J TECHNICAL DATA SHEET Nozzles 01.01.2007 NOZZLE DK 6   04    A57°C (- T) Version 1 Page 1 of 1 FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.  © FOGTEC Bran dschutz GmbH & Co. KG Schanzen str. 19A 51063 K öln Germany  [email protected]  www.fogtec.com Tel.: +49-(0)-221 96 22 30 Description This nozzle is used for automatic systems (wet pipe, dry pipe and pre-action). It requires no additional detection system (except pre – action system). In stand-by mode, the water is blocked by a piston inside the nozzle. As result of heat, the glass bulb bursts and the piston is pushed downwards by a spring. This opens the water way and water is discharged. Optional protective Teflon caps prevent passing contamination inside the nozzle. General Properties K – Factor: 1,200 Flow r ate (at 100 bar): 12,00 l/min Glass bulb: Fast Response 57°C Material nozzle body and cage: Stainless steel Material micro – nozzles: Stainless steel with brass swirling device Material micro – filter: Stainless steel with copper seal Material O – ring: NBR* Material piston : Brass Material spring: Stainless Steel Material protecti ve cap: Teflon Weight: 0,200 kg * O – ring is recommended to be changed every 10 years Part Number Descrip tion Part Number DK 6 – 04 A57°C 33000918 DK 6 – 04 A57°C T 33000792

Data Sheet Examples

Embed Size (px)

Citation preview

Page 1: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 1/23

J

TECHNICAL DATA SHEET  Nozzles 01.01.2007

NOZZLE  DK 6  – 04  –  A57°C (- T) Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

This nozzle is used for automatic systems (wet pipe, dry pipe and pre-action). Itrequires no additional detection system (except pre – action system). In stand-by mode,the water is blocked by a piston inside the nozzle. As result of heat, the glass bulbbursts and the piston is pushed downwards by a spring. This opens the water way andwater is discharged.Optional protective Teflon caps prevent passing contamination inside the nozzle.

General Properties

K – Factor : 1,200

Flow rate (at 100 bar): 12,00 l/min

Glass bulb: Fast Response 57°C

Material nozzle body and cage: Stainless steel

Material mic ro – nozzles: Stainless steel with brass swirling device

Material micro – filter: Stainless steel with copper seal

Material O – ring: NBR*

Material piston : Brass

Material spring: Stainless SteelMaterial protecti ve cap: Teflon

Weight: 0,200 kg

* O – ring is recommended to be changed every 10 years

Part Number

Descrip tion Part Number

DK 6 – 04 – A57°C 33000918

DK 6 – 04 – A57°C – T 33000792

Page 2: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 2/23

J

TECHNICAL DATA SHEET  Nozzles 01.01.2007

NOZZLE  DK 5  – 11  – O (- T) Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

This nozzle is used for deluge systems. It requires a system with manual, electric orpneumatic activation. As soon as the system is activated, water mist is discharged.Optional protective Teflon caps prevent passing contamination inside the nozzle.

General Properties

K – Factor : 0,290

Flow rate (at 100 bar): 2,90 l/min

Material nozzle body: Stainless steel

Material mic ro – nozzles: Stainless steel with brass swirling device

Material micro – filter: Stainless steel with copper seal

Material O – ring: NBR*

Material protecti ve cap: Teflon

Weight: 0,200 kg

* O – ring is recommended to be changed every 10 years

Part Number

Descrip tion Part Number

DK 5 – 11 – O 33000080

DK 5 – 11 – O – T 33000081

Page 3: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 3/23

 

TECHNICAL DATA SHEET  Sockets 01.01.2007

INDUSTRIAL SOCKET OT L12 Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

© FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

Socket is to be used only with FOGTEC nozzles. Socket has one pipe connection inaddition to nozzle inlet. Cutting ring and nut are included to socket assembly.

General Properties

Material (socket and nuts): Stainless steel

Material (cutting ring): Stainless steel

Pipe tolerances: 12mm (ø12x1,0 DIN2391)

Max pressure: 200 bar

Weight: 0,160 kg

Part Number

Descrip tion Part Number

Industrial Socket OT L12 33100003

Page 4: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 4/23

 

TECHNICAL DATA SHEET  Sockets 01.01.2007

T-SOCKET OT L12 Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

© FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

Socket is to be used only with FOGTEC nozzles. Socket has two pipe connections inaddition to nozzle inlet. Cutting rings and nuts are included to socket assembly.

General Properties

Material (socket and nuts): Stainless steel

Material (cutting ring): Stainless steel

Pipe tolerances: 12mm (ø12x1,0 DIN2391)

Max pressure: 200 bar

Weight: 0,340 kg

Part Number

Descrip tion Part Number

T-Socket OT L12 33100030

Page 5: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 5/23

 

TECHNICAL DATA SHEET  Wall Cabinets 01.01.2007

W ALL C ABINET B WITH FOGGUN 2 Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

The FOGGUN wall cabinet system is designed for manual fire fighting. It can be eitherstand-alone or be part of a FOGTEC fixed installation with automatic or open nozzles. TheFOGGUN wall cabinet system includes the wall cabinet and the FOGGUN 2 fire fighting gun.The FOGGUN 2 has two different spray pattern settings which can be chosen. The first set-ting creates a very effective fine droplet water mist, so even fluid or dust fires normally canbe put out without splashing. The fine mist can be used in conjunction with a centrally locat-ed jet that creates a coarse mist. The central jet is used to achieve greater reach or to ena-ble the use of mist on deep seated fires by using higher momentum of the droplets. TheFOGGUN also produces lateral jets which protect the fire fighter from radiated heat.

General Properties

Material of box: Carbon steel and corrosion resistant painting

Colour: Red (RAL3000)

Fire fighting gun: FOGGUN 2:- Flow 25l/min @ 100 bar

- Maximum pressure 120 bar- 12 side nozzles and 1 center nozzle 

Hose: DN12, 35 or 70 meters, stainless steel fittings

Connection to the system: Stainless steel fitting for pipe L15 (DIN2391)

Part Number

Descrip tion Hose Length Part Number

Wall Cabinet B with FOGGUN 2 30 m 34000051

Wall Cabinet B with FOGGUN 2 50 m 34000052

Page 6: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 6/23

J

TECHNICAL DATA SHEET  Section Valves 01.01.2007

SECTION V ALVE – SOLENOID G 1“ (DN25) Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

The section valve is meant to be used with deluge system and open nozzles. The pressure range ofvalve is designed for pump systems.

The section valve is a 2/2 – way solenoid valve that is controlled by an external fire detection system.They can be installed in different locations or they can be centralized in a valve station with a separatesupply pipe to each section, or decentralized at each distribution point from the main high pressure sup-ply pipe to the individual sections.

The test connection is used for air/water bleeding and testing the function of the solenoid section valve.

General Properties

Materials (contact to water): Stainless Steel

Connections: BSP - ISO 1719-1

Valve operation : Normally Closed

Maximum operating pressure: 150 barSolenoids: 24V(1,9A), 110V(0,42A), 230V(0,2A)

Part Number

Descrip tion Part Number

SECTION VALVE - SOLENOID G1”(150bar) – 24V 35000074

SECTION VALVE - SOLENOID G1”(150bar) – 110V 35000095

SECTION VALVE - SOLENOID G1”(150bar) – 230V 35000025

Page 7: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 7/23

J

TECHNICAL DATA SHEET  Section Valves 01.10.2008

SECTION V ALVE – OH G 1“ (DN25) Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

Valve is meant for automatic systems where the main pipes are wet until automatic nozzles. Thesection valve is especially design for Ordinary Hazard Group 1 applications. The section valvegroups nozzles to separate zones. The section valve has several functions which are following:

 A. Detection of activated zone and giving an alarm signalB. Closing section manuallyC. Test connection for regular operation tests without activating nozzleD. Check valve function allowing drainage of main pipes without draining section pipingE. Pressure gauge for visual pressure level check

The section valve can be equipped on request with limit switch to control the portion of manualclosing valve. The section valve will be delivered without fittings. 

General Properties

Materials (contact to water): Stainless Steel / Brass

Connections: ISO 1719-1

Maximum operating pressure: 140 bar

Pressure loss: 3.5bar @ 150l/min

Flow switch: Max 200V, 1A, 20VA

Pressure gauge: 0-250bar

Part Number  Descrip tion Part Number

SECTION V ALVE – OH G1 (140bar) Standard 35000255

SECTION V ALVE – OH G1 (140bar) with limit switch on request

Page 8: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 8/23

J

TECHNICAL DATA SHEET  Section Valves 01.01.2007

SECTION V ALVE – PNEUMATIC G 1“ (DN25)Version 1

Page 1 of 1

Fogtec Brandschutz GmbH & Co. KG  Schanzenstr. 19 A D–51063 Köln (Cologne)Tel: +49-221-96223-0 Fax: +49-221-96223-30 [email protected] www.fogtec.com

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. The document is protected under copyright law. Allrights with regard to the contents are reserved. These documents are to be treated confidentially. They may not be copied and third parties may not be allowed access to themwithout written consent. They are to be returned to us on request. These documents may not be translated, microfilmed nor stored or further processed in electronic systemswithout written consent. In the case of contravention of our rights legal action will be taken. Any rights to claim compensation are reserved  

Description

This valve is meant for deluge systems where the main pipes are wet until section valves. Sectionpiping is dry and only open nozzles are used.The valve combines following parts. A. Manual service valve, B. Testing connection and C. pneumatic driven main valve. 

General Properties

Materials: Stainless Steel

Connections: BSP - ISO 1719-1Valve operation: Normally Closed

Maximum operating pressure: 120 bar

 Ai r supply: 6 bar

Power supply: 24 V, DC

Part Number

Descrip tion Part Number

SECTION V ALVE – PNEUMATIC G 1” (120bar) 35000098

Page 9: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 9/23

J

TECHNICAL DATA SHEET  Section Valves 01.01.2007

SECTION V ALVE – PRE- ACTION G 1“ (DN25)Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

This valve is to be used in water mist systems with automatic nozzles and wet pipe work until thesection valve, where the pipework after section valve shall be under pressurized air in stand-bysituation.The valve combines following parts. A. Manual service valve, B. Two pressure gauges, C. Pressure sensor, D. Testing connection andE. Pneumatic driven main valve. 

General Properties

Materials: Stainless Steel

Connections: BSP - ISO 1719-1Valve operation: Normally Closed

Maximum operating pressure: 120 bar

 Ai r supply: 6 bar

Power supply: 24 V, DC

Part Number

Descrip tion Part Number

SECTION V ALVE – PRE-ACTION G1” (120bar) 35000104

Page 10: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 10/23

 

TECHNICAL DATA SHEET  Cylinder systems 01.01.2007

80-LITRE M ASTER MODULE

ELECTRIC RELEASE/DRY PIPE SYSTEM 

Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

© FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ●  [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

The activation is triggered by an electric signal. The nitrogen cylinder valve is a solenoid op-erated valve with manual override for safety reasons in case of electric failure. After activa-tion the nitrogen is released to the slave module which will pressurize the pipe work and thenozzles starts the extinguishing. A pressure switch in the water manifold of the slave modulegives a message of activated system.

General Properties

Nitrogen cy linder : 1 x 80 litre (pressure 200 bar at 20°C)

Release method: Solenoid valve (electric signal or manual override)

Compatible Slave Modules: 31100380, 31100381, 31100382, 31100383,

31100384, 31100385

Connections:

Slave port Stainless steel fitting for pipe L12 (DIN2391)

N2 filling port W21,8x1/14” (DIN477)

Electric components:

Solenoid 24V (10W) available also in 230V on request

Pressure switch 230V (max. 6A), set value 30bar

Part Number

Descrip tion Part Number

Dry Pipe Master Cylinder Module 1 x 80l N2, Electric release 31100311

Page 11: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 11/23

 

TECHNICAL DATA SHEET  Cylinder systems 01.01.2007

80-LITRE SLAVE MODULE 6 X 80L DRY PIPE SYSTEM 

Version 1

Page 1 of 1

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

The activation is triggered by pressure increase caused by activation of the master cylinder. After activation the nitrogen is released to the water cylinder which will pressurize the pipework and the nozzles starts the extinguishing. A pressure switch in the water manifold givesa message of activated system. This module shall only used in combination with dry pipesystem master modules. 

General Properties

Water cylinder: 4 x 80 litre

Nitrogen cylinder: 1 x 80 litre (pressure 200 bar at 20°C)

Release method:  Activated by Dry Pipe System Master Module

Compatible Master Modules: 31100311, 31100316

Connections:

Water port Stainless steel fitting for pipe L12 (DIN2391)

N2 filling port W21,8x1/14” (DIN477)

Part Number

Descrip tion Part Number

Dry Pipe Slave Cylinder Module 4 x 80l H20 + 1 x 80l N2 31100382

Page 12: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 12/23

 

TECHNICAL DATA SHEET  Pump systems 00.00.2007

PUMP UNIT 2X120 L/MIN AUTOMATIC 

Version 1

Page 1 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

This 2x120 l/min pump unit is designed to be used in automatic systems. The pump unit is built modularand with reduced number of components. The jockey pump is meant to keep the pre-pressure of approx.20bar in wet pipes. The high-pressure pump type used is a triplex plunger high-pressure pump with themaximum flow rate of 120l/min at maximum pressure of 120bar. Both pumps in the pump unit assemblyhave individual electric motors, couplings and safety valves. Other main components are connected tothe suction and high-pressure manifolds that are shown in the dimension drawing.

Dimensions and main components

Specifications

Materials (contact to water): Stainless Steel / Brass

Suction connection: DN80

Discharge connection: DN32

Maximum operating pressure: 120 bar

Maximum f low rate: 2x120 l/min

Jockey pump unit

Frame

Suction manifold

Electric motor

Housing and coupling

High-pressure pump

High-pressure manifold

Page 13: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 13/23

 

TECHNICAL DATA SHEET  Pump systems 00.00.2007

PUMP UNIT 2X120 L/MIN AUTOMATIC 

Version 1

Page 2 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Safety valve: One per pump

Strainer / filter: One per pump

Electric motor: 2x30kW (400V, 50Hz)

Weight: 1060kg

Part numbers and arrangement

The pump unit is available in two versions. The standard version has all pipe connections to the rightside of the pump unit. The mirrored version has all pipe connections to the left side.

2x120 l/min Automatic, Standard (30100835) 2x120 l/min Automatic, Mirro red (30100857)

Descript ion Version Part number

2 x 120l/min Automatic Standard 30100835

2 x 120l/min Automatic Mirrored 30100857

Compatibility

Pump unit can be connected to the following tank, suction line / filling units and return line. (See technicaldata sheets of tank units in order to see the different layout possibilities with different tank and pump unitcombinations) 

2x120 l/min Automatic, Standard (30100835):

2x120 l/min Automatic, Mirrored (30100857):

Tank unit / Suction line Part Number Return line (optional) Compressor (optional)

500L, DN80Standard30000729

DN5030000716

 All suitable

1000L, DN80Standard30000735 

DN5030000716 

 All suitable

3000L, DN80Standard30000745 

DN5030000716 

 All suitable

4000L (On request) - - -

Tank unit / Suction line Part Number Return line (optional) Compressor (optional)

500L, DN80Mirrored

30000732 DN50

30000716 All suitable

1000L, DN80Mirrored

30000740 DN50

30000716  All suitable

3000L, DN80Mirrored

30000750 DN50

30000716  All suitable

4000L (On request) - - -

Page 14: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 14/23

 

TECHNICAL DATA SHEET  Pump systems 13.04.2007

PUMP UNIT 2X120 L/MINDELUGE 

Version 1

Page 1 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

© FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

This 2x120 l/min pump unit is designed to be used in deluge systems. The pump unit is built modular andwith reduced number of components. The pump type used is a triplex plunger high-pressure pump withthe maximum flow rate of 120l/min at maximum pressure of 120bar. Both pumps in the pump unit as-sembly have individual electric motors, couplings and safety valves. Other main components are con-nected to the suction and high-pressure manifolds that are shown in the dimension drawing.

Dimensions and main components

Specifications

Materials (contact to water): Stainless Steel / Brass

Suction connection: DN80

Discharge connection: DN32

Maximum operating pressure: 120 bar

Maximum f low rate: 2x120 l/min

Safety valve: One per pump

Strainer / filter: One per pump

Electric motor: 30kW (400V, 50Hz)

Weight: 1060kg

Frame

Suction manifold

Electric motor

Housing and coupling

High-pressure pump

High-pressure manifold

Page 15: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 15/23

 

TECHNICAL DATA SHEET  Pump systems 13.04.2007

PUMP UNIT 2X120 L/MINDELUGE 

Version 1

Page 2 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

© FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Part numbers and arrangement

The pump unit is available in two versions. The standard version has all pipe connections to the rightside of the pump unit. The mirrored version has all pipe connections to the left side.

2x120 l/min Deluge, Standard (30100856) 2x120 l/min Deluge, Mirrored (30100858)

Descript ion Version Part number

2 x 120l/min Deluge Standard 30100856

2 x 120l/min Deluge Mirrored 30100858

Compatibility

Pump unit can be connected to the following tank, suction line / filling units and return line. (See technicaldata sheets of tank units in order to see the different layout possibilities with different tank and pump unitcombinations) 

2x120 l/min Deluge, Standard (30100856):

2x120 l/min Deluge, Mirro red (30100858):

Tank unit / Suction line Pump unit Return line (optional) Compressor (optional)

500L, DN80Standard30000729

DN5030000716

 All suitable

1000L, DN80Standard30000735 

DN5030000716 

 All suitable

3000L, DN80Standard

30000745 

DN50

30000716  All suitable

4000L (On request) - - -

Tank unit / Suction line Pump unit Return line (optional) Compressor (optional)

500L, DN80Mirrored

30000732 DN50

30000716 All suitable

1000L, DN80Mirrored

30000740 DN50

30000716  All suitable

3000L, DN80Mirrored

30000750 DN50

30000716  All suitable

4000L (On request) - - -

Page 16: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 16/23

 

TECHNICAL DATA SHEET  Pump systems 17.04.2007

COMPRESSOR Version 1

Page 1 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

© FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

The compressor produces compressed air that is needed in pre-action and dry pipe systems for filling thepipes or using pneumatic operated valves in deluge systems. The compressor for all systems is thesame, but there are two different mounting versions. The compressor with wall mounting kit can be usedwith all pump units. The compressor with pump unit mounting kit is available only with 2 and 3 x 120l/min pump systems.

Types and Dimensions

Part numbers and Compatibility

Part number Type Compatibility

30100855Standard compressor with wall

mounting kit All pump units

30100834Standard compressor with pump

mounting kit

2x120l/min Deluge(30100856, 30100858)

2x120l/min Automatic(30100835, 30100857)

3x120l/min Deluge(30100860, 30100862)

3x120l/min Automatic(30100859, 30100861)

COMPRESSOR WITH WALLMOUNTING KIT

COMPRESSOR WITH PUMP

MOUNTING KIT

Page 17: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 17/23

 

TECHNICAL DATA SHEET  Pump systems 17.04.2007

COMPRESSOR Version 1

Page 2 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

© FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Specifications

Pressure connection: ¼“ connection, equipped with quickcoupling for DN6 hose

Capacity: 150l/min @ 6bar

Maximum pressure 10bar

Volume of tank: 24 litres

Power requirement: 1.2kW (400V, 50Hz)

Page 18: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 18/23

 

TECHNICAL DATA SHEET  Tank Unit 00.00.2007

1000 LITRE T ANK UNIT Version 1

Page 1 of 4

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

The 1000 litre tank unit can be used with all standard pump units. The tank unit can work as total volumestorage or as break tank where water is supplied from a tank to the pumps. The tank is simultaneouslyfilled with fresh water from an external water supply in brake tank arrangement. The main water supplymust assure the minimum flow rate of the pump system within a pressure range of 1,5 to 6 bar to tankfilling. Tanks should be placed generally close to the pump unit, but the tank pump orientation can bechanged to different layouts.

The standard tank is made of black polyethylene*. The tank frame is galvanized carbon steel. The fillingunit and suction line assemblies are part of the tank unit, but depended on the used pump configuration.The available suction line and filling unit assemblies are available in different sizes. The return line as-sembly can optionally be installed. The tank overflow is used to protect the tank against overfilling. Thetank overflow should always be connected to water drain.

 A level measurement is mounted to the side wall of the tank. This level measurement optically indicatesthe water level in the tank. It also includes switches, giving opening signals via the PLC control to thetank filling valve as well as a minimum alarm if the water level in the tank reaches the lowest level.

Dimensions and main components**

* 1000 litre stainless steel tank unit is also available on request, please contact FOGTEC Fire Protection.** Notice! Dimensions might change slightly depending on chosen filling unit and suction line assembly

Main filter

Frame

Overflow

Return line

Suction connection

Filling valve

Page 19: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 19/23

 

TECHNICAL DATA SHEET  Tank Unit 00.00.2007

1000 LITRE T ANK UNIT Version 1

Page 2 of 4

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Specifications

Tank material: Polyethylene (black)

Suction line size: DN40, DN50, DN80, DN100 and DN125

Filling unit assemblies: DN25, DN40 and DN50

Overflow connection: DN80

Return l ine assembly (optional): DN25 and DN50

Filtration rate (water): 100µm (abs.)

Filtration rate (air): 10 µm (abs.)

VersionsPump unit is available in two versions, standard and mirrored. The standard version has always all pipeconnections to the left side of the tank unit, which means that it can be connected to standard pump unitversions. The mirrored version means connections to the right side and only mirrored pump units. Themain dimensions of standard and mirrored pump units are exactly same.

1000 Lit re Tank Unit Standard 1000 Lit re Tank Unit Mirrored

Page 20: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 20/23

 

TECHNICAL DATA SHEET  Tank Unit 00.00.2007

1000 LITRE T ANK UNIT Version 1

Page 3 of 4

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Possible layout arrangements

The connections between tank unit and pump units are flexible, which enables changing of the layouteasily. The following drawing shows approximate areas where tank unit can be positioned. The drawingshows standard pump and tank units, but this can be mirrored with mirrored pump and tank units.

Possible tank unit installation areawith standard supply components

There is minimum distance between tank and pump unit that varies depending on the pump unit configu-ration. The normal minimum distance is 1.5 metre. This can be reduced to 0.7 metre if the pump unitconfigurations of 1-2 times 50l/min pumps or 1 time 120l/min pump units are used.

Part numbers and compatibility

The part numbers of different pump unit configurations are shown in the following table. The tank unitincludes always the suction line and filling unit assembly. These have to be dimensioned according topump unit configuration. All compatibilities between different pump units and 1000 litre tank unit are ex-plained in the table. The return line assembly is an optional selection with the different part number.

Notice! 1x50l/min and 1x120l/min standard pump units can be used with both tank designs. 

Page 21: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 21/23

 

TECHNICAL DATA SHEET  Tank Unit 00.00.2007

1000 LITRE T ANK UNIT Version 1

Page 4 of 4

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

1000 Litre Tank Unit Standard:

Filling unit size: *DN25, **DN40 and ***DN50

1000 Litre Tank Unit Mirrored:

Filling unit size: *DN25, **DN40 and ***DN50

Tank unit / Suction lineCompatibilit y 50l/min pump

units

Compatibility 120l/min pump

units

Return line assembly

(Optional)

1000L, DN40*30000733

1x50l/min deluge standard30100870

1x50l/min automatic standard30100869

2x50l/min deluge standard30100880

2x50l/min automatic standard30100881

-DN 25

30000753

1000L, DN50*30000734  -

1x120l/min deluge standard30100868

1x120l/min automatic standard30100867

DN 5030000716

1000L, DN80**30000735 

-

2x120l/min deluge standard

301008562x120l/min automatic standard

30100835

DN 5030000716 

1000L, DN100***30000736 

-

3x120l/min deluge standard30100860

3x120l/min automatic standard30100859

DN 5030000716 

1000L, DN125***30100737

-

4x120l/min deluge standard30100864

4x120l/min automatic standard30100863

DN 5030000716 

Tank unit / Suction lineCompatibility 50l/min pump

unitsCompatibility 120l/min pump

unitsReturn line assembly

(Optional)

1000L, DN40*30000738

1x50l/min deluge standard30100870

1x50l/min automatic standard30100869

2x50l/min deluge standard30100882

2x50l/min automatic standard30100883

-DN 25

30000753

1000L, DN50**30000739  -

1x120l/min deluge standard30100868

1x120l/min automatic standard

30100867

DN 5030000716

1000L, DN80***30000740 

-

2x120l/min deluge mirrored30100858

2x120l/min automatic mirrored30100857

DN 5030000716 

1000L, DN100***30000741 

-

3x120l/min deluge mirrored30100862

3x120l/min automatic mirrored30100861

DN 5030000716 

1000L, DN125***30100742

-

4x120l/min deluge mirrored30100866

4x120l/min automatic mirrored30100865

DN 5030000716 

Page 22: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 22/23

 

TECHNICAL DATA SHEET  Pump systems 16.04.2007

CONTROL C ABINETS FOR 120L/MIN PUMP UNITS Version 1

Page 1 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

 © FOGTEC Brandschutz GmbH & Co. KG ● Schanzenstr. 19A ● 51063 Köln ● Germany [email protected] ● www.fogtec.com ● Tel.: +49-(0)-221 96 22 30

Description

The control cabinet controls and monitors all electrical components in the pump system according theFOGTEC software that is installed to the PLC. Control cabinet controls both tank unit and pump unit. Theelectrical connections to tank unit are standard independent which tank unit is used, but they differ de-pending on the pump concept. All pump units will have a different control cabinet depending on the num-ber of pumps and used system type (deluge/automatic). Control cabinets are available with two possiblemounting possibilities depending on the size. Smaller systems with 1 to 2 pumps use cabinets with wallmounting. Larger pump systems are built to self standing cabinets.

Notice! Control cabinets have different sizes depending on mounting method and number of controlledpumps.

 All control cabinets have several self-diagnostic functions and failures are detected automatically. Controlcabinets have different programs for service runs. Pumps can also be manually operated and tested with

push buttons on the door of control cabinet.

Specifications

Power supply: 400V 50Hz (L1,L2,L3,PEN-4 wires)

Power requirement: 1x120 l/min = 30kW (main fuses 80A)2x120 l/min = 60kW (main fuses 125A)3x120 l/min = 90kW (main fuses 200A)4x120 l/min = 120kW (main fuses 250A)

IP class: 54

Potential free contacts :  A. Common failure

B. System runningC. Start signal (only deluge systems)Colour: RAL7035

Part numbers, Compatibi lity and Dimensions

Page 23: Data Sheet Examples

8/16/2019 Data Sheet Examples

http://slidepdf.com/reader/full/data-sheet-examples 23/23

 

TECHNICAL DATA SHEET  Pump systems 16.04.2007

CONTROL C ABINETS FOR 120L/MIN PUMP UNITS Version 1

Page 2 of 2

FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification.

Part number Type (compatibilit y) Mounting method Dimensions (x,y,z)

30300241 1x120l/min Automatic Wall 760x760x300

30300242 2x120l/min Automatic Wall 1000x1000x300

30300243 3x120l/min Automatic Wall Cabinet 1000x1400x30030300244 3x120l/min Automatic Standing 1000x2000x400

30300245 4x120l/min Automatic Standing 1600x2000x400

30300246 1x120l/min Open Wall 760x760x300

30300247 2x120l/min Open Wall 1000x1000x300

30300248 3x120l/min Open Wall Cabinet 1000x1400x300

30300249 3x120l/min Open Standing 1000x2000x400

30300250 4x120l/min Open Standing 1600x2000x400

For pre-action systems and dry pipe systems, please contact FOGTEC to receive project related specifi-cations.