DATASHEET - DILEM-10(400V50HZ,440V60HZ)
Contactor, 3p+1N/O, 4kW/400V/AC3
Part no. DILEM-10(400V50HZ,440V60HZ)Catalog No. 051788Eaton Catalog No. XTMC9A10N
Technical dataGeneralStandards IEC/EN 60947, VDE 0660, CSA, UL
Lifespan, mechanical; Coil 50/60 Hz Operations x 106 7
Lifespan, mechanical Operations x 106 10
Maximum operating frequency
Mechanical Ops./h 9000
electrical (Contactors without overload relay) Operations/h Page 05/070
Climatic proofing Damp heat, constant, to IEC 60068-2-78Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +50
Enclosed °C - 25 - 40
Storage °C
Min. ambient temperature, storage °C - 40
Ambient temperature, storage max. °C + 80
Mounting position As required, except vertical with terminals A1/A2 at the bottom
Mounting position
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Basic unit without auxiliary contact module
Main contacts, make contacts g 10
Main contacts Make/break contacts g
Make g 8
Basic unit with auxiliary contact module
Main contacts make contact g
Make g 10
Auxiliary contacts Make/break contacts g 20 / 20
Degree of Protection IP20
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Weight kg 0.17
Terminal capacity of auxiliary and main contacts
Screw terminals
Solid mm2 1 x (0.75 - 2.5)2 x (0.75 - 2.5)
Flexible with ferrule mm2 1 x (0.75 - 1.5)2 x (0.75 - 1.5)
Solid or stranded AWG 18 - 14
Stripping length mm 8
Terminal screw M3.5
07/31/2018 Eaton 051788 ED2018 V46.0 EN 1 / 12
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.51 x 6
Max. tightening torque Nm 1.2
Main conducting pathsRated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui V AC 690
Rated operational voltage Ue V AC 690
Safe isolation to EN 61140
between coil and contacts V AC 300
between the contacts V AC 300
Making capacity (cos ϕ to IEC/EN 60947) A 110
Breaking capacity
220 V 230 V A 90
380 V 400 V A 90
500 V A 64
660 V 690 V A 42
Short-circuit protection maximum fuse
Type ”2”, 500 V gL/gG A 10
Type ”1”, 500 V gL/gG A 20
ACAC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C Ith =Ie A 22
at 50 °C Ith =Ie A 20
at 55 °C Ith =Ie A 19
enclosed Ith A 16
Notes At maximum permissible ambient air temperature.
Conventional free air thermal current, 1 pole
Notes At maximum permissible ambient air temperature.
open Ith A 50
enclosed Ith A 40
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
Notes At maximum permissible ambient air temperature.
220 V 230 V Ie A 9
240 V Ie A 9
380 V 400 V Ie A 9
415 V Ie A 9
440V Ie A 9
500 V Ie A 6.4
660 V 690 V Ie A 4.8
Motor rating P kWh
220 V 230 V P kW 2.2
240V P kW 2.5
380 V 400 V P kW 4
415 V P kW 4.3
440 V P kW 4.6
500 V P kW 4
660 V 690 V P kW 4
AC-4
07/31/2018 Eaton 051788 ED2018 V46.0 EN 2 / 12
Rated operational current
Open, 3-pole: 50 – 60 Hz
Notes At maximum permissible ambient air temperature.
220 V 230 V Ie A 6.6
240 V Ie A 6.6
380 V 400 V Ie A 6.6
415 V Ie A 6.6
440 V Ie A 6.6
500 V Ie A 5
660 V 690 V Ie A 3.4
Motor rating P kWh
220 V 230 V P kW 1.5
240 V P kW 1.8
380 V 400 V P kW 3
415 V P kW 3.1
440 V P kW 3.3
500 V P kW 3
660 V 690 V P kW 3
DCRated operational current open
DC-1
12 V Ie A 20
24 V Ie A 20
60 V Ie A 20
110 V Ie A 20
220 V Ie A 20
Current heat losses (3- or 4-pole)
at Ith, 50 °C W 5.9
at Ie to AC-3/400 V W 1.2
Magnet systemsVoltage tolerance
AC operated
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz Pick-up x Uc 0.8 - 1.1
Dual-frequency coil 50/60 Hz Pick-up x Uc
Voltage tolerance Dual-frequency coil 50/60 Hz, max. pick-up voltage x Uc 1.1
Power consumption
AC operation
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz Pick-up VA 25
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz Pick-up W 22
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz Sealing VA 4.6
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz Sealing W 1.8
Duty factor % DF 100
Switching times at 100 % Uc
Make contact ms
Closing delay ms
Closing delay min. ms 14
Closing delay max. ms 21
Opening delay ms
Opening delay min. ms 8
Opening delay max. ms 18
Closing delay with top mounting auxiliary contact ms 45
Reversing contactors
Changeover time at 110 % Uc
Changeover time min. ms 16
07/31/2018 Eaton 051788 ED2018 V46.0 EN 3 / 12
Changeover time max. ms 21
Arcing time at 690 V AC ms 12
Auxiliary contactsPositive operating contacts to EN 60947-5-1 appendix L, including auxiliary contactmodule
Yes
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui V AC 690
Rated operational voltage Ue V AC 600
Safe isolation to EN 61140
between coil and auxiliary contacts V AC 300
between the auxiliary contacts V AC 300
Rated operational current
AC-15
220 V 240 V Ie A 6
380 V 415 V Ie A 3
500 V Ie A 1.5
DC L/R ≦ 15 ms
Contacts in series: A
1 24 V A 2.5
2 60 V A 2.5
3 100 V A 1.5
3 220 V A 0.5
Conv. thermal current Ith A 10
Control circuit reliability Failure rate λ <10-8, < one failure at 100 million operations(at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
Component lifespan at Ue = 240 V
AC-15 Operations x 106 0.2
DC current
L/R = 50 ms: 2 contacts in series at Ie = 0.5 A Operations x 106 0.15
Notes Switch-on and switch-off conditions based on DC-13, time constant as specified
Short-circuit rating without welding
Maximum overcurrent protective device
Short-circuit protection only PKZM0-4
Short-circuit protection maximum fuse
500 V A gG/gL 6
500 V A fast 10
Current heat loss at a load of Ith per contact W 1.1
Rating data for approved typesSwitching capacity
Maximum motor rating
Three-phase
200 V208 V
HP 2
230 V240 V
HP 3
460 V480 V
HP 5
575 V600 V
HP 5
Single-phase
115 V120 V
HP 0.5
230 V240 V
HP 1.5
General use A 15
Auxiliary contacts
Pilot Duty
07/31/2018 Eaton 051788 ED2018 V46.0 EN 4 / 12
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 0.5
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 5
max. Fuse A 45
Design verification as per IEC/EN 61439Technical data for design verification
Rated operational current for specified heat dissipation In A 9
Heat dissipation per pole, current-dependent Pvid W 0.4
Equipment heat dissipation, current-dependent Pvid W 1.2
Static heat dissipation, non-current-dependent Pvs W 1.8
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 50
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heatand fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton willprovide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must beobserved.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must beobserved.
10.13 Mechanical function The device meets the requirements, provided the information in the instructionleaflet (IL) is observed.
Technical data ETIM 6.0Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching ([email protected] [AAB718012])
Rated control supply voltage Us at AC 50HZ V 400 - 400
Rated control supply voltage Us at AC 60HZ V 440 - 440
Rated control supply voltage Us at DC V 0 - 0
07/31/2018 Eaton 051788 ED2018 V46.0 EN 5 / 12
Voltage type for actuating AC
Rated operation current Ie at AC-1, 400 V A 22
Rated operation current Ie at AC-3, 400 V A 9
Rated operation power at AC-3, 400 V kW 4
Rated operation current Ie at AC-4, 400 V A 6.6
Rated operation power Ie at AC-4, 400 V kW 3
Modular version No
Number of auxiliary contacts as normally open contact 1
Number of auxiliary contacts as normally closed contact 0
Type of electrical connection of main circuit Screw connection
Number of normally closed contacts as main contact 0
Number of main contacts as normally open contact 3
ApprovalsProduct Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No. E29096
UL Category Control No. NLDX
CSA File No. 012528
CSA Class No. 3211-04
North America Certification UL listed, CSA certified
Specially designed for North America No
07/31/2018 Eaton 051788 ED2018 V46.0 EN 6 / 12
Characteristics
1: Overload relay2: Suppressor3: Auxiliary contact modulesEnclosure totally insulated
07/31/2018 Eaton 051788 ED2018 V46.0 EN 7 / 12
Squirrel-cage motorOperating characteristicsStarting:from restStopping:after attaining full running speedElectrical characteristicsMake: up to 6 x rated motor currentBreak: up to 1 x rated motor currentUtilization category100 % AC-3Typical applicationsCompressorsLiftsMixersPumpsEscalatorsAgitatorsFansConveyor beltsCentrifugesHinged flapsBucket-elevatorsAir conditioning systemGeneral drives in manufacturing and processing machines
07/31/2018 Eaton 051788 ED2018 V46.0 EN 8 / 12
Extreme switching dutySquirrel-cage motorOperating characteristicsInching, plugging, reversingElectrical characteristicsMake: up to 6 x rated motor currentBreak: up to 6 x rated motor currentUtilization category100 % AC-4Typical applicationsPrinting pressesWire-drawing machinesCentrifugesSpecial drives for manufacturing and processing machines
07/31/2018 Eaton 051788 ED2018 V46.0 EN 9 / 12
Switching duty for non-motor loads, 3-pole, 4-poleOperating characteristicsNon-inductive or slightly inductive loadsElectrical characteristicsMake: 1 x rated currentBreak: 1 x rated currentUtilization category100 % AC-1Typical applicationsElectric heat
07/31/2018 Eaton 051788 ED2018 V46.0 EN 10 / 12
Short-time loading, 3-poleTime interval between two loading cycles: 15 minutes
Dimensions
07/31/2018 Eaton 051788 ED2018 V46.0 EN 11 / 12