(c) 2014, Georg Fischer Rohrleitungssysteme AG
Pressure Retaining Valve Type 586 Compact, Easy to adjust, Flexible
Benefits Easy Installation:
- Compact design enables installation even when space is limited
- Radially dismountable - Integrated assembling aid enables direct
assembly of the valves to mounting sets - Significantly shorter take-out length with
union connections Easy Operation:
- No re-torqueing needed anymore due to central housing nut
- Easily adjustable set pressure - Constant and low vibrating control behavior - Tightness resistant with temperature cycles - Low-maintenance - Pressure setting even during operation
Flexible: - Manometer optional for neutral and
aggressive media - Various connection options due to the true
union or spigot version. - Low pressure spring set available - Easy on spare parts due to modular design,
one part might fit more than one valve Market Segments • Water Treatment • Chemical Process Industry • Microelectronics • Solar industry
Function The pressure retaining valve maintains the line pressure to a set value on the valve inlet. The inlet pressure is in direct relation to the flow. Independent of pressure fluctuations the system pressure stays largely constant. Flow Media Neutral and aggressive media with low number of particles/ solids. Depending on selected valve material mind the chemical resistance. � Please refer to Georg Fischer Piping System Chemical Resistance List Media Temperature See pressure-/ temperature diagram Pressure Rating PN 10 @ +20°C (150 psi @ 68°F) Set-Range Standard: 0.5- 9.0 bar (7 – 130 psi) Optional: 0.3 – 3 bar (4 – 44 psi) Hysteresis Difference between opening and closing pressure: Approx. 0.1 – 0.4 bar (1.5 – 5.8 psi) Dimensions DN 10 - DN 50 (3/8” – 2”)
(c) 2014, Georg Fischer Rohrleitungssysteme AG
Wetted Parts (Body, Piston, Inner-housing) • PVC-U / CPVC (Polyvinylchlorid) • PP (Polypropylen) • PVDF (Polyvinylidenfluorid) Valve Housing PP-GF (orange) Diaphragm • EPDM/PTFE Seals • EPDM • FPM Connections • Body with cementing resp. welding spigots • Body true union type connection to match all standard GF unions and inserts (similar to diaphragm valve) Available on request: Various inserts from the GF range, e.g. transition to metal or PE. Mounting Threaded inserts available for safe mounting Flow Direction Always according to arrow on body Valve Function and Design The piston/diaphragm position of the valve is in balance between the inlet pressure P1 (primary side) and set spring force. If the inlet pressure rises above the set value, the diaphragm is lifted against the spring force. The valve opens until a balanced condition is reached again. If the inlet pressure drops below the set value, the diaphragm is pressed down by the spring force. The valve starts closing until a balanced condition is reached again. Hence the inlet pressure remains largely constant independent of increasing or decreasing system pressure (as long as the inlet pressure > set pressure).
Pressure-Temperature Diagram The following Pressure-Temperature Diagrams are based on a lifetime of 25 years with water or similar media.
P Permissible pressure in bar, psi
T Temperature in °C, °F
Flow Values KV100 @ delta p = 1 bar CV100 @ delta p= 1 psi
DN inch d KV100 CV100
[mm] [mm] [L/min] [L/h] [gpm]
10 3/8 16 50 3'020 3.5 15 1/2 20 53 3'150 3.6 20 3/4 25 114 6'840 7.9 25 1 32 125 7'500 8.6 32 1 1/4 40 263 15'760 18.1 40 1 1/2 50 286 17'140 19.7
50 2 63 293 17'610 20.2 Standards • Tightness according to ISO 9393 • Leak rate according to EN 12266
(c) 2014, Georg Fischer Rohrleitungssysteme AG
Sectional View Pressure Retaining Valve Type 586
No. Description
1 Protecting Cap
2 Lock-Nut
3 Spindle
4 Housing
5 Spring(s)
6 Spring Retainer
7 Retainer Ring
8 Diaphragm
9 Cartridge with Piston
10 Body
Dimensions Type 586 with Unions, Cementing resp. Welding Sockets
All
Mat
eria
ls d (mm) DN (mm) DN (inch) D H H1 H2
16 | 20 10 | 15 3/8 | ½ 79 132 111 21 25 | 32 20 | 25 ¾ | 1 100 177 148 29 40 | 50 32 | 40 1 ¼ | 1 ½ 147 251 207 44
63 50 2 147 251 207 44
All
Mat
eria
ls if
n
ot
ind
icat
ed d (mm) DN (mm) DN (inch) L*
PVC/ PP L* PVDF
L2 L3 L4 z PVC/ PP
z PVDF
16 | 20 10 | 15 3/8 | ½ 134 150 120 42 77 126 130 25 | 32 20 | 25 ¾ | 1 174 190 150 53 88 156 160 40 | 50 32 | 40 1 ¼ | 1 ½ 224 240 205 76 111 211 215 63 50 2 244 260 205 76 111 211 215
* L for Spigot Version only
1
2
4
3
5
6
7
8
9
10
(c) 2014, Georg Fischer Rohrleitungssysteme AG
Characteristic Curve Type 586 The curves below are valid for the set range 0.5- 9.0 bar (7 – 130 psi) and show the secondary or outlet pressure P2 over the flow Q in l/h. Parameter is the set pressure pE at Q = 0 l/h. There curves are valid for water at +20 °C for a flow velocity of 2 m/s. Special version set range 0.3 – 3 bar (4 – 44 psi) available on request.