Upload
lylien
View
256
Download
6
Embed Size (px)
Citation preview
>
Ventilation Air Conditioning RefrigerationHeating
22ºCInside
OUTSIDEHUMIDITY
PROVIDED BYHEINEN & HOPMAN
35 C
90%
productsdampers - Ht
dampers - HT
There are different types of dampers:• Fire and gas dampers• Shut-off dampers• Balancing dampers• Non-return dampers / Pressure relief dampers• Blast dampers• Air-flow adjustment dampers
Fire and gas dampers Fire and gas dampers prevent the spread of fire, smoke and gas between fire zones, where people must have the maximum amount of time to react to possible fire. The dampers are type-approved according to A0 (A60) or H0 (H120).The patented blade structure of the FDB2 dampers have special seals that are effective up to 300 °C and thermally activated graphite seals that expand when the heat rises to 150 °C in ductwork. These unique safety features ensure air tightness and low leakage to prevent fire, gas and smoke progression in a ductwork.
FeX HO (H120) fire and gas dampers
Frame: AISI 316 or AISI 316 with painted steel.Thickness: 3 or 3-5 mm.Blades: AISI 316. Blades without seals.sizes: 100x100 ~ 1200x1200 mm.Circular connection pieces: 100 ~ 1250 mmNote: Special drilling patterns available as an option. Modules case by case.
FdB2 aO (a60) fire and gas dampers
Frame: AISI 316 or painted or galvanized steel. Thickness: 3 or 3-5 mm.Blades: AISI 316 or galvanized steel. Blades have thermal expansion and special seals.sizes: 100x100 ~ 1200x1600 mm.Circular connection pieces: 100 ~ 1250 mm.Note: Special drilling patterns available as an option.Modules possible.
FdL aO (a60) fire dampers
Frame: AISI 316 or painted or galvanized steel.Thickness: 3 or 3-5 mm.Blades: AISI 316 or painted or galvanized steel. Blades without seals.sizes: 100x100 ~ 1300x1200 mm.Circular connection pieces: from 100 ~ 1250 mm.Note: Special drilling patterns available as an option.Modules possible.
Fdd aO (a60) fire and gas dampers
Frame: AISI 316 or painted or galvanized steel.Thickness: min. 3 mm.Blades: AISI 316. Blades have thermal expansion and glass-fiber seals.sizes: Ø100, 125, 160, 200, 250, 315 mmNote: Special drilling patterns available as an option.Modules possible.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
shut-off dampersShut-off dampers shut off the airflow in ductwork where tightness, thermal insulation and reliability are important. The dampers meet international standards for rectangular and circular ducts. The leakage class is accordance with the EM1751 standards.
UTT shut-off dampers
Frame: AISI 316 or galvanized steel.Thickness: 1 mm.Blades: AISI 316 or galvanized steel. Blades are insulated and have seals.sizes: 100x100 ~ 2400x2400 mm at 50-mm intervals (special sizes available).Circular connection pieces: 100 ~ 1250 mm.Operation system: by static air pressure.
Balancing dampers Balancing dampers adjust or control the air flow rates in ductwork where leakage does not have significant importance.
UTK balancing dampers
Frame: AISI 316 or galvanized steel. Thickness: 1 mm.Blades: AISI 316 or galvanized steel. Blades have seals (tightness class 1).size: 100x100 ~ 2400x2400 mm at 50-mm intervals (special sizes available).Circular connection pieces: 100 ~ 1250 mm.Operation system: by static air pressure. Maximum pressure across the dampers: 4000 Pa. Maximum air velocity: 16 m/s.
Non-return dampers / pressure relief dampers Non-return dampers and pressure relief dampers are used in oil and gas applications to prevent backflow and relieve the pressure through ventilation ductwork. The opening pressure can be individually adjusted. The dampers are also applicable in marine ventilation systems.
BLd non-return dampers / Brd pressure relief dampers
Frame: AISI 316 or painted or galvanized steel.Thickness: 3 mm.Blades: AISI 316 or galvanized steel. Blades have special seals.size: 100x100 ~ 1200x1400 mmCircular connection pieces: 100 ~ 1250 mm.Note: Special drilling patterns available as an option. BRD dampers have counterweights. Modules possible.
Blast dampers Blast dampers protect ventilation systems against the effects of explosions. The dampers shield industrial facilities and related buildings against destructive blast forces. The dampers offer higher air flow capacity and increased level of safety as well as flexibility for design of duct systems.
HV blast dampers
material: AISI 316 or galvanized steel.Blast protection: up to 1 bar (14,5 psi).standard sizes: 300x300 ~ 1500x1500 mm.Note: Modular construction available for high airflows and large ducts. Maintenance-free design. Minimum leakage on pass-through pressure and impulse. Minimum turbulence and pressure drop.
air flow adjustment dampersPRA air flow adjustment dampers are manually adjustable measurement units for circular ducts. The dampers are used in duct systems to control the air flow.
pra air flow adjustment dampers
Casing and blades: Galvanized steel.Circular construction: 100 to 315 and 350 to 1000 mm. Adjustable cone and air flow measurement taps for differential pressure adjustment.Classification of casing leakage: EN1751 Class C.
Control The dampers can be controlled electrically, pneumatically or manually. In case of fire, the fire and gas dampers will close automatically.
The electrically and pneumatically controlled dampers are driven by an actuator.
Belimo actuators: As standard actuator. schischeck actuators: Actuator used in explosion-proof areas or if the actuator must open/close within 3s/900.
Certified quality In addition to ISO 9001, ISO 14001, quality and environmental management certificates, marine fire dampers conform to leading classification societies worldwide. Several dampers are ATEX-certified and shock-tested products for naval applications, ships and submarines.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Part Material Finishing
Frame Carbon steel Painted or galvanized
Frame Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI 316L)
-
Blades Steel Galvanized
Blades Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI 316L)
-
Bearings Stainless steel EN 1.4404 (AISI 316L) / Bronze bearings optional
-
Shafts Stainless steel EN 1.4404 (AISI 316L) -
FdB2 fire and gas dampersFDB2 fire and gas dampers are used in offshore, marine and navy ventilation systems. The dampers are type-approved according to A-0 (A-60). The dampers can be installed in rectangular or circular ducts. The dampers have a fusible link and prevent the spread of fire and gases within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in any position. An open-closed indicator is visible on the outside of the dampers. Non-standard dimensions are available on request.
• Type-approved by most recognized classification societies: class A0 without insulation, class A15-A60 when suitably insulated.• Available as ATEX-approved. Shock tested.• Blades contain silicone (effective up to 300 ºC) for low leakage in normal conditions and thermal expansion graphite seals (effective from 150 ºC) to increase tightness up to 50% in case of fire. Closed damper meets the requirement of leakage class 3 (EN1751:1998) Tested size 1000x1000 mm.• Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available.• Low weight due to patented double skin blade structure.• Automatic electrical, pneumatic or spring operation system available.• Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s.
dimensions and material thicknessThe dampers meet international standards for rectangular (width B 100-1200 mm and height H 100-1600 mm, 1 mm division) and circular ducts (Ø 100-1250 mm). Modular constructions are available for larger sizes. Non-standard dimensions and flange drilling are available on request.
Frame thickness according to sOLas
actuator effect in dimensions
Dimensions S L
If B or H > 100, but < 449 3 210
If B or H > 450, but < 649 4 212
If B or H > 650 5 215
Actuator Dimensions
R A
Electrical GGA 326, 1E 100H< 300 = 300
H>300 = H
Pneumatic PNLLinear actuator
245/300N170
H<500 = 500 H>500 = H
Pneumatic PNRPneumatic rotating
atuator AT100170
H<300 = 300 H>300 = H
Pneumatic PNRPneumatic rotating
actuator AT200190
H<350 = 350 H>350 = H
Spring Spring 140 H
Dimensions in mm
Dimensions in mm
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
ø12
10
MIN. 50
H+
58
B+58
15
0
n*1
50
n*1
50
15
0
150
n*150n*150
150
10
10
10
B+4
H+
4R30
MIN
. 50
18
A
AC
TU
AT
OR
GENERAL FDB2 DRAWING
GENERAL FDB2 DRAWING, TOP
S, A
CC
OR
DIN
G
TO
SO
LA
S
21
5, S
=5
21
2, S
=4
21
0, S
=3
16
0
24
0, B
LA
DE
S IN
OP
EN
PO
SIT
ION
FDB2 CIRCULAR CONNECTIONS
361, S=3
S, A
CC
OR
DIN
G T
O S
OL
AS
365, S=4
370, S=5
ØD
367, S=3
373, S=4
380, S=5
S, AC
CORD
ING
TO S
OLAS
ØD
FDB2 CIRCULAR, WITH CONNECTION FLANGES
GENERAL FDB2 MODULE ASSEMBLY
ø12
10
MIN. 50
H+
58
B+58
15
0
n*1
50
n*1
50
15
0
150
n*150n*150
150
10
10
10
B+4
H+
4
R30
MIN
. 50
18
A
AC
TU
AT
OR
GENERAL FDB2 DRAWING
GENERAL FDB2 DRAWING, TOP
S, A
CC
OR
DIN
G
TO
SO
LA
S
21
5, S
=5
21
2, S
=4
21
0, S
=3
16
0
24
0, B
LA
DE
S IN
OP
EN
PO
SIT
ION
FDB2 CIRCULAR CONNECTIONS
361, S=3
S, A
CC
OR
DIN
G T
O S
OL
AS
365, S=4
370, S=5
ØD
367, S=3
373, S=4
380, S=5
S, AC
CORD
ING
TO S
OLAS
ØD
FDB2 CIRCULAR, WITH CONNECTION FLANGES
GENERAL FDB2 MODULE ASSEMBLY
ø12
10
MIN
. 50
H+58
B+
58
150
n*150n*150
150
15
0 n*1
50
n*1
501
50
10
10
10
B+
4
H+4
R3
0
MIN. 50
18
A
ACTUATOR
GE
NE
RA
L F
DB
2 D
RA
WIN
G
GE
NE
RA
L F
DB
2 D
RA
WIN
G, T
OP
S, ACCORDING
TO SOLAS
215, S=5
212, S=4
210, S=3
160
240, BLADES IN OPEN POSITION
FD
B2 C
IRC
ULA
R C
ON
NE
CT
ION
S
36
1, S
=3
S, ACCORDING TO SOLAS
36
5, S
=4
37
0, S
=5
ØD
367,
S=3
373,
S=4
380,
S=5
S, ACCORDING TO SOLAS
ØD
FD
B2 C
IRC
ULA
R, W
ITH
CO
NN
EC
TIO
N F
LA
NG
ES
GE
NE
RA
L F
DB
2 M
OD
ULE
AS
SE
MB
LY
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
FeX fire and gas dampersFEX fire and gas dampers are used in offshore, nuclear and navy ventilation systems. The dampers are type-approved according to H0 (H120). The dampers protect the integrity of bulkheads where they are penetrated by ventilation ducts. The dampers can be installed in rectangular or circular ducts. The dampers have a fusible link and prevent the spread of fire and gases (low-leakage model) within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in bulkheads. An open-closed indicator is visible on the outside of the dampers.
• Type-approved by most recognized classification societies: class H0 (H120) when suitably insulated.• Fixed frame and blades of stainless steel AISI 316L. Painted frame surface as an option available on request.• Welding cleaned by acid treatment.• Lifting lugs as standard.• Blades have thermal expansion seals.• Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available.• Automatic electrical, pneumatic or spring operation system available.• Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s.• ATEX-approved.
dimensions and material thickness The dampers are for rectangular and circular ducts. Sizes for rectangular ducts (BxH) are available from 100x100 to 1200x1200 mm in 1-mm increments of duct. Sizes for circular ducts (BxH) are available from Ø 100 mm to 1250 mm. Non-standard dimensions are available on request. Standard flange size: 40 mm. Flanges and drilling are available according to ISO 15138 standards or customer specifications. Standard frame material thickness: 3 mm. Blades are made of two sheets of 1 mm thickness each.
actuators effect on dimensions
The table shows only some examples of actuators and their effect on dimensions.
Part Material Finishing Note
Frame Stainless steel Painted -
Frame Stainless steel - -
Blades Stainless steel - -
Blades Stainless steel - -
Maintenance-free bearings Stainless steel - Bronze bearings optional
Shafts Stainless steel - -
Actuator Dimensions
R A
Electrical GGA 326, 1E 100H< 300 = 300
H>300 = H
PneumaticPneumatic rotating
atuator170
H<300 = 300 H>300 = H
Electrical, EXSchischek ExMax /
RedMax180
H<300 = 300 H>300 = H
Spring Spring 140 H
Dimensions in mm
B+4
n*150
150
B+84
MIN.50
30 R
23.0
150
n*150
A
23.0
MIN
.50
23.0
H+4
n*15
0
H+84
150
n*15
0
150
23.0
40.0
12x14
AC
TU
AT
OR
GENERAL FEX DRAWING
GENERAL FEX DRAWING, TOP
255
160
3
FEX CIRCULAR CONNECTIONS
361
ØD
367Ø
D
FEX CIRCULAR, WITH CONNECTION FLANGES
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
FdL fire dampersFDL fire dampers are used in offshore, marine and navy ventilation systems. The dampers are type-approved according to A-0 (A-60). The dampers can be installed in rectangular or circular ducts. The dampers have a fusible link and spring return actuator. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in any position. An open-closed indicator is visible on the outside of the dampers. Non-standard dimensions are available on request.
• Type-approved by most recognized classification societies: class A0 without insulation, class A15-A60 when suitably insulated.• Available as ATEX approved. Shock-tested.• Fixed frame and blades of painted, galvanized or stainless steel. Maintenance-free stainless-steel bearings and shafts.• Blades without sealing.• Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available.• Can be installed in any position.• Automatic electrical, pneumatic or spring operation system available.• Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s.
dimensions and material thickness The dampers meet international standards for rectangular (width B 100-1300 mm and height H 100-1200 mm, 1 mm division) and circular ducts (Ø 100-1250 mm). Modular constructions are available for bigger sizes. Modular constructions are available for larger sizes. Non-standard dimensions and flange drilling are available on request. Standard flange size: 27 mm. Flanges and drilling are available according to ISO 15138. Modular construction sizes up to 2600x2400 mm. Standard frame material thickness: 3-5 mm. Material thickness according to SOLAS available on request.
Frame thickness according to sOLas
actuators effect on dimensions
The table shows only some examples of actuators and their effect on dimensions.
Part Material Finishing
Frame Carbon steel Painted or galvanized
Frame Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI 316L)
-
Blades Steel Galvanized
Blades Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI 316L)
-
Bearings Stainless steel EN 1.4404 (AISI 316L) / Bronze bearings optional
-
Shafts Stainless steel EN 1.4404 (AISI 316L) -
Dimensions S L
If B or H > 100, but < 449 3 210
If B or H > 450, but < 649 4 212
If B or H > 650 5 215
Actuator Dimensions
R A
Electrical GGA 326, 1E 100H< 300 = 300
H>300 = H
Pneumatic PNLLinear actuator
245/300N170
H<500 = 500 H>500 = H
Pneumatic PNRPneumatic rotating
atuator AT100170
H<300 = 300 H>300 = H
Pneumatic PNRPneumatic rotating
actuator AT200190
H<350 = 350 H>350 = H
Spring Spring 140 H
Dimensions in mm
Dimensions in mm
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Ø12
9
MIN. 50
H+
56
B+56
15
0
n*1
50
n*1
50
15
0
150
n*150n*150
150
9
9
9
B+2
H+
2R30
MIN
. 50
18
A
AC
TU
AT
OR
GENERAL FDL DRAWING
GENERAL FDL DRAWING, TOP
FDL CIRCULAR CONNECTIONS
367, S=3
373, S=4
380, S=5S,
ACCO
RDIN
G TO
SOL
AS
ØD
FDL CIRCULAR, WITH CONNECTION FLANGES
S, A
CC
OR
DIN
G
TO
SO
LA
S
21
7, S
=5
21
4, S
=4
21
2, S
=3
16
0
24
0, B
LA
DE
S IN
OP
EN
PO
SIT
ION
361, S=3
S, A
CC
OR
DIN
G T
O S
OL
AS
365, S=4
370, S=5
ØD
GENERAL FDL MODULE ASSEMBLY
Flat bar steel both sideof the damper
FDB2 Max.1204
FDL Max.1302
FDL Nominal with+56
FDB2 Nominal with+58
FDB
2 M
ax.1
604
FDL
Max
.120
2
>50 nx 150 nx 150 >50
nx15
0nx
150
>50
>50
2
2
FDB
2 N
omin
al h
eigh
t+58
FDL
Nom
inal
hei
ght+
56
10(F
DB
2)9
(FD
L)
10 (FDB2)9 (FDL)
C
210-300L± 2
Flat bars to be sealed with pyrocryl sealant SM
in 3
Max
10
Flat bar steel
Flat bar cross steel
DETAIL CSCALE 1 : 5
Size limitation:
FDB2:
Nominal Width 2060 x Nominal Height 3260
or
Nominal Width 2460 x Nominal Height 2860
FDL
Nominal Width 2660 x Nominal Height 2460
Ø12
9
MIN. 50
H+
56
B+56
15
0
n*1
50
n*1
50
15
0
150
n*150n*150
150
9
9
9
B+2
H+
2
R30
MIN
. 50
18
A
AC
TU
AT
OR
GENERAL FDL DRAWING
GENERAL FDL DRAWING, TOP
FDL CIRCULAR CONNECTIONS
367, S=3
373, S=4
380, S=5
S, AC
CORD
ING
TO S
OLAS
ØD
FDL CIRCULAR, WITH CONNECTION FLANGES
S, A
CC
OR
DIN
G
TO
SO
LA
S
21
7, S
=5
21
4, S
=4
21
2, S
=3
16
0
24
0, B
LA
DE
S IN
OP
EN
PO
SIT
ION
361, S=3
S, A
CC
OR
DIN
G T
O S
OL
AS
365, S=4
370, S=5
ØD
GENERAL FDL MODULE ASSEMBLY
Flat bar steel both sideof the damper
FDB2 Max.1204
FDL Max.1302
FDL Nominal with+56
FDB2 Nominal with+58
FDB
2 M
ax.1
604
FDL
Max
.120
2
>50 nx 150 nx 150 >50
nx15
0nx
150
>50
>50
2
2
FDB
2 N
omin
al h
eigh
t+58
FDL
Nom
inal
hei
ght+
56
10(F
DB
2)9
(FD
L)
10 (FDB2)9 (FDL)
C
210-300L± 2
Flat bars to be sealed with pyrocryl sealant SM
in 3
Max
10
Flat bar steel
Flat bar cross steel
DETAIL CSCALE 1 : 5
Size limitation:
FDB2:
Nominal Width 2060 x Nominal Height 3260
or
Nominal Width 2460 x Nominal Height 2860
FDL
Nominal Width 2660 x Nominal Height 2460
Ø12
9
MIN. 50
H+
56
B+56
15
0
n*1
50
n*1
50
15
0
150
n*150n*150
150
9
9
9
B+2
H+
2
R30
MIN
. 50
18
A
AC
TU
AT
OR
GENERAL FDL DRAWING
GENERAL FDL DRAWING, TOP
FDL CIRCULAR CONNECTIONS
367, S=3
373, S=4
380, S=5
S, AC
CORD
ING
TO S
OLAS
ØD
FDL CIRCULAR, WITH CONNECTION FLANGES
S, A
CC
OR
DIN
G
TO
SO
LA
S
21
7, S
=5
21
4, S
=4
21
2, S
=3
16
0
24
0, B
LA
DE
S IN
OP
EN
PO
SIT
ION
361, S=3
S, A
CC
OR
DIN
G T
O S
OL
AS
365, S=4
370, S=5
ØD
GENERAL FDL MODULE ASSEMBLY
Flat bar steel both sideof the damper
FDB2 Max.1204
FDL Max.1302
FDL Nominal with+56
FDB2 Nominal with+58
FDB
2 M
ax.1
604
FDL
Max
.120
2
>50 nx 150 nx 150 >50
nx15
0nx
150
>50
>50
2
2
FDB
2 N
omin
al h
eigh
t+58
FDL
Nom
inal
hei
ght+
56
10(F
DB
2)9
(FD
L)
10 (FDB2)9 (FDL)
C
210-300L± 2
Flat bars to be sealed with pyrocryl sealant SM
in 3
Max
10
Flat bar steel
Flat bar cross steel
DETAIL CSCALE 1 : 5
Size limitation:
FDB2:
Nominal Width 2060 x Nominal Height 3260
or
Nominal Width 2460 x Nominal Height 2860
FDL
Nominal Width 2660 x Nominal Height 2460
Fdd fire and gas dampersFDD fire and gas dampers are used in offshore and marine ventilation systems. The dampers are type-approved according to A-0 (A-60). The dampers can be installed in circular ducts. The dampers have a fusible link and prevent the spread of fire and gases within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. The dampers are set from outside and can be installed in any position. An open-closed indicator is visible on the outside of the dampers.
• Type-approved by most recognized classification societies: class A0-A60 when suitably insulated.• Fixed frame of painted, galvanized or stainless steel. Blades of stainless steel. Flanges available as an option.• Blades have glass-fiber seals (effective up to 300 ºC) and thermal-expansion graphite seals (effective from 150 ºC).• Nominal fuse release temperature: 50 ºC, 74 ºC or 100 ºC. Other temperatures available.• Very low leakage.• Automatic electrical, pneumatic or spring operation system available.• Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s.
dimensions and material thickness The dampers meet international standards for circular ducts (Ø100-315 mm). Sizes Ø100 and Ø125 are not available in stainless steel. Special flange drilling is available on request. Standard flange size: 27 mm. Frame material thickness: min. 3 mm.
Part Material Finishing
Frame Carbon steel Painted or galvanized
Frame Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI 316L)
-
Blades Steel Galvanized
Blades Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI 316L)
-
Bearings Stainless steel EN 1.4404 (AISI 316L) / Bronze bearings optional
-
Shafts Stainless steel EN 1.4404 (AISI 316L) -
FDD-EL FDD-PNL FDD-PNR FDD-SP
D L R R R R
100 200 317 317 - -
125 200 317 317 - -
160 200 317 317 - -
200 320 362 362 - -
250 320 362 362 - -
315 320 362 362 - -
FDD-EL FDD-PNL FDD-PNR FDD-SP
D S K T N L H A R H A R H A R H A R
100 200 120 7 4 206 295 300 320 295 500 520 340 300 - 295 200 -
125 225 150 7 4 206 310 315 320 310 515 520 355 315 - 310 225 -
160 260 185 7 4 206 350 330 320 350 530 520 395 330 - 350 260 -
200 300 225 7 4 326 390 350 365 390 550 565 435 350 - 390 300 -
250 350 280 10 8 326 440 375 365 440 575 365 485 375 - 440 350 -
315 415 355 10 8 326 505 410 365 505 610 565 550 410 - 505 415 -
Dimensions in mm
Dimensions in mm
12
FDD - A0(A60) Fire And Gas Damper
FDD DIMENSIONS AND MATERIAL THICKNESS
FDD fire dampers meet international standards for
circular ducts (Ø100-315 mm). Sizes Ø100 and Ø125 are
not available of stainless steel. Special flange drilling is
available on request. Standard flange width 27 mm.
Frame material thickness minimum 3 mm.
D
GENERAL FDD DRAWING (without flanges)
FDD Dimensions with flanges (as an option)
FDD DRAWING (without flanges), TOP
L
FDD-EL FDD-PNL FDD-PNR FDD-SP
D S K T N L H A R H A R H A R H A R
100 200 120 7 4 206 295 300 320 295 500 520 340 300 - 295 200 -
125 225 150 7 4 206 310 315 320 310 515 520 355 315 - 310 225 -
160 260 185 7 4 206 350 330 320 350 530 520 395 330 - 350 260 -
200 300 225 7 4 326 390 350 365 390 550 565 435 350 - 390 300 -
250 350 280 10 4 326 440 375 365 440 575 565 485 375 - 440 350 -
315 415 355 10 8 326 505 410 365 505 610 565 550 410 - 505 415 -
H
S
K
D
A
Ø TN pcs
Optional flange
ACTUATOR
GENERAL FDD DRAWING (with flanges)
FDD DRAWING (with flanges), TOP
FD
D
Fired
am
pe
r
XX
XX
La
hti Fin
lan
d
No
:
CLOSED
OPEN
HALTO
NX
XX
X
R
ALT. POSITION OF ACTUATOR
GENERAL FDD DRAWING (without flanges)
FDD-EL FDD-PNL FDD-PNR FDD-SP
D L R R R R
100 200 317 317 - -
125 200 317 317 - -
160 200 317 317 - -
200 320 362 362 - -
250 320 362 362 - -
315 320 362 362 - -
FDD Dimensions without flanges (standard)
L
WIT
HO
UT
FLA
NG
ES L
-6
R
WIT
HO
UT
FLA
NG
ES R
-3
ALTERNATIVE POSITION OF ACTUATOR
ACTUATOR
12
FDD - A0(A60) Fire And Gas Damper
FDD DIMENSIONS AND MATERIAL THICKNESS
FDD fire dampers meet international standards for
circular ducts (Ø100-315 mm). Sizes Ø100 and Ø125 are
not available of stainless steel. Special flange drilling is
available on request. Standard flange width 27 mm.
Frame material thickness minimum 3 mm.
D
GENERAL FDD DRAWING (without flanges)
FDD Dimensions with flanges (as an option)
FDD DRAWING (without flanges), TOP
L
FDD-EL FDD-PNL FDD-PNR FDD-SP
D S K T N L H A R H A R H A R H A R
100 200 120 7 4 206 295 300 320 295 500 520 340 300 - 295 200 -
125 225 150 7 4 206 310 315 320 310 515 520 355 315 - 310 225 -
160 260 185 7 4 206 350 330 320 350 530 520 395 330 - 350 260 -
200 300 225 7 4 326 390 350 365 390 550 565 435 350 - 390 300 -
250 350 280 10 4 326 440 375 365 440 575 565 485 375 - 440 350 -
315 415 355 10 8 326 505 410 365 505 610 565 550 410 - 505 415 -
H
S
K
D
A
Ø TN pcs
Optional flange
ACTUATOR
GENERAL FDD DRAWING (with flanges)
FDD DRAWING (with flanges), TOP
FD
D
Fired
am
pe
r
XX
XX
La
hti Fin
lan
d
No
:
CLOSED
OPEN
HALTO
NX
XX
X
R
ALT. POSITION OF ACTUATOR
GENERAL FDD DRAWING (without flanges)
FDD-EL FDD-PNL FDD-PNR FDD-SP
D L R R R R
100 200 317 317 - -
125 200 317 317 - -
160 200 317 317 - -
200 320 362 362 - -
250 320 362 362 - -
315 320 362 362 - -
FDD Dimensions without flanges (standard)
L
WIT
HO
UT
FLA
NG
ES L
-6
R
WIT
HO
UT
FLA
NG
ES R
-3
ALTERNATIVE POSITION OF ACTUATOR
ACTUATOR
12
FDD - A0(A60) Fire And Gas Damper
FDD DIMENSIONS AND MATERIAL THICKNESS
FDD fire dampers meet international standards for
circular ducts (Ø100-315 mm). Sizes Ø100 and Ø125 are
not available of stainless steel. Special flange drilling is
available on request. Standard flange width 27 mm.
Frame material thickness minimum 3 mm.
D
GENERAL FDD DRAWING (without flanges)
FDD Dimensions with flanges (as an option)
FDD DRAWING (without flanges), TOP
L
FDD-EL FDD-PNL FDD-PNR FDD-SP
D S K T N L H A R H A R H A R H A R
100 200 120 7 4 206 295 300 320 295 500 520 340 300 - 295 200 -
125 225 150 7 4 206 310 315 320 310 515 520 355 315 - 310 225 -
160 260 185 7 4 206 350 330 320 350 530 520 395 330 - 350 260 -
200 300 225 7 4 326 390 350 365 390 550 565 435 350 - 390 300 -
250 350 280 10 4 326 440 375 365 440 575 565 485 375 - 440 350 -
315 415 355 10 8 326 505 410 365 505 610 565 550 410 - 505 415 -
H
S
K
D
A
Ø TN pcs
Optional flange
ACTUATOR
GENERAL FDD DRAWING (with flanges)
FDD DRAWING (with flanges), TOP
FD
D
Fired
am
pe
r
XX
XX
La
hti Fin
lan
d
No
:
CLOSED
OPEN
HALTO
NX
XX
X
R
ALT. POSITION OF ACTUATOR
GENERAL FDD DRAWING (without flanges)
FDD-EL FDD-PNL FDD-PNR FDD-SP
D L R R R R
100 200 317 317 - -
125 200 317 317 - -
160 200 317 317 - -
200 320 362 362 - -
250 320 362 362 - -
315 320 362 362 - -
FDD Dimensions without flanges (standard)
L
WIT
HO
UT
FLA
NG
ES L
-6
R
WIT
HO
UT
FLA
NG
ES R
-3
ALTERNATIVE POSITION OF ACTUATOR
ACTUATOR
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
UTT shut-off dampers / UTK balancing dampersUTK, UTT• Temperature operation range up to +100°C, optionally up to +200°C.• Classification of casing leakage EN 1751 class B.
UTK• Shut-off, balancing, adjustment or control damper with opposed blades.• Tightness in closed position meets EN 1751 class 1 requirements.
UTT• Shut-off and balancing damper for outdoor air intake and exhaust air with opposed blades.• Blades have thermal insulation.• Tightness in closed position meets EN 1751 class 4 requirements (tested size 600x600 mm).
product models and accessories• Model with stainless steel EN 1.4404 (AISI316L) design• Model with mineral-wool (20 mm) insulated casing• Model with heat-proof design• Circular duct connections• Several actuator options
dimensions and material thickness The dampers are for rectangular (width B 100-2400 mm and height H 100-2400 mm, 1 mm division) and circular ducts (Ø100-1250 mm). Non-standard dimensions and flange drilling are available on request Modular construction sizes up to 4900x4900 mm. Standard frame material thickness: 1 mm.
Qmin 1 m/s duct velocity Qmax 6 m/s duct velocity
HxW (mm)
Qmin (l/s) m3/h Qmax
(l/s) m3/h
200x200 160 576 480 1728
400x400 320 1152 960 3456
400x800 640 2304 1920 6912
800x800 1280 4608 3840 13824
1000x1000 2000 7200 6000 21600
1000x2000 4000 14000 12000 43200
W H
100, 200, ..., 2400 100, 200, ..., 2400
ØD WxH
100 150x150
125 150x150
160 200x200
200 200x200
250 250x250
315 300x300
400 400x400
500 500x500
630 600x600
710 800x800
800 800x800
1000 1000x1000
1250 1250x1250
Part Material Note
Casing Galvanized steel Stainless steel EN 1.4404 (AISI 316L) also available
Blades (sand-wich design)
Galvanized steel Stainless steel EN 1.4404 (AISI 316L) also available
Blade gaskets Silicon Heat-proof model: LTE silicon
Duct gasket Rubber compound Circular connections
Slides bearings Alloy of polyamide and molybdenum sulphide Self-lubricated heat-proof model stain-less steel AISI 316L
Drive shaft Galvanized steel Rectangular bar (15x15 mm)
Part Material Note
Casing Galvanized steelStainless steel EN 1.4404 (AISI 316L)
also available
Blades (sand-wich design) Galvanized steel
Stainless steel EN 1.4404 (AISI 316L) also available
Blade insulation Polyurethane CFC-free
Blade gaskets Silicon Heat-proof model: LTE silicon
Gaskets inside the casing (only
UTT)Silicon Fixed in an aluminium profile
Duct gasket Rubber compound Circular connections
Slides bearings Alloy of polyamide and molybdenum sulphideSelf-lubricated heat-proof model stain-
less steel AISI 316L
Drive shaft Galvanized steel Rectangular bar (15x15 mm)
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Dimensions in mm
55
W H
100,200,...,2400 100,200,...,2400
CT=D1; CT=D2
ØD WxH
100 150x150
125 150x150
160 200x200
200 200x200
250 250x250
315 300x300
400 400x400
500 500x500
630 600x600
710 800x800
800 800x800
1000 1000x1000
1250 1250X1250
UTK/UTT - Multi-blade Damper
20
/UT
K,U
TT
/15
00
/12
11
/EN
G
DIMENSIONS
Models with circular connections
Product models and Accessories
ADJUSTMENT & CONTROL OPTIONS CODE NOTE
Manual handle adjustment MO = MA
Manual extension bar adjustment AC = BA Handle extension arrangement
Flexible coupling bar AC = FS For remote actuator coupling
Actuator operation MO= See Actuator options
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
BLd non-return dampersBLD non-return dampers are used in offshore and marine applications to prevent backflow through ventilation ductwork. The dampers do not require an actuator or motor. The dampers can be installed in rectangular or circular ducts, horizontally or vertically. If required, the dampers can easily be set by adjusting the weight of each damper/installation. Weights for the dampers are available as an option. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance (with weights). Non-standard dimensions are available on request.
• Fixed frame in painted, galvanized or stainless steel. Blades of galvanized or stainless steel.• Models for horizontal or vertical installation.• Closed damper meets the leakage requirement of NORSOK. Leakage class of closed damper according to EN 1751 class 2 (VTT test report no. RTE4306/04).• Blades have silicone seal to lower the leakage through blades.• Blades linked and open in parallel.• Adjustable by changing the position of counterweights. Counterweights available on request.• Standard construction places weights on the right-hand side. Weights on the left-hand side available as an option.• Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s.• ATEX approved.
dimensions and material thickness The dampers meet international standards for rectangular (width B 200-1200 and height H200-1400 mm, 1 mm division) and circular ducts (Ø 100- 1250 mm). Non-standard dimensions are available on request. Modular construction sizes up to 2400x2800 mm are available. Standard frame material thickness: 3 mm. Standard flange width: 27 mm. Blades are made of two sheets of 0.8 mm thickness each.
Part Material Finishing Note
Frame Carbon steel Painted or galvanized -
Frame Stainless steel - -
Blades Steel Galvanized -
Blades Stainless steel - -
Maintenance-free bearings Stainless steel -Bronze bearings
optional
Shafts Stainless steel - -
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
34
V3
M0
2Y
20
09
/Ha
lto
n M
ari
ne
re
se
rve
s t
he
rig
ht
to a
lte
r p
rod
ucts
wit
ho
ut
a n
oti
ce
.
BLD - Non-Return Damper
18
5 IF
H=
<2
00
20
IF H
=>
25
0
130
B+58
B+4
nx150 nx150 Min50
10
10
Ø 12
H+
4
H+
58
nx
15
0n
x1
50
27
24
Min
50
RIGHT HAND MODEL
BLD DIMENSIONS AND MATERIAL THICKNESS
BLD non-return dampers meet international standards
for both rectangular (width B 200-1200 and height H
200-1400 mm, 1mm division) and circular ducts (Ø100
- 1250 mm). Special non-standard dimensions are
19
0
130
25
2
3
GENERAL BLD DRAWING BLD DRAWING TOP
HE
IGH
T+
58
WIDTH+58
DIA
ME
TE
R-2
nx1
50
nx1
50
10
nx150 nx150
Min
50
Min50
130
ALL BOLT HOLES Ø 12
BOLTS M10x30
BLD DRAWING, CIRCULAR CONNECTIONS
available on request. Modular construction sizes up to
2400x2800 mm are available. Standard frame material
thickness 3 mm. Standard flange width 27 mm.
Blades made of two sheets, each being 0.8 mm thick.
18
5 IF
H=
20
0
20
IF
H>
20
0190
358
ØD
BLD DRAWING, CIRCULAR CONNECTIONS
18
5 I
F H
<2
50
20
IF
H=
>2
50
190
ØD
364
AIRFLOW
BLD CIRCULAR, WITH CONNECTION FLANGES
34
V3
M0
2Y
20
09
/Ha
lto
n M
ari
ne
re
se
rve
s t
he
rig
ht
to a
lte
r p
rod
ucts
wit
ho
ut
a n
oti
ce
.
BLD - Non-Return Damper
18
5 IF
H=
<2
00
20
IF H
=>
25
0
130
B+58
B+4
nx150 nx150 Min50
10
10
Ø 12
H+
4
H+
58
nx
15
0n
x1
50
27
24
Min
50
RIGHT HAND MODEL
BLD DIMENSIONS AND MATERIAL THICKNESS
BLD non-return dampers meet international standards
for both rectangular (width B 200-1200 and height H
200-1400 mm, 1mm division) and circular ducts (Ø100
- 1250 mm). Special non-standard dimensions are
19
0
130
25
2
3
GENERAL BLD DRAWING BLD DRAWING TOP
HE
IGH
T+
58
WIDTH+58
DIA
ME
TE
R-2
nx1
50
nx1
50
10
nx150 nx150
Min
50
Min50
130
ALL BOLT HOLES Ø 12
BOLTS M10x30
BLD DRAWING, CIRCULAR CONNECTIONS
available on request. Modular construction sizes up to
2400x2800 mm are available. Standard frame material
thickness 3 mm. Standard flange width 27 mm.
Blades made of two sheets, each being 0.8 mm thick.
18
5 IF
H=
20
0
20
IF
H>
20
0
190
358
ØD
BLD DRAWING, CIRCULAR CONNECTIONS
18
5 I
F H
<2
50
20
IF
H=
>2
50
190
ØD
364
AIRFLOW
BLD CIRCULAR, WITH CONNECTION FLANGES
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Brd pressure relief dampersBRD pressure-relief dampers are used in offshore and marine applications to prevent backflow through ventilation ductwork. The dampers do not require an actuator or motor. The dampers can be installed in rectangular or circular ducts, horizontally or vertically. The opening pressure can easily be set by adjusting the weight of each damper/installation. Weights are included in the delivery. Non-standard dimensions are available on request.
• Fixed frame in painted, galvanized or stainless steel. Blades of galvanized or stainless steel.• Models for horizontal or vertical installation.• Blades have silicone seal to lower the leakage through blades.• Available as ATEX-approved.• Leakage class of closed damper according to EN 1751 class 2. Tested size 1000x1000 mm.• Blades linked and open in parallel.• Opening pressure adjusted by changing the position of counterweight(s).• Opening pressure range: 30 Pa ~ 150 Pa (up to 300 Pa optional).• Counterweights included.• Standard construction places weights on the right-hand side. Weights on the left-hand side available as an option.• Final adjustment of counterweights carried out during commissioning.• Maximum duct pressure: 5000 Pa. Maximum air velocity: 15 m/s.
dimensions and material thickness The dampers meet international standards for rectangular (width B 200-1200 mm and height H 200-1400 mm, 1 mm division) and circular ducts (Ø 100-1250 mm). Non-standard dimensions are available on request. Standard flange width: 27 mm. Flanges and drilling are available according to ISO 15138 standards. Modular construction sizes up to 2400x2800 mm. Standard frame material thickness: 3 mm. Blades are made of two sheets of 0.8 mm thickness each.
Part Material Finishing
Frame Carbon steel Painted or galvanized
Frame Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI 316L)
-
Blades Steel Galvanized
Blades Stainless steel EN 1.4301 (AISI 304), EN 1.4404 (AISI 316L), EN 1.4432 (AISI L)
-
Bearings Stainless steel EN 1.4404 (AISI 316L) / Bronze bearings optional
-
Shafts Stainless steel EN 1.4404 (AISI 316L) -
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
HV blast dampersHV blast dampers protect ventilation systems against the effects of vapor and dust cloud explosions. The dampers shield industrial facilities and related buildings against destructive blast forces. The dampers offer higher air flow capacity and increased level of safety as well as flexibility for design of duct systems. The structure of the dampers is corrosion-free, hot-dip galvanized steel (AISI316 in the HV-SS version). The dampers have spring-loaded closing blades in a fully welded damper body to close the air passage in case of explosion or sudden increase of overpressure in the HVAC system. The threshold trigger pressure can be adjusted according customer specification. When the blades are closed, they will remain in closed position until they are manually reset. The dampers are approved according ATEX (Ex II 2 G D) for equipment in hazardous environment.
• Made of galvanized or stainless steel, AISI316.• Fully welded damper body made of 5-mm steel.• Closing blades and shafts with stainless-steel bearings.• Adjustable trigger mechanism.• Fragment grill.• Flow guides.
General drawing The dampers are dimensioned according to the duct size or wall opening.
Standard sizes:• 300x300 mm• 500x500 mm• 700x700 mm• 1000x1000 mm• 1500x1500 mm
The dampers are also available in custom sizes with steps of 100 mm in each direction between the limits.
TypeDimensions (mm) and Weights (kg)
A B C D E F G H Depth
HV-300x300 300 300 410 410 360 360 105 105 500
HV-500x500 500 500 610 610 560 560 130 130 500
HV-700x700 700 700 810 810 760 760 80 80 500
HV 1000x1000 1000 1000 1110 1110 1060 1060 80 80 500
HV 1500x1500 1500 1500 1610 1610 1560 1560 105 105 500
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Dimensions in mm
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
pra air flow adjustment dampers• Airflow balancing, adjustment and measurement unit.• Manual adjustment, no tools required.• Accurate airflow measurement based on flow nozzle principle.• Reduced sound generation due to conical adjustment section.• Temperature operation range from -30 °C to +70 °C.• Self-locking adjustment mechanism; position can be ensured with locking screw.• Duct cleaning enabled through the unit up to size 315.• Adjustment position marker indicates proper position (e.g. repositioning after cleaning).• Inlet and outlet spigots have integral rubber gaskets.• Application option as supply air jet nozzle for air diffusion in large spaces.• Classification of casing leakage EN 1751 class C.
Qmin 1 m/s duct velocity Qmax 6 m/s duct velocity
Part Material Note
Casing Galvanized steel -
Blades Galvanized steel -
Operating mechanism ABS and PBT classic Sizes 100...315
Duct gaskets 1C-polyurethane hybrid -
Measurement taps Polyurethane -
ØD (mm)
Qmin (l/s) m3/h Qmax m3/h
100 8 28 47 170
125 12 44 74 265
160 20 72 121 434
200 31 113 188 679
250 49 177 298 1060
315 78 281 468 1683
350 96 346 577 2078
400 126 452 754 2714
500 196 707 1178 4241
630 312 1122 1870 6733
800 503 1810 3016 10857
1000 785 2827 4712 16965
PRA 100...315
NS ØD
100 99
125 124
160 159
200 199
250 249
315 214
PRA 315...1000
NS ØD H
350 349 70
400 399 70
500 499 70
630 629 70
800 799 70
1000 999 85
Dimensions in mm
Dimensions in mm
www.heinenhopman.com
Heinen & Hopman encourages a more
sustainable world. By providing eco-friendly solutions and serviceswe offer our clients
the option of reducing energy consumption
and thus co2 emissions. Visit
greenmanifest.info for more information.
BrazilT: +5521 3587 4241/4244E: [email protected]
France - La CiotatT: +334 4204 8685E: [email protected]
France - GrasseT: +336 3090 7786 E: [email protected]
GermanyT:+49 4073 1680E: [email protected]
IndiaT: +9133 6499 1293E: [email protected]
ItalyT: +3901 8745 7970E: [email protected]
The Netherlands (HQ)T: +313 3299 2500E: [email protected]
The Netherlands (rotterdam)T: +317 8890 8050E: [email protected]
NorwayT: +47 6919 0900E: [email protected]
peoples republic of ChinaT: +8621 3253 2896E: [email protected]
peoples republic of ChinaT: +86 510 8528 1763E: [email protected]
polandT: +489 1433 1800E: [email protected]
romaniaT: +402 3644 8222E: [email protected]
russiaT: +7 (4012) 308 801E: [email protected]
singaporeT: +65 6897 7879E: [email protected]
south KoreaT: +8270 4901 0000E: [email protected]
spainT: +349 3225 9668E: [email protected]
swedenT: +46 3121 7500E: [email protected]
TurkeyT: +9021 6493 8118E: [email protected]
Uae (abu dhabi) T:+971 2550 4147E: [email protected]
Uae (dubai)T: +971 4263 5453E: [email protected]
Usa - Fort Lauderdale, FloridaT: +195 4463 0110E: [email protected]
Usa - Houma, Louisiana T: +198 5876 7989E: [email protected]