8
Data sheet 3VA6110-6HM41-2AA0 CIRCUIT BREAKER 3VA6 UL FRAME 150 BREAKING CAPACITY CLASS H 65KA @ 480V 4-POLE, LINE PROTECTION ETU330, LIG, IN=100A OVERLOAD PROTECTION IR=40A ...100A SHORT CIRCUIT PROTECTION II=1,5...12 X IN NEUTRAL PROTECTION ADJUSTABLE(OFF,50%,100%) GROUND-FAULT-PROTECTION IG=0,2... 1 X IN, TG=0,1/0,3S W/O CONNECTION Model Product brand name SENTRON Product designation Molded-case circuit breaker Design of the product System protection Design of the load switch / acc. to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type) Yes Design of the overcurrent release ETU330 Protective function of the overcurrent release LIG Number of poles 4 General technical data Tension assignée d'isolement Ui 600 V Max. rated operational voltage Ue with AC 50/60Hz 600 V Active power loss / for rated value of the current / at AC / in hot operating state / per device 13 W Active power loss / for rated value of the current / at AC / in hot operating state / per pole 4.33 W Mechanical service life (switching cycles) / typical 20 000 3VA6110-6HM41-2AA0 Subject to change without notice Page 1/ 8 12/06/2017 © Copyright Siemens

Data sheet 3VA6110-6HM41-2AA0

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Data sheet 3VA6110-6HM41-2AA0CIRCUIT BREAKER 3VA6 UL FRAME 150 BREAKING CAPACITYCLASS H 65KA @ 480V 4-POLE, LINE PROTECTION ETU330,LIG, IN=100A OVERLOAD PROTECTION IR=40A ...100A SHORTCIRCUIT PROTECTION II=1,5...12 X IN NEUTRAL PROTECTIONADJUSTABLE(OFF,50%,100%) GROUND-FAULT-PROTECTIONIG=0,2... 1 X IN, TG=0,1/0,3S W/O CONNECTION

ModelProduct brand name SENTRONProduct designation Molded-case circuit breakerDesign of the product System protectionDesign of the load switch / acc. to UL 489 / Heating,Air Conditioning, and Refrigeration circuit breaker(HACR Type)

Yes

Design of the overcurrent release ETU330Protective function of the overcurrent release LIGNumber of poles 4

General technical dataTension assignée d'isolement Ui 600 VMax. rated operational voltage Ue with AC 50/60Hz 600 VActive power loss / for rated value of the current / atAC / in hot operating state / per device

13 W

Active power loss / for rated value of the current / atAC / in hot operating state / per pole

4.33 W

Mechanical service life (switching cycles) / typical 20 000

3VA6110-6HM41-2AA0 Subject to change without noticePage 1/8 12/06/2017 © Copyright Siemens

Electrical endurance (switching cycles) / at AC-1 / at380/415 V 50/60 Hz

9 000

Electrical endurance (switching cycles) / at AC-1 / at690 V 50/60 Hz

5 000

Electrical endurance (switching cycles) / at 480 V / at50/60 Hz

9 000

Electrical endurance (switching cycles) / at 600 V / at50/60 Hz

9 000

Neutral conductors / upgradeable/retrofittable NoGround fault monitoring version Summation current formation L + N-conductorProduct function

● communication function No

● other measurement function No

ElectricityMarking / acc. to UL 489 / 100%-rated breaker YesMax. rated operational voltage of the size of thecircuit-breaker

150 A

Courant permanent assigné Iu 100 AOperating current

● at 40 °C 100 A

● at 45 °C 100 A

● at 50 °C 100 A

● at 55 °C 100 A

● at 60 °C 100 A

● at 65 °C 100 A

● at 70 °C 100 A

Switching capacity according to IEC 60947Switching capacity class of the circuit breaker HMaximum short-circuit current breaking capacity (Icu)

● at 240 V 110 kA

● at 415 V 85 kA

● at 690 V 2.5 kA

Operational short-circuit current breaking capacity(Ics)

● at 240 V 110 kA

● at 415 V 85 kA

● at 690 V 2.5 kA

Short-circuit current making capacity (Icm)

● at 240 V 242 kA

● at 415 V 187 kA

● at 690 V 3.8 kA

Switching capacity according to UL 489

3VA6110-6HM41-2AA0 Subject to change without noticePage 2/8 12/06/2017 © Copyright Siemens

Breaking capacity current

● at 240 V 100 kA

● at 480 Y/277 V 65 kA

● at 480 V 65 kA

● at 600 Y/347 V 22 kA

● at 600 V 22 kA

Adjustable parametersAdjustable response value current / lg min. 40 AAdjustable response value current / lg min. 100 AAdjustable response value current / lg min. 0.5Adjustable response value current / lg min. 17Adjustable response value current / li min. 150 AAdjustable response value current / li max. 1 200 AGround fault protection can be switched ON/OFF NoGround fault protection / tripping switchable /I2t=ON/OFF

Yes

Adjustable response value current / lg min. 20 AAdjustable response value current / lg max. 100 AAdjustable response value current / tg min. 0.1 sAdjustable response value current / lg min. 0.3 s

Mechanical DesignHeight [in] 7.8 inHeight 198 mmWidth [in] 5.5 inWidth 140 mmDepth [in] 3.4 inDepth 86 mm

ConnectionsArrangement of electrical connectors / for maincurrent circuit

Without connection

Type of electrical connection / for main current circuit Without

Auxiliary circuitNumber of CO contacts / for auxiliary contacts 0

AccessoriesProduct extension / optional / motor drive Yes

Environmental conditionsProtection class IP / on the front IP40Ambient temperature

● during operation / minimum -25 °C

● during operation / maximum 70 °C

● during storage / minimum -40 °C

3VA6110-6HM41-2AA0 Subject to change without noticePage 3/8 12/06/2017 © Copyright Siemens

● during storage / maximum 80 °C

CertificatesEquipment marking / acc. to DIN EN 81346-2 QCertificate of suitability / as approval for NAVAL (nocombat vessels) / Supplement SB

No

General Product Approval EMC Declaration ofConformity

ShippingApproval

other

Miscellaneous

Further informationInformation- and Downloadcenter (Catalogs, Brochures,…)http://www.siemens.com/lowvoltage/catalogs

Industry Mall (Online ordering system)https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VA6110-6HM41-2AA0

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)https://support.industry.siemens.com/cs/ww/en/ps/3VA6110-6HM41-2AA0

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA6110-6HM41-2AA0

CAx-Online-Generatorhttp://www.siemens.com/cax

Tender specificationshttp://www.siemens.com/specifications

3VA6110-6HM41-2AA0 Subject to change without noticePage 4/8 12/06/2017 © Copyright Siemens

52.5

[2.07]

140

[5.51]

198

[7.8

0]

157

[6.1

8]35

[1.38]

35

[1.38]

35

[1.38]

20

[0.79]

20.5

[0.8

1]

20.5

[0.8

1]

9

[0.35]

19

[0.75]

38

[1.50]

18

[0.71]

18

[0.71]

4

[0.16]

83

[3.27]

93

[3.66]

107

[4.21]

70

[2.7

6]

81

[3.1

9]

31

[1.2

2]

136

[5.3

5]

31

[1.2

2]

28.3

[1.1

1]

28.3

[1.1

1]

35

[1.38]

70

[2.76]

73

[2.8

7]

146

[5.7

5]

26

[1.0

2]

4.7

[0.19]

3VA6110-6HM41-2AA0 Subject to change without noticePage 5/8 12/06/2017 © Copyright Siemens

SIEMENS

I>>

N

L

I

N

G

ETU330

-Q

I> I> I> I>

-X2

1 3 5 N

2 4 6 N.EFB

3VA6110-6HM41-2AA0 Subject to change without noticePage 6/8 12/06/2017 © Copyright Siemens

SIEMENS

I>>I

ETU330

-CB

L

NN

G

1

3

5

2

4

6

-X2EFB/AFB

N N.

3VA6110-6HM41-2AA0 Subject to change without noticePage 7/8 12/06/2017 © Copyright Siemens

last modified: 11/23/2017

3VA6110-6HM41-2AA0 Subject to change without noticePage 8/8 12/06/2017 © Copyright Siemens