of air control dampers in HVAC system• Torque: 16Nm• Nominal voltage: AC/DC 24V• Control modulating: DC 2(0)...10V• Position feedback: DC 2...10V
Dimensions / weight Dimensions (LxWxH) 220x116x83mmWeight Approximately 1.7kg
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
31
Technical data
Electrical data Nominal voltage
Power consumption
Power supply range
Wire/transformer sizing 5VA
Connection cable - MotorCable 1m, 3x0.75mm2
Functional data Torque - Motor2Nm
Direction of rotation Selectable by mounting L/R
Angle of rotation
Running time - Motor
Sound power level
75s25s @ -20...50°C / max. 60s @ -30°C
Position indication
Service lifeWorking conditions Protection class
Degree of protection
EMC
Mode of operation
Ambient temperature range
Non-operation temperature
Humidity test
Maintenance
Dimensions / weight Dimensions (LxWxH)
Shaft length Clamp down Clamp up Min. 84mm
Min. 20mm
Shaft diameter 6...12mm Weight Approximately 600g
- Spring return
- Spring return
Auxiliary switch TF24-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
- Auxiliary switch TF24-S
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator TF24(-S)
• For operation of air control dampers that perform safety function• Torque: 2Nm• Nominal voltage: AC/DC 24V• Control: Open/Close• Integrated auxiliary switch (TF24-S)
84
6...12
104
8420 36
61
77
176
AC 24V 50/60Hz, DC 24V
2.5W @ running / 1.5W @ holding
AC 19.2...28.8V, DC 21.6...28.8V
Cable 1m, 2x0.75mm2
2Nm @ nominal voltage
Max. 95°, 37...100% adjustable by mechanical stops
Motor max. 50dB(A), Spring approximately 62dB(A)
Mechanical
> 60,000 full cycles
III (safety extra-low voltage)
IP42 in any direction
CE according to 89/336/EEC
Type 1. AA to EN 60730-1
-30...+50°C
-40...+80°C95% RH, non-condensing (EN 60730-1)
Maintenance-free
140x77x84mm
32 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Technical data
Electrical data AC 24V 50/60Hz
2.5W @ running / 1W @ holding
AC 19.2...28.8V
4VA
Cable 1m, 4x0.75mm
Functional data 2Nm @ nominal voltage 2Nm
Selectable by mounting L/R
Max. 95°, 37...100% adjustable by mechanical stops
Motor max. 35dB(A), Spring approximately 62dB(A)
150s ( 0...2Nm)25s @ -20...50°C/max. 60s @ -30°C
Mechanical
> 60,000 full cycles
Working conditions III (safety extra-low voltage)
IP42 in any direction
CE according to 89/336/EEC
Type 1. AA to EN 60730-1
-30...+50°C
-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Dimensions / weight 140x77x84mm
Min. 84mmMin. 20mm
Approximately 600g
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator TF24-3
6...12mm
Nominal voltage
Nominal supply range
Power consumption
Wire/transformer sizing
Connection : Motor
Torque - Motor- Spring return
- Spring return
Direction of rotation
Angle of rotation
Running time - Motor
Sound power level
Position indication
Service life
Protection class
Degree of protection
EMC
Ambient temperature
Mode of operation
Maintenance
Non-operation temperature
Humidity test
Shaft length Clamp upClamp down
Dimensions (LxWxH)
Weight
Shaft diameter
• For operation of air control dampers that perform safety function• Torque: 2Nm• Nominal voltage: AC 24V• Control: 3-point
84
6117
6
77
20 84
104
6...12
36
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
33
Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption 2.5W @ running / 1W @ holding
Power supply range AC 19.2...28.8V, DC 21.6...28.8V
Wire/transformer sizing 4VA
Connection cable Cable 1m, 4x0.75mm2
Functional data Torque - Motor 2Nm @ nominal voltage 2Nm
Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
DC 2(0)...10V (input impedance 100kΩ)
Direction of rotation
Running time - Motor
Sound power level Motor max. 35dB(A), Spring approximately 62dB(A)
150s (0...2Nm)25s @ -20...50°C/max. 60s @ -30°C
Position indication MechanicalService life > 60,000 full cycles
Working conditions Protection class III (safety extra-low voltage)Degree of protection IP42 in any directionEMC CE according to 89/336/EECMode of operation Type 1.AA to EN 60730-1
Ambient temperature -30...+50°CNon-operation temperature -40...+80°CHumidity test 95% RH, non-condensing (EN 60730-1)Maintenance Maintenance-free
Dimensions / weight Dimensions (LxWxH) 140x77x84mmShaft length
Clamp down Clamp up Min. 84mm
Min. 20mmShaft diameterWeight Approximately 600g
- Spring return
- Spring return
Control signal
DC 2...10VFeedback signal
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator TF24-SR
6...12mm
• For operation of air control dampers that perform safety function• Torque: 2Nm• Nominal voltage: AC/DC 24V • Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
84
6...12
84
104
20 36
6117
6
77
Technical data
AC 100...240V 50/60HzAC 85...265V2.5W @ running / 1.5W @ holding5VA
Cable 1m, 2x0.75mm2
Cable 1m, 3x0.75mm2
2Nm @ nominal voltage 2NmSelectable by mounting L/R
Max. 95°, 37...100% adjustable by mechanical stops
Motor max. 50dB(A), Spring approximately 62dB(A)
75s25s @ -20...50°C/max. 60s @ -30°C
Mechanical> 60,000 full cyclesII (totally insulated)IP42 in any direction
CE according to 89/336/EECCE according to 73/23/EEC
Type 1. AA to EN 60730-1-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free
Electrical data
Functional data
Working conditions
Dimensions / weight 140x77x84mmMin. 84mmMin. 20mm
Approximately 600g
• For operation of air control dampers that perform safety function• Torque: 2Nm• Nominal voltage: AC 100...240V• Control: Open/Close• Integrated auxiliary switch (TF230-S)
1 SPDT, 1mA...3 (0.5)A, AC 250V , adjustable
Dimensions [mm]
6...12
166
71
48
104
8420 36
77
6...12mm
Nominal voltageNominal supply rangePower consumptionWire/transformer sizingAuxiliary switch TF230-S
Connection cable - Motor - Auxiliary switch TF230-S
Torque - Motor- Spring return
- Spring return
Direction of rotation - MotorAngle of rotation
Running time - Motor
Sound power levelPosition indicationService lifeProtection classDegree of protection
EMCLow voltage directive
Ambient temperatureMode of operation
Maintenance
Non-operation temperatureHumidity test
Shaft length Clamp upClamp down
Dimensions (LxWxH)
WeightShaft diameter
34 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Mechanical Fail-Safe Damper Actuator TF230(-S)
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
35
Technical data
Electrical data Nominal voltage
Power consumptionPower supply range
Wire/transformer sizing 5.5VAConnection power supply Cable 1m, 2x0.75mm2
Functional data Torque - Motor2Nm
Cable 1m, 3x0.75mm2
Selectable by mounting L/R
Angle of rotation
DC 2(0)...10V (input impedance 100kΩ)
Direction of rotation
Running time - Motor
Sound power level
150s (0...2Nm)25s @ -20...50°C/max. 60s @ -30°C
Position indicationService life
Working conditions Protection classDegree of protection
EMCLow-voltage directive CE according to 2006/95/EC
Mode of operationAmbient temperature rangeNon-operation temperatureHumidity testMaintenance
Dimensions / weight Dimensions (LxWxH)
Shaft lengthClamp downClamp up Min. 84mm
Min. 20mm
Shaft diameterWeight
- Spring return
- Spring return
Control signal
DC 2...10VFeedback signal
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator TF230-SR
6...12mm
• For operation of air control dampers that perform safety function• Torque: 2Nm• Nominal voltage: AC 100...240V • Control signal: DC 2(0)...10V• Position feedback: DC 2...10V
AC 100...240V 50/60Hz
2.5W @ running / 2W @ holdingAC 85...265V
2Nm @ nominal voltage
Max. 95°, 37...100% adjustable by mechanical stops
Motor max. 35dB(A), Spring approximately 62dB(A)Mechanical> 60,000 full cyclesII (totally insulated)IP42 in any direction
CE according to 2004/108/EEC
Type 1.AA to EN 60730-1
-30...+50°C-40...+80°C95% RH, non-condensing (EN 60730-1)Maintenance-free140x77x84mm
Approximately 630g
616
1784
104
8420 36
77
6...12
36 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Technical data
Electrical data Nominal voltage
Power consumption
Power supply range
Wire/transformer sizing 7VA
Connection cable - MotorCable 1m, 3x0.75mm2
Functional data Torque - Motor4Nm4Nm @ nominal voltage
Direction of rotation Selectable by mounting L/R
Angle of rotation Max. 95°, 37...100% adjustable by mechanical stops
Running time - Motor
Sound power level
40...75s (0...4Nm)Approximately 20s @ -20...50°C/max. 60s @ -30°C
Position indication
Service life
Working conditions Protection classDegree of protection IP54 in any directionEMC
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Humidity test
MaintenanceDimensions / weight Dimensions (LxWxH)
Shaft length Clamp down Clamp up Min. 84mm
Min. 20mmShaft diameter 8...16mmWeight
- Spring return
- Spring return
Auxiliary switch LF24-S 1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
- Auxiliary switch LF24-S
AC 24V 50/60Hz, DC 24V
5W @ running / 2.5W @ holding
AC 19.2...28.8V, DC 21.6...28.8V
Cable 1m, 2x0.75mm2
Motor max. 50dB(A), Spring approximately 62dB(A)
Mechanical
> 60,000 full cyclesIII (safety extra-low voltage)
CE according to 2004/108/EC
95% RH, non-condensing (EN 60730-1)
Maintenance-free181x98x82mm
Approximately 1400g
Dimensions [mm]
02.
4.6.8.1
181
155
12.6256.5
93
125
18
9849806.
518
.5
82 57
Mechanical Fail-Safe Damper Actuator LF24(-S)
• For the operation of air dampers that perform safety function• Torque: 4Nm• Nominal voltage: AC/DC 24V• Control: Open/Close• Integrated auxiliary switch (LF24-S)
8...16
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
39
Mechanical Fail-Safe Damper Actuator LF230(-S)
Technical data
Electrical data AC 230V 50/60HzAC 198...264V5W @ running / 3W @ holding
7VA
Cable 1m, 2x0.75mm2
Cable 1m, 3x0.75mm2
Functional data 4Nm @ nominal voltage4Nm
Selectable by mounting L/RMax. 95°, 37...100% adjustable by mechanical stops
Motor max. 50dB(A), Spring approximately 62dB(A)
40...75s (0...4Nm)Approximately 20s @ -20...50°C/max. 60s @ -30°C
Mechanical> 60,000 full cycles
Working conditions II (totally insulated)IP54 in any direction
CE according to 2004/108/ECCE according to 2006/95/EC
-30...+50°C
-40...+80°C95% RH, non-condensing (EN60730-1)Maintenance-free
Dimensions / weight 181x98x82mmMin. 84mmMin. 20mm
8...16mmApproximately 1550g
Dimensions [mm]
- Auxiliary switch LF230-S
1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable0
2.4.6.8.1
Nominal voltageNominal supply rangePower consumptionWire/transformer sizingAuxiliary switch LF230-S
Connection cable - Motor
Torque - Motor- Spring return
- Spring return
Direction of rotation Angle of rotation
Running time - Motor
Sound power level
Position indication
Service lifeProtection classDegree of protection
EMC
Ambient temperature
Low voltage directive
Maintenance
Non-operation temperature
Humidity test
Shaft length Clamp upClamp down
Dimensions (LxWxH)
WeightShaft diameter
• For the operation of air dampers that perform safety function• Torque: 4Nm• Nominal voltage: AC 230V• Control: Open/Close• Integrated auxiliary switch (LF230-S)
155
9318
6.512.625
82 5718
.56.
580 98
125
181
8...16
40 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Technical data
Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V
Power consumption In operation
For wire sizing 9.5VA
Nominal voltage range AC 19.2...264V, DC 20.4...126.5V
Functional data Torque - Motor Min. 10Nm @ nominal voltageMin. 10Nm
Direction of rotation Selectable by mounting L/R
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sidesby means of adjustable, mechanical end stops
Running time - Motor
Sound power level - Motor
< 75s (0...10Nm) < 20s @ -20...50°C/max. 60s @ -30°C
Max. 50dB(A)
Position indication Mechanical
Life time >60,000 full cycles Working conditions
Degree of protection IP54
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Maintenance Maintenance-free
Dimensions / weightWeight Approximately 2000gDimensions (LxWxH) 236x98x58mm
Dimensions [mm]
Humidity test 95% RH, non-condensing
Connection Cable 1m, 2x0.75mm2
Mechanical Fail-Safe Damper Actuator NFU
Protection class II (totally insulated)
EMC CE according to 2004/108/ECLow voltage directive
Control pollution degree
Rated Impulse Voltage
Mode of operation
3
4kv
Type 1.AA
CE according to 2006/95/EC
6.0W @ running/2.5W @ holding
- Spring return
- Spring return
~62dB(A)- Spring return
Damper actuator for operating air control dampers in ventilationand air-conditioning systems for building services installations
• Torque: 10Nm• Nominal voltage: AC 24...240V/DC 24...125V• Control: Open/Close
Standard :¾”- clamp (with insert)
Length≥85 10
10≥15
Optional 1: 1”- clamp (without insert)
Length≥85≥15
½”
Damper shaft Length≥85 10...19≥15 10...19
Damper shaft
Damper shaft
Optional 2: - clamp (optional via configuration)
5920
85
2-FRO
NT
32162172182236
9880
10...2210...22
19...25.419...25.4
12...18
14...2014...20
12...18
14...25.414...25.4
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
41
Technical data
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator NFU-S2
Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V
Power consumption
For wire sizing 9.5VA
Auxiliary switch 2x SPDT, 1mA...3(0.5)A, AC 250Vone fixed at 10%, one adjustable 10...90%
Nominal voltage range AC 19.2...264V, DC 20.4...126.5V
Functional data Torque - Motor Min. 10Nm @ nominal voltageMin. 10Nm
Direction of rotation Selectable by mounting L/R
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sidesby means of adjustable, mechanical end stops
Running time - Motor
Sound power level - Motor
< 75s (0...10Nm)
< 20s @ -20...50°C/max. 60s @ -30°C
Max. 50dB(A)
Position indication Mechanical
Life time >60,000 full cycles
Working conditionsDegree of protection IP54
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Maintenance Maintenance-free
Dimensions / weightWeight Approximately 2200g
Dimensions (LxWxH) 236x98x58mm
Humidity test 95% RH, non-condensing
Connection Cable 1m, 2x0.75mm2
Protection class II (totally insulated)
EMC CE according to 2004/108/ECLow voltage directive
Control pollution degree
Rated Impulse Voltage
Mode of operation
3
Supply: 4kVSwitch: 2.5kV
Type 1.AA
CE according to 2006/95/EC
6.0W @ running / 2.5W @ holding
- Spring return
- Spring return
~62dB(A)- Spring return
Damper actuator for operating air control dampers in ventilationand air-conditioning systems for building services installations
• Torque: 10Nm• Nominal voltage: AC 24...240V/DC 24...125V• Control: Open/Close • 2x SPDT auxiliary switches built-in
5920
85
2-FRO
NT
32 27162172182236
9880
Standard :¾”-clamp (with insert)
Length
≥85 10...22 14...25.4
19...25.4 12...18
12...1819...25.4
14...25.4101010...22≥15
≥15
≥15
Optional 1: 1”- clamp (without insert)
Length
≥85
½”
Damper shaft Length
≥85 10...1910...19 14...20
14...20
Damper shaft
Damper shaft
Optional 2: - clamp (optional via configuration)
42 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Technical data
Dimensions [mm]
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption in operation
For wire sizing 6.0VA
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Position feedback (Measuring voltage) DC 2...10V, max. 1mAPosition accuracy ±5%
Functional data Torque - Motor Min. 10Nm @ nominal voltageMin. 10Nm
Direction of rotation - Motor
Direction of rotation at Y=0V
Reversible with switch or
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sidesby means of adjustable, mechanical end stops
Running time - Motor
Sound power level - Motor
150s/90°< 20s @ -20...50°C/max. 60s @ -30°C
Max. 40dB(A)
Position indication MechanicalWorking conditions
Degree of protection IP54
Ambient temperature -30...+50°CNon-operation temperature -40...+80°C
Maintenance Maintenance-freeDimensions / weight
Weight Approximately 2000g
Dimensions (LxWxH) 236x98x58mm
Humidity test 95% RH, non-condensing (EN 60730-1)
Connection Cable 1m, 4x0.75mm2
Mechanical Fail-Safe Damper Actuator NFU24-SR
Protection class III (safety extra-low voltage)
EMC CE according to 2004/108/EC
Control pollution degree
Rated Impulse Voltage
Mode of operation
3
800V
Type 1.AA
3.5W @ running/2.5W @ holding
- Spring return
- Spring return Selectable by mounting L/R
Control Control signal Y DC 0...10V, typical input impedance 100KΩDC 2...10VWorking range
- Spring return
~62dB(A)- Spring return
Damper actuator for operating air control dampers in ventilationand air-conditioning systems for building services installations
• Torque: 10Nm• Nominal voltage: AC/DC 24V• Control: modulating DC 2(0)...10V
position feedback DC 2...10V
At switch position resp. 1
5920
85
2-FRO
NT
32162172182236
9880
Standard :¾”- clamp (with insert)
Length≥85 10
10≥15
Optional 1: 1”- clamp (without insert)
Length≥85≥15
½”
Damper shaft Length≥85 10...19≥15 10...19
Damper shaft
Damper shaft
Optional 2: - clamp (optional via configuration)
10...2210...22
19...25.419...25.4
12...18
14...2014...20
12...18
14...25.414...25.4
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
43
Technical data
Dimensions [mm]
Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V
Power consumption
Nominal voltage range AC 19.2...264V, DC 20.4...126.5V
Functional data Torque - Motor Min. 20Nm @ nominal voltageMin. 20Nm
Direction of rotation Selectable by mounting L/R
Manual override By manual override key
Angle of rotation Max. 95° , limited on both sidesby means of adjustable, mechanical end stops
Running time - Motor
Sound power level - Motor
Max. 75s (0...20Nm) Max. 20s @ -20...50°C/max. 60s @ -30°C
Max. 45dB(A)
Position indication Mechanical
Working conditionsDegree of protection IP54
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Maintenance Maintenance-free
Dimensions / weightWeight Approximately 2200g
Dimensions (LxWxH) 236x98x58mm
Humidity test 95% RH, non-condensing
Connection Cable 1m, 2x0.75mm2
Protection class II (Totally insulated)
EMC CE according to 2004/108/ECLow voltage directive
Control pollution degree
Rated Impulse Voltage
Mode of operation
3
4kv
Type 1.AA
CE according to 2006/95/EC
7.0W @ running / 3.5W @ holding
Wire/transformer sizing 7.0VA @ AC 24V8.5VA @ AC 120V18.0VA @ AC 240V
- Spring return
- Spring return
Max. 62dB(A)- Spring return
Mechanical Fail-Safe Damper Actuator SFU
Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations
• Torque: 20Nm• Nominal voltage: AC 24...240V
DC 24...125V• Control: Open/Close
5920
85
2-FRO
NT
32162172182236
9880
Standard :¾”-clamp (with insert)
Length
≥85≥15
≥15
≥15
10...22 101010...22 14...25.4
14...25.4
Optional 1: 1”- clamp (without insert)
Length
≥85
½”
Damper shaft Length
≥85 10...19 14...20
12...1819...25.4
19...25.4 12...18
14...2010...19
Damper shaft
Damper shaft
Optional 2: - clamp (optional via configuration)
44 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Technical data
Dimensions [mm]
Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V
Power consumption
Nominal voltage range AC 19.2...264V, DC 21.6...143V
Functional data Torque - Motor Min. 20Nm @ nominal voltageMin. 20Nm
Direction of rotation Selectable by mounting L/RManual override By manual override key
Angle of rotation Max. 95° , limited on both sidesby means of adjustable, mechanical end stops
Running time - Motor
Sound power level - Motor
Max. 75s (0...20Nm) Max. 20s @ -20...50°C/max. 60s @ -30°C
Max. 45dB(A)
Position indication MechanicalWorking conditions
Degree of protection IP54
Ambient temperature -30...+50°CNon-operation temperature -40...+80°C
Maintenance Maintenance-free
Dimensions / weightWeight Approximately 2400g
Dimensions (LxWxH) 236x98x58mm
Humidity test 95% RH, non-condensing
Connection - Motor Cable 1m, 2x0.75mm2
Cable 1m, 6x0.75mm2
Protection class II (totally insulated)
EMC CE according to 2004/108/ECLow voltage directive
Control pollution degree
Rated Impulse Voltage
Mode of operation
3Supply: 4kVSwitch: 2.5kV
Type 1.AA
CE according to 2006/95/EC
7.0W @ running / 3.5W @ holdingWire/transformer sizing 7.0VA @ AC 24V
Auxiliary switch 2X SPDT, 1mA...3(0.5)A, AC 250Von fixed at 10%, one adjustable 10...90%
8.5VA @ AC 120V18.0VA @ AC 240V
- Spring return
- Auxiliary switches
- Spring return
Max. 62dB(A)- Spring return
Mechanical Fail-Safe Damper Actuator SFU-S2
Damper actuator for operating air control dampers in ventilationand air-conditioning systems for building services installations
• Torque: 20Nm• Nominal voltage: AC 24...240V DC 24...125V• Control: Open/Close• 2x SPDT auxiliary switches built-in
5920
85
2F-RONT
32 27162172182236
9880
Standard :¾”-clamp (with insert)
Length
≥85≥15
≥15
≥15
10...22 101010...22 14...25.4
14...25.4
Optional 1: 1”- clamp (without insert)
Length
≥85
½”
Damper shaft Length
≥85 10...19 14...20
12...1819...25.4
19...25.4 12...18
14...2010...19
Damper shaft
Damper shaft
Optional 2: - clamp (optional via configuration)
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
45
Technical data
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator SFU24-SR
Modulating Mechanical Fail-Safe Actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings
• Torque: 20Nm • Nominal voltage: AC/DC 24V• Control Modulating: DC 2(0)...10V• Position feedback: DC 2...10V
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V
Power consumption
Nominal voltage range AC 19.2...28.8V, DC 21.6...28.8V
Functional data Torque - Motor Min. 20Nm @ nominal voltageMin. 20Nm
Direction of rotationSelectable by mounting L/RReversible with switch /
Manual override With hand crank and interlocking switch
Angle of rotation Max. 95° , can be limitedby means of adjustable, mechanical end stops
Running time - Motor
Sound power level - Motor
150s/90°Max. 20s @ -20...60°C/max. 60s @ -30°C
Max. 40dB(A) @ 150s running time
Position indication Mechanical
Working conditionsDegree of protection IP54
Ambient temperature -30...+50°C
Non-operation temperature -40...+80°C
Maintenance Maintenance-freeDimensions / weight
Weight Approximately 2200gDimensions (LxWxH) 236x98x58mm
Humidity test 95% RH, non-condensing
Connection Cable 1m, 4x0.75mm2
Protection class III (safety extra-low voltage)
EMC CE according to 2004/108/EC
Control pollution degree
Rated Impulse Voltage
Mode of operation
3
0.8kV
Type 1.AA
5.0W @ running / 3.5W @ holding
Wire/transformer sizing 7.0VA
Feedback signal
Control signal DC 2(0)...10V, input impedance 100kΩDC 2...10V, max. 0.5mA
Position accuracy ±5%
- Spring return
- Spring return
Max. 62dB(A)- Spring return
5920
85
2-FRO
NT
32162172182236
9880
Standard :¾”- clamp (with insert)
Length≥85 10
10≥15
Optional 1: 1”- clamp (without insert)
Length≥85≥15
½”
Damper shaft Length≥85 10...19≥15 10...19
Damper shaft
Damper shaft
Optional 2: - clamp (optional via configuration)
10...2210...22
19...25.4(26.7)
12...18
14...2014...20
12...18
14...25.414...25.4
570901 5
210
51
0354065709
01 5
60°120°
57 06 5403
51
09015
210
60750901 5
210
5403
15
0
6075
90
105
120
5403
75 06 5403
15
09015
102
6075091 50
102
5403
15
09150
120
6075
90
105
120
5403
09150
120
6075
90
105
120
5403
1
2
2.5°
2.5°
90°
75 60 5430
15
09150
210
60750901 5
120
4503
15
90015
210
0675
90
015
10
2
45 03
1
2
09015
120
6075
90
105
210
5403
8
57 06 4503
51
90150
102
09015
120
6075
09
105
120
5403
90150
210
6075
90
015
10
2
4503
6Nm
!
2 3
4
1
70 ± 20mm
mm23>
3.1...3.2mm
6...12.7mm
0
A
24V
max. 95°
75 60 5403
15
09150
102
6075091 50
102
5403
15
CMU24-SR..
46 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
CMU.. mounting instructions
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
47
LMU../LMS.. mounting instructions
21
6...20 > 6 < 20
1
1
2
36 Nm
mm1
018
4
65°
5
Z-PI
12
> 73
48 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
NMU../NMS.. mounting instructions
40
8...26
10...26
1
1
1
2
3
1mm
10
9Nm
10
4
65°
5
Z-PI
2
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
49
SMU../SMS.. mounting instructions
48
10...20
10...20
1 2
1
1
2
3 9Nm
1mm
1010
4
65°
5
Z-PI
50 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
GMU../GMS.. mounting instructions
1 2
2
1
1
3
4
65°
2
1
Z-PI
5
2> 0 1
2
3
4
5
12
mm1
31
15Nm
2
1
1
2
1
12...22 mm 12...18 mm
22...26.7 mm 12...18 mm
25>
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
51
LMQU24../NMQU24.. mounting instructions
1 2
2
1
1
3
4
65°
2
1
Z-PI
5
2> 0 1
2
3
4
5
12
mm1
31
15Nm
2
1
1
2
1
12...22mm 12...18mm
22...26.7mm 12...18mm
25>
52 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
SMQU24.. mounting instructions
1 2
2
1
1
3
4
65°
2
1
Z-PI
5
2> 0 1
2
3
4
5
12
mm1
31
15Nm
2
1
1
2
1
12...22mm 12...18mm
22...26.7mm 12...18mm
25>
Sub
ject
to
tech
nica
l cha
nges
.
53
TF.. mounting instructions
6...12.7
min. 84
1
LL
2
R
R
3
37...100%
4
ZG-TF1
max 1 Nm
L
54 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
TF../LF.. mounting instructions
min. 20
6...12.7
1
L
ZDB-TF
2
R
ZDB-TFR
3
37...100%
4
L
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
55
NFU../SFU.. mounting instructions
min. 8510...21
21...26
min. 1510...21
21...26
10 Nm13
A B
33...100%
.2.4.6
.8.9.8.7
.6.5
.4.3 .2 .1
56 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Open/Close control 3-point control
0
-
T
+
~
-
T
+
~
-
T
+
~
1 2 3 1 2 3
AC/DC 24V AC/DC 24V
CMU24(-T)CMU24-F8(-F10)
CMU24(-T)CMU24-F8(-F10)
Open/Close control 3-point control
1 2 32 3
0
1
AC 100...240V
CMU230CMU230-F8(-F10)
N L AC 100...240V N L
CMU230CMU230-F8(-F10)
Open/Close control
1 2 3
AC 230V
CMU230-RESCMU230-F8 (-F10)-RES
N L
Modulating
DC 2(0)…10V
DC 2…1V
YCMU24-SR-R
5321
U
AC/DC 24V
-
T ~
+
Y
U
OGWHRDBK
Wiring diagrams : CMU.. series actuators
Connection via safetyisolated transformer
Connection via safetyisolated transformer
Connection via safetyisolated transformer
Connection via safetyisolated transformer
Notes:• Parallel connection of several actuators is possible.• Power consumption must be observed.
!
!
!
!
Wiring diagrams — General Damper Actuator
LMU24(-T/-F), NMU24(-T/-F)SMU24(-T/-F), GMU24*
LMU24(-T/-F), NMU24(-T/-F)SMU24(-T/-F), GMU24LMQU24, NMQU24, SMQU24
1 2 3
0...100%
S1 S2 S3
0...100%
0
S1 S2 S31
0
S1 S2 S31
0
S1 S2 S31
0
S1 S2 S31
0
S1 S2 S31
0
S1 S2 S31
0
S1 S2 S31
0
S1 S2 S31
0
Direction of rotation
Direction of rotationDirection of rotation
1
0
LMU24-S, NMU24-SSMU24-S
LMU24-S, NMU24-SSMU24-S
LMU230(-F), NMU230(-F)SMU230(-F), GMU230*
LMU230(-F), NMU230(-F)SMU230(-F), GMU230
1-wire control 2-wire control
1 2 3
0...100%
S1 S2 S3
N L1
1 2 3
1 2 3
0...100%
S1 S2 S3
0
N L1
LMU230-S, NMU230-SSMU230-S
LMU230-S, NMU230-SSMU230-S
anti-clockwise-closingdamper
100
0 Y [ V ] 10 0
% of 95°
50
2 5
Closed
Reversingswitch 1Y = 0
Reversingswitch 0Y = 0
OpenOpen
Closed
clockwise-closingdamper
AC/DC 24VAC/DC 24V
AC 100...240V
Y DC 2(0)…10V
U DC 2…10V
Y
1 2 1 2 3
LMU230SR, NMU230SRSMU230SR
5
U
T ~
N L1
Measuring voltage Ufor position indicatingor as master-slavecontrol signal.
AC 100...240V
AC 24V power output
AC 100...240V
Wiring diagrams: Open/Close actuators—Parallel connection possible, please note the performance data
Wiring diagram: Modulating actuators—Parallel connection possible, please note the performance data
Position - signal voltage
Connection via safetyisolated transformer
Y DC 2(0)…10V
U DC 2…10V
Measuring voltage Ufor position indicatingor as master-slavecontrol signal.
Y LMU24-SR, NMU24-SR SMU24-SR, GMU24-SRLMQU24-SR, NMQU24-SR, SMQU24-SR
51 2 3
U
AC/DC 24V
-
T ~
+
Connection via safetyisolated transformer
Connection via safetyisolated transformer
(while direction of rotation reverses)
1
0
1
0
1
0
(while direction of rotation reverses)
1
0
*GMU.. only for Open/Close application
!
!
!
-
T
+
~
-
T
+
~
-
T
+
~
Wiring diagrams—General Damper ActuatorV
4. 1
2. 2
010
. Sub
ject
to
mod
ifica
tion
57
58 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Wiring diagrams: Open/Close actuators
NFU-S2, SFU-S2
NFU, SFU
AC/DC 24V AC/DC 24V
1 2 S1 S2 S3 1 2 S1 S2 S3
TF230-S, TF24-SM
TF230, TF24M
AC 100...240V (for TF230..)N L1
> x
< xx = 0...100%
AC 24...240VDC 24...125V
N L1
LF230-S, LF24-SM
LF230, LF24M
AC 230V (for LF230..)N L1
> x
< xx = 0...100%
Connect via safetyisolating transformer Connect via safety
isolating transformer
Notes:• Parallel connection of several actuators is possible.• Power consumption must be observed.
Wiring diagrams—Mechanical Fail-Safe Damper Actuator
! !
1 2
M
S1 S2 S3 S4 S5 S6
10% 10%...90% adjustable
M
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
59
Wiring diagrams: 3-point actuators
~T
~TAC 24V
1 32 4
Y1 Y2
a b
L0
.2
.4
.6
.8
1
R0
.2
.4
.6
.8
1
a(Y 1)
b(Y 2)
Mounting side
Reversing switch
stop stop stop stop
LF24-3, NFS24-3, SF24-3
AC/DC 24V
stop stop stop stop
a b(Y1) (Y2) R L R L
Reversing switch
Mounting side
TF24-3
Wiring diagrams—Mechanical Fail-Safe Damper Actuator
Connect via safetyisolating transformer
Connect via safetyisolating transformer
Notes:• Connection via safety isolating transformer.• Parallel connection of several actuators is possible.• Power consumption must be observed.
!
!
60 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Wiring diagram: Modulating actuators
AC/DC 24V
AC/DC 24V
Y DC 2(0)...10V
U DC 2...10V
LF24-SR, NFU24-SR, SFU24-SR
L0
.2
.4
.6
.8
1
R0
.2
.4
.6
.8
1
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
withY = 0
R L
Reversing switch
R L
Mounting side
YU
1 32 5
DC 2(0)…1VDC 2…10V
– +
T
T
~
– +
T ~
L0
.2
.4
.6
.8
1
R0
.2
.4
.6
.8
1
Mounting side
Reversing switch
TF24-SR
TF230-SR
Connect via safetyisolating transformer
Connect via safetyisolating transformer
Notes:• Connection via safety isolating transformer.• Parallel connection of several actuators is possible.• Power consumption must be observed.
!
!
Connect via safetyisolating transformer!
N
1 2
L
M
1 3 5
YU
DC 2(0)…10V DC 2…10V
Mounting side
Reversing switch
Wiring diagrams—Mechanical Fail-Safe Damper Actuator
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
61
Starting point: Actuator in safe position
ProcedureTurn the knob of the auxiliary switch until the tip of the arrow is pointing to the required switching position (see right). Example: Switching point setting = 4 corresponds to 40% angle of rotation.
When the actuator runs to the operating position (ccw ), the switch knob will also rotate counter-clockwise (ccw ) and the auxiliary switch will operate as the tip of the arrow passes the scale zero (S1–S3 linked).
Auxiliary switch adjustment
Auxiliary switch adjustment for General Damper Actuators
1
1
2
S1
S2 S3
S1
S2 S3
1
0.2
.4
.6.8
S1S2
S3
S1S2
S30.2
.4
.6
.8
1
R
Auxiliary switch adjustment for Mechanical Fail-Safe Damper Actuators
1. Press the pushbutton, manually operate the universal clamp to desired switch position.
2. Turn switch pointer to the middle line.
3. When actuator moves clockwise (counter clockwise) to switch position, switch indicator passes the middle line counter clockwise (clockwise), the contact between S1 and S3 is disconnected (connected) and the contact between S1 and S2 is connected (disconnected).
Note: The switching point should be about 5° from the mechanical end stops (1 short step on the scale).
Fast Running Q.. Actuators operating controls and indicators
LF..-S (Mounting side R); NFU-S2, SFU-S2 (Mounting side L)
62 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Electrical accessories
S..A..
P..A..
SGA24
SGE24
SGF24
ZAD24
Auxiliary switch, add-onS1A 1x SPDT 3A(0.5A), AC 250VS2A 2x SPDT 3A(0.5A), AC 250VS2A-F 2x SPDT 3A(0.5A), AC 250V
Feedback potentiometer, add-onP140A..P500A..P1000A..P2800A..P5000A..P10000A..P200A-F
140Ω500Ω
1000Ω2800Ω5000Ω
10000Ω200Ω
1) For ..-SR
Spindle clamp for LF...For damper spindles 16...20mm
Shaft extensionLength approximately 170mmFor damper spindles 6...20mmExtension 10mm
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
63
Mechanical accessories
NMUNMQULMQU
SMUSMQU
Shaft extensionLength approximately 250mmFor damper spindles 8...25mmExtension 20mm
Spindle clampFor damper spindles 8...20mm
Reversible spindle clampFor damper spindles 8...20mm
Reversible spindle clampFor damper spindles 10...20mm
Ball jointSuitable for damper crank arm KH8For round steel rod with 8mmZinc-plated steel
Ball jointSuitable for damper crank arm KH8For round steel rod with 10mmZinc-plated steel
AN-20
AH-25
AH-GMA
AV8-25
AV6-20
K6-1
K-ENSA
K-NA
K-SA
KG8
KG10A
Actuator arm
Actuator arm
Actuator arm
IND-AFB NFU/SFU.. position indicator
K7-2 NFU/SFU.. standard clamp 1/2", 3/4", 1.05"
64 V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
Mechanical accessories
ZG-GMA
ZG-LF1
ZG-LF3
ZG-NMA
ZG-SMA
ZG-TF1
Z-AF
ZG-AFB
ZG-118
ZG-AFB118
Retrofit adapter for NG NFU/SFU.. while replacing old NF/AF/AFR..
ZF10-NSA-F 10x10 formfit adaptor mutipack 20pieces
ZF12-NSA-F 12x12 formfit adaptor mutipack 20pieces
ZF16-NSA-F 16x16 formfit adaptor mutipack 20pieces
Damper linkage kit For flat mounting
Mounting kitFor flat and side mounting
Mounting kitFor flat and side mounting
Mounting kitFor flat and side mounting
Damper linkage kitFor side mounting (with 2 ball joints KG8)
Damper linkage kitFor side mounting (with 2 ball joints KG8)
NFU/SFU.. crank arm adapter kit.
NFU/SFU.. mounting bracket
NFU/SFU.. crank arm adapter kit
NMUNMQULMQU
SMUSMQU
V4.
12.
201
0 . S
ubje
ct t
o m
odifi
catio
n
65
Replacement table for Mechanical Fail-Safe Damper Actuators
NFU.. NF24
NF230
NF24-S
NF230-S
NF24-SR
AF24
AFR24
SFU..
AF230
AFR230
AF24-S
AFR24-S
AF230-S
AFR230-S
AF24-SR
NFU
NFU-S2
NFU24-SR
SFU
SFU-S2
SFU24-SR
Open/Close 10Nm
Open/Close 10Nm
Series Old models New Generation Description
Open/Close 10Nm, 2x SPDT auxiliary switch
Open/Close 10Nm, 2x SPDT auxiliary switch
Modulating 10Nm
Open/Close 20Nm
Open/Close 20Nm
Open/Close 20Nm
Open/Close 20Nm
Open/Close 20Nm, 2x SPDT auxiliary switch
Open/Close 20Nm, 2x SPDT auxiliary switch
Open/Close 20Nm, 2x SPDT auxiliary switch
Open/Close 20Nm, 2x SPDT auxiliary switch
Modulating 20Nm
Modulating 20NmAFR24-SR
ASIA PACIFIC HEADQUARTERSBelimo Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]
Belimo AUSTRALIAMelbourne Office: Belimo Actuators Pty. Ltd.12 Enterprise Court Mulgrave Business Park Mulgrave, VIC 3170, Australia Tel: +61 (0)3 9545 0844 Fax: +61 (0)3 9545 0855 E-mail: [email protected]
Sydney Office: Belimo Actuators Pty. Ltd. Suite 2.20, 32 Delhi RoadNorth Ryde, NSW 2113AustraliaTel: +61 (0)2 9805 1777Fax: +61 (0)2 9805 1722E-mail: [email protected]
Belimo CHINA Shanghai Office:Belimo Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]
Beijing Office:Belimo Actuators Ltd.Room 605, Hai Chang Edifice44 Liang Ma Qiao RoadBeijing 100016, P.R. ChinaTel: +86 10 6462 1382Fax: +86 10 6462 1383E-mail: [email protected]
Japan Office:Belimo Actuators Ltd. 7th Floor, Honjo-Azumabashi DJ Building 4-19-3, Honjo, Sumida-kuTokyo 130-0004, Japan Tel: +81 3 6823 6961 Fax: +81 3 3626 3911 E-mail: [email protected]
Malaysia Office:Belimo Actuators Ltd.12-1, Jalan PJS 10/2, Subang Indah46000 Petaling Jaya Selangor, MalaysiaTel: +603 5631 2188Fax: +603 5638 2189E-mail: [email protected]
Singapore Office: Belimo Actuators Ltd.1 Tannery Road #08-04, One TannerySingapore 347719Tel: +65 6842 1626Fax: +65 6842 1630 E-mail: [email protected]
Taiwan Office:Belimo Actuators Ltd. 7F-2, No. 343, Jhonghe Road, Yonghe CityTaipei County 234, Taiwan Tel: +886 2 2922 8805 Fax: +886 2 2922 8806 E-mail: [email protected]
Thailand Office:Belimo Actuators Ltd.90/2 Pensiri PlaceSoi Phaholyothin 32, Phaholyothin RoadChandrakasem, JatujakBangkok 10900, ThailandTel: +662 9415582-3Fax: +662 9415584E-mail: [email protected]
Belimo INDIAMumbai Office:Belimo Actuators India Pvt. Ltd. 23/ ABCD, Govt. Industrial Estate,Charkop, Kandivali West,Mumbai 400067, IndiaTel: +91 22 4025 4800Fax: +91 22 4025 4899E-mail: [email protected]
Bangalore Office:Belimo Actuators India Pvt. Ltd. Sreerama Complex,No. 13, 2nd Floor, 5th Cross Road,6th Block, Koramangala,Bangalore 560097, IndiaTel: +91 80 4090 6311Fax: +91 80 4090 6288E-mail: [email protected]
New Delhi Office:Belimo Actuators India Pvt. Ltd.Flat No. 516, DLF Tower – B, Jasola Distt. Centre, Jasola, New Delhi 110025, IndiaPhone: +91 11 4107 8501 to 4107 8507 Fax: +91 11 4107 8508E-mail: [email protected]
Chennai Office:Belimo Actuators India Pvt. Ltd.#25, Bagavadam Street, T-NagarChennai 600017, IndiaTel: +91 44 4299 9450 Fax: +91 44 4299 9451 E-mail: [email protected]
Chongqing Office:Belimo Actuators Ltd.Room 4, 9th floor, Unit 7, Luoma Jiari GardenNo. 36, QingLong Road, Nan’an District Chongqing 400060, P.R. ChinaTel: +86 23 6275 3155Fax: +86 23 6280 3380 *519E-mail: [email protected]
Guangzhou Office:Belimo Actuators Ltd.Room 1202, Skyline Plaza644 Tong Fu East Road, Haizhu AreaGuangzhou 510240, P.R. ChinaTel: +86 20 3435 1860Fax: +86 20 3435 1870 E-mail: [email protected]
Belimo HONG KONGHong Kong Office:Belimo Actuators Ltd.Room 207, 2/F, New Commerce Center19 On Sum Street, Shatin, N.T., Hong KongTel: +852 2687 1716Fax: +852 2687 1795E-mail: [email protected]
Market Asia Pacific
9301
0-00
139
Innovation, Quality and Consultancy:A partnership for motorising HVAC Actuators
BELIMO Actuators (Shanghai) Trading Ltd. 479 Chun Dong Road, Building C-2Xin Zhuang Industry Park Shanghai 201108, P.R. China Tel: +86 21 5483 2929 Fax: +86 21 5483 2930 E-mail: [email protected]
BELIMO Aircontrol (USA), Inc.43 Old Ridgebury RoadDanbury, CT 06813-2928, USATel: +800 543-9038 / 203 791-9915Fax: +800 228-8283 / 203 791-9919
BELIMO Automation AGBrunnenbachstrasse 18340 Hinwil, SwitzerlandTel: +41 43 843 61 11Fax: +41 43 843 62 68E-mail: [email protected]