704 REFRIGERATION HERMETIC CONDENSING UNITS DANFOSS-MANEUROP REFRIGERATION HERMETIC CONDENSING UNITS Air Cooled: CMT/CMTE/CLT/CLTE Water Cooled: CMW/CMEW/CLW/CLEW 60 Hz R-22, R-407C, R-134a, R-404A, R-507, R-502 Air Cooled Condensing Units Type CMT(E) and CLT(E) include: Maneurop compressor with oil level sight glass and rotolock service valves. Dual fan condenser with guards and end covers. High capacity receiver with liquid shutoff valve. Prewired electrical box with contactor and with start kit or transformer when appropriate. PTC compressor crankcase heater (prewired). Dual pressure control (prewired). Air Cooled Units Water Cooled Condensing Units Type CM(E)W and CL(E)W include: Maneurop compressor with oil level sight glass and rotolock service valves. Tube in tube water cooled condenser with water regulating valve mounted. High capacity receiver with liquid shutoff valve. Prewired electrical box with contactor and with start kit or transformer when appropriate. Dual pressure control (prewired). Water Cooled Units CMT High to Medium Temp. R-22 CMTE High to Medium Temp. R-134a CMT Medium to Low Temp. R-502 CMTE Med. to Low Temp. R-404A/R-507 CLTE Extra Low Temp. R-404A/R-507 CLT Extra Low Temp. R-502 CMW High to Medium Temp. R-22 CMEW High to Medium Temp. R-134a CMW Medium to Low Temp. R-502 CMEW Med. to Low Temp. R-404A/R-507 CLEW Extra Low Temp. R-404A/R-507 CLW Extra Low Temp. R-502

DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

Embed Size (px)

Citation preview

Page 1: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

704

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROPREFRIGERATION HERMETIC

CONDENSING UNITS

Air Cooled: CMT/CMTE/CLT/CLTEWater Cooled: CMW/CMEW/CLW/CLEW

60 Hz

R-22, R-407C, R-134a, R-404A, R-507, R-502

Air Cooled Condensing Units Type CMT(E) and CLT(E) include:

• Maneurop compressor with oil level sight glass and rotolock service valves.• Dual fan condenser with guards and end covers.• High capacity receiver with liquid shutoff valve.• Prewired electrical box with contactor and with start kit or transformer when appropriate.• PTC compressor crankcase heater (prewired).• Dual pressure control (prewired).Air Cooled Units

Water Cooled Condensing Units Type CM(E)W and CL(E)W include:

• Maneurop compressor with oil level sight glass and rotolock service valves.• Tube in tube water cooled condenser with water regulating valve mounted.• High capacity receiver with liquid shutoff valve.• Prewired electrical box with contactor and with start kit or transformer when appropriate.• Dual pressure control (prewired).

Water Cooled Units

CMT High to Medium Temp. R-22CMTE High to Medium Temp. R-134aCMT Medium to Low Temp. R-502CMTE Med. to Low Temp. R-404A/R-507CLTE Extra Low Temp. R-404A/R-507CLT Extra Low Temp. R-502

CMW High to Medium Temp. R-22CMEW High to Medium Temp. R-134aCMW Medium to Low Temp. R-502CMEW Med. to Low Temp. R-404A/R-507CLEW Extra Low Temp. R-404A/R-507CLW Extra Low Temp. R-502

Page 2: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

705

REFRIGERATION HERMETIC CONDENSING UNITS

Condensing Unit Nomenclature

CM(T) E W - 50 - 3 - AA

Model SeriesCM(T) = Condensing Unit with MT CompressorCL(T) = Condensing Unit with LT Compressor

NOTE: The “T” is left out for water-cooled units

Type of OilE = P.O.E. oil (polyolester oil)Space left blank = Mineral Oil

Condenser TypeSpace left blank = Air CooledW = Water Cooled

Bill of Material CodeAA = Standard Product

Unit Power Supply1 = (208-230/1/60)3 = (208-230/3/60)4 = (460/3/60)

Compressor Size

How to Order:

To order a condensing unit, the following is required:

1. Model series2. Type of oil3. Condenser type4. Compressor size5. Unit power supply6. BOM CodeExample:

To order a 460/3/60 water cooled condensing unit with POEoil and a MT 50 compressor, the model number is:

CMT E W - 50 - 4 - AA

1 2 3 4 5 6

SPECIAL BULLETINS

It is impossible to list complete details for all lines, but we will gladly furnishspecial catalogs and bulletins upon request.

Page 3: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

706

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMT/CMTE/CLT/CLTE AIR COOLEDCONDENSING UNITSPerformance Data — CMT High-to-Medium Temperature — R-22

Low Profile Units

Standard Units

NOTES:1. Btu/h = Capacity.2. kW = Total Input Power including fans.

3. Rated Conditions: 65° F/*40° F Return Gas, 5° F Subcooling, 60 Hzoperation.

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)40 30 25 20 10 0 -10*

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMT1890 15,060 1.70 12,280 1.56 11,000 1.47 9,730 1.39 7,350 1.22 5,340 1.05 3300 0.8695 14,350 1.74 11,770 1.59 10,540 1.50 9,320 1.44 7,020 1.23 5,120 1.06 3150 0.89

100 13,650 1.78 11,260 1.62 10,080 1.53 8,910 1.46 6,710 1.25 4,890 1.07

CMT2290 20,740 2.23 16,760 2.02 14,910 1.91 13,160 1.80 9,960 1.58 7,210 1.35 4900 1.0795 19,840 2.28 16,120 2.06 14,220 1.95 12,520 1.83 9,420 1.60 6,740 1.36 4500 1.08

100 18,940 2.33 15,440 2.10 13,530 1.98 11,890 1.86 8,900 1.62 6,280 1.38

CMT2890 26,230 3.12 21,440 2.75 19,100 2.57 16,890 2.40 12,840 2.06 9,260 1.73 8200 1.6395 25,220 3.20 20,700 2.83 18,470 2.64 16,340 2.46 12,430 2.10 8,960 1.75 7750 1.64

100 24,260 3.28 20,000 2.89 17,850 2.70 15,780 2.52 12,000 2.14 8,660 1.78

CMT3290 23,120 3.25 20,670 3.04 18,350 2.84 14,010 2.44 10,160 2.05 8750 1.8995 22,360 3.32 19,980 3.10 17,730 2.89 13,540 2.48 9,820 2.07 8200 1.91

100 21,590 3.38 19,290 3.16 17,120 2.95 13,070 2.52 9,490 2.10

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)40 30 25 20 10 0 -10*

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMT36

90 36,060 3.96 29,900 3.61 27,010 3.44 24,250 3.27 19,170 2.95 14,670 2.63 11,100 1.8795 34,740 4.07 28,780 3.70 25,970 3.52 23,290 3.34 18,330 3.00 13,920 2.67 10,450 1.91

100 33,420 4.18 27,650 3.79 24,920 3.60 22,320 3.41 17,490 3.05 13,160 2.71110 30,720 4.41 25,340 3.97 22,790 3.76 20,340 3.55 15,790 3.16

CMT50

90 47,090 5.45 37,890 4.96 33,760 4.72 29,950 4.48 23,260 4.00 17,780 3.54 13,020 2.6795 45,290 5.58 36,400 5.07 32,400 4.82 28,700 4.57 22,220 4.08 16,880 3.61 12,280 2.73

100 43,480 5.70 34,900 5.17 31,040 4.91 27,460 4.66 21,180 4.16 15,980 3.68110 39,810 5.93 31,870 5.37 28,280 5.09 24,940 4.83 19,100 4.30

CMT64

90 60,450 6.92 49,150 6.30 43,960 5.99 39,070 5.68 30,270 5.05 22,740 4.43 15,910 2.9395 58,240 7.11 47,340 6.46 42,310 6.13 37,570 5.81 29,020 5.16 21,660 4.52 15,090 2.97

100 56,050 7.29 45,560 6.61 40,700 6.27 36,110 5.93 27,820 5.26 20,640 4.60110 51,750 7.64 42,070 6.88 37,570 6.52 33,300 6.15 25,550 5.43

CMT72

90 65,530 7.58 53,770 6.86 48,300 6.52 43,100 6.18 33,580 5.53 25,280 4.90 18,460 3.8695 63,180 7.81 51,840 7.06 46,540 6.69 41,510 6.34 32,270 5.66 24,150 5.02 17,570 3.96

100 60,820 8.04 49,940 7.26 44,840 6.88 39,980 6.51 31,020 5.81 23,100 5.14110 56,230 8.55 46,300 7.68 41,580 7.28 37,070 6.88 28,720 6.12

CMT100

90 89,900 10.41 72,970 9.69 65,250 9.33 58,030 8.96 45,110 8.21 34,190 7.45 24,450 5.8095 86,270 10.68 69,900 9.89 62,420 9.60 55,410 9.11 42,850 8.31 32,180 7.51 22,710 5.84

100 82,720 10.95 66,910 10.10 59,680 9.67 52,880 9.25 40,690 8.41 30,280 7.57110 75,800 11.51 61,190 10.51 54,460 10.03 48,110 9.55 36,700 8.61 26,840 7.69

CMT125

90 118,300 13.25 96,840 12.18 86,980 11.66 77,750 11.14 60,980 10.13 46,660 9.14 33,670 7.2095 113,540 13.60 92,930 12.47 83,500 11.92 74,530 11.38 58,330 10.32 44,420 9.30 31,880 7.33

100 108,800 13.95 89,130 12.75 79,990 12.17 71,350 11.61 55,740 10.51 42,260 9.45110 99,410 14.61 81,410 13.29 73,040 12.65 65,130 12.03 50,730 10.84 38,150 9.71

CMT144

90 133,330 14.69 109,390 13.47 98,360 12.88 88,060 12.29 69,350 11.15 53,330 10.06 39,060 8.0695 127,780 15.08 104,950 13.78 94,320 13.16 84,300 12.56 66,250 11.37 50,760 10.23 36,910 8.19

100 122,420 15.45 100,410 14.09 90,310 13.44 80,670 12.80 63,270 11.57 48,230 10.40110 111,520 16.18 91,510 14.68 82,300 13.96 73,460 13.27 57,470 11.94 43,460 10.68

CMT160

90 144,830 16.50 118,940 15.08 107,040 14.39 95,830 13,72 75,570 12.43 58,180 11.18 42,440 9.0395 138,960 16.93 114,070 15.43 102,610 14.71 91,800 14.01 72,230 12.66 55,400 11.37 40,250 9.16

100 133,130 17.35 109,240 15.77 98,220 15.01 87,810 14.28 68,960 12.88 52,720 11.54110 121,410 18.17 99,620 16.42 89,510 15.59 79,960 14.79 62,600 13.27 47,590 11.84

Page 4: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

707

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMT/CMTE/CLT/CLTE AIR COOLEDCONDENSING UNITSPerformance Data — CMT High-to-Medium Temperature — R-134a

Low Profile Units

Standard Units

NOTES:1. Btu/h = Capacity.2. kW = Total Input Power including fans.

3. Rated Conditions: 20° F Superheat, 5° F Subcooling, 60 Hzoperation.

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)50 40 30 25 20 10 0

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMTE1890 13,800 1.63 11,200 1.52 8,900 1.40 7,850 1.35 6,800 1.29 5000 1.18 3600 1.0895 13,300 1.67 10,700 1.55 8,500 1.42 7,450 1.37 6,400 1.31 4800 1.20 3300 1.09

100 12,800 1.69 10,300 1.57 8,100 1.44 7,100 1.38 6,100 1.32 4500 1.21 3000 1.10

CMTE2290 18,000 1.92 14,400 1.78 11,800 1.64 10,200 1.57 8,600 1.50 6400 1.37 4800 1.2495 17,200 1.96 13,900 1.81 11,200 1.66 9,750 1.59 8,300 1.52 6100 1.38 4400 1.25

100 16,600 1.99 13,300 1.84 10,500 1.69 9,300 1.61 7,900 1.54 5700 1.40 4000 1.26

CMTE2890 21,400 2.38 18,000 2.17 13,600 1.98 12,100 1.89 10,600 1.79 9900 1.62 5700 1.4595 20,500 2.41 17,400 2.21 13,000 2.01 11,500 1.91 10,000 1.82 7400 1.64 5200 1.47

100 19,900 2.46 16,700 2.24 12,400 2.04 11,000 1.94 9,600 1.84 6900 1.66 4800 1.48

CMTE3290 23,200 2.64 18,900 2.41 15,000 2.18 13,300 2.08 11,600 1.97 8500 1.76 6200 1.5795 22,200 2.69 18,000 2.44 14,300 2.25 12,650 2.11 11,000 2.00 8100 1.78 5700 1.59

100 21,300 2.73 17,300 2.47 13,400 2.24 11,900 2.13 10,400 2.02 7600 1.81 5200 1.60

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)50 40 30 25 20 10 0

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMTE36

90 27,500 3.18 22,400 2.95 17,600 2.72 15,600 2.61 13,600 2.50 10,100 2.28 7,200 2.0795 26,500 3.25 21,500 2.99 16,800 2.76 14,850 2.65 12,900 2.53 9,600 2.30 6,700 2.09

100 25,400 3.30 22,400 3.04 16,000 2.81 14,050 2.69 12,100 2.56 8,700 2.33 6,000 2.11110 23,600 3.40 18,800 3.12 14,500 2.86 12,650 2.74 10,800 2.61 7,800 2.37 5,000 2.14

CMTE50

90 44,000 4.43 33,400 4.10 26,000 3.77 23,000 3.61 20,000 3.44 15,000 3.11 11,000 2.7995 40,000 4.53 32,000 4.18 24,800 3.84 21,900 3.66 19,000 3.48 14,000 3.15 10,200 2.82

100 38,200 4.63 30,800 4.27 23,600 3.90 20,800 3.72 18,000 3.54 13,000 3.19 9,400 2.85110 35,200 4.80 28,200 4.45 21,200 4.01 18,600 3.83 16,000 3.64 11,200 3.27 7,500 2.91

CMET64

90 51,000 4.95 41,000 4.54 32,000 4.15 28,300 3.97 24,600 3.78 18,000 3.40 13,000 3.0495 49,000 5.05 39,000 4.63 31,000 4.22 27,150 4.03 23,300 3.83 17,000 3.44 12,000 3.06

100 47,500 5.25 37,500 4.73 29,500 4.30 25,850 4.09 22,200 3.88 16,000 3.49 11,000 3.10110 43,200 5.34 34,500 4.88 26,900 4.42 23,450 4.21 20,000 4.00 14,000 3.58 9,200 3.16

CMTE72

90 56,400 5.48 45,400 5.02 35,700 4.58 31,850 4.36 28,000 4.14 20,500 3.72 15,000 3.3195 54,800 5.59 43,800 5.12 34,000 4.66 30,100 4.44 26,200 4.21 19,200 3.76 13,900 3.35

100 52,500 5.69 42,000 5.22 32,200 4.75 28,600 4.51 25,000 4.27 18,000 3.81 12,500 3.38110 48,000 5.93 38,000 5.39 29,200 4.88 25,600 4.63 22,000 4.38 15,800 3.92 10,000 3.46

CMTE100

90 78,500 8.33 64,000 7.67 52,000 7.04 45,500 6.73 39,000 6.41 28,500 5.80 21,500 5.2395 74,000 8.70 61,500 7.81 49,000 7.15 43,000 6.83 37,000 6.50 27,000 5.88 20,000 5.27

100 73,000 8.85 58,800 7.95 47,000 7.28 41,000 6.94 35,000 6.60 25,500 5.95 19,000 5.33110 54,000 8.16 42,000 7.45 36,500 7.10 31,000 6.74 22,000 6.08 15,000 5.43

CMTE125

90 102,000 8.41 82,000 7.90 65,000 7.42 57,500 7.08 50,000 6.73 36,000 6.08 26,000 5.5595 98,000 8.51 79,000 8.03 62,000 7.43 54,500 7.20 47,000 6.97 34,000 6.45 24,000 5.86

100 95,000 8.56 75,500 8.14 59,000 7.62 51,500 7.36 44,000 7.13 32,000 6.59 22,000 6.00110 87,000 8.88 69,000 8.18 53,000 7.78 46,500 7.55 40,000 7.32 28,000 6.78 18,000 6.17

CMTE144

90 115,000 10.84 92,000 10.00 72,000 9.14 64,000 8.72 56,000 8.30 42,000 7.47 30,000 6.6795 111,000 11.13 89,000 10.23 69,000 9.32 61,250 8.87 53,500 8.42 39,000 7.58 28.000 6.73

100 106,000 11.33 85,000 10.42 66,000 9.47 58,000 9.02 50,000 8.56 37,000 7.66 25,000 6.81110 98,000 11.80 78,000 10.76 60,000 9.75 52,250 9.28 44,500 8.80 32,000 7.86 21,000 6.95

CMTE160

90 126,000 12.16 102,000 11.12 80,000 10.13 71,000 9.64 62,000 9.15 46,000 8.20 33,000 7.2795 121,500 12.40 97,000 11.39 76,000 10.34 67,500 9.83 59,000 9.31 43,000 8.32 30,500 7.36

100 118,000 12.63 94,000 11.58 73,000 10.51 64,500 9.62 56,000 9.44 40,000 8.42 28,000 7.44110 108,000 13.15 88,000 11.95 65,500 10.79 57,750 10.24 50,000 9.68 35,000 8.64 23,200 7.61

Page 5: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

708

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMT/CMTE/CLT/CLTE AIR COOLEDCONDENSING UNITSPerformance Data — CMT Medium-to-Low Temperature — R-502

Low Profile Units

Standard Units

NOTES:1. Btu/h = Capacity.2. kW = Total Input Power including fans.3. Rated Conditions: 65° F/40° F Return Gas, 5° F Subcooling, 60 Hz operation.

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)25 20 10 0 –10 –20

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMT1890 11,880 1.57 10,700 1.50 8,210 1.30 5,700 1.10 3,870 1.00 2400 0.7295 11,380 1.60 10,250 1.55 7,740 1.34 5,330 1.13 3,590 1.03 2150 0.75

100 10,890 1.63 9,800 1.60 7,400 1.38 4,950 1.15 3,300 1.05 1900 0.77

CMT2290 15,440 1.98 13,880 1.87 10,960 1.60 8,030 1.36 5,390 1.10 2980 0.8495 14,650 2.03 13,170 1.91 10,370 1.64 7,590 1.39 5,060 1.13 2720 0.87

100 13,860 2.07 12,460 1.94 9,760 1.67 7,150 1.42 4,720 1.15 2470 0.89

CMT2890 20,630 2.75 18,580 2.60 15,900 2.25 13,220 1.90 9,500 1.75 5800 1.4895 19,950 2.82 17,980 2.66 15,340 2.30 12,860 1.95 9,040 1.79 5460 1.51

100 19,280 2.89 17,360 2.72 14,780 2.36 12,510 2.00 8,550 1.83 5100 1.54

CMT3290 22,320 3.26 20,190 3.05 17,140 2.63 14,080 2.20 10,240 2.05 7000 1.7595 21,580 3.32 19,500 3.10 16,530 2.68 13,500 2.25 9,790 2.10 6640 1.78

100 20,830 3.38 18,830 3.15 15,920 2.72 13,060 2.30 9,340 2.15 6280 1.81

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)25 20 10 0 –10 –20

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMT36

90 27,950 3.61 25,540 3.44 20,820 3.08 16,320 2.70 12,060 2.31 8,080 1.9295 26,750 3.72 24,450 3.54 19,950 3.16 15,630 2.77 11,520 2.36 7,660 1.96

100 25,510 3.82 23,330 3.63 19,050 3.23 14,910 2.83 10,950 2.42 7,220 2.01110 22,910 4.01 20,970 3.80 17,140 3.37 13,380 2.94 9,740 2.51 6,270 2.08

CMT50

90 37,020 5.20 33,570 4.99 27,040 4.55 21,090 4.09 15,710 3.61 10,930 3.1395 35,320 5.30 32,010 5.08 25,730 4.61 19,980 4.13 14,770 3.63 10,120 3.14

100 33,620 5.40 30,450 5.16 24,440 4.67 18,890 4.16 13,840 3.65 9,330 3.16110 30,180 5.58 27,310 5.31 21,830 4.77 16,720 4.22 12,030 3.67 7,790 3.17

CMT64

90 46,310 6.55 42,030 6.22 33,930 5.57 26,590 4.94 20,030 4.31 14,250 3.7195 44,190 6.67 40,020 6.32 32,150 5.63 24,990 4.96 18,560 4.33 12,880 3.69

100 42,120 6.80 38,090 6.42 30,470 5.69 23,490 4.99 17,190 4.35 11,620 3.67110 38,230 7.08 34,500 6.65 27,390 5.83 20,800 5.05 14,780 4.37 9,400 3.62

CMT72

90 51,560 7.28 46.860 6.92 37,940 6.21 29,780 5.51 22,370 4.82 15,780 4.1695 49,300 7.43 44,790 7.06 36,210 6.32 28,320 5.59 21,130 4.89 14,700 4.21

100 47,060 7.58 42,750 7.19 34,510 6.43 26,890 5.68 19,920 4.95 13,660 4.25110 42,570 7.91 38,670 7.48 31,150 6.66 24,120 5.85 17,610 5.08 11,710 4.35

CMT100

90 69,140 10.13 62,640 9.72 50,380 8,91 39,230 8.13 29,210 7.37 20,360 6.6595 66,160 10.31 59,910 9,87 48,080 9.03 37,280 8.21 27,520 7.44 18,880 6.69

100 63,270 10.48 57,230 10.02 45,910 9.13 35,460 8.29 25,980 7.48 17,530 6.72110 57,780 10.79 52,350 10.29 41,940 9.32 32,250 8.40 23,350 7.54 15,330 6.74

CMT125

90 90,200 12.28 81,570 11.73 65,800 10.69 51,980 9.74 40,140 8.87 30,230 8.0695 85,990 12.56 77,720 11.98 62,590 10.91 49,280 9.93 37,850 9.02 28,270 8.19

100 81,850 12.83 73,950 12.23 59,460 11.11 46,680 10.10 35,680 9.16 26,450 8.31110 73,740 13.34 66,700 12.69 53,490 11.49 41,840 10.40 31,750 9.40 23,250 8.49

CMT144

90 102,190 13.88 92,490 13.24 74,680 12.02 59,060 10.90 45,610 9.88 34,290 8.9395 97,250 14.18 87,980 13,51 70,880 12.25 55,850 11.09 42,880 10.03 31,940 9.06

100 92,390 14.47 83.540 13.77 67,180 12.46 52,760 11.26 40,280 10.17 29,740 9.17110 82,830 15.03 74,860 14.27 60,070 12.86 46,930 11.58 35,500 10.42 25,800 9.36

CMT160

90 110,930 15.83 100,080 15.04 80,240 13.57 62,970 12.24 48,200 11.03 37,790 9.9295 105,950 16.15 94,490 15.33 76,350 13.81 59,650 12.43 45,350 11.18 35,370 10.04

100 101,030 16.47 90,980 15.61 72,540 14.04 56,440 12.61 42,630 11.32 33,100 10.15110 91,340 17.09 82,130 16.17 65,190 14.47 50,340 12.95 37,560 11.57 28,960 10.34

Page 6: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

709

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMT/CMTE/CLT/CLTE AIR COOLEDCONDENSING UNITSPerformance Data — CMTE Medium-to-Low Temperature — R-404A, R-507

Low Profile Units

Standard Units

NOTES:1. Btu/h = Capacity.2. kW = Total Input Power including fans.3. Rated Conditions: 20° F Superheat, 5° F Subcooling, 60 Hz operation.

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)30 25 20 10 0 -10 -20 -25

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMTE1890 13,000 1.98 11,115 1.94 9,880 1.87 7,695 1.71 5,795 1.56 4085 1.39 2660 1.25 1995 1.1395 12,200 2.00 10,403 1.96 9,215 1.88 7,220 1.72 5,320 1.57 3800 1.40 2470 1.26 1710 1.14

100 9,833 1.97 8,645 1.89 6,650 1.73 4,750 1.58 3515 1.41 2185 1.27 1520 1.15

CMTE2290 18,200 2.60 15,580 2.54 13,870 2.43 10,640 2.21 7,980 2.01 5890 1.76 3705 1.54 3040 1.3195 17,300 2.62 14,725 2.56 13,015 2.45 10,070 2.22 7,410 2.02 5320 1.77 3420 1.55 2565 1.32

100 13,918 2.57 12,255 2.47 9,405 2.23 6,840 2.03 5035 1.78 3040 1.56 2185 1.36

CMTE2890 21,200 3.58 18,335 3.41 16,530 3.19 13,585 2.85 10,450 2.54 7600 2.31 5320 2.05 4465 1.8595 15,580 3.21 12,635 2.88 9,595 2.55 7125 2.32 4940 2.06 4180 1.86

100

CMTE3290 20,093 3.79 18,335 3.53 14,915 3.16 11,780 2.76 8645 2.56 6175 2.24 5130 2.0295 13,810 3.18 11,210 2.77 7980 2.57 5700 2.25 4750 2.03

100

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)30 25 20 10 0 -10 -20 -10

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CMTE36

90 28,000 4.69 24,320 4.50 22,040 4.24 18,050 3.83 14,060 3.44 10,070 3.17 7,220 2.82 6,080 2.5795 26,400 4.77 22,990 4.55 20,900 4.28 16,910 3.85 13,110 3.45 9,310 3.18 6,650 2.84 5,700 2.58

100 25,000 4.82 21,565 4.58 19,380 4.30 15,770 3.87 11,970 3.46 8,550 3.19 6,080 2.86 5,130 2.59110 17,290 4.37 13,680 3.89 10,070 3.47 7,220 3.20 5,130 2.88 4,370 2.60

CMTE50

90 43,500 6.15 37,858 5.75 34,390 5.49 27,930 4.91 21,850 4.37 16,150 3.87 11,400 3.37 7,600 3.1795 41,000 6.25 35,673 5.88 32,395 5.57 26,315 4.92 20,710 4.38 15,200 3.88 10,925 3.39 7,315 3.18

100 39,000 6.30 34,438 5.95 31.825 5.62 24,700 4.93 19,190 4.39 14,250 3.89 10,165 3.41 6,650 3.19110 34,400 6.40 27,645 6.07 22,610 5.71 21.850 4.95 17,005 4.43 12,350 3.90 8,550 3.42 5,700 3.20

CMET64

90 51,700 7.75 45,553 7.29 41,990 6.88 33,725 6.08 26,790 5.40 19,950 4.72 14,250 4.07 9,690 3.8295 49,000 7.82 43,225 7.39 39,900 6.96 31,825 6.10 25,555 5.42 19,900 4.73 13,300 4.09 9,215 3.83

100 46,200 7.88 40,565 7.45 37,240 7.01 29,640 6.12 23,750 5.42 17,575 4.74 12,350 4.12 8,455 3.85110 41,500 8.00 36,290 7.57 33,155 7.11 26,125 6.16 20,615 5.44 15,200 4.75 10,650 4.14 6,650 3.87

CMTE72

90 57,500 8.73 50,588 8.26 46,550 7.75 37,050 6.83 29,450 6.06 21,850 5.27 16,150 4.57 10,925 4.2795 54,500 8.80 47,975 8.36 44,175 7.88 34,960 6.85 27,550 6.08 20,710 5.28 15,200 4.59 10,260 4.28

100 51,600 8.89 45,410 8.43 41,800 7.92 32,300 6.89 25,650 6.10 19,000 5.29 14,060 4.61 9,500 4.29110 40,375 8.57 36,860 8.02 28,500 6.90 21,850 6.15 16,340 5.30 11,875 4.63 7,600 4.30

CMTE100

90 80,000 11.30 69,825 10.80 63,650 10.28 56,810 9.44 42,275 8.64 32,300 7.80 24,510 6.80 20,900 6.5095 75,500 11.40 65,883 10.96 60,040 10.40 48,640 9.54 39,900 8.65 30,400 7.81 22,800 6.86 19,950 6.56

100 71,000 11.50 61,988 11.08 56,525 10.52 45,600 9.61 37,050 8.69 28,025 7.82 21,375 6.87 18,715 6.57110 54,625 11.35 49,400 10.79 39,900 9.69 32,300 8.70 24,225 7.83 18,050 6.89 16,150 6.58

CMTE125

90 107,000 13.70 92,625 13.11 83,600 12.57 72,200 11.52 56,050 10.58 41,800 9.55 31,350 8.25 27,550 7.8595 101,500 13.92 87,638 13.45 78,850 12.74 66,500 11.67 53,200 10.60 39,900 9.56 28,595 8.26 25,650 7.86

100 96,000 14.15 82,650 13.61 74,100 12.89 62,700 11.79 49,400 10.61 36,575 9.57 27,550 8.27 24,700 7.87110 84,000 14.55 73,150 13.91 66,500 13.21 53,200 11.93 42,750 10.62 31,350 9.58 23,750 8.28 20,900 7.89

CMTE144

90 120,000 15.28 104,500 14.58 95,000 13.98 76.950 12.82 62,700 11.76 47,500 10.55 36,100 9.10 30,400 8.6595 114,000 15.50 98,800 14.86 89,300 14.14 73,150 12.96 58,900 11.80 45,600 10.56 34,200 9.12 28,500 8.67

100 107,000 15.72 92,625 15.14 83,600 14.34 68,400 13.09 55,100 11.85 41,800 10.57 31,350 9.14 28,600 8.68110 95,000 16.16 82,175 15.50 74,100 14.70 59,850 13.28 47,500 11.89 36,100 10.58 26,600 9.16 22,800 8.69

CMTE160

90 130,000 16.90 113,050 16.76 102,600 15.95 84,550 14.54 68,400 13.28 52,250 11.90 39,900 10.20 33,250 9.7095 122,000 17.20 106,400 17.00 96,900 16.15 79,800 14.70 64,600 13.30 48,450 11.91 37,050 10.21 31,350 9.75

100 115,000 17.60 100,225 17.00 91,200 16.35 74,100 14.86 59,850 13.32 45,600 11.92 35,150 10.22 29,450 9.77110 102,000 18.40 88,825 17.00 80,750 16.75 64,600 15.02 51,300 13.33 38,950 11.93 30,400 10.23 26,600 9.79

Page 7: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

710

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMT/CMTE/CLT/CLTE AIR COOLEDCONDENSING UNITSPerformance Data — CLTE Extra Low Temperature — R-404A, R-507

NOTES:1. Btu/h = Capacity.2. kW = Total Input Power including fans.

3. Rated Conditions: 20° F Superheat, 5° F Subcooling, 60 Hzoperation.

Performance Data — CLT Extra Low Temperature — R-502

NOTES:1. Btu/h = Capacity.2. kW = Total Input Power including fans.

3. Rated Conditions: 40° F/*20° F Return Gas, 5° F Subcooling, 60 Hzoperation.

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)-5 -10 -15 -20 -25 -30 -35 -40

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CLTE22

90 8,000 2.47 7,200 2.19 6,400 2.05 5,700 1.93 4,850 1.81 4,100 1.69 3,400 1.58 2,850 1.4895 7,800 2.50 6,800 2.20 6,000 2.05 5,200 1.92 4,600 1.79 3,900 1.67 3,200 1.55 2,600 1.44

100 7,100 2.53 6,300 2.21 5,600 2.06 4,750 1.91 4,300 1.78 3,500 1.64 2,900 1.52110 6,100 2.59 5,400 2.21 4,750 2.04 4,100 1.88 3,600 1.73 2,900 1.59

CLTE28

90 11,600 3.24 10,400 3.03 9,300 2.83 8,100 2.64 7,000 2.45 6,000 2.29 5,000 2.13 4,000 1.9795 11,000 3.27 9,700 3.05 8,700 2.83 7,600 2.62 6,400 2.42 5,800 2.25 4,600 2.08 3,600 1.96

100 10,300 3.29 9,000 3.06 8,000 2.83 7,000 2.61 6,000 2.40 5,000 2.22 4,100 2.02110 8,600 3.35 8,200 3.07 6,900 2.81 6,000 2.57 5,000 2.28 4,100 2.12

CLTE44

90 19,500 5.43 17,400 5.12 15,200 4.80 13,400 4.49 11,300 4.18 9,600 3.87 8,400 3.57 7,000 3.2595 18,000 5.45 16,000 5.13 14,000 4.81 12,200 4.49 10,400 4.16 9,000 3.85 7,700 3.53 8,300 3.22

100 17,000 5.45 14,700 5.13 13,000 4.81 11,400 4.48 9,600 4.15 8,400 3.82 7,000 3.50 5,800 3.18110 14,400 5.47 12,800 5.12 11,100 4.77 9,600 4.43 8,200 4.09 6,900 3.76 5,900 3.44 4,800 3.11

CLTE50

90 22,600 6.88 20,000 6.47 18,200 6.05 16,000 5.65 14,400 5.27 12,000 4.90 10,400 4.54 8,400 4.2095 21,000 6.93 19,200 6.49 16,800 6.07 15,000 5.67 13,200 5.27 11,400 4.89 9,700 4.52 8,000 4.17

100 19,600 6.97 17,800 6.51 15,800 6.07 14,000 5.66 12,100 5.27 10,400 4.87 8,900 4.49 7,800 4.13110 16,800 7.05 15,300 6.55 13,500 6.08 12,000 5.62 10,300 4.76 8,600 4.78 7,300 4.38

CLTE88

90 37,000 9.68 33,400 9.13 29,000 8.56 25,200 7.99 21,900 7.42 18,400 6.85 15,800 6.28 12,900 5.7095 35,100 9.81 31,200 9.19 27,200 8.59 23,900 7.99 20,300 7.39 17,300 6.78 14,400 6.20 11,800 5.60

100 32,800 9.89 29,000 9.26 25,200 8.63 21,900 7.99 18,600 7.36 15,800 6.72 13,000 6.10 10,400 5.47110 28,300 10.06 24,400 9.33 21,600 8.62 18,400 7.91 16,000 7.23 12,800 6.55 10,200 5.91 8,300 5.26

CLTE100

90 48,000 12.02 42,500 11.22 38,000 10.45 33,000 9.72 28,500 8.99 24,000 8.28 20,500 7.59 16,500 6.9095 45,200 12.14 40,000 11.33 35,300 10.52 30,500 9.75 27,000 8.99 22,500 8.24 19,000 7.53 15,000 6.81

100 42,500 12.26 38,000 11.39 33,000 10.58 29,000 9.78 24,800 8.99 21,000 8.21 17,500 7.47 13,500 6.73110 36,500 12.49 32,500 11.54 28,500 10.61 24,500 9.74 21,000 8.89 17,500 8.07 14,000 7.28 10,000 6.54

MODELSAMBIENT

TEMP(°F)

EVAPORATING TEMPERATURE (°F)-5 -10 -15 -20 -25 -30 -35 -40

Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CLT22

90 8,835 2.22 7,820 1.97 6,880 1.75 5,940 1.53 5,080 1.50 4,220 1.46 3,435 1.32 2,650 1.1895 8,335 2.26 7,350 2.01 6,435 1.78 5,520 1.54 4,685 1.50 3,850 1.46 3,325 1.33 2,800 1.19

100 7,845 2.30 6,890 2.04 6,000 1.80 5,110 1.55 4,290 1.51 3,470 1.47110 6,885 2.39 5,990 2.11 5,150 1.84 4,310 1.57 3,530 1.52 2,750 1.47

CLT28

90 12,715 2.96 11,260 2.76 10,000 2.57 8,740 2.37 7,685 2.18 6,630 1.98 5.715 1.79 4,800 1.6095 12,105 2.99 10,700 2.78 9,475 2.58 8,250 2.38 7,225 2.18 6,200 1.98 5,305 1.79 4,410 1.60

100 11,485 3.02 10,130 2.81 8,940 2.60 7,750 2.39 6,755 2.19 5,760 1.98 4,890 1.79 4,020 1.59110 10,190 3.08 8,930 2.85 7,820 2.63 6,710 2.41 5,780 2.20 4,850 1.98

CLT44

90 20,035 4.38 17,860 4.15 15,865 3.90 13,870 3.65 12,075 3.39 10,280 3.12 8,635 2.85 6,990 2.5895 18,920 4.40 16,830 4.16 14,905 3.90 12,980 3.64 11,250 3.37 9,520 3.10 7,920 2.83 6,320 2.55

100 17,830 4.42 15,820 4.17 13,975 3.91 12,130 3.64 10,455 3.36 8,780 3.08 7,225 2.80 5,670 2.52110 15,675 4.49 13,860 4.22 12,170 3.93 10,480 3.64 8,925 3.35 7,370 3.05

CLT50

90 24,900 5.77 22,270 5.43 19,880 5.07 17,490 4.70 15,370 4.33 13,250 3.96 11,300 3.58 9,350 3.2095 23,590 5.85 21,050 5.49 18,730 5.12 16,410 4.74 14,345 4.36 12,280 3.97 10,365 3.58 8,450 3.19

100 22,320 5.94 19,870 5.56 17,620 5.17 15,370 4.77 13,355 4.37 11,340 3.97 9,470 3.58 7,600 3.18110 19,850 6.10 17,590 5.67 15,485 5.24 13,380 4.81 11,475 4.39 9,570 3.96 7,785 3.55 6,000 3.13

CLT88

90 40,010 8.74 35,360 8.15 31,245 7.62 27,130 7.08 23,585 6.59 20,040 6.09 16,930 5.64 13,820 5.1995 37,800 8.78 33,370 8.12 29,435 7.60 25,500 7.08 22,100 6.57 18,700 6.06 15,700 5.59 12,700 5.12

100 35,620 8.90 31,420 8.22 27,670 7.67 23,920 7.11 20,665 6.58 17,410 6.04 14,520 5.55 11,630 5.06110 31,325 9.21 27,590 8.50 24,225 7.86 20,860 7.21 17,910 6.63 14,960 6.05

CLT100

90 49,320 11.64 44,040 10.76 39,325 10.01 34,610 9.25 30,500 8.60 26,390 7.94 22,745 7.38 19,100 6.8195 46,620 11.75 41,660 10.85 37,155 10.08 32,650 9.30 27,235 8.63 21,820 7.96 19,820 7.39 17,820 6.81

100 43,940 11.86 39,280 10.15 35,020 10.15 30,760 9.36 27,040 8.68 23,320 7.99 19,970 7.40 16,620 6.81110 38,665 12.11 34,610 10.31 30,865 10.31 27,120 9.48 23,825 8.77 20,530 8.05 17,505 7.43 14,480 6.81

Page 8: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

711

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMT/CMTE/CLT/CLTE AIR COOLEDCONDENSING UNITSTechnical Specifications — Air Cooled Units

*Voltage Code.MCA = Minimum Circuit AmpacityMFS = Maximum Fuse Size

FLA = Full Load AmperageNOTE: Units with voltage code 1 or 3 have 208-230/1/60 fan motors. Unitswith voltage code 4 have 460/1/60 fan motors.

*Voltage Code.NOTE: CMT(E) indicates CMT or CMTE. CLT(E) indicates CLT or CLTE.

ELECTRICAL

CONDENSINGUNIT MODEL

COMPRESSORMODEL

VOLTAGE CODE FAN MOTOR (each)

1208-230/1/60

3208-230/3/60

4460/3/60 Hp Rpm

Voltage Code1 & 3 4

MCA MFS MCA MFS MCA MFS FLA FLACMT(E)18*A3 MT(Z)18JA 13.6 20 10.0 15 4.1 15

1/15 1550 1.0 0.5CMT(E)22*B3 MT(Z)22JC 17.1 25 11.9 20 5.0 15CMT(E)28*B3 MT(Z)28JE 24.4 40 17.1 25 7.3 15CMT(E)32*B3 MT(Z)32JF 25.3 40 19.9 30 8.1 15CMT(E)36*E1 MT(Z)36JG 30.6 50 23.4 35 9.0 15 1/4 1075 1.8 0.5CMT(E)50*F1 MT(Z)50HK 36.6 60 24.1 40 12.8 20

1/3 1075 1.8 1.0CMT(E)64*G1 MT(Z)64HM 51.0 80 31.2 50 15.4 25CMT(E)72*H1 MT(Z)72HN 30.4 50 15.4 25CMT(E)100*K1 MT(Z)100HS 48.6 75 23.4 35

1/2 1075 3.7 1.9CMT(E)125*L1 MT(Z)125HU 58.5 90 27.9 45CMT(E)144*M1 MT(Z)144HV 67.3 100 30.6 50CMT(E)160*M1 MT(Z)160HW 72.7 110 35.9 60

CLT(E)22*A3 LT(Z)22JE 17.2 25 11.8 20 5.0 151/15 1550 1.0 0.5

CLT(E)28*B3 LT(Z)28JH 24.3 40 17.2 25 5.7 15CLT(E)44*D1 LT(Z)44HM 34.0 50 23.2 35 9.9 15

1/4 1075 1.8 0.5CLT(E)50*E1 LT(Z)50HP 36.6 60 24.1 40 11.7 20CLT(E)88*G1 LT(Z)88HU 34.9 60 17.2 25

1/3 1075 1.8 1.0CLT(E)100*J1 LT(Z)100HW 42.0 70 21.6 35

MECHANICAL

CONDENSINGUNIT MODEL

COMPRESSORMODEL

DIMENSIONS (in.) CONNECTIONS (in.)RECEIVERCAPACITY(lb @ 90%)

CONDENSERAIRFLOW

APPROX.SHIPPING

WT (lb)L W HMountingCenters Liquid

(Flare)Suction(ODS)

ML MW CFM Fan (in.)CMT(E)18*A3 MT(Z)18JA

28-3/8 25 14-1/2 27-3/8 15-5/16 3/8 5/8 10.0 1300 11

160CMT(E)22*B3 MT(Z)22JC 165CMT(E)28*B3 MT(Z)28JE 170CMT(E)32*B3 MT(Z)32JF 170CMT(E)36*E1 MT(Z)36JG 39-3/8 27-1/2 22-1/2 37-3/8 19-1/2 1/2 5/8 17.5 2050 14 265CMT(E)50*F1 MT(Z)50HK

47-5/8 35-1/2 24-1/2 45-5/8 21-5/8 1/2 7/8 19.5 4400 18 355CMT(E)64*G1 MT(Z)64HMCMT(E)72*H1 MT(Z)72HN 47-5/8 35-1/2 24-1/2 45-5/8 21-5/8 1/2 1-1/8 26.0 4400 18 360CMT(E)100*K1 MT(Z)100HS 59-1/2 35-1/2 26-1/2 57-1/2 21-5/8 1/2 1-1/8 36.0 7800 22 465CMT(E)125*L1 MT(Z)125HU 59-1/2 35-1/2 30-1/2 57-1/2 21-5/8 1/2 1-1/8 36.0 7800 22 510CMT(E)144*M1 MT(Z)144HV

59-1/2 35-1/2 34-1/2 57-1/2 21-5/8 1/2 1-3/8 43.0 7800 22545

CMT(E)160*M1 MT(Z)160HW 555CLT(E)22*A3 LT(Z)22JE

28-3/8 31-1/2 14-1/2 27-3/8 19-1/2 3/8 5/8 10.0 1300 11165

CLT(E)28*B3 LT(Z)28JH 170CLT(E)44*D1 LT(Z)44HM 39-3/8 31-1/2 22-1/2 37-3/8 19-1/2 1/2 7/8 17.5 2050 14 290CLT(E)50*E1 LT(Z)50HP 39-3/8 31-1/2 22-1/2 37-3/8 19-1/2 1/2 7/8 26.0 2050 14 355CLT(E)88*G1 LT(Z)88HU 47-5/8 35-1/2 24-1/2 45-5/8 21-5/8 1/2 1-1/8 26.0 4400 18 400CLT(E)100*J1 LT(Z)100HW 47-5/8 35-1/2 26-1/2 45-5/8 21-5/8 1/2 1-1/8 36.0 4400 18 410

P4127

*Hole patterns: 4 holes 5/16-in. bolt, 0.354 in. diameter of hole.

Page 9: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

712

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMW/CMEW/CLW/CLEW WATER COOLEDCONDENSING UNITSPerformance Data — CMW High-to-Medium Temperature — R-22

Btu/h = Capacity.kW = Input Power.GPM = Water Flow in gpm.PSI = Water Pressure Drop through condenser in psi.

Rated Conditions: 65° F/*40° F Return Gas, 5° F Subcooling, 60 Hz operation, 105° F Condensing, 75° F Entering Water (30° ITD).For 20° ITD (ITD = condensing temperature - entering water temperature) allow 3 gpm/ton water flow.

MODELEVAPORATING TEMPERATURE (°F)

40 30 25 20 10 0 -10*

CMW18

Btu/h 17,000 12,800 11,000 9400 6700 4550 2940kW 1.43 1.34 1.29 1.23 1.10 0.96 0.80

GPM 1.9 1.3 1.1 0.9 0.6 0.4 0.3PSI 2.2 1.3 1.0 0.7 0.4 0.3 0.1

CMW22

Btu/h 23,350 18,150 15,850 13,700 10,000 6850 4230kW 1.88 1.77 1.69 1.61 1.42 1.21 0.98

GPM 3.1 2.2 1.8 1.5 1.0 0.7 0.4PSI 4.8 2.8 2.1 1.6 0.9 0.5 0.2

CMW28

Btu/h 31,250 25,050 22,250 19,600 15,000 10,900 7450kW 2.48 2.38 2.31 2.23 2.03 1.79 1.54

GPM 3.3 2.5 2.2 1.9 1.5 1.2 0.9PSI 1.8 1.2 0.9 0.8 0.6 0.4 0.3

CMW36

Btu/h 39,350 31,800 28,350 25,100 19,400 14,300 9940kW 3.30 3.11 2.99 2.87 2.61 2.33 2.05

GPM 5.2 3.7 3.2 2.7 2.0 1.5 1.1PSI 3.7 2.1 1.7 1.3 0.8 0.6 0.4

CMW50

Btu/h 51,950 40,400 35,450 31,000 23,400 17,250 12,450kW 4.28 3.97 3.80 3.62 3.23 2.82 2.41

GPM 5.2 3.5 2.9 2.4 1.8 1.4 1.1PSI 2.4 1.3 1.0 0.8 0.6 0.4 0.3

CMW64

Btu/h 66,750 52,450 46,200 40,400 30,500 22,100 15,200kW 5.50 5.17 4.97 4.75 4.26 3.72 3.15

GPM 8.1 5.3 4.3 3.6 2.5 1.8 1.3PSI 3.4 1.8 1.4 1.1 0.8 0.6 0.5

CMW72

Btu/h 72,600 57,590 50,920 44,740 33,850 24,620 16,900kW 6.14 5.70 5.46 5.22 4.71 4.19 3.66

GPM 7.9 5.9 5.1 4.5 3.5 2.7 1.9PSI 2.4 1.4 1.2 0.9 0.6 0.4 0.2

CMW80

Btu/h 82,750 65,660 58,060 51,030 38,620 28,090 19,280kW 6.94 6.43 6.16 5.80 5.30 4.71 4.12

GPM 9.9 7.1 6.1 5.2 4.0 3.1 2.2PSI 3.5 2.0 1.5 1.2 0.7 0.5 0.3

CMW100

Btu/h 101,240 79,340 69,760 61,000 45,830 33,320 23,200kW 7.85 7.56 7.34 7.09 6.49 5.80 5.05

GPM 13.4 8.4 6.8 5.5 3.7 2.6 1.9PSI 4.2 1.8 1.2 0.9 0.5 0.3 0.3

CMW125

Btu/h 131,510 103,820 91,680 80,550 61,250 45,270 32,270kW 10.39 9.84 9.51 9.15 8.37 7.52 6.64

GPM 17.8 12.2 10.2 8.6 6.4 5.0 4.1PSI 4.6 2.4 1.8 1.4 1.0 0.7 0.6

CMW144

Btu/h 149,580 117,910 104,070 91,420 69,560 51,560 37,030kW 11.65 11.03 10.66 10.26 9.39 9.45 7.47

GPM 15.7 11.2 9.6 8.3 6.4 5.3 4.0PSI 3.1 1.7 1.3 1.0 0.6 0.5 0.4

CMW160

Btu/h 165,160 130,280 115,050 101,140 77,100 57,330 41,400kW 13.06 12.37 11.96 11.51 10.54 9.49 8.41

GPM 19.1 13.2 11.2 9.6 7.2 5.6 4.5PSI 4.4 2.3 1.7 1.3 0.8 0.5 0.4

Page 10: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

713

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMW/CMEW/CLW/CLEW WATER COOLEDCONDENSING UNITSPerformance Data — CMEW High-to-Medium Temperature — R-134a

Btu/h = Capacity.kW = Input Power.GPM = Water Flow in gpm.PSI = Water Pressure Drop through condenser in psi.

Rated Conditions: 20° F superheat, 5° F Subcooling, 60 Hz operation, 105° F Condensing, 75° F Entering Water (30° ITD).For 20° ITD (ITD = condensing temperature - entering water temperature) allow 3 gpm/ton water flow.

MODELEVAPORATING TEMPERATURE (°F)

50 40 30 25 20 10 0

CMEW18

Btu/h 15,561 12,146 9272 8075 6878 4905 3297kW 1.07 1.00 0.92 0.87 0.82 0.73 0.63

GPM 1.5 1.1 0.8 0.7 0.6 0.4 0.3PSI 1.6 1.0 0.6 0.5 0.4 0.2 0.1

CMEW22

Btu/h 19,618 15,312 11,690 10,181 8672 6184 4156kW 1.35 1.26 1.16 1.11 1.05 0.92 0.80

GPM 2.2 1.6 1.1 0.9 0.8 0.6 0.5PSI 2.8 1.7 1.0 0.8 0.6 0.4 0.2

CMEW28

Btu/h 24,738 19,308 14,740 12,838 10,935 7798 5240kW 1.70 1.59 1.46 1.39 1.31 1.16 1.00

GPM 2.3 1.7 1.4 1.2 1.1 0.8 0.6PSI 1.0 0.7 0.5 0.4 0.4 0.3 0.2

CMEW36

Btu/h 31,123 24,291 18,544 16,151 13,757 9810 6593kW 2.13 2.00 1.84 1.75 1.65 1.46 1.26

GPM 3.2 2.3 1.7 1.5 1.3 0.9 0.7PSI 1.6 1.0 0.7 0.6 0.5 0.3 0.3

CMEW50

Btu/h 44,079 34,403 26,264 22,874 19,484 13,894 9337kW 3.03 2.84 2.60 2.47 2.34 2.07 1.79

GPM 3.5 2.5 1.9 1.6 1.4 1.1 0.8PSI 1.3 0.8 0.6 0.4 0.4 0.3 0.3

CMEW64

Btu/h 55,440 43,270 33,034 28,770 24,506 17,475 11,744kW 3.81 3.57 3.28 3.11 2.95 2.61 2.25

GPM 5.1 3.5 2.5 2.1 1.8 1.3 1.0PSI 1.7 1.1 0.8 0.7 0.6 0.5 0.44

CMEW72

Btu/h 62,247 48,583 37,090 32,303 27,515 19,620 13,186kW 4.27 4.01 3.68 3.50 3.31 2.93 2.53

GPM 5.9 4.5 3.5 3.1 2.7 2.0 1.3PSI 1.4 0.9 0.6 0.5 0.4 0.4 0.1

CMEW80

Btu/h 69,889 54,547 41,643 36,268 30,892 22,029 14,805kW 4.80 4.50 4.14 3.94 3.73 3.29 2.84

GPM 10.4 8.2 6.3 5.5 4.7 3.3 2.1PSI 3.9 2.5 1.6 1.3 1.0 0.6 0.3

CMEW100

Btu/h 88,149 68,799 52,524 45,744 38,964 27,785 18,672kW 6.05 5.67 5.21 4.95 4.69 4.14 3.58

GPM 9.1 5.9 3.9 3.3 2.8 2.0 1.4PSI 2.1 1.0 0.5 0.4 0.4 0.3 0.2

CMEW125

Btu/h 110,888 86,547 66,073 57,544 49,015 34,952 23,489kW 7.62 7.14 6.56 6.23 5.91 5.21 4.51

GPM 12.2 8.6 6.3 5.5 4.9 4.1 3.6PSI 2.4 1.4 0.9 0.8 0.7 0.5 0.5

CMEW144

Btu/h 124,493 97,166 74,179 64,604 55,029 39,240 26,371kW 8.55 8.02 7.36 7.00 6.63 5.85 5.06

GPM 11.0 8.2 6.3 5.6 4.9 3.9 3.1PSI 1.6 1.0 0.6 0.5 0.5 0.3 0.3

CMEW160

Btu/h 139,768 109,088 83,280 72,530 61,780 44,055 29,607kW 9.60 9.00 8.48 7.96 7.45 6.57 5.68

GPM 13.3 9.6 7.2 6.3 5.5 4.3 3.3PSI 2.2 1.3 0.8 0.6 0.5 0.4 0.3

Page 11: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

714

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMW/CMEW/CLW/CLEW WATER COOLEDCONDENSING UNITSPerformance Data — CMW Medium-to-Low Temperature — R-502

Btu/h = Capacity.kW = Input Power.GPM = Water Flow in gpm.PSI = Water Pressure Drop through condenser in psi.

Rated Conditions: 65° F/*40° F Return Gas, 5° F Subcooling, 60 Hz operation, 105° F Condensing, 75° F Entering Water (30° ITD).For 20° ITD (ITD = condensing temperature - entering water temperature) allow 3 gpm/ton water flow.

MODELEVAPORATING TEMPERATURE (°F)

25 20 10 0 -10 -20*

CMW18

Btu/h 11,900 10,300 7500 5200 3400 1950kW 1.31 1.25 1.12 0.98 0.83 0.68

GPM 1.2 1.0 0.7 0.5 0.3 0.2PSI 1.1 0.9 0.5 0.3 0.2 0.1

CMW22

Btu/h 16,650 14,650 11,000 7800 4950 2450kW 1.73 1.65 1.44 1.22 0.98 0.74

GPM 2.0 1.7 1.1 0.8 0.5 0.2PSI 2.3 1.8 1.0 0.6 0.3 0.1

CMW28

Btu/h 23,300 20,900 16,450 12,300 8500 5050kW 2.37 2.28 2.08 1.84 1.59 1.32

GPM 2.3 2.1 1.6 1.3 0.9 0.7PSI 1.0 0.9 0.6 0.4 0.3 0.2

CMW36

Btu/h 29,750 26,750 21,200 16,150 11,550 7400kW 3.09 2.98 2.70 2.39 2.04 1.68

GPM 3.4 3.0 2.2 1.7 1.3 0.9PSI 1.8 1.5 1.0 0.6 0.4 0.3

CMW50

Btu/h 40,200 35,800 27,900 21,000 15,000 9850kW 4.23 4.10 3.75 3.35 2.89 2.41

GPM 3.5 3.0 2.2 1.7 1.3 0.9PSI 1.3 1.1 0.7 0.5 0.4 0.3

CMW64

Btu/h 50,500 45,050 35,150 26,500 18,950 12,450kW 5.55 5.31 4.78 4.20 3.59 2.96

GPM 5.2 4.3 3.1 2.2 1.6 1.1PSI 1.7 1.4 0.9 0.7 0.5 0.4

CMW72

Btu/h 55,990 50,050 39,250 29,800 21,550 14,400kW 6.19 5.93 5.36 4.70 4.10 3.48

GPM 5.8 5.1 4.1 3.3 2.4 1.7PSI 1.4 1.2 0.8 0.6 0.3 0.2

CMW80

Btu/h 63,240 56,520 44,310 33,670 24,440 16,480kW 7.02 6.72 6.04 5.32 4.57 3.62

GPM 7.0 6.1 4.7 3.7 2.8 1.9PSI 2.0 1.6 1.0 0.7 0.4 0.2

CMW100

Btu/h 74,950 66,800 52,020 39,170 28,040 18,480kW 8.04 7.75 7.12 6.45 5.75 5.04

GPM 7.9 6.5 4.5 3.2 2.3 1.7PSI 1.6 1.2 0.6 0.4 0.3 0.2

CMW125

Btu/h 97,290 86,410 67,290 51,390 38,320 27,740kW 10.01 9.63 8.85 8.07 7.29 6.54

GPM 13.0 9.6 7.1 5.5 4.5 3.9PSI 2.7 1.7 1.1 0.8 0.6 0.6

CMW144

Btu/h 103,050 91,360 72,740 59,810 44,280 30,570kW 11.56 11.10 10.15 9.21 8.29 7.40

GPM 9.8 8.5 6.8 5.7 4.6 3.7PSI 1.3 1.0 0.7 0.6 0.4 0.3

CMW160

Btu/h 122,630 109,440 85,703 65,720 49,050 35,310kW 13.30 12.74 11.61 10.50 9.41 8.36

GPM 12.6 10.8 8.2 6.4 5.1 4.1PSI 2.1 1.6 1.0 0.7 0.5 0.4

Page 12: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

715

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMW/CMEW/CLW/CLEW WATER COOLEDCONDENSING UNITSPerformance Data — CMEW High-to-Low Temperature — R-404A, R-507

Btu/h = Capacity.kW = Input Power.GPM = Water Flow in gpm.PSI = Water Pressure Drop through condenser in psi.

Rated Conditions: 20° F Superheat, 5° F Subcooling, 60 Hz operation, 105° F Condensing, 75° F Entering Water (30° ITD).For 20° ITD (ITD = condensing temperature - entering water temperature) allow 3 gpm/ton water flow.

MODELEVAPORATING TEMPERATURE (°F)

40 30 25 20 10 0 -10 -20 -25

CMEW18

Btu/h 18,402 14,590 12,647 11,023 8026 5674 3810 2351 1672kW 1.51 1.48 1.44 1.38 1.25 1.10 0.93 0.79 0.67

GPM 2.1 1.6 1.3 1.1 0.8 0.5 0.4 0.3 0.2PSI 2.6 1.7 1.3 1.0 0.6 0.4 0.2 0.1 0.1

CMEW22

Btu/h 25.859 20,509 17,834 15,564 11,348 8026 5432 3323 2351kW 2.12 2.07 2.02 1.92 1.75 1.55 1.30 1.07 0.88

GPM 3.7 2.7 2.3 1.9 1.3 0.9 0.6 0.4 0.3PSI 6.5 3.8 2.9 2.2 1.2 0.7 0.4 0.2 0.1

CMEW28

Btu/h 32,504 25,940 23,185 20,266 15,238 11,348 7622 5268 4297kW 3.04 2.84 2.72 2.62 2.36 2.08 1.85 1.59 1.39

GPM 3.8 2.8 2.4 2.1 1.6 1.3 0.9 0.7 0.6PSI 2.2 1.4 1.1 0.9 0.6 0.4 0.3 0.3 0.2

CMEW36

Btu/h 41,016 32,749 29,182 25,534 19,293 14,348 9726 6810 5513kW 3.82 3.57 3.42 3.30 2.97 2.62 2.35 2.00 1.75

GPM 5.9 4.1 3.5 2.9 2.1 1.6 1.2 0.9 0.8PSI 4.5 2.5 1.9 1.5 0.9 0.5 0.4 0.3 0.3

CMEW50

Btu/h 57,228 46,610 41,746 37.694 29,021 21,803 15,483 10,700 6971kW 5.50 5.10 4.77 4.57 4.07 3.55 3.05 2.55 2.33

GPM 7.1 4.7 4.0 3.4 2.4 1.6 1.3 1.0 0.8PSI 3.9 2.0 1.6 1.3 0.8 0.5 0.4 0.3 0.3

CMEW64

Btu/h 71,982 57,656 52,606 47,339 36,559 27,398 19,454 13,376 8754kW 7.06 6.55 6.12 5.87 5.22 4.57 3.90 3.25 2.98

GPM 10.6 6.9 5.8 4.9 3.3 2.4 1.7 1.2 1.0PSI 5.3 2.6 2.0 1.6 1.0 0.7 0.6 0.4 0.4

CMEW72

Btu/h 80,815 65,821 59,090 53,174 41,016 30,721 21,722 15,077 9809kW 8.07 7.47 7.00 6.70 5.97 5.22 4.45 3.75 3.43

GPM 10.3 7.5 6.5 5.7 4.4 3.3 2.5 1.8 1.2PSI 3.9 2.2 1.7 1.4 0.9 0.6 0.4 0.2 0.1

CMEW80

Btu/h 90,787 73,927 66,305 59,658 46,040 34,531 24,477 16,858 11,025kW 9.18 8.50 7.95 7.63 6.78 5.93 5.05 4.25 3.88

GPM 13.2 9.3 7.8 6.8 5.1 3.9 2.9 2.1 1.5PSI 6.2 3.3 2.4 1.9 1.1 0.7 0.5 0.3 0.2

CMEW100

Btu/h 114,131 91,597 81,304 72,062 56,577 43,933 32,181 24,073 19,941kW 9.15 9.37 8.55 8.25 7.60 6.92 6.10 5.10 4.80

GPM 18.3 12.2 9.3 7.6 5.2 3.7 2.6 1.9 1.7PSI 7.2 3.5 2.2 1.5 0.8 0.5 0.3 0.3 0.2

CMEW125

Btu/h 139,870 113,805 102,213 90,704 71,089 55,283 40,530 30,237 25,128kW 12.27 11.42 10.97 10.60 9.72 8.87 7.85 6.55 6.15

GPM 21.2 14.9 12.6 10.6 7.8 6.0 4.8 4.0 3.8PSI 6.4 3.4 2.5 1.9 1.2 0.9 0.7 0.6 0.5

CMEW144

Btu/h 157,092 127,830 114,779 102,830 79,924 62,090 45,475 35,000 28,128kW 13.87 12.91 12.40 11.97 11.02 10.05 8.85 7.40 6.95

GPM 18.2 13.1 11.3 9.8 7.6 6.0 4.8 4.0 3.5PSI 4.0 2.2 1.7 1.3 0.9 0.6 0.4 0.4 0.3

CMEW160

Btu/h 176,385 143,477 128,889 114,299 89,652 69,711 51,067 38,098 31,614kW 15.95 14.85 14.25 13.75 12.65 11.55 10.20 8.50 8.00

GPM 23.4 16.4 13.9 11.8 8.8 6.9 5.4 4.3 3.9PSI 6.3 3.3 2.5 1.8 1.1 0.7 0.5 0.4 0.3

Page 13: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

716

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMW/CMEW/CLW/CLEW WATER COOLEDCONDENSING UNITSPerformance Data — CLEW — Extra Low Temperature — R-404A, R-507

Btu/h = Capacity.kW = Input Power.GPM = Water Flow in gpm.PSI = Water Pressure Drop through condenser in psi.

Rated Conditions: 20° F Superheat, 5° F Subcooling, 60 Hz operation, 105° FCondensing, 75° F Entering Water (30° ITD).For 20° ITD (ITD = condensing temperature - entering water temperature) allow3 gpm/ton water flow.

Performance Data — CLW Extra Low Temperature — R-502

Btu/h = Capacity.kW = Input Power.GPM = Water Flow in gpm.PSI = Water Pressure Drop through condenser in psi.

Rated Conditions: 40° F/*20° F Return Gas, 5° F Subcooling, 60 Hz operation,105° F Condensing, 75° F Entering Water (30° ITD).For 20° ITD (ITD = condensing temperature - entering water temperature) allow3 gpm/ton water flow.

MODELSEVAPORATING TEMPERATURE (°F)

-5 -10 -15 -20 -25 -30 -35 -40Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CLEW22

Btu/h 8997 7833 6755 5757 4831 3979 3199 2370kW 1.83 1.71 1.59 1.47 1.35 1.22 1.10 0.97

GPM 1.1 0.9 0.8 0.6 0.5 0.4 0.4 0.3PSI 0.9 0.7 0.6 0.5 0.4 0.3 0.2 0.1

CLEW28

Btu/h 13,331 11,619 10,020 8550 7177 5907 4733 3495kW 2.71 2.54 2.37 2.19 2.00 1.82 1.63 1.45

GPM 2.0 1.6 1.4 1.1 0.9 0.8 0.6 0.5PSI 2.3 1.8 1.3 1.0 0.8 0.5 0.4 0.3

CLEW44

Btu/h 23,349 19,872 16,808 14,119 11,778 9747 8009 6076kW 4.61 4.34 4.05 3.75 3.44 3.12 2.81 2.48

GPM 2.1 1.8 1.6 1.4 1.2 1.0 0.9 0.8PSI 0.7 0.6 0.5 0.4 0.4 0.3 0.3 0.3

CLEW50

Btu/h 29,158 25,301 21,810 18,658 15,808 13,250 10,958 8489kW 5.83 5.52 5.20 4.86 4.51 4.17 3.81 3.46

GPM 2.9 2.5 2.1 1.8 1.6 1.4 1.2 1.0PSI 1.0 0.8 0.7 0.6 0.5 0.4 0.4 0.3

CLEW88

Btu/h 43,900 37,706 32,120 27,120 22,639 18,641 15,103 11,258kW 8.46 8.05 7.57 7.06 6.51 5.92 5.31 4.69

GPM 5.6 4.5 3.7 3.0 2.5 2.0 1.7 1.4PSI 1.9 1.5 1.1 0.9 0.8 0.6 0.6 0.5

CLEW100

Btu/h 57,245 49,353 42,197 35,734 29,904 24,653 19,957 14,.891kW 10.58 10.01 9.39 8.75 8.07 7.36 6.65 5.93

GPM 7.7 6.5 5.5 4.7 4.1 3.5 2.9 2.4PSI 2.3 1.7 1.3 1.0 0.8 0.6 0.5 0.3

MODELSEVAPORATING TEMPERATURE (°F)

-5 -10 -15 -20 -25 -30 -35 -40Btu/h kW Btu/h kW Btu/h kW Btu/h kW

CLW22

Btu/h 9125 7900 6800 5700 4750 3800 2950 2100kW 1.69 1.63 1.54 1.45 1.34 1.22 1.09 0.96

GPM 1.0 0.9 0.8 0.6 0.5 0.4 0.3 0.3PSI 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1

CLW28

Btu/h 14,000 12,150 10,625 9100 7850 6600 5550 4500kW 2.71 2.55 2.38 2.20 2.02 1.83 1.64 1.45

GPM 2.0 1.7 1.5 1.2 1.0 0.8 0.6 0.5PSI 2.5 1.9 1.5 1.1 0.9 0.6 0.5 0.4

CLW44

Btu/h 21.975 19,100 16,650 14,200 12,050 9900 8050 6200kW 4.05 3.84 3.60 3.36 3.09 2.82 2.54 2.25

GPM 1.9 1.7 1.5 1.3 1.2 1.0 0.9 0.7PSI 0.6 0.5 0.4 0.4 0.4 0.3 0.3 0.2

CLW50

Btu/h 27,650 24,200 21,225 18,250 15,675 13,100 10,825 8550kW 5.23 4.98 4.67 4.36 4.01 3.65 3.28 2.90

GPM 2.6 2.3 2.0 1.7 1.5 1.3 1.1 0.9PSI 0.9 0.7 0.6 0.5 0.5 0.4 0.3 0.3

CLW88

Btu/h 44,425 38,150 33,000 27,850 23,675 19,500 16,050 12,600kW 7.86 7.36 6.86 6.35 5.86 5.36 4.88 4.40

GPM 5.4 4.3 3.5 2.8 2.4 2.0 1.7 1.4PSI 1.8 1.4 1.1 0.9 0.7 0.6 0.5 0.5

CLW100

Btu/h 56,995 49,240 42,940 36,640 31,615 26,590 22,655 18,720kW 10.57 9.82 9.14 8.45 7.83 7.20 6.64 6.08

GPM 7.7 6.4 5.5 4.7 4.1 3.6 3.1 2.7PSI 2.3 1.7 1.3 1.0 0.8 0.6 0.5 0.4

Page 14: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

717

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMW/CMEW/CLW/CLEW WATER COOLEDCONDENSING UNITSTechnical Specifications — Water Cooled Units

*Voltage Code.MCA = Minimum Circuit AmpacityMFS = Maximum Fuse Size

*Voltage Code.ML = distance between mounting holes on “L” side.MW = distance between mounting holes on “W” side.NOTE: CMT(E)W indicates CMTW or CMTEW. CLT(E) indicates CLTW orCLTEW.

ELECTRICAL

CONDENSINGUNIT MODEL

COMPRESSORMODEL

VOLTAGE CODE1

208-230/1/603

208-230/3/604

460/3/60MCA MFS MCA MFS MCA MFS

CM(E)W18* MT(Z)18JA 11.6 20 8.0 15 3.1 15CM(E)W22* MT(Z)22JC 15.1 25 9.9 15 4.0 15CM(E)W28* MT(Z)28JE 22.4 40 15.1 25 6.3 15CM(E)W36* MT(Z)36JG 26.8 45 19.6 35 8.0 15CM(E)W50* MT(Z)50HK 33.0 50 20.5 35 10.8 15CM(E)W64* MT(Z)64HM 47.4 80 27.6 50 13.4 20CM(E)W72* MT(Z)72HN 26.8 45 13.4 20CM(E)W80* MT(Z)80HP 37.5 60 20.5 35CM(E)W100* MT(Z)100HS 38.4 60 19.6 35CM(E)W125* MT(Z)125HU 48.3 80 24.1 40CM(E)W144* MT(Z)144HV 57.1 100 26.8 45CM(E)W160* MT(Z)160HW 62.5 110 32.1 50CL(E)W22* LT(Z)22JE 17.0 25 11.0 20 4.5 15CL(E)W28* LT(Z)28JH 26.0 40 17.0 25 5.3 15CL(E)W44* LT(Z)44HM 34.0 60 22.0 35 10.0 15CL(E)W50* LT(Z)50HP 37.0 60 23.0 40 12.0 20CL(E)W88* LT(Z)88HU 38.0 50 17.0 25CL(E)W100* LT(Z)100HW 43.0 60 22.0 35

MECHANICAL

CONDENSINGUNIT MODEL

COMPRESSORMODEL

DIMENSIONS (in.) CONNECTIONS (in.)RECEIVERCAPACITY(lb @ 90%)

APPROX.SHIPPING

WT (lb)L W HMountingCenters Liquid

(Flare)Suction(ODS)

Water(FPT)

ML MWCM(E)W18* MT(Z)18JA

24 18 15-3/4 22 16 3/8 5/8 3/8 10.0135

CM(E)W22* MT(Z)22JC 140CM(E)W28* MT(Z)28JE 24 18 15-3/4 22 16 3/8 7/8 1/2 10.0 140CM(E)W36* MT(Z)36JG 25-1/4 21 22 23-1/4 19 1/2 7/8 1/2 10.0 140CM(E)W50* MT(Z)50HK

25-1/4 21 22 23-1/4 19 1/2 7/8 3/4 16.0 190CM(E)W64* MT(Z)64HMCM(E)W72* MT(Z)72HN

25-1/4 21 22 23-1/4 19 1/2 1-1/8 3/4 16.0 195CM(E)W80* MT(Z)80HPCM(E)W100* MT(Z)100HS

31-1/2 28-3/8 25 30-1/2 26-3/8 1/2 1-1/8 1 26.0 290CM(E)W125* MT(Z)125HUCM(E)W144* MT(Z)144HVCM(E)W160* MT(Z)160HWCL(E)W22* LT(Z)22JE 24 18 15-3/4 22 16 3/8 5/8 3/8 10.0 140CL(E)W28* LT(Z)28JH 24 18 15-3/4 22 16 3/8 7/8 3/8 10.0 140CL(E)W44* LT(Z)44HM 25-1/4 21 19-1/2 23-1/4 19 1/2 7/8 1/2 16.0 180CL(E)W50* LT(Z)50HP 25-1/4 21 22 23-1/4 19 1/2 7/8 1/2 16.0 190CL(E)W88* LT(Z)88HU

31-1/2 28-3/8 25 30-1/2 26-3/8 1/2 1-1/8 3/4 26.0270

CL(E)W100* LT(Z)100HW 290

P4129

Page 15: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

718

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CONDENSING UNIT SPECIFICATIONSAIR COOLED CONDENSING UNITS

WATER COOLED CONDENSING UNITS

MCA = Minimum Current AmpsNOTE: Units with voltage codes 1 or 3 have 208-230/1/60 fan motors.

CONDENSINGUNIT MODEL

COMPRESSORMODEL HP

VOLTAGE CODE DIMENSIONS (in.) CONNECTIONS (in.)RECEIVERCAPACITY(lb $ 90%)

APPROXSHIPPING

WT (lb)

1 3 4L W H Liquid

(Flare)Suction(ODS)208-230/1/60 208-230/3/60 460/3/60

MCA MCA MCACMT(E)18AA MT(Z)18 1.5 13.6 10 4.1 28-3/8 25 14-1/2 3/8 5/8 10 160CMT(E)22AA MT(Z)22 2 17.1 11.9 5 28-3/8 25 14-1/2 3/8 5/8 10 165CMT(E)28AA MT(Z)28 2.5 24.4 17.1 7.3 28-3/8 25 14-1/2 3/8 5/8 10 170CMT(E)32AA MT(Z)32 2.75 25.3 19.9 8.1 28-3/8 25 14-1/2 3/8 5/8 10 170CMT(E)36AA MT(Z)36 3 30.6 23.4 9 39-3/8 27-1/2 22-1/2 1/2 5/8 17.5 265CMT(E)50AA MT(Z)50 4 36.6 24.1 12.8 47-5/8 35-1/2 24-1/2 1/2 7/8 19.5 355CMT(E)64AA MT(Z)64 5 51 31.2 15.4 47-5/8 35-1/2 24-1/2 1/2 7/8 19.5 355CMT(E)72AA MT(Z)72 6 — 30.4 15.4 47-5/8 35-1/2 24-1/2 1/2 1-1/8 26 360CMT(E)100AA MT(Z)100 9 — 48.6 23.4 59-1/2 35-1/2 26-1/2 1/2 1-1/8 36 465CMT(E)125AA MT(Z)125 10 — 58.5 27.9 59-1/2 35-1/2 30-1/2 1/2 1-1/8 36 510CMT(E)144AA MT(Z)144 12 — 67.3 30.6 59-1/2 35-1/2 34-1/2 1/2 1-3/8 43 545CMT(E)160AA MT(Z)160 13.5 — 72.7 35.9 59-1/2 35-1/2 34-1/2 1/2 1-3/8 43 555CLT(E)22AA LT(Z)22 2 17.2 11.8 5 28-3/8 31-1/2 14-1/2 3/8 5/8 10 165CLT(E)28AA LT(Z)28 2.5 24.3 17.2 5.7 28-3/8 31-1/2 14-1/2 3/8 5/8 10 170CLT(E)44AA LT(Z)44 3 34 23.2 9.9 39-3/8 31-1/2 22-1/2 1/2 7/8 17.5 290CLT(E)50AA LT(Z)50 4 36.6 24.1 11.7 39-3/8 31-1/2 22-1/2 1/2 7/8 26 355CLT(E)88AA LT(Z)88 6 — 34.9 17.2 47-5/8 35-1/2 22-1/2 1/2 1-1/8 26 400CLT(E)100AA LT(Z)100 9 — 42 21.6 47-5/8 35-1/2 22-1/2 1/2 1-1/8 36 410

CONDENSINGUNIT MODEL

COMPRESSORMODEL HP

VOLTAGE CODE DIMENSIONS (in.) CONNECTIONS (in.)RECEIVERCAPACITY(lb $ 90%)

APPROXSHIPPING

WT (lb)

1 3 4L W H

DischargeConn.(Flare)

SuctionConn.(ODS)

WaterConn.(FPT)

208-230/1/60 208-230/3/60 460/3/60MCA MCA MCA

CMEW18AA MT(Z)18 1.5 11.6 8.0 3.1 24 18 15-3/4 3/8 5/8 3/8 10 135CMEW22AA MT(Z)22 2 15.1 9.9 4.0 24 18 15-3/4 3/8 5/8 3/8 10 140CMEW28AA MT(Z)28 2.5 22.4 15.1 6.3 24 18 15-3/4 3/8 5/8 1/2 10 140CMEW36AA MT(Z)36 3 26.8 19.6 8.0 25-1/4 21 22 ½ 5/8 1/2 10 140CMEW50AA MT(Z)50 4 33.0 20.5 10.8 25-1/4 21 22 ½ 7/8 3/4 16 190CMEW64AA MT(Z)64 5 47.4 27.6 13.4 25-1/4 21 22 ½ 7/8 3/4 16 190CMEW72AA MT(Z)72 6 26.8 13.4 25-1/4 21 22 1/2 1-1/8 3/4 16 195CMEW80AA MT(Z)80 7 37.5 20.5 25-1/4 21 22 1/2 1-1/8 3/4 16 195CMEW100AA MT(Z)100 9 38.4 19.6 31-1/2 28-3/8 25 1/2 1-1/8 1 26 290CMEW125AA MT(Z)125 10 48.3 24.1 31-1/2 28-3/8 25 1/2 1-1/8 1 26 290CMEW144AA MT(Z)144 12 57.1 26.8 31-1/2 28-3/8 25 1/2 1-3/8 1 26 290CMEW160AA MT(Z)160 13.5 62.5 32.1 31-1/2 28-3/8 25 1/2 1-3/8 1 26 290CLEW22AA LT(Z)22 2 17.0 11.0 4.5 24 18 15-3/4 3/8 5/8 3/8 10 140CLEW28AA LT(Z)28 2.5 26.0 17.0 5.3 24 18 15-3/4 3/8 5/8 3/8 10 140CLEW44AA LT(Z)44 3 34.0 22.0 10.0 25-1/4 21 19-1/2 1/2 7/8 1/2 16 180CLEW50AA LT(Z)50 4 37.0 23.0 12.0 25-1/4 21 22 1/2 7/8 1/2 16 190CLEW88AA LT(Z)88 6 38.0 17.0 31-1/2 28-3/8 25 1/2 1-1/8 3/4 26 270CLEW100AA LT(Z)100 9 43.0 22.0 31-1/2 28-3/8 25 1/2 1-1/8 3/4 26 290

Page 16: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

719

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CONDENSING UNIT SPECIFICATIONS (cont)Water Cooled Condensing Units (cont)

MCA = Minimum Current AmpsNOTE: Units with voltage codes 1 or 3 have 208-230/1/60 fan motors.

CONDENSINGUNIT MODEL

COMPRESSORMODEL HP

VOLTAGE CODE DIMENSIONS (in.) CONNECTIONS (in.)RECEIVERCAPACITY(lb $ 90%)

APPROXSHIPPING

WT (lb)

1 3 4L W H

DischargeConn.(Flare)

SuctionConn.(ODS)

WaterConn.(FPT)

208-230/1/60 208-230/3/60 460/3/60MCA MCA MCA

CMEW 18 AA MT(Z) 18 1.5 11.6 8.0 3.1 24 18 15-3/4 3/8 5/8 3/8 10 135CMEW 22 AA MT(Z) 22 2 15.1 9.9 4.0 24 18 15-3/4 3/8 5/8 3/8 10 140CMEW 28 AA MT(Z) 28 2.5 22.4 15.1 6.3 24 18 15-3/4 3/8 5/8 1/2 10 140CMEW 36 AA MT(Z) 36 3 26.8 19.6 8.0 25-1/4 21 22 1/2 5/8 1/2 10 140CMEW 50 AA MT(Z) 50 4 33.0 20.5 10.8 25-1/4 21 22 1/2 7/8 3/4 16 190CMEW 64 AA MT(Z) 64 5 47.4 27.6 13.4 25-1/4 21 22 1/2 7/8 3/4 16 190CMEW 72 AA MT(Z) 72 6 26.8 13.4 25-1/4 21 22 1/2 1-1/8 3/4 16 195CMEW 80 AA MT(Z) 80 7 37.5 20.5 25-1/4 21 22 1/2 1-1/8 3/4 16 195CMEW 100 AA MT(Z) 100 9 38.4 19.6 31-1/2 28-3/8 25 1/2 1-1/8 1 26 290CMEW 125 AA MT(Z) 125 10 48.3 24.1 31-1/2 28-3/8 25 1/2 1-1/8 1 26 290CMEW 144 AA MT(Z) 144 12 57.1 26.8 31-1/2 28-3/8 25 1/2 1-3/8 1 26 290CMEW 160 AA MT(Z) 160 13.5 62.5 32.1 31-1/2 28-3/8 25 1/2 1-3/8 1 26 290CLEW 22 AA LT(Z) 22 2 17.0 11.0 4.5 24 18 15-3/4 3/8 5/8 3/8 10 140CLEW 28 AA LT(Z) 28 2.5 26.0 17.0 5.3 24 18 15-3/4 3/8 5/8 3/8 10 140CLEW 44 AA LT(Z) 44 3 34.0 22.0 10.0 25-1/4 21 19-1/2 1/2 7/8 1/2 16 180CLEW 50 AA LT(Z) 50 4 37.0 23.0 12.0 25-1/4 21 22 1/2 7/8 1/2 16 190CLEW 88 AA LT(Z) 88 6 38.0 17.0 31-1/2 28-3/8 25 1/2 1-1/8 3/4 26 270CLEW 100 AA LT(Z) 100 9 43.0 22.0 31-1/2 28-3/8 25 1/2 1-1/8 3/4 26 290

Page 17: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

720

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CONDENSING UNIT SPECIFICATIONS (cont)Air Cooled Condensing Unit Accessories

*Fan motor rotation is counterclockwise from the shaft in.

Outdoor Enclosures

PartNo.

DescriptionL x W x H (in.)

Medium Temp: CMT = R-22; CMTE = R-134aLow Temp: CLT = R-502;

CLTE = R-404A/R

CMTCMTE

18

CMTCMTE

22

CMTCMTE

28

CMTCMTE

32

CMTCMTE

36

CMTCMTE

50

CMTCMTE

64

CMTCMTE

72

CMTCMTE

100

CMTCMTE

125

CMTCMTE

144

CMTCMTE

160

CLTCLTE

22

CLTCLTE

28

CLTCLTE

44

CLTCLTE

50

CLTCLTE

88

CLTCLTE100

1-A3B3 28-3/8 x 25 x 15-1/2 (27 lb) X X X X X X

2-DE 40-9/16 x 31-5/8 x 23-1/2 (50 lb) X X X

3-FGH 48-13/16 x 35-11/16 x 25-1/2 (65 lb) X X X X

4-J 48-13/16 x 35-5/8 x 27-1/2 (65 lb) X

5-K 60-5/8 x 35-5/8 x 28-5/8 (79 lb) X

6-L 60-5/8 x 35-5/8 x 32-5/8 (83 lb) X

7-M 60-5/8 x 35-5/8 x 35-1/2 (90 lb) X X

Air Cooled Condenser Assemblies

PartNo.

Description Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;CLTE = R-404A/R

7401551 Condenser slab coil only X X

7401552 Condenser slab coil only X X X X

7401553 Condenser slab coil only X X X

7401523 Condenser slab coil only X

7401524 Condenser slab coil only X X X

7401526 Condenser slab coil only X

7401527 Condenser slab coil only X

7401528 Condenser slab coil only X

7401529 Condenser slab coil only X X

Fan Motors *

PartNo.

DescriptionL x W x H (in.)

Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;CLTE = R-404A/R

7605518 230 v/1 ph/60 Hz1/15-hp, 1550 rpm, 1.0 FLA

X X X X X X

7605526 230 v/1 ph/60 Hz1/4-hp, 1075 rpm, 1.8 FLA

X X X

7605524 230 v/1 ph/60 Hz1/3-hp, 1075 rpm, 1.8 FLA

X X X X X

7605523 230 v/1 ph/60 Hz3/4-hp

X X X X

7605516 460 v/1 ph/60 Hz1/15-hp, 1550 rpm, .5 FLA

X X X X X X

7605525 460 v/1 ph/60 Hz1/4-hp, 1075 rpm, .5 FLA

X X X

7605527 460 v/1 ph/60 Hz1/3-hp, 1075 rpm, 1.0 FLA

X X X X X

7605528 460 v/1 ph/60 Hz3/4-hp

X X X X

7605520 575 v/1 ph/60 Hz3/4-hp

X X X X

Fan Blades

PartNo.

Description Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;CLTE = R-404A/R

7002503 11 in., 5 blade, 32 deg,5/16 in. bore

X X X X X X

7002000 14 in., 4 blade, 32 deg.,1/2 in. bore

X X X

7002001 18 in., 4 blade, 32 deg.,1/2 in. bore

X X X X X

7002002 22 in., 4 blade, 32 deg.,1/2 in. bore

X X X X

Page 18: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

721

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CONDENSING UNIT SPECIFICATIONS (cont)Air Cooled Condensing Unit Accessories (cont)

*Receiver requires valve code no. 6804527 purchased separately.

Fan Guards and Motor Mounts

PartNo.

DescriptionL x W x H (in.)

Medium Temp: CMT = R-22; CMTE = R-134aLow Temp: CLT = R-502;

CLTE = R-404A/R

CMTCMTE

18

CMTCMTE

22

CMTCMTE

28

CMTCMTE

32

CMTCMTE

36

CMTCMTE

50

CMTCMTE

64

CMTCMTE

72

CMTCMTE

100

CMTCMTE

125

CMTCMTE

144

CMTCMTE

160

CLTCLTE

22

CLTCLTE

28

CLTCLTE

44

CLTCLTE

50

CLTCLTE

88

CLTCLTE100

7006501 Fan Guard/Motor Mountfor 11-in. fan

X X X X

TO10317P01 Fan Guard for 22-in. Fan X X X X

7006507 Fan Guard for 18-in. Fan X X X X X

7006506 Fan Guard for 14-in. Fan X X X

TO10314P01 Motor Mount (Band Type) X X X X

Receiver

PartNo.

Description(in.) Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;

CLTE = R-404A/R

6808517 Receiver 5 x 12 X X X X X X

6808507* Receiver 6 x 18

6808508* Receiver 6 x 20 X X

6808509* Receiver 6 x 22 X X

6808510* Receiver 8-5/8 x 18 X X X

6808511* Receiver 8-5/8 x 21 X X X

6808512* Receiver 8-5/8 x 25 X X

6804527 Receiver Valve 1-in. Rotolocx 1/2-in. SAE

X X X X X X X X X X X X

Pressure Controls

PartNo.

DescriptionL x W x H (in.) Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;

CLTE = R-404A/R

6902502 Dual Pressure Control for all Models X X X X X X X X X X X X X X X X X X

6902507 Dual Pressure ControlAuto Reset

X X X X X X X X X X X X X X X X X X

Run Capacitors

PartNo.

Description Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;CLTE = R-404A/R

7304533 25 MFD 440 VAC X

7304522 45 MFD 440 VAC X X X X X X X

7304523 55 MFD 440 VAC X

7304528 50 MFD 440 VAC X X

7304531 15 MFD 440 VAC

Prewired Start Relay and Start Capacitor Assembly

PartNo.

Description Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;CLTE = R-404A/R

7505541 All Units Except OnesUsing MT(Z) 18-1

X X X X X X X X X X X X X X X X X

7305548 For Units Using MT(Z) 18-1 X

Contactors

PartNo. Description Medium Temp: CMT = R-22; CMTE = R-134a Low Temp: CLT = R-502;

CLTE = R-404A/R

7305502 600 v, 3 pole, 60A, 208-240 Coil 144-3 160-3

7305503 600 v, 3 pole, 40A, 208-240 Coil 64-3 72-3 100-3 144-4 160-4 88-3 100-3

7305504 600 v, 3 pole, 30A, 208-240 Coil 50-3 125-4 50-3 100-4

7305505 600 v, 3 pole, 50A, 208-240 Coil 125-3

7305507 600 v, 2 pole, 50A, 208-240 Coil 64-1

7305508 600 v, 2 pole, 40A, 208-240 Coil 50-1 50-1

7305510 600 v, 3 pole, 25A, 208-240 Coil 18-3,4 22-3,4 36-3,4 50-4 64-4 72-4 100-4 22-3,4 28-3,4 44-3,4 50-4 88-4

7305512 600 v, 2 pole, 25A, 208-240 Coil 28-1

7305513 600 v, 2 pole, 30A, 204-240 Coil 36-1 44-1

7305514 600 v, 2 pole, 20A, 204-240 Coil 18-1 22-1 22-1

Page 19: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

722

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CONDENSING UNIT SPECIFICATIONS (cont)Water Cooled Condensing Unit Accessories

Water Cooled Condensers

PartNo.

Description

Medium Temp: CMW = R-22; CMEW = R-134aLow Temp: CLW = R-502;

CLEW = R-404A/R

CMWCMEW

18

CMWCMEW

22

CMWCMEW

28

CMWCMEW

36

CMWCMEW

50

CMWCMEW

64

CMWCMEW

72

CMWCMEW

80

CMWCMEW

100

CMWCMEW

125

CMWCMEW

144

CMWCMEW

160

CLWCLEW

22

CLWCLEW

28

CLWCLEW

44

CLWCLEW

50

CLWCLEW

88

CLWCLEW

100

7402501 Condenser Only X X X X

7402503 Condenser Only X X

7402504 Condenser Only X X X

7402505 Condenser Only X X

7402506 Condenser Only X X X

7402510 Condenser Only X

7402511 Condenser Only X

7402512 Condenser Only X X

Cupro Nickel Water Cooled Condensers

PartNo.

Description Medium Temp: CMW = R-22; CMEW = R-134a Low Temp: CLW = R-502;CLEW = R-404A/R

7402514 Nickel Condenser Only X X X X

7402507 Nickel Condenser Only X X X X

7402513 Nickel Condenser Only X X X

7402508 Nickel Condenser Only X X X

7402515 Nickel Condenser Only X

Water Valves

PartNo.

Description Medium Temp: CMW = R-22; CMEW = R-134a Low Temp: CLW = R-502;CLEW = R-404A/R

6804532 3/8-in. Danfoss WVFX 10 X X X X

6804531 1/2-in. Danfoss WVFX 15 X X X X

6804530 3/4-in. Danfoss WVFX 20 X X X X X X

6804546 1-in. Danfoss WVFX 25 X X X X

Receivers

PartNo.

Description (in.) Medium Temp: CMW = R-22; CMEW = R-134a Low Temp: CLW = R-502;CLEW = R-404A/R

6808517 Receiver 5 x 12 X X X X X X

6808507* Receiver 6 x 18 X X X X X X

6808510* Receiver 8-5/8 x 18 X X X X X X

6804527 Receiver Valve 1-in. R x1/2-in. SAE (* required)

X X X X X X X X X X X X X X

Pressure Controls

PartNo. Description Medium Temp: CMW = R-22; CMEW = R-134a Low Temp: CLW = R-502;

CLEW = R-404A/R

6902502 Dual Pressure Control for allModels

X X X X X X X X X X X X X X X X X X

6902507 Dual Pressure Control/Auto. Reset

X X X X X X X X X X X X X X X X X X

Run Capacitors

PartNo.

Description Medium Temp: CMW = R-22; CMEW = R-134a Low Temp: CLW = R-502;CLEW = R-404A/R

7304533 25 MFD 440 VAC X

7304519 35 MFD 440 VAC

7304522 45 MFD 440 VAC X X X X X X X

7304523 55 MFD 440 VAC X

7304528 50 MFD 440 VAC X X

Page 20: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

723

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CONDENSING UNIT SPECIFICATIONS (cont)Water Cooled Condensing Unit Accessories (cont)

Prewired Start Relay and Capacitor Assembly

PartNo.

Description

Medium Temp: CMW = R-22; CMEW = R-134aLow Temp: CLW = R-502;

CLEW = R-404A/R

CMWCMEW

18

CMWCMEW

22

CMWCMEW

28

CMWCMEW

36

CMWCMEW

50

CMWCMEW

64

CMWCMEW

72

CMWCMEW

80

CMWCMEW

100

CMWCMEW

125

CMWCMEW

144

CMWCMEW

160

CLWCLEW

22

CLWCLEW

28

CLWCLEW

44

CLWCLEW

50

CLWCLEW

88

CLWCLEW

100

7305548 All Units Except OnesUsing MT(Z) 18-1

X X X X X X X X X X X X X X X X X

7305541 For Units Using MT(Z) 18-1 X

Contactors

CodeNo. Description Medium Temp: CMW = R-22; CMEW = R-134a Low Temp: CLW = R-502;

CLEW = R-404A/R

7305502600 v, 3 pole, 60A,

208-240 Coil144-3 160-3

7305503 600 v, 3 pole, 40A,208-240 Coil

64-3 72-3 100-3 144-4 160-4 88-3 100-3

7305504 600 v, 3 pole, 30A,208-240 Coil

50-3 125-4 50-3 100-4

7305507 600 v, 3 pole, 50A208-240 Coil

64-1

7305508 600 v, 2 pole, 40A,208-240 Coil

50-1 50-1

7305510 600 v, 3 pole, 25A,208-240 Coil

18-3,4 22-3,4 36-3,4 50-4 64-4 72-4 72-4 100-4 22-3,4 28-3,4 44-3,4 50-4 88-4

7305512 600 v, 2 pole, 25A,208-240 Coil

28-1

7305513 600 v, 2 pole, 30A,204-240 Coil

36-1 44-1

7305514 600 v, 2 pole, 20A,204-240 Coil

18-1 22-1 22-1

Page 21: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

724

REFRIGERATION HERMETIC CONDENSING UNITS

DANFOSS-MANEUROP CMT/CMTE/CLT/CLTE AIR COOLEDCONDENSING UNITSOutdoor Enclosures (Air cooled units only, shipped unassembled)

ENCLOSURE KIT MODELS1-A3B3 2-DE 3-FGH 4J 5K 6L 7-M

CMT(E)18 CMT(E)36 CMT(E)50 CLT(E)100 CMT(E)100 CMT(E)125 CMT(E)160CMT(E)22 CLT(E)44 CMT(E)64 CMT(E)144CMT(E)28 CLT(E)50 CMT(E)72CMT(E)32 CLT(E)88CLT(E)22CLT(E)28

P4128

HOUSINGMODEL

DIMENSIONS (in.) APPROX. SHIPPINGWEIGHT (lb)Length Width Height

1-A3B3 28-3/8 25 15-1/2 272-DE 40-9/16 31-5/8 23-1/2 50

3-FGH 48-13/16 35-11/16 25-1/2 654-J 48-13/16 35-5/8 27-1/2 675-K 60-5/8 35-5/8 28-5/8 796-L 60-5/8 35-5/8 32-5/8 837-M 60-5/8 35-5/8 35-1/2 90

Page 22: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

725

RECIPROCATING COMPRESSORS

DANFOSS-MANEUROP RECIPROCATING COMPRESSORS — TYPE MT/MTZIntroduction

Maneurop reciprocating compressors aredesigned for residential and light commercial airconditioning applications as well as refrigerationapplications. Thanks to the very large internal vol-ume, large oil sump, the sturdy design of compres-sor parts and its 100% suction gas cooled motor,the Maneurop reciprocating compressor hasproven its ability to withstand the most harsh con-ditions where other compressors may fail.

Features

Both MT and MTZ compressors have a largeacoustic jackets to obtainlower sound levels internal free volume that reduces the risk ofwithout riskof overheating. slugging when liquid refrigerant enters the A sight glass andoil equalization connection are compressor. Because they are fully cooledby features in these compressors. suction gas, no additional compressorcooling is required. Compressors can be insulated with

Serial Number Nomenclature

Format: AB CC DDDDDDD

Where A = year built, B = month built, CC = Factory code,DDDDDDD = Serial number Example: MC 10 5264747 = com-pressor built in March 2001 at Trevoux factory

Year Month Factory CodeF = 1995 A = Jan 10 = Trevoux, FranceG = 1996 B = Feb 11 = Anse, FranceH = 1997 C = March 14 = Lawrenceville, GAJ = 1998 D = AprilK = 1999 E = MayL = 2000 F = JuneM = 2001 G = JulyN = 2002 H = AugP = 2003 J = SeptQ = 2004 K = Oct

L = NovM = Dec

MT Z 64 HM 4 - VE -Compressortype

Lubricant(Z: Polyolester oil-: mineral oil)

Motor power(divide by 12 toconvert to HP)

Displacement code

Optioncode

Oil equalizationport & threadedsight glass(-: standardversion)

Design version

Motor voltage code1=208-230v / 1 ph / 60 Hz3=200-230v / 3 ph / 60 Hz4=460v / 3ph / 60 Hz

Page 23: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

726

RECIPROCATING COMPRESSORS

DANFOSS-MANEUROP RECIPROCATING COMPRESSORS — TYPE MT/MTZ(cont)COMPRESSOR NOMENCLATURE

*Motor Codes:

LEGEND

NOTES: Ratings at ARI conditions for R-134a/R-22/R-407C: 45° F evap, 130° F cond, 15° F subcooling, 20° F superheat.Ratings at ARI conditions for R-404A/R-507: 20° F evap, 120° F cond, 15° F subcooling, 20° F superheat.

PART NO.AVAILABLE

MOTORCODES*

HPMT-R 22 MTZ-R 407C MTZ-R 134a MTZ-R 404A/507A

MCC LRADISCHARGE

CONN.(in.)

SUCTIONCONN.

(in.)

SHIPWT(lb)kW Btuh EER kW Btuh EER kW Btuh EER kW Btuh EER

MT/MTZ18 1,3,4 1.5 1.74 15,900 9.15 1.67 15,300 9.13 1.22 11,200 9.2 1.76 10,300 5.1 13 51 1 1 50

MT/MTZ22 1,3,4 2 2.27 22,000 9.68 2.17 19,600 9 1.54 14,800 9.63 2.05 14,100 6.01 17 49.3 1 1-1/4 50

MT/MTZ28 1,3,4 2.5 3.07 30,200 9.86 2.83 25,100 8.9 2.04 19,300 9.42 2.68 18,300 5.96 25 81 1 1-1/4 55

MT/MTZ32 1,3,4 2.75 3.58 33,000 9.22 3.21 28,400 8.86 2.39 20,900 8.76 2.99 20,100 5.85 26.5 84 1 1-1/4 60

MT/MTZ36 1,3,4 3 4.05 38,000 9.38 3.75 32,700 8.73 2.75 24,500 8.91 3.34 23,200 6.05 30 84 1 1-1/4 60

MT/MTZ40 1,3,4 3.5 4.63 42,900 9.27 4.33 37,400 8.64 3.08 27,900 9.03 3.77 26,400 6.11 34 99 1 1-1/4 60

MT/MTZ44 1,3,4 4 4.67 45,200 9.69 4.37 43,000 9.84 3.14 29,800 9.51 4.18 27,800 6.65 31 97 1-1/4 1-3/4 85

MT/MTZ50 1,3,4 4.5 5.18 50,500 9.74 4.96 48,100 9.71 3.6 34,500 9.57 4.83 32,500 6.73 36 114 1-1/4 1-3/4 85

MT/MTZ56 1,3,4,7 5 6.05 56,400 9.32 5.67 54,300 9.59 3.95 38,000 9.62 5.44 36,500 6.71 46 146 1-1/4 1 90

MT/MTZ64 1,3,4 5.5 6.8 64,800 9.53 6.36 60,400 9.5 4.68 45,300 9.66 6.12 41,500 6.78 53 148 1-1/4 1-3/4 90

MT/MTZ72 3,4 6 7.58 70,100 9.26 7.22 67,900 9.41 5.19 50,000 9.63 6.91 46,500 6.72 31 135 1-1/4 1-3/4 90

MT/MTZ80 3,4 7 8.56 80,000 9.35 8.24 76,900 9.33 6 56,500 9.42 8.03 52,500 6.54 36 140 1-1/4 1-3/4 90

MT/MTZ100 3,4,7 9 9.59 95,900 10 9.9 94,400 9.53 6.5 63,900 9.84 8.72 60,800 6.07 43 157 1-1/4 1-3/4 145

MT/MTZ125 3,4,7 10 12.81 124,600 9.73 12.62 122,100 9.67 7.72 78,900 10.22 11.37 78,400 6 54 210 1-1/4 1-3/4 150

MT/MTZ144 3,4,7 12 14.36 140,700 9.8 14.47 137,200 9.48 9.82 96,900 9.87 13 92,300 6.19 64 259 1-1/4 1-3/4 155

MT/MTZ160 3,4,7 13.5 16.09 156,800 9.75 16.67 155,100 9.31 10.92 107,600 9.85 14.74 100,300 5.93 70 259 1-1/4 1-3/4 165

Code Description

1 208-230V / 1ph / 60Hz

3 200-230V / 3ph / 60Hz

4 460V / 3ph / 60Hz

7 575V / 3ph / 60hz

LRA — Locked Rotor AmpsMCC — Maximum Continuous Current (A)

Page 24: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

727

RECIPROCATING COMPRESSORS

DANFOSS-MANEUROP RECIPROCATING COMPRESSORS — TYPE MT/MTZ(cont)Reciprocating Compressor Accessories

PART NO. DESCRIPTIONCOMPRESSOR TYPES AND SIZES

Type MT / MTZ Type LT / LTZ18 22 28 32 36 40 44 50 56 64 72 80 100 125 144 160 22 28 44 50 88 100

Rotolock Valves6804500 Rotolock 1 in. R x 3/8 in. S X X X X X X X X

6804501 Rotolock 1 in. R x 1/2 in. S X X X X X X X X

6804502 Rotolock 1-1/4 in. R x 5/8 in. S X X X X X X X

6804503 Rotolock 1-1/4 in. R x 3/4 in. S X X X X X X X X X X X X X X X X X X X X X

6804504 Rotolock 1-1/4 in. R x 7/8 in. S X X X X X X X X X X X X X X X X X X X X X

6804505 Rotolock 1-3/4 in. R x 7/8 in. S X X X X X X X X X X X X X X

6804506 Rotolock1-3/4 in. R x 1-1/8 in. S X X X X X X X X X X X X X X

6804010 Rotolock1-3/4 in. R x 1-3/8 in. S X X X X X X X X X X X X X X

8156009 Complete Teflon Gasket Kit X X X X X X X X X X X X X X X X X X X X X X

Rotolock Solder Sleeves (non standard sizes)Part No. Description Type MT / MTZ Type LT / LTZ8153012 1-1/4 in. R x 7/8 in. S X X X X X X X X X X X X X X X X X X X

8153003 1-3/4 in. R x 1-3/8 in. S X X X X X X X X X X X X X X

Rotolock NutsPart No. Description Type MT / MTZ Type LT / LTZ

A104174P01 1-1/4 in. Rotolock Nut X X X X X X X X X X X X X X X X X X X X X

A104174P02 1-3/4 in. Rotolock Nut X X X X X X X X X X X X X X

A104174P05 1 in. Rotolock Nut X X X X X X X X

Installation / Mounting Kits (* some mounting kits are voltage speci c)Part No. Description Type MT / MTZ Type LT / LTZ

5710058P01Mounting kits include mountinggrommets, sleeves, nuts bolts

washers, also included are soldersleeves, te on gaskets and

installation instructions

X X X X X X

5710058P02 X X X

5710058P03 X X

5710058P04 X X X X X X

5710058P05 X X X X X X

Crankcase HeatersPart No. Description Type MT / MTZ Type LT / LTZ

PTC 35 watt, 200-600 volt X X X X X X X X X X X X X X X X X X X X X X

Oil Sight GlassPart No. Description Type MT / MTZ Type LT / LTZ6204001 Oil Sight glass (all models) X X X X X X X X X X X X X X X X X X X X X X

LubricantsPart No. Description Type MT / MTZ Type LT / LTZ7754027 1 Gallon POE oil for LTZ X X X X X X

Acoustic HoodsPart No. Description Type MT / MTZ Type LT / LTZ7755001 Acoustic Hood X X X X X X X X

7755002 Acoustic Hood X X X X X X X X

7755003 Acoustic Hood X X X X X X

Page 25: DANFOSS-MANEUROP REFRIGERATION HERMETIC … · Air Cooled Condensing Units Type CMT(E) and CLT(E) include: • Maneurop compressor with oil level sight glass and rotolock service

728

RECIPROCATING COMPRESSORS

DANFOSS-MANEUROP RECIPROCATING COMPRESSORS — TYPE LT/LTZ

*Motor Codes

LEGEND

*Rated Condition: R-404A/R-507, –10° F Evap, 130° F Cond, 15° F subcooling, 20° F superheat.**Rated Condition: R-404A/R-507, –30° F Evap, 120° F Cond, 15° subcooling, 20° F superheat.

PART NO.AVAILABLE

MOTORCODES*

HPR-404A/R-507A LTZ R-502 LT

MCC LRADISCHARGE

CONN.(in.)

SUCTIONCONN.

(in.)

SHIPWT(lb)

–10° F Evap –30° F Evap –10° F Evap –30° F EvapkW Btuh kW Btuh kW Btuh kW Btuh

LT/LTZ22 1,3,4 2 1.75 5,230 1.16 2,950 1.81 5,925 1.2 2,720 17 49.3 1 1-1/4 50LT/LTZ28 1,3,4 2.5 2.58 7,890 1.7 4,510 2.71 9,805 1.8 5,385 25 81 1 1-1/4 50

LT/LTZ44 1,3,4 4 4.37 13,520 3.1 7,540 4.02 16,051 2.75 7,820 34 103 1-1/4 1-3/4 80LT/LTZ50 1,3,4 4.5 5.46 17,470 3.93 10,360 5.33 19,027 3.65 10,420 37 143 1-1/4 1-3/4 85LT/LTZ88 3,4 7.5 8.32 26,860 5.86 14,440 7.74 29,427 5.3 16,000 43 157 1-1/4 1-3/4 140

LT/LTZ100 3,4 9 10.56 35,480 7.23 19,930 10.32 38,911 7.25 22,615 54 210 1-1/4 1-3/4 150

Code Description

1 208-230V / 1ph / 60Hz

3 200-230V / 3ph / 60Hz

4 460V / 3ph / 60Hz

LRA — Locked Rotor AmpsMCC — Maximum Continuous Current (A)

LT Z 64 HM 4 - VE -Compressortype

Lubricant(Z: Polyolester oil-: mineral oil)

Motor power(divide by 12 toconvert to HP)

Displacement code

Optioncode

Oil equalizationport & threadedsight glass(-: standardversion)

Design version

Motor voltage code1=208-230v / 1 ph / 60 Hz3=200-230v / 3 ph / 60 Hz4=460v / 3ph / 60 Hz