The calculation system consider: the heat dissipated from the enclosure surfaces in conformity with IEC 60890 standard. The system calculates: # the air flow required to dissipate heat from the enclosure by fan filter, if ambient temperature is allways lower than max inside temperature. # the cooling power required to dissipate heat from the enclosure by thermoelectric unit or by conditioner if inside temperature has to be, at least sometimes, lower then ambient temperature
Citation preview
Parameter Model DC03CDNC1A
Dimensions, Weight & MountExternal Dimensions (Height x Width x Depth) mm 545×315×170External Dimensions (Height x Width x Depth) With Flange mm 583×352×170Weight kg 18Mounting Method Door MountedApplication Outdoor Environmental Protection & PerformanceWorking Temperature Range ºC -15 to +55Noise Level dB(A) 60Protection from Dust, Water and Wind Driven Rain IP 55Refrigerant R134a RoHS Compliant YesCooling/Heating Capacity Cooling Capacity@L25/L35 W 250Cooling Capacity@L35/L35 W 350Heating Capacity (Optional) W \Power ConsumptionPower Consumption@L25/L35 W 90Power Consumption@L35/L35 W 100Current@L25/L35 A 1.90 Current@L35/L35 A 2.10 AirflowInternal Airflow m3/h 150Power SupplyPower Supply Range VDC -44~-58Rated operating voltage - Controller VDC -48Rated operating voltage - Cooling/Heating System VDC -48Max. Current A 5.5Key ComponentsController EnvicoolFans Telecom LevelCompressor Telecom LevelHeater \External MaterialsSheet Metal Parts SECC + Powder PaintingColor (Optional) RAL 7035