Daylight and Sunlight Assessment for
Proposed Student Accommodation at
Dublin City University - Glasnevin Campus
09 Sep 2019
Version: V05
Prepared for:
Dublin City University
GLASNEVIN
DUBLIN 9
Prepared by:
Geraghty Energy Consultants Ltd.
THE DIGITAL HUB
10-13 THOMAS STREET
DUBLIN 8
T: 01 532 9363
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 1 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Document Control Sheet
Project Title: Proposed Student Residence at DCU Glasnevin Campus
Project Ref: 1804
Report title: Daylight and Overshadow Assessment
Date: 09 September 2019
Name Title Signature Date
Prepared Shubham Sotwal Energy Engineer SS 09/09/2019
Checked Shubham Sotwal Energy Engineer SS 09/09/2019
Approved Shane Geraghty Energy Engineer SG 09/09/2019
Issue Version Description Date Signed
1 - - 19/10/2018
2 V1 Building heights and amenity areas
revised
12/12/2018
3 V2 Daylight assessment included in report 04/01/2019
4 V3 Comments from design team incorporated 25/01/2019
5 V4 Updated courtyard layouts included 11/02/2019
6 V5 Draft 05/09/2019
7 V5 Final 09/09/2019
This report has been prepared with all reasonable skill, care and diligence. Information reported herein is based on the interpretation of the data collected and has been accepted in good faith as being accurate and valid. Please note that the assessment is based on the drawings and specifications provided. Should any changes be made to these documents or to the design for of the proposed scheme, the results and conclusions in this report may not be valid.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 2 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Summary
An assessment of daylight and overshadow was carried out for the proposed student residence
development at Dublin City University Glasnevin Campus in support of the SHD planning application. The
aim of the assessments is to demonstrate that the proposed scheme has been designed to provide
adequate levels of sunlight and daylight for the occupants.
The scope of the assessment was as follows:
• Daylight levels within the proposed scheme
• Impact on daylight within the existing nearby residences (College Park and Hampstead)
• Sunlight access within the new amenity areas of the proposed scheme
• Impact on sunlight access received by the existing Mall Area
The report outlines best practice guidelines for daylight and sunlight provision in new developments,
local and national planning guidelines, the assessment methods and analysis of the results.
The assessment has been carried out in accordance with the methods described in the approved
planning guidance documents: Building Research Establishment (BRE) 2011 ‘’Site Planning for Daylight
and Sunlight: A Guide to Good Practice”, and Code of Practice for Daylighting BS 8206-2: 2008.
A large sample of worst-case rooms within the proposed scheme was assessed for daylight using the ADF
method and all rooms either meet or greatly exceed the minimum recommended ADF levels. Because
the assessed rooms are the worst case, we can safely conclude that all other rooms are well above the
minimum standards.
Having carried out an extensive assessment of the impact on daylight within the existing residences
(College park and Hampstead), we consider that, on the assumption that the proposed modifications are
made, daylight levels will be adequate or more than adequate.
An assessment of the courtyards, which have been designed to maximise access to direct sunlight, shows
that these areas will receive adequate sunlight levels throughout the year. The assessment of the impact
on sunlight at the Mall Area shows that the area will continue to receive more than adequate levels of
sunlight throughout the year.
Overall, we are satisfied that daylight and sunlight provision were a prior concern of the design team and
that the occupants will enjoy a high standard of accommodation in this regard.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 3 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table of Contents
Document Control Sheet ................................................................................................................... 1
Summary ........................................................................................................................................... 2
Table of Contents .............................................................................................................................. 3
Table of Figures ................................................................................................................................. 5
Table of Tables .................................................................................................................................. 7
1 Introduction............................................................................................................................... 8
2 Brief Description of the Development Site ................................................................................. 9
Proposed Scheme Description .......................................................................................... 10
3 Planning Policy and Numerical Guidelines ................................................................................ 11
National Guidelines .......................................................................................................... 11
Local Planning Policy: Dublin Development Plan 2016-2022 ............................................. 12
BRE 209: Site Layout planning for daylight and Sunlight: A guide to Good practice (2011) 12
British Standard BS8206-2:2008 Lighting for Buildings – Part 2: Code of Practice for Daylighting 12
4 Calculation Procedure and Numerical Guidelines ..................................................................... 13
Daylight............................................................................................................................ 13
Distance Check ................................................................................................................. 13
Angular Assessment ......................................................................................................... 13
Vertical Sky Component ................................................................................................... 14
No Skyline ........................................................................................................................ 15
Average Daylight Factor ................................................................................................... 15
Assessment Methodology – Sunlight ................................................................................ 15
5 Site Layout and Typical Room Designs ...................................................................................... 17
Typical Room Designs ....................................................................................................... 19
Proposed Façades (Brick / Ceramic Rainscreen) ................................................................ 23
Window Arrangements for Proposed Block V4 ................................................................. 24
External Amenity Courtyards ............................................................................................ 26
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 4 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
6 Calculation Methods ................................................................................................................ 28
Analysis Software ............................................................................................................. 28
Impact on Daylight within Proposed Buildings .................................................................. 28
Impact on Daylight within the Existing Buildings (College Park and Hampstead Residences)30
6.3.1 New Window Installation in College Park .................................................................. 30
6.3.1 Window Modification in Hampstead Park ................................................................. 31
Sunlight and Annual Probable Sunlight Hours ................................................................... 32
7 Results ..................................................................................................................................... 33
Daylight within the Proposed Scheme .............................................................................. 33
Daylight within the Existing Scheme ................................................................................. 33
Sunlight Availability within Amenity Areas of Proposed Scheme ....................................... 33
7.3.1 Available Sun-hours in Courtyards ............................................................................ 33
Impact on Sunlight Levels in Existing Mall Area................................................................. 36
8 Conclusions ............................................................................................................................. 38
9 Appendix A: Results of Average Daylight Factor Analysis .......................................................... 39
Appendix A1: Average Daylight Factor for each space within the Proposed Scheme ......... 39
Appendix A2: Average Daylight Factor for each space within the Existing Scheme ............ 53
10 Appendix B: Architectural Drawing Schedule ........................................................................ 58
Appendix B1: Floor Layout Drawings with Room References within the Proposed Scheme59
Appendix B2: Floor Layout Drawings with Room References within the Existing Scheme .. 82
10.2.1 Appendix B2.1: Existing Block – Hampstead Court .................................................... 82
10.2.2 Appendix B2.2: Window Modification in Hampstead Court ....................................... 85
10.2.3 Appendix B2.3: Existing Block – College Park............................................................. 86
10.2.4 Appendix B2.4: New Window Installation in College Park ......................................... 91
11 Appendix C: 3-D Representation of the Digital Model ........................................................... 92
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 5 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table of Figures
Figure 2-1 Aerial view of the Proposed site for development ............................................................. 9
Figure 2-2 CGI Image of the Site (Proposed and Existing scheme) .................................................... 10
Figure 4-1 Angular assessment - 25 DEG rule ................................................................................... 13
Figure 5-1 Proposed site plan with Block and Courtyard references ................................................. 17
Figure 5-2 Proposed Site Layout with Mall area to the north-east .................................................... 18
Figure 5-3 3-D View of typical Kitchen/Living/Dining Room .............................................................. 19
Figure 5-4 Typical layout for Kitchen/Living/Dining Room with internal dimensions ......................... 19
Figure 5-5 Typical layout for an accessible bedroom with internal dimensions ................................. 20
Figure 5-6 Longitudinal section through Standard Bedroom ............................................................ 21
Figure 5-7 Furniture layout for Standard Bedroom........................................................................... 21
Figure 5-8 Typical layout for a Standard Bedroom with internal dimensions .................................... 22
Figure 5-9 Proposed Façades ........................................................................................................... 23
Figure 5-10 Block V4 - Southeast Elevation ...................................................................................... 24
Figure 5-11 Block V4 - Southeast Elevation (Window Arrangement Highlighted) .............................. 24
Figure 5-12 Preview of the Window Arrangement for Block V4 - Southeast Elevation ...................... 25
Figure 5-13 Courtyard No. 1............................................................................................................. 26
Figure 5-14 Courtyard No. 2 and 3 ................................................................................................... 27
Figure 5-15 Courtyard No. 4............................................................................................................. 27
Figure 7-1 Sun exposure scale.......................................................................................................... 36
Figure 7-2 Sun Exposure levels at The Mall (1m*1m grid) ................................................................ 36
Figure 7-3 Close-up of Sun Exposure levels at The Mall (1m*1m grid) .............................................. 37
Figure 7-4 Close-up of Sun Exposure levels at the southeast end of The Mall (1m*1m grid) ............. 37
Figure 10-1 Floor Layout of Block V3 – Ground Floor ....................................................................... 59
Figure 10-2 Floor Layout of Block V3 – Upper Ground Floor ............................................................. 60
Figure 10-3 Floor Layout of Block V3 – Second Floor ........................................................................ 61
Figure 10-4 Floor Layout of Block V4 – Ground Floor ....................................................................... 62
Figure 10-5 Floor Layout of Block V4 – Upper Ground Floor ............................................................. 63
Figure 10-6 Floor Layout of Block V4 – Second Floor ........................................................................ 64
Figure 10-7 Floor Layout of Block V5 – Ground Floor ....................................................................... 65
Figure 10-8 Floor Layout of Block V5 – Upper Ground Floor ............................................................. 66
Figure 10-9 Floor Layout of Block V5 – Third Floor ........................................................................... 67
Figure 10-10 Floor Layout of Block V1 – Ground Floor ..................................................................... 68
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 6 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-11 Floor Layout of Block V1 – Upper Ground Floor ........................................................... 69
Figure 10-12 Floor Layout of Block V1 – First Floor........................................................................... 70
Figure 10-13 Floor Layout of Block V1 – Fourth Floor ....................................................................... 71
Figure 10-14 Floor Layout of Block V6 – Upper Ground Floor ........................................................... 72
Figure 10-15 Floor Layout of Block V6 – Second Floor ...................................................................... 73
Figure 10-16 Floor Layout of Block V7 – Upper Ground Floor ........................................................... 74
Figure 10-17 Floor Layout of Block V7 – First Floor........................................................................... 75
Figure 10-18 Floor Layout of Block V7 – Second Floor ...................................................................... 76
Figure 10-19 Floor Layout of Block V7 – Fourth Floor ....................................................................... 77
Figure 10-20 Floor Layout of Block V8 - Upper Ground Floor ............................................................ 78
Figure 10-21 Floor Layout of Block V8 – First Floor........................................................................... 79
Figure 10-22 Floor Layout of Block V8 – Second Floor ...................................................................... 80
Figure 10-23 Floor Layout of Block V8 – Fourth Floor ....................................................................... 81
Figure 10-24 Floor Layout of Hampstead Court - Ground floor ......................................................... 82
Figure 10-25 Floor Layout of Hampstead Court - First floor .............................................................. 83
Figure 10-26 Floor Layout of Hampstead Court - Second floor ......................................................... 84
Figure 10-27 Window Modification Highlighted in Hampstead Court (East Elevation) ...................... 85
Figure 10-28 Floor Layout of College Park - Ground floor ................................................................. 86
Figure 10-29 Floor Layout of College Park - First floor ...................................................................... 87
Figure 10-30 Floor Layout of College Park - Second floor ................................................................. 88
Figure 10-31 Floor Layout of College Park - Third floor ..................................................................... 89
Figure 10-32 Floor Layout of College Park - Fourth floor .................................................................. 90
Figure 10-33 New Window Installation Highlighted in College Park .................................................. 91
Figure 11-1 Plan view of Existing Buildings and Proposed Scheme ................................................... 92
Figure 11-2 South aerial view of Existing Buildings (Test Rooms highlighted)................................... 93
Figure 11-3 East aerial view of Existing Buildings (Test Rooms highlighted) ...................................... 93
Figure 11-4 South aerial view of Existing Buildings and Proposed Scheme........................................ 94
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 7 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table of Tables
Table 6-1 Summary of the assessed rooms in Proposed Scheme ...................................................... 28
Table 6-2 Input Parameter for Proposed Scheme ............................................................................. 29
Table 6-3 Summary Table of the ADF levels for Proposed Scheme ................................................... 30
Table 6-4 Input Parameter for Existing Scheme................................................................................ 31
Table 6-5 Summary Table of the ADF levels for Existing Scheme ...................................................... 32
Table 9-1 Average Daylight Factor for Proposed Block V3 ................................................................ 39
Table 9-2 Average Daylight Factor for Proposed Block V4 ................................................................ 40
Table 9-3 Average Daylight Factor for Proposed Block V5 ................................................................ 42
Table 9-4 Average Daylight Factor for Proposed Block V1 ................................................................ 45
Table 9-5 Average Daylight Factor for Proposed Block V8 ................................................................ 48
Table 9-6 Average Daylight Factor for Proposed Block V7 ................................................................ 50
Table 9-7 Average Daylight Factor for Proposed Block V6 ................................................................ 52
Table 9-8 Average Daylight Factor for Existing Block - Hampstead Court .......................................... 53
Table 9-9 Average Daylight Factor for Existing Block - College Park .................................................. 56
Table 10-1 Architectural Drawing Schedule...................................................................................... 58
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 8 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
1 Introduction
Geraghty Energy Consultants have been appointed by the Coady Architects to prepare a daylight and
sunlight assessment in support of the planning application.
This report provides an assessment of the significant effects of the proposed development on the
environment with respect to daylight, sunlight and overshadowing.
The proposed development comprises the development of student accommodation at Dublin City
University Glasnevin Campus.
The report is structured as follows:
• Overview of the Proposed Scheme
• Policy Guidelines
• Assessment Methodology
• Daylight within the Proposed Scheme and Impact on Existing Residences
• Sunlight to Open Areas within the Proposed Scheme and Impact on Existing Open Areas
The report is supplemented with the following appendices:
• Appendix A: Results of Average Daylight Factor Analysis
• Appendix A1: Average Daylight Factor for each space within the Proposed Scheme
• Appendix A2: Average Daylight Factor for each space within the Existing Scheme
• Appendix B: Architectural Drawing Schedule
• Appendix B1: Floor Layout Drawings with Room References within the Proposed Scheme
• Appendix B2: Floor Layout Drawings with Room References within the Existing Scheme
• Appendix B2.1: Existing Block – Hampstead Court
• Appendix B2.2: Window Modification in Hampstead Court
• Appendix B2.3: Existing Block – College Park
• Appendix B2.4: New Window Installation in College Park
• Appendix C: 3-D Representation of the Digital Model
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 9 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
2 Brief Description of the Development Site
The proposed Student Residence development is located at DCU’s Glasnevin Campus. Figure 1 below
shows an aerial view of the existing site which consists of soccer pitches (A), Surface car parking (B), and
existing student residences (C).
Figure 2-1 Aerial view of the Proposed site for development
The two existing student residences to the south-west of area C are between four and five storeys high.
It is intended to demolish the student building in the centre of area C which was constructed c. 1970, in
order to make way for a more energy efficient and sustainable student residence.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 10 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Proposed Scheme Description
The development is being led by Coady Architects in collaboration with Feilden Clegg Bradley Studios.
The proposed development will consist of 1240 bedrooms. The buildings will range in height from
predominantly 5 storeys, to 6,7 and 10 storeys. The scheme accommodates a basement car park and
under croft podium in order to best utilise external space for active uses. Figure 2-2 below shows an
aerial view from due south of the proposed scheme.
Figure 2-2 CGI Image of the Site (Proposed and Existing scheme)
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 11 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
3 Planning Policy and Numerical Guidelines
The BRE209 Guidelines Site Planning for Daylight and Sunlight – A Guide to Good Practice, 2nd Edition
2011, by P. J. Littlefair, together with BS8206-2 Code of Practice for Daylighting, have been used as
reference standards. While these are non-statutory guidelines, they are referenced in national and local
policy in Ireland as standards to consider for the provision of daylight and sunlight in new developments.
National Guidelines
The recently adopted, Section 28 Guidelines, Urban Building Height Guidelines (December 2018)
published by the Department of Housing, Planning and Local Government identify that as reflected in
‘the National Planning Framework …. that there is significant scope to accommodate anticipated
population growth and development needs, whether for housing, employment or other purposes, by
building up and consolidating the development of our existing urban areas’ and that ‘securing compact
and sustainable urban growth means focusing on reusing previously developed ‘brownfield’ land,
building up infill sites (which may not have been built on before) and either reusing or redeveloping
existing sites and buildings, in well serviced urban locations, particularly those served by good public
transport and supporting services, including employment opportunities’.
The Guidelines reference NPO 13 (from the NPF) which states that ‘in urban areas, planning and
related standards, including in particular building height and car parking will be based on performance
criteria that seek to achieve well-designed high-quality outcomes in order to achieve targeted growth.
These standards will be subject to a range of tolerance that enables alternative solutions to be
proposed to achieve stated outcomes, provided public safety is not compromised and the environment
is suitably protected’. One of the key performance indicators identified in these statutory guidelines
relates to daylight and sunlight standards. Section 3.0 of the Urban Building Height Guidelines provide
guidance for Planning Authorities /An Bord Pleanala in considering development proposals for
buildings taller than prevailing building heights in pursuit of the Guidelines. In respect of the
site/buildings scale the guidelines require consideration of:
• The form, massing and height of proposed developments should be carefully modulated so as to
maximise access to natural daylight, ventilation and views and minimise overshadowing and loss of
light.
• Appropriate and reasonable regard should be taken of quantitative performance approaches to
daylight provision outlined in guides like the Building Research Establishment’s ‘Site Layout Planning
for Daylight and Sunlight (2nd Edition or BS 8206-2:2008 – ‘Lighting for Buildings- Part Local Planning
Policy and Guidelines
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 12 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Local Planning Policy: Dublin Development Plan 2016-2022
The “Dublin City Development Plan 2016-2022” Chapter 16 “Development Standards: Design, Layout,
Mix of Uses and Sustainable Design” addresses the local planning policy and guidelines for the area.
This document states “Development shall be guided by the principles of Site Layout Planning for Daylight
and Sunlight, A guide to good practice (Building Research Establishment Report, 2011).”
As such, the 2011 (Second Edition) of this document has been considered in this report, Building research
Establishment “Site Layout Planning for Daylight and Sunlight: A Guide to Good Practice” by PJ Littlefair,
2011 Second Edition.
BRE 209: Site Layout planning for daylight and Sunlight: A guide to Good practice (2011)
The second edition of BRE 209, published in 2011 contains guidance on how to design developments,
whilst minimising the impacts on existing buildings from overshadowing and reduced levels of daylight
and sunlight. In addition, The BRE report provides advice on how to design buildings to ensure that good
practice levels of daylight and sunlight are provided.
As well as advice, the report contains a methodology to assess levels of daylight, sunlight and
overshadowing, and specifies criteria to determine the potential impacts of a new development on
surrounding buildings, and also to determine whether new developments are well lit internally.
However, the report does state that the good practice guidelines are not mandatory but should be
considered as a guide to help rather than constrain the designer.
British Standard BS8206-2:2008 Lighting for Buildings – Part 2: Code of Practice for Daylighting
Recommendations for daylight standards in dwellings are based on the British Standard BS8206-2:2008
Code of Practice for Lighting in Buildings.
It is important to note that the standard advises that the degree of satisfaction with visual comfort for
the occupants is related to the expectation of sunlight. If a dwelling is located in a group, the absence of
sunlight is more acceptable than where its exclusion seems arbitrary.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 13 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
4 Calculation Procedure and Numerical Guidelines
The daylight and sunlight assessment, presented in this report, has been carried out in accordance with
the methodology outlined in the Building Research Establishment (BRE) Guide ‘’Site Layout Planning for
Sunlight and Daylight: A Guide to Good Practice, and the British Standard BS8206-2:2008 Lighting for
Buildings – Part 2: Code of Practice for Daylighting.
Daylight
The quality and quantity of daylighting in an interior space depends on two main factors: the external
environment and internal room layout. External factors include obstructions from nearby buildings or
structures whereas internal layouts and window size affect daylight distribution with a room. Section 2.1
of the BRE guide describe a number of methods for calculating daylight levels within buildings and that
only habitable rooms should be assessed against the criteria.
Distance Check
The BRE Guide states that existing windows do not need to be assessed if the distance of each part of
the new development from the existing window is three or more times its height above the centre of the
existing window. If the proposed development is closer than this, an angular assessment should be
carried out to establish the obstruction angle.
Angular Assessment
Initial screening tests whether a plane perpendicular to a window intersects an obstruction at an angle(θ)
of more than 25° above horizontal at the centre of the window. If this is the case, a more detailed check
is needed to evaluate the VSC received by the window. In the case of existing building’s, a check can be
made on the change in VSC between an existing condition and with a proposed development in place.
The figure below illustrates this principle.
Figure 4-1 Angular assessment - 25 DEG rule
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 14 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Vertical Sky Component
If an obstruction angle of more than 25° exists at the centre of a window, further assessment to
determine the VSC at the centre of the window can be undertaken. The VSC is a measure of the amount
of the sky that is visible from the centre of an obstructed window relative to an unobstructed sky
hemisphere and provides a measure of the potential for daylight where room layouts and window sizes
are not known.
The excerpt from BRE below summarises the methodology for assessing access to daylight for existing
buildings.
‘If any part of a new building or extension, measured in a vertical section perpendicular to a main window
wall of an existing building, from the centre of the lowest window, subtends an angle of more than 25°
to the horizontal, then the diffuse daylight of the existing building may be adversely affected.
This will be the case if either:
• The VSC measured at the centre of an existing window is less than 27 degrees, and less than 0.8
times its former value.
• The area of the working plane in a room which can receive direct skylight is reduced to less than 0.8
times its former value.
The excerpt from BRE below summarises the methodology for assessing access to light from the sky for
new buildings.
‘Obstructions can limit access to light from the sky. This can be checked by measuring or calculating the
angle (θ) of visible sky, angle of obstruction or vertical sky component (VSC) at the centre of the lowest
window where daylight is required.
If VSC is:
• At least 27% (Θ is greater than 65°, obstruction angle less than 25°) conventional window design will
usually give reasonable results
• Between 15% and 27% (Θ is between 45° and 65°, obstruction angle between 25° and 45°) special
measures (larger windows, changes to room layout) are usually needed to provide adequate daylight
• Between 5% and 15% (Θ is between 25° and 45°, obstruction angle between 45° and 65°) it is very
difficult to provide adequate daylight unless very large windows are used
• Less than 5% (Θ less than 25°, obstruction angle more than 65°) it is often impossible to achieve
reasonable daylight, even if the whole window wall is glazed’
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 15 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
No Skyline
Where room layouts and window arrangements are known, the No Skyline can be plotted on the working
plane of a room, which will illustrate the dividing line between parts of the room that do and do not have
a view of the sky. The No Skyline is used to assess the impact of a new development on an existing
building by evaluating the area having a view of the sky with and without the new development in place.
If a new development causes the No Skyline to move so the area of a room having a view of the sky is
reduced to less than 0.8 times its former value, the impact of the new development will be noticeable to
occupants.
Average Daylight Factor
The most accurate measure of daylight provision in new and existing rooms is the ADF which is a measure
of the amount of daylight entering a room, taking into account the room layout, surface reflectance,
window size and glass light transmittance. British Standard Code of practice for daylighting, BS 8206-2
sets recommended values of ADF for different room types as follows:
• Non-domestic rooms including offices: 2.0 %
• Bedrooms: 1.0 %
• Living rooms: 1.5 %
• Kitchens: 2.0 %
Although BS 8206-2 recommend that ADF levels in common rooms should meet the standard set for
kitchens of 2%, we have set the threshold to minimum level set for living rooms at 1.5%. This is because
the kitchen area will only occupy about 25% of the total floor area whereas the area for dining and
seating will be approximately 75%.
Assessment Methodology – Sunlight
The BRE Guideline sets out the following methodology for assessing access to direct sunlight for existing
buildings.
‘If a living room of an existing dwelling has a main window facing within 90° of due south, and any part
of a new development subtends an angle of more than 25° to the horizontal measured from the centre
of the window in a vertical section perpendicular to the window in a vertical section perpendicular to
the window, then the sun-lighting of the existing window may be adversely affected.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 16 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
This will be the case if the centre of the window:
• Receives less than 25% of annual probable sunlight hours, or less than 5% of annual probable sunlight
hours between 21 September and 21 March and;
• Receives less than 0.8 times its former sunlight hours during either period and;
• Has a reduction in sunlight received over the whole year greater than 4% of annual probable sunlight
hours.
The BRE Guideline provides the methodology outlined below for assessing access to direct sunlight for
gardens and open spaces.
‘It is recommended that for it to appear adequately sunlit throughout the year, at least half of a garden
or amenity area should receive at least two hours of sunlight on 21 March. If as a result of a new
development an existing garden or amenity area does not meet the above, and the area which can
receive two hours of sun on 21 March is less than 0.8 times its former value, then the loss of sunlight is
likely to be noticeable. If a detailed calculation cannot be carried out, it is recommended that the centre
of the area should receive at least two hours of sunlight on 21 March.’
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 17 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
5 Site Layout and Typical Room Designs
The proposed layout for each block and associated courtyard is shown in the site layout plan below.
Figure 5-1 Proposed site plan with Block and Courtyard references
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 18 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 5-2 Proposed Site Layout with Mall area to the north-east
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 19 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Typical Room Designs
The scheme is designed to accommodate approximately 1240 bedrooms. Typical layouts with
dimensions are shown below for kitchen-living-dining rooms, standard bedrooms and accessible
bedrooms.
Figure 5-3 3-D View of typical Kitchen/Living/Dining Room
Figure 5-4 Typical layout for Kitchen/Living/Dining Room with internal dimensions
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 20 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 5-5 Typical layout for an accessible bedroom with internal dimensions
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 21 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 5-6 Longitudinal section through Standard Bedroom
Figure 5-7 Furniture layout for Standard Bedroom
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 22 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 5-8 Typical layout for a Standard Bedroom with internal dimensions
Window Arrangements for Proposed Block V4
Figure 5-10 Block V4 - Southeast Elevation
Figure 5-11 Block V4 - Southeast Elevation (Window Arrangement Highlighted)
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 25 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 5-12 Preview of the Window Arrangement for Block V4 - Southeast Elevation
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 26 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
External Amenity Courtyards
The scheme is designed to contain seven blocks which sit around central accessible courtyards. The
courtyards while primarily for use by the students in the adjacent accommodation also provides for
access by wider student body and as a means of accessing through the blocks to other areas of the
campus. The scheme contains four designated courtyards which are shown below.
In each courtyard, the useable amenity space was coordinated with other features including louvred
openings for natural ventilation of the under-croft car parks and SUDS measures in the form of rainwater
garden areas. Additionally, the public routes to the east of the three upper courtyards have been
excluded from the assessment as they are not designated open spaces.
The courtyard layouts as shown below, indicate the areas which have been assessed for available sunlight
hours. The proposed layout for each courtyard is presented in the following diagrams.
Figure 5-13 Courtyard No. 1
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 27 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 5-14 Courtyard No. 2 and 3
Figure 5-15 Courtyard No. 4
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 28 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
6 Calculation Methods
Analysis Software
The daylight and sunlight analysis have been carried out using the following software programs:
• IES VE 2018 Model-It for development of the three-dimensional geometrical model
• IESVE 2018 SunCast for analysis of Probable Sunlight Hours at Restaurant Roof Window
• IESVE 2018 Radiance and FlucsDL for calculation of Daylight Factors within the proposed scheme
A digital model was created to represent the physical layout of the site, individual buildings, room layouts
including window arrangements and window reveals. The models were developed in accordance with
the drawings provided by the architectural team.
Impact on Daylight within Proposed Buildings
An assessment of daylight using the average daylight factor method has been carried out for 450
bedrooms and 96 common rooms within the proposed development. Reference rooms in the
assessment which were likely to fall below the required ADF were selected based on the orientation of
the building and overshadow of adjacent building.
Our initial ADF calculations on a number of worst-case units showed that a small number of spaces fell
below the guidelines. We worked closely with the designers in devising alternative designs that would
improve daylight levels. The changes to the design included modifications to the size of the windows,
setting out of the windows, depth of window reveals at various levels and interior finishes for maximising
reflections.
A comprehensive ADF assessment was then carried out for the whole scheme in order to ensure the
proposed design changes would provide the required levels of daylight thereby maximising visual
comfort. A summary of the assessed rooms is shown below:
Table 6-1 Summary of the assessed rooms in Proposed Scheme
Block Bedrooms Kitchen-Living-Dining Total no. of
rooms
V3 44 7 51
V4 63 6 69
V5 88 17 105
V1 117 26 143
V8 76 23 99
V7 63 17 80
Total 451 96 547
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 29 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
The input parameters to the ADF calculations including surface reflectances are outlined in the following
table.
Table 6-2 Input Parameter for Proposed Scheme
Element Value Source
Location and Climate File Dublin Airport -
Sky conditions Standard CIE Overcast sky Commission Internationale de L’Eclaraige
Surface reflectance: CIBSE Society of Light and Lighting
Ceiling 80% CIBSE Guide A Table 1.12
Internal Walls 70% CIBSE Guide A Table 1.12
Floors 35% CIBSE Guide A Table 1.12
External walls 15%
External ground 10%
Working plane height 0.70 metres BS8206 Part 2:2008
Area of interest defined (perimeter border depth) 0.5 metres CIBSE Code for interior lighting
Window specifications:
Light transmission 75% Typical triple-glazed specification
Outdoor reflectance 11% Typical triple-glazed specification
Indoor reflectance 7% Typical triple-glazed specification
Average frame thickness 50mm Typical for wood-framed casement windows
Room surface maintenance factor 0.90 CIBSE Society of Light and Lighting
The analysis shows that ADF levels for all assessed rooms are in line with the minimum recommended ADF
levels. All assessed bedrooms meet or exceed an ADF threshold of 1%, and all KLD spaces meet or greatly
exceed 1.5%. A summary of the ADF levels are presented in the following table.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 30 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 6-3 Summary Table of the ADF levels for Proposed Scheme
Overall pass rate as a function of the number of rooms (KLDs + Bedrooms)
Block Bedroom Kitchen-Living-Dining
Total no. of rooms
ADF result % of rooms achieving ADF target
Above Below
V3 44 7 51 51 0 100
V4 63 6 69 69 0 100
V5 88 17 105 105 0 100
V1 117 26 143 143 0 100
V8 76 23 99 99 0 100
V7 63 17 80 80 0 100
V6 26 10 36 36 0 100
The ADF levels for each assessed room are detailed in section 9.1 Appendix A1.
Impact on Daylight within the Existing Buildings (College Park and Hampstead Residences)
Even though BRE advocate the VSC method to assess the impact on daylight within existing buildings, we
have adopted the same approach adopted for the new scheme using the ADF method. This is because
the VSC method does not consider window size, glass transmissivity, room size and internal surface
reflectance’s, whereas the ADF method does.
An additional point is that the existing buildings (Hampstead and College Park) near the proposed
development are part of the DCU Campus which means that we had full access to all the rooms which
may be affected in terms of daylight access.
Naturally, there will be an impact on daylight levels within the existing buildings because, at the moment,
the proposed development site comprises a carpark and playing fields.
Our initial calculations showed that several units would fall well below the recommended daylight levels
which would be below the required levels. A number of modifications are therefore recommended, and
proposed as part of this application, to address this. These were as follows:
6.3.1 New Window Installation in College Park
Because the room depth and moderately small windows in the KLD rooms in College Park, the daylight
levels at the lower floors are only just adequate. The proposed scheme would cause these levels to drop
below the recommended standards. The room layout will facilitate the relatively easy installation of a
new window in the sidewall of the KLD room thus creating a dual aspect space with significantly higher
daylight levels.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 31 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
This measure is proposed for 10 no. KLD rooms in College Park, as specified in the table of ADF results
for contained in section 9.2 Appendix A2. The proposed window arrangement is detailed in the architects
drawing in section 10.2.4 Appendix B2.4.
6.3.1 Window Modification in Hampstead Park
In the case of a single KLD room in the Hampstead Residence, it is necessary to modify the existing
windows of that room. It has been agreed to drop the windowsill from the current height of
approximately 1200 mm above finished floor level to 150mm above finished floor level. This will mean
that the room will achieve the recommended ADF level. The proposed window modification is detailed
in the architects drawing in section 10.2.2 Appendix B2.2.
Table 6-4 Input Parameter for Existing Scheme
Element Standard Source
Software program - IESVE Radiance Version 2018
Sky conditions CIE Overcast Sky CIE
Surface Reflectance:
Ceiling 82% BS 00E55 White
Internal Walls 71% BS 08B15 Off White
Floors 61% As per floor specification provided by Coady
(Marmoleum Concrete S 1510-G90Y)
External Ground 40% As per design specification
External Walls 40% As per design specification
External Roof 25% As per design specification
Window specifications:
Visible light transmission 80% Standard double pane
Outdoor reflectance 13% Standard double pane
Indoor reflectance 13% Standard double pane
Working plane height 0.70m -
Area of interest (perimeter border depth) 0.5m CIBSE Code for Interior Lighting
Maintenance Factor 0.96 BS 8206-2: 2008
Obstructions due to curtains and furniture Excluded -
Grid size for assessment area 0.5m -
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 32 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
The above works which have been included in this planning application to An Bord Pleanala will mean that
all the rooms which will be affected by the proposed scheme will either meet or significantly exceed the
minimum recommended ADF levels in BS8206-2. A summary of the ADF levels are presented in the following
table.
Table 6-5 Summary Table of the ADF levels for Existing Scheme
Overall pass rate as a function of the number of rooms (KLDs + Bedrooms)
Block Total no. of rooms ADF result
% of rooms achieving ADF target Above Below
Hampstead Residence 102 102 0 100.00
College Park 90 90 0 100.00
The ADF levels for each assessed room are detailed in section 9.2 Appendix A2.
Sunlight and Annual Probable Sunlight Hours
A computer simulation program was used to analyse sunlight within this development. IESVE Model-it
v2018 and IESVE SunCast v2018 were used to calculate annual probable sunlight hours in the amenity
areas.
A digital model was created to represent the physical layout of the site including the buildings, landscape,
and parapet walls. The model was based on the drawings provided by the architects, FCBS.
Our initial sunlight calculations showed that a small number of amenity areas fell below the guidelines.
We worked closely with the architects in devising alternative layouts that would improve available
sunlight in these areas. The changes to the design included modifications to the site layout, building
heights and areas designated as amenity space. These modifications consequently led to the
achievement of the required ADF for the failing amenity areas.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 33 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
7 Results
Daylight within the Proposed Scheme
The analysis shows that ADF levels for all assessed rooms are in line with the minimum recommended
ADF levels. All assessed bedrooms meet or exceed an ADF threshold of 1%, and all KLD spaces meet or
greatly exceed 1.5%.
Daylight within the Existing Scheme
The analysis shows that ADF levels for all assessed rooms are in line with the agreed planning guidelines.
All assessed bedrooms meet or exceed an ADF threshold of 1%, and all KLD spaces meet or exceed 1.5%.
Sunlight Availability within Amenity Areas of Proposed Scheme
The sunlight assessment for each courtyard shows that more than 50% of the area designated for
amenity purposes will receive at least 2 hours of sunshine on the 21 March.
The expected sunlight levels for each courtyard is illustrated in the following sun-hour diagrams.
7.3.1 Available Sun-hours in Courtyards
Sun-hours Exposure scale and key plan
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 34 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Courtyard 2 Area = 470.49 m2
Percentage ground where sun hours meet or exceed 2 hours = 58.87%
Courtyard 1 Area = 1469 m2
Percentage area of amenity space where sun hours meet or exceed 2 hours = 66.84%
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 35 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Courtyard 3 Area = 469.62 m2
Percentage ground where sun hours meet or exceed 2 hours = 57.49%
Courtyard 4 Area = 469.62 m2
Percentage ground where sun hours meet or exceed 2 hours = 51.11%
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 36 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Impact on Sunlight Levels in Existing Mall Area
The sunlight analysis for the Mall area located to the north of the proposed scheme shows that
overshadowing will occur but overall, the open area will significantly exceed recommended guidelines.
The calculated sunlight levels for the Mall Area with the proposed scheme are illustrated in the following
diagrams.
The solar exposure scale should be read in conjunction with the sun hour charts on the following page.
Figure 7-1 Sun exposure scale
Figure 7-2 Sun Exposure levels at The Mall (1m*1m grid)
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 37 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 7-3 Close-up of Sun Exposure levels at The Mall (1m*1m grid)
Figure 7-4 Close-up of Sun Exposure levels at the southeast end of The Mall (1m*1m grid)
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 38 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
8 Conclusions
An assessment of daylight and sunlight was carried out for the proposed student residence development
at Dublin City University Glasnevin Campus in support of the SHD planning application. The scope of the
assessment was as follows:
• Daylight levels within the proposed scheme
• Impact on daylight within the existing nearby residences (College Park and Hampstead)
• Sunlight access within the new amenity areas of the proposed scheme
• Impact on sunlight access received by the existing Mall Area
A large sample of worst-case rooms within the proposed scheme was assessed for daylight using the ADF
method and all rooms either meet or greatly exceed the minimum recommended ADF levels. Because
the assessed rooms are worst case, we can safely conclude that all other rooms are well above the
minimum standards.
Having carried out an extensive assessment of the impact on daylight within the existing residences
(College park and Hampstead), we consider that, on the assumption that the proposed modifications are
made, daylight levels will be adequate or more than adequate.
An assessment of the courtyards, which have been designed to maximise access to direct sunlight, shows
that these areas will receive adequate sunlight levels throughout the year. The assessment of the impact
on sunlight at the Mall Area shows that the area will continue to receive more than adequate levels of
sunlight throughout the year.
Overall, we are satisfied that daylight and sunlight provision were a prior concern of the design team and
that the occupants will enjoy a high standard of accommodation in this regard.
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 39 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
9 Appendix A: Results of Average Daylight Factor Analysis
Appendix A1: Average Daylight Factor for each space within the Proposed Scheme
Table 9-1 Average Daylight Factor for Proposed Block V3
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V3 Ground Bedroom Room 0002 3.6 1 Pass
V3 Ground Bedroom Room 0003 3.2 1 Pass
V3 Ground Bedroom Room 0005 3.4 1 Pass
V3 Ground Living/Dining/Kitchen Room 0001 2.2 1.5 Pass
V3 Ground Bedroom Room 0004 3.1 1 Pass
V3 Ground Bedroom Room 0006 3.3 1 Pass
V3 Ground Bedroom Room 0009 2.3 1 Pass
V3 Ground Bedroom Room 0012 3.6 1 Pass
V3 Ground Bedroom Room 0010 3.1 1 Pass
V3 Ground Bedroom Room 0007 2.1 1 Pass
V3 Ground Bedroom Room 0014 2.1 1 Pass
V3 Upper Ground Bedroom Room 0016 2.6 1 Pass
V3 Upper Ground Bedroom Room 0017 2.3 1 Pass
V3 Upper Ground Bedroom Room 0018 2.5 1 Pass
V3 Upper Ground Living/Dining/Kitchen Room 0015 1.5 1.5 Pass
V3 Upper Ground Bedroom Room 0019 2.2 1 Pass
V3 Upper Ground Bedroom Room 0021 2.3 1 Pass
V3 Upper Ground Bedroom Room 0030 1.6 1 Pass
V3 Upper Ground Bedroom Room 0033 2.5 1 Pass
V3 Upper Ground Bedroom Room 0031 2.3 1 Pass
V3 Upper Ground Bedroom Room 0020 1.5 1 Pass
V3 Upper Ground Bedroom Room 0035 1.5 1 Pass
V3 Upper Ground Living Room Room 0029 1.5 1.5 Pass
V3 Upper Ground Bedroom Room 0034 2.4 1 Pass
V3 Upper Ground Bedroom Room 0032 2.4 1 Pass
V3 Upper Ground Bedroom Room 0023 2.1 1 Pass
V3 Upper Ground Bedroom Room 0025 2.1 1 Pass
V3 Upper Ground Bedroom Room 0026 2.4 1 Pass
V3 Upper Ground Bedroom Room 0028 2.3 1 Pass
V3 Upper Ground Living/Dining/Kitchen Room 0027 1.5 1.5 Pass
V3 Upper Ground Bedroom Room 0024 2 1 Pass
V3 Level 2 Bedroom Room 0073 1.9 1 Pass
V3 Level 2 Bedroom Room 0075 2.1 1 Pass
V3 Level 2 Living/Dining/Kitchen Room 0071 1.5 1.5 Pass
V3 Level 2 Bedroom Room 0074 1.7 1 Pass
V3 Level 2 Bedroom Room 0076 1.9 1 Pass
V3 Level 2 Bedroom Room 0086 1.6 1 Pass
V3 Level 2 Bedroom Room 0089 2.1 1 Pass
V3 Level 2 Bedroom Room 0087 1.9 1 Pass
V3 Level 2 Bedroom Room 0077 1.5 1 Pass
V3 Level 2 Bedroom Room 0091 1.4 1 Pass
V3 Level 2 Living/Dining/Kitchen Room 0085 1.5 1.5 Pass
V3 Level 2 Bedroom Room 0090 1.9 1 Pass
V3 Level 2 Bedroom Room 0088 2 1 Pass
V3 Level 2 Bedroom Room 0079 1.6 1 Pass
V3 Level 2 Bedroom Room 0081 1.6 1 Pass
V3 Level 2 Bedroom Room 0082 2 1 Pass
V3 Level 2 Bedroom Room 0084 1.8 1 Pass
V3 Level 2 Living/Dining/Kitchen Room 0085 1.5 1.5 Pass
V3 Level 2 Bedroom Room 0080 1.6 1 Pass
V3 Level 2 Bedroom Room 0072 2.1 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 40 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 9-2 Average Daylight Factor for Proposed Block V4
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 41 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
V4 Level 2 Living/Dining/Kitchen Room 0240 2.1 1.5 Pass
V4 Level 2 Living/Dining/Kitchen Room 0243 2 1.5 Pass
V4 Level 2 Living/Dining/Kitchen Room 0229 1.9 1.5 Pass
V4 Level 2 Bedroom Room 0232 1.7 1 Pass
V4 Level 2 Bedroom Room 0234 1.8 1 Pass
V4 Level 2 Bedroom Room 0230 1.9 1 Pass
V4 Level 2 Bedroom Room 0231 1.7 1 Pass
V4 Level 2 Bedroom Room 0233 1.6 1 Pass
V4 Level 2 Bedroom Room 0235 1.8 1 Pass
V4 Level 2 Bedroom Room 0239 1.7 1 Pass
V4 Level 2 Bedroom Room 0241 1.8 1 Pass
V4 Level 2 Bedroom Room 0244 1.8 1 Pass
V4 Level 2 Bedroom Room 0245 1.7 1 Pass
V4 Level 2 Bedroom Room 0247 1.6 1 Pass
V4 Level 2 Bedroom Room 0249 1.8 1 Pass
V4 Level 2 Bedroom Room 0248 1.8 1 Pass
V4 Level 2 Bedroom Room 0246 1.5 1 Pass
V4 Level 2 Bedroom Room 0238 1.7 1 Pass
V4 Level 2 Bedroom Room 0236 1.7 1 Pass
V4 Level 2 Bedroom Room 0256 1.7 1 Pass
V4 Level 2 Bedroom Room 0254 1.8 1 Pass
V4 Level 2 Bedroom Room 0253 1.7 1 Pass
V4 Level 2 Bedroom Room 0251 1.8 1 Pass
V4 Level 2 Bedroom Room 0250 1.7 1 Pass
V4 Level 2 Bedroom Room 0252 1.6 1 Pass
V4 Level 2 Living/Dining/Kitchen Room 0255 3.6 1.5 Pass
V4 Level 2 Bedroom Room 0242 1.9 1 Pass
V4 Level 2 Bedroom Room 0237 1.7 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 42 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 9-3 Average Daylight Factor for Proposed Block V5
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V5 Ground Living/Dining/Kitchen Room 0286 2.7 1.5 Pass
V5 Ground Living/Dining/Kitchen Room 0292 2.4 1.5 Pass
V5 Ground Living/Dining/Kitchen Room 0304 2.6 1.5 Pass
V5 Ground G_Bedroom_ 00 Room 0285 3 1 Pass
V5 Ground G_Bedroom_ 01 Room 0287 2.9 1 Pass
V5 Ground G_Bedroom_ 02 Room 0289 2.9 1 Pass
V5 Ground G_Bedroom_ 03 Room 0290 4 1 Pass
V5 Ground G_Bedroom_ 04 Room 0288 3.2 1 Pass
V5 Ground G_Bedroom_ 05 Room 0294 2.3 1 Pass
V5 Ground G_Bedroom_ 06 Room 0298 2.9 1 Pass
V5 Ground G_Bedroom_ 07 Room 0297 2.8 1 Pass
V5 Ground G_Bedroom_ 08 Room 0296 2.9 1 Pass
V5 Ground G_Bedroom_ 09 Room 0295 2.8 1 Pass
V5 Ground G_Bedroom_ 10 Room 0291 3.3 1 Pass
V5 Ground G_Bedroom_ 11 Room 0293 2.6 1 Pass
V5 Ground G_Bedroom_ 12 Room 0300 3.4 1 Pass
V5 Ground G_Bedroom_ 13 Room 0299 3.3 1 Pass
V5 Ground G_Bedroom_ 14 Room 0303 2.4 1 Pass
V5 Ground Living/Dining/Kitchen Room 0308 4.3 1.5 Pass
V5 Ground Living/Dining/Kitchen Room 0305 3.6 1.5 Pass
V5 Ground Living/Dining/Kitchen Room 0309 2.2 1.5 Pass
V5 Ground G_Bedroom_ 15 Room 0306 3.4 1 Pass
V5 Ground G_Bedroom_ 16 Room 0307 3 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 43 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
V5 Upper Ground Living/Dining/Kitchen Room 0351 1.5 1.5 Pass
V5 Upper Ground UG-Room 01 Room 0349 2 1 Pass
V5 Upper Ground UG-Room 02 Room 0347 1.9 1 Pass
V5 Upper Ground UG-Room 03 Room 0346 1.8 1 Pass
V5 Upper Ground UG-Room 04 Room 0348 2.3 1 Pass
V5 Upper Ground UG-Room 05 Room 0350 1.8 1 Pass
V5 Upper Ground UG-Room 06 Room 0352 1.8 1 Pass
V5 Upper Ground Living/Dining/Kitchen Room 0332 1.9 1.5 Pass
V5 Upper Ground Living/Dining/Kitchen Room 0339 1.8 1.5 Pass
V5 Upper Ground UG-Room 07 Room 0333 1.6 1 Pass
V5 Upper Ground UG-Room 08 Room 0334 1.6 1 Pass
V5 Upper Ground UG-Room 09 Room 0336 2 1 Pass
V5 Upper Ground UG-Room 10 Room 0338 1.9 1 Pass
V5 Upper Ground UG-Room 11 Room 0340 1.6 1 Pass
V5 Upper Ground UG-Room 12 Room 0341 2 1 Pass
V5 Upper Ground UG-Room 13 Room 0343 2 1 Pass
V5 Upper Ground UG-Room 15 Room 0344 2.4 1 Pass
V5 Upper Ground UG-Room 16 Room 0342 1.9 1 Pass
V5 Upper Ground UG-Room 17 Room 0337 2.3 1 Pass
V5 Upper Ground UG-Room 18 Room 0335 2.3 1 Pass
V5 Upper Ground Living/Dining/Kitchen Room 0331 1.9 1.5 Pass
V5 Upper Ground UG-Room 19 Room 0330 2.3 1 Pass
V5 Upper Ground UG-Room 20 Room 0329 1.8 1 Pass
V5 Upper Ground UG-Room 21 Room 0328 2.4 1 Pass
V5 Upper Ground UG-Room 22 Room 0327 2.4 1 Pass
V5 Upper Ground UG-Room 23 Room 0326 2.3 1 Pass
V5 Upper Ground UG-Room 24 Room 0325 1.5 1 Pass
V5 Upper Ground UG-Room 25 Room 0324 1.5 1 Pass
V5 Upper Ground UG-Room 26 Room 0323 1.5 1 Pass
V5 Upper Ground UG-Room 27 Room 0322 1.9 1 Pass
V5 Upper Ground UG-Room 28 Room 0320 1.7 1 Pass
V5 Upper Ground UG-Room 29 Room 0318 1.5 1 Pass
V5 Upper Ground Living/Dining/Kitchen Room 0319 1.6 1.5 Pass
V5 Upper Ground UG-Room 30 Room 0321 2 1 Pass
V5 Upper Ground UG-Room 31 Room 0316 1.9 1 Pass
V5 Upper Ground Living/Dining/Kitchen Room 0312 1.7 1.5 Pass
V5 Upper Ground UG-Room 32 Room 0314 2.2 1 Pass
V5 Upper Ground UG-Room 36 Room 0317 1 1 Pass
V5 Upper Ground UG-Room 33 Room 0311 1.6 1 Pass
V5 Upper Ground UG-Room 34 Room 0313 2 1 Pass
V5 Upper Ground UG-Room 35 Room 0315 1.9 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 44 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
V5 Level 3 L3_Bedroom_ 00 Room 0475 1.6 1 Pass
V5 Level 3 L3_Bedroom_ 01 Room 0473 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 02 Room 0472 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 03 Room 0474 1.8 1 Pass
V5 Level 3 L3_Bedroom_ 04 Room 0476 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 05 Room 0478 1.4 1 Pass
V5 Level 3 Living/Dining/Kitchen Room 0458 1.7 1.5 Pass
V5 Level 3 Living/Dining/Kitchen Room 0465 1.8 1.5 Pass
V5 Level 3 L3_Bedroom_ 06 Room 0459 1.3 1 Pass
V5 Level 3 L3_Bedroom_ 07 Room 0460 1.3 1 Pass
V5 Level 3 L3_Bedroom_ 08 Room 0462 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 09 Room 0464 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 10 Room 0466 1.3 1 Pass
V5 Level 3 L3_Bedroom_ 11 Room 0467 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 12 Room 0469 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 13 Room 0471 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 14 Room 0470 2.1 1 Pass
V5 Level 3 L3_Bedroom_ 15 Room 0468 1.6 1 Pass
V5 Level 3 L3_Bedroom_ 16 Room 0463 1.8 1 Pass
V5 Level 3 L3_Bedroom_ 17 Room 0461 1.9 1 Pass
V5 Level 3 Living/Dining/Kitchen Room 0457 1.8 1.5 Pass
V5 Level 3 L3_Bedroom_ 18 Room 0456 1.8 1 Pass
V5 Level 3 L3_Bedroom_ 19 Room 0455 1.4 1 Pass
V5 Level 3 L3_Bedroom_ 20 Room 0454 1.9 1 Pass
V5 Level 3 L3_Bedroom_ 21 Room 0453 1.9 1 Pass
V5 Level 3 L3_Bedroom_ 22 Room 0452 1.8 1 Pass
V5 Level 3 L3_Bedroom_ 23 Room 0451 1.3 1 Pass
V5 Level 3 L3_Bedroom_ 24 Room 0450 1.2 1 Pass
V5 Level 3 L3_Bedroom_ 25 Room 0449 1.3 1 Pass
V5 Level 3 L3_Bedroom_ 26 Room 0448 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 27 Room 0446 1.4 1 Pass
V5 Level 3 L3_Bedroom_ 28 Room 0444 1.3 1 Pass
V5 Level 3 Living/Dining/Kitchen Room 0445 1.7 1.5 Pass
V5 Level 3 L3_Bedroom_ 29 Room 0447 1.5 1 Pass
V5 Level 3 L3_Bedroom_ 30 Room 0442 1.5 1 Pass
V5 Level 3 Living/Dining/Kitchen Room 0438 1.7 1 Pass
V5 Level 3 L3_Bedroom_ 31 Room 0440 1.8 1 Pass
V5 Level 3 L3_Bedroom_ 32 Room 0443 1.4 1 Pass
V5 Level 3 L3_Bedroom_ 33 Room 0437 1.3 1 Pass
V5 Level 3 L3_Bedroom_ 34 Room 0439 1.6 1 Pass
V5 Level 3 L3_Bedroom_ 35 Room 0441 1.5 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 45 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 9-4 Average Daylight Factor for Proposed Block V1
Block Level Room type Room reference (Arch) ADF results Target Conclusion
V1 Ground Living/Dining/Kitchen Room 1105 2.3 1.5 Pass
V1 Ground Bedroom Room 1104 3.1 1 Pass
V1 Ground Bedroom Room 1103 3.1 1 Pass
V1 Ground Bedroom Room 1102 3 1 Pass
V1 Ground Living/Dining/Kitchen Room 1099 2.2 1.5 Pass
V1 Ground Bedroom Room 1095 3.1 1 Pass
V1 Ground Bedroom Room 1097 3.2 1 Pass
V1 Ground Bedroom Room 1100 3.1 1 Pass
V1 Ground Bedroom Room 1101 3.2 1 Pass
V1 Ground Bedroom Room 1087 2.6 1 Pass
V1 Ground Bedroom Room 1089 2.6 1 Pass
V1 Ground Bedroom Room 1091 2.6 1 Pass
V1 Ground Bedroom Room 1093 3 1 Pass
V1 Ground Bedroom Room 1092 3.5 1 Pass
V1 Ground Bedroom Room 1090 3 1 Pass
V1 Ground Living/Dining/Kitchen Room 1088 2.2 1.5 Pass
V1 Ground Bedroom Room 1098 2.3 1 Pass
V1 Ground Bedroom Room 1096 2.6 1 Pass
V1 Ground Bedroom Room 1094 2.6 1 Pass
V1 Upper Ground Bedroom Room 1109 1.8 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1107 1.5 1.5 Pass
V1 Upper Ground Bedroom Room 1111 2 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1106 2.8 1.5 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1110 2.2 1.5 Pass
V1 Upper Ground Bedroom Room 1115 1.7 1 Pass
V1 Upper Ground Bedroom Room 1113 2.1 1 Pass
V1 Upper Ground Bedroom Room 1117 1.8 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1114 1.6 1.5 Pass
V1 Upper Ground Bedroom Room 1116 2 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1118 2.2 1 Pass
V1 Upper Ground Bedroom Room 1120 2 1 Pass
V1 Upper Ground Bedroom Room 1130 2 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1137 1.5 1.5 Pass
V1 Upper Ground Bedroom Room 1135 2.3 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1138 1.6 1.5 Pass
V1 Upper Ground Bedroom Room 1133 2.3 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1136 1.7 1.5 Pass
V1 Upper Ground Bedroom Room 1132 2.6 1 Pass
V1 Upper Ground Bedroom Room 1131 2.1 1 Pass
V1 Upper Ground Living/Dining/Kitchen Room 1126 1.6 1.5 Pass
V1 Upper Ground Bedroom Room 1125 2 1 Pass
V1 Upper Ground Bedroom Room 1124 2.5 1 Pass
V1 Upper Ground Bedroom Room 1123 2.5 1 Pass
V1 Upper Ground Bedroom Room 1122 2.6 1 Pass
V1 Upper Ground Bedroom Room 1121 2.5 1 Pass
V1 Upper Ground Bedroom Room 1127 2.5 1 Pass
V1 Upper Ground Bedroom Room 1129 2.5 1 Pass
V1 Upper Ground Bedroom Room 1128 1.9 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 46 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
V1 Level 1 Bedroom Room 1174 1.8 1 Pass
V1 Level 1 Bedroom Room 1175 2.3 1 Pass
V1 Level 1 Bedroom Room 1178 1.6 1 Pass
V1 Level 1 Bedroom Room 1179 1.6 1 Pass
V1 Level 1 Bedroom Room 1180 2 1 Pass
V1 Level 1 Bedroom Room 1181 1.6 1 Pass
V1 Level 1 Bedroom Room 1182 2.4 1 Pass
V1 Level 1 Bedroom Room 1184 1.8 1 Pass
V1 Level 1 Bedroom Room 1185 2.5 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1190 2.8 1.5 Pass
V1 Level 1 Bedroom Room 1187 2.3 1 Pass
V1 Level 1 Bedroom Room 1189 1.8 1 Pass
V1 Level 1 Bedroom Room 1191 2.2 1 Pass
V1 Level 1 Bedroom Room 1192 2.3 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1183 1.5 1.5 Pass
V1 Level 1 Bedroom Room 1186 2.2 1 Pass
V1 Level 1 Bedroom Room 1188 1.7 1 Pass
V1 Level 1 Bedroom Room 1173 2.3 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1172 1.5 1.5 Pass
V1 Level 1 Bedroom Room 1164 2.4 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1159 1.5 1.5 Pass
V1 Level 1 Bedroom Room 1158 1.9 1 Pass
V1 Level 1 Bedroom Room 1156 2.4 1 Pass
V1 Level 1 Bedroom Room 1154 2.3 1 Pass
V1 Level 1 Bedroom Room 1155 2.4 1 Pass
V1 Level 1 Bedroom Room 1157 2.4 1 Pass
V1 Level 1 Bedroom Room 1160 2.3 1 Pass
V1 Level 1 Bedroom Room 1162 2.4 1 Pass
V1 Level 1 Bedroom Room 1165 2.4 1 Pass
V1 Level 1 Bedroom Room 1167 2.3 1 Pass
V1 Level 1 Bedroom Room 1168 2.4 1 Pass
V1 Level 1 Bedroom Room 1170 1.9 1 Pass
V1 Level 1 Bedroom Room 1171 1.9 1 Pass
V1 Level 1 Bedroom Room 1169 2 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1163 1.7 1.5 Pass
V1 Level 1 Bedroom Room 1161 2.2 1 Pass
V1 Level 1 Bedroom Room 1153 1.8 1 Pass
V1 Level 1 Bedroom Room 1152 1.9 1 Pass
V1 Level 1 Bedroom Room 1149 2.4 1 Pass
V1 Level 1 Bedroom Room 1147 2.3 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1151 1.6 1.5 Pass
V1 Level 1 Bedroom Room 1148 2 1 Pass
V1 Level 1 Bedroom Room 1146 1.6 1 Pass
V1 Level 1 Bedroom Room 1150 1.6 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1140 1.6 1.5 Pass
V1 Level 1 Bedroom Room 1144 1.9 1 Pass
V1 Level 1 Bedroom Room 1142 2.3 1 Pass
V1 Level 1 Bedroom Room 1145 1.6 1 Pass
V1 Level 1 Bedroom Room 1143 2 1 Pass
V1 Level 1 Bedroom Room 1141 1.9 1 Pass
V1 Level 1 Bedroom Room 1139 1.6 1 Pass
V1 Level 1 Bedroom Room 1177 1.8 1 Pass
V1 Level 1 Bedroom Room 1176 1.9 1 Pass
V1 Level 1 Living/Dining/Kitchen Room 1166 1.6 1.5 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 47 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
V1 Level 4 Bedroom Room 1323 1.4 1 Pass
V1 Level 4 Bedroom Room 1324 1.9 1 Pass
V1 Level 4 Bedroom Room 1327 1.2 1 Pass
V1 Level 4 Bedroom Room 1328 1.2 1 Pass
V1 Level 4 Bedroom Room 1329 1.6 1 Pass
V1 Level 4 Bedroom Room 1330 1.2 1 Pass
V1 Level 4 Bedroom Room 1331 2 1 Pass
V1 Level 4 Bedroom Room 1333 1.4 1 Pass
V1 Level 4 Bedroom Room 1334 2 1 Pass
V1 Level 4 Living/Dining/Kitchen Room 1339 2.1 1.5 Pass
V1 Level 4 Bedroom Room 1336 1.9 1 Pass
V1 Level 4 Bedroom Room 1338 1.4 1 Pass
V1 Level 4 Bedroom Room 1340 1.8 1 Pass
V1 Level 4 Bedroom Room 1341 1.9 1 Pass
V1 Level 4 Living/Dining/Kitchen Room 1332 1.6 1.5 Pass
V1 Level 4 Bedroom Room 1335 1.6 1 Pass
V1 Level 4 Bedroom Room 1337 1.2 1 Pass
V1 Level 4 Bedroom Room 1322 1.9 1 Pass
V1 Level 4 Living/Dining/Kitchen Room 1321 1.5 1.5 Pass
V1 Level 4 Bedroom Room 1313 2 1 Pass
V1 Level 4 Living/Dining/Kitchen Room 1308 2.1 1.5 Pass
V1 Level 4 Bedroom Room 1307 1.4 1 Pass
V1 Level 4 Bedroom Room 1305 1.9 1 Pass
V1 Level 4 Bedroom Room 1303 1.8 1 Pass
V1 Level 4 Bedroom Room 1304 1.9 1 Pass
V1 Level 4 Bedroom Room 1306 2 1 Pass
V1 Level 4 Bedroom Room 1309 1.9 1 Pass
V1 Level 4 Bedroom Room 1311 1.9 1 Pass
V1 Level 4 Bedroom Room 1314 1.9 1 Pass
V1 Level 4 Bedroom Room 1316 1.9 1 Pass
V1 Level 4 Bedroom Room 1317 1.9 1 Pass
V1 Level 4 Bedroom Room 1319 1.5 1 Pass
V1 Level 4 Bedroom Room 1320 1.4 1 Pass
V1 Level 4 Bedroom Room 1318 1.6 1 Pass
V1 Level 4 Living/Dining/Kitchen Room 1312 1.5 1.5 Pass
V1 Level 4 Bedroom Room 1310 1.7 1 Pass
V1 Level 4 Bedroom Room 1302 1.8 1 Pass
V1 Level 4 Bedroom Room 1326 1.5 1 Pass
V1 Level 4 Bedroom Room 1325 1.4 1 Pass
V1 Level 4 Living/Dining/Kitchen Room 1315 1.7 1.5 Pass
V1 Level 4 Bedroom Room 1301 1.6 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 48 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 9-5 Average Daylight Factor for Proposed Block V8
Block Level Room type Room reference (Arch) ADF results Target Conclusion
V8 Upper Ground Living/Dining/Kitchen Room 0851 1.7 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0850 2.8 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0854 2.2 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0857 1.6 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0861 2.2 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0879 1.5 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0880 2.4 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0878 1.7 1.5 Pass
V8 Upper Ground Living/Dining/Kitchen Room 0868 1.6 1.5 Pass
V8 Upper Ground Bedroom Room 0853 1.9 1 Pass
V8 Upper Ground Bedroom Room 0855 2 1 Pass
V8 Upper Ground Bedroom Room 0856 1.9 1 Pass
V8 Upper Ground Bedroom Room 0858 1.8 1 Pass
V8 Upper Ground Bedroom Room 0859 2 1 Pass
V8 Upper Ground Bedroom Room 0862 2 1 Pass
V8 Upper Ground Bedroom Room 0873 1.9 1 Pass
V8 Upper Ground Bedroom Room 0877 2.3 1 Pass
V8 Upper Ground Bedroom Room 0875 2.3 1 Pass
V8 Upper Ground Bedroom Room 0874 2.5 1 Pass
V8 Upper Ground Bedroom Room 0872 2.1 1 Pass
V8 Upper Ground Bedroom Room 0867 2 1 Pass
V8 Upper Ground Bedroom Room 0866 2.5 1 Pass
V8 Upper Ground Bedroom Room 0865 2.5 1 Pass
V8 Upper Ground Bedroom Room 0864 2.6 1 Pass
V8 Upper Ground Bedroom Room 0863 2.5 1 Pass
V8 Upper Ground Bedroom Room 0869 2.5 1 Pass
V8 Upper Ground Bedroom Room 0871 2.5 1 Pass
V8 Upper Ground Bedroom Room 0870 2.1 1 Pass
V8 Level 1 Living/Dining/Kitchen Room 0921 2.2 1.5 Pass
V8 Level 1 Living/Dining/Kitchen Room 0927 1.6 1.5 Pass
V8 Level 1 Living/Dining/Kitchen Room 0934 2.9 1.5 Pass
V8 Level 1 Bedroom Room 0917 2.4 1 Pass
V8 Level 1 Bedroom Room 0918 2 1 Pass
V8 Level 1 Bedroom Room 0919 2.5 1 Pass
V8 Level 1 Bedroom Room 0922 1.7 1 Pass
V8 Level 1 Bedroom Room 0923 1.7 1 Pass
V8 Level 1 Bedroom Room 0924 2.1 1 Pass
V8 Level 1 Bedroom Room 0925 1.7 1 Pass
V8 Level 1 Bedroom Room 0926 2.6 1 Pass
V8 Level 1 Bedroom Room 0928 2 1 Pass
V8 Level 1 Bedroom Room 0929 2.6 1 Pass
V8 Level 1 Bedroom Room 0931 2.5 1 Pass
V8 Level 1 Bedroom Room 0933 1.9 1 Pass
V8 Level 1 Bedroom Room 0935 2.4 1 Pass
V8 Level 1 Bedroom Room 0936 2.5 1 Pass
V8 Level 1 Bedroom Room 0930 2.2 1 Pass
V8 Level 1 Bedroom Room 0932 1.7 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 49 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
V8 Level 2 Living/Dining/Kitchen Room 0945 1.6 1.5 Pass
V8 Level 2 Living/Dining/Kitchen Room 0950 1.6 1.5 Pass
V8 Level 2 Living/Dining/Kitchen Room 0969 1.6 1.5 Pass
V8 Level 2 Living/Dining/Kitchen Room 0957 1.8 1.5 Pass
V8 Level 2 Living/Dining/Kitchen Room 0938 2.3 1.5 Pass
V8 Level 2 Living/Dining/Kitchen Room 0972 1.5 1.5 Pass
V8 Level 2 Living/Dining/Kitchen Room 0962 1.6 1.5 Pass
V8 Level 2 Bedroom Room 0946 1.2 1 Pass
V8 Level 2 Bedroom Room 0944 1.6 1 Pass
V8 Level 2 Bedroom Room 0947 1.4 1 Pass
V8 Level 2 Bedroom Room 0951 1.4 1 Pass
V8 Level 2 Bedroom Room 0965 1.7 1 Pass
V8 Level 2 Bedroom Room 0964 1.9 1 Pass
V8 Level 2 Bedroom Room 0963 1.5 1 Pass
V8 Level 2 Bedroom Room 0956 1.2 1 Pass
V8 Level 2 Bedroom Room 0955 1.9 1 Pass
V8 Level 2 Bedroom Room 0954 2 1 Pass
V8 Level 2 Bedroom Room 0953 2 1 Pass
V8 Level 2 Bedroom Room 0952 1.8 1 Pass
V8 Level 2 Bedroom Room 0959 1.9 1 Pass
V8 Level 2 Bedroom Room 0961 1.9 1 Pass
V8 Level 2 Bedroom Room 0960 1.3 1 Pass
V8 Level 2 Bedroom Room 0958 1.7 1 Pass
V8 Level 2 Bedroom Room 0948 1.4 1 Pass
V8 Level 2 Bedroom Room 0940 1.4 1 Pass
V8 Level 2 Bedroom Room 0942 1.4 1 Pass
V8 Level 2 Bedroom Room 0937 1.3 1 Pass
V8 Level 2 Bedroom Room 0939 1.6 1 Pass
V8 Level 2 Bedroom Room 0941 1.6 1 Pass
V8 Level 2 Bedroom Room 0943 1.3 1 Pass
V8 Level 2 Bedroom Room 0966 1.9 1 Pass
V8 Level 2 Bedroom Room 0968 1.9 1 Pass
V8 Level 2 Bedroom Room 0967 1.7 1 Pass
V8 Level 2 Bedroom Room 0970 1.9 1 Pass
V8 Level 2 Bedroom Room 0971 1.4 1 Pass
V8 Level 4 Living/Dining/Kitchen Room 1326 1.7 1.5 Pass
V8 Level 4 Living/Dining/Kitchen Room 1327 1.8 1.5 Pass
V8 Level 4 Living/Dining/Kitchen Room 1329 1.5 1.5 Pass
V8 Level 4 Living/Dining/Kitchen Room 1339 2.1 1.5 Pass
V8 Level 4 Bedroom Room 1322 1.8 1 Pass
V8 Level 4 Bedroom Room 1323 1.5 1 Pass
V8 Level 4 Bedroom Room 1324 1.9 1 Pass
V8 Level 4 Bedroom Room 1331 2 1 Pass
V8 Level 4 Bedroom Room 1333 1.4 1 Pass
V8 Level 4 Bedroom Room 1334 2 1 Pass
V8 Level 4 Bedroom Room 1330 1.6 1 Pass
V8 Level 4 Bedroom Room 1336 1.9 1 Pass
V8 Level 4 Bedroom Room 1338 1.4 1 Pass
V8 Level 4 Bedroom Room 1340 1.8 1 Pass
V8 Level 4 Bedroom Room 1341 1.8 1 Pass
V8 Level 4 Bedroom Room 1335 1.6 1 Pass
V8 Level 4 Bedroom Room 1337 1.3 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 50 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 9-6 Average Daylight Factor for Proposed Block V7
Block Level Room type Room reference (Arch) ADF results Target Conclusion
V7 Upper Ground Living/Dining/Kitchen Room 0603 2.1 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0602 2.8 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0606 2.2 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0609 1.6 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0613 2.2 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0632 1.5 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0633 2.4 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0631 1.7 1.5 Pass
V7 Upper Ground Living/Dining/Kitchen Room 0620 1.6 1.5 Pass
V7 Upper Ground Bedroom Room 0607 2 1 Pass
V7 Upper Ground Bedroom Room 0605 2 1 Pass
V7 Upper Ground Bedroom Room 0608 1.9 1 Pass
V7 Upper Ground Bedroom Room 0610 1.8 1 Pass
V7 Upper Ground Bedroom Room 0611 2 1 Pass
V7 Upper Ground Bedroom Room 0614 2 1 Pass
V7 Upper Ground Bedroom Room 0625 1.9 1 Pass
V7 Upper Ground Bedroom Room 0630 2.3 1 Pass
V7 Upper Ground Bedroom Room 0628 2.3 1 Pass
V7 Upper Ground Bedroom Room 0627 2.5 1 Pass
V7 Upper Ground Bedroom Room 0626 2.1 1 Pass
V7 Upper Ground Bedroom Room 0619 2 1 Pass
V7 Upper Ground Bedroom Room 0618 2.5 1 Pass
V7 Upper Ground Bedroom Room 0617 2.5 1 Pass
V7 Upper Ground Bedroom Room 0616 2.6 1 Pass
V7 Upper Ground Bedroom Room 0615 2.5 1 Pass
V7 Upper Ground Bedroom Room 0623 2.5 1 Pass
V7 Upper Ground Bedroom Room 0624 2.5 1 Pass
V7 Upper Ground Bedroom Room 0622 2.1 1 Pass
V7 Level 1 Bedroom Room 0670 2.4 1 Pass
V7 Level 1 Bedroom Room 0671 2 1 Pass
V7 Level 1 Bedroom Room 0672 2.5 1 Pass
V7 Level 1 Bedroom Room 0677 2.1 1 Pass
V7 Level 1 Bedroom Room 0678 1.7 1 Pass
V7 Level 1 Bedroom Room 0679 2.6 1 Pass
V7 Level 1 Bedroom Room 0681 2 1 Pass
V7 Level 1 Bedroom Room 0683 2.6 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 51 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Block Level Room type Room reference (Arch) ADF Results Target Conclusion
V4 Ground Bedroom Room 0161 2.3 1 Pass
V4 Ground Bedroom Room 0163 2.1 1 Pass
V4 Ground Living/Dining/Kitchen Room 0167 2.2 1.5 Pass
V4 Ground Bedroom Room 0172 2.1 1 Pass
V4 Ground Bedroom Room 0170 2 1 Pass
V4 Ground Bedroom Room 0171 2.3 1 Pass
V4 Ground Bedroom Room 0169 2.3 1 Pass
V4 Ground Bedroom Room 0168 2.3 1 Pass
V4 Ground Bedroom Room 0162 2.3 1 Pass
V4 Ground Bedroom Room 0165 2.5 1 Pass
V4 Ground Living/Dining/Kitchen Room 0155 2 1.5 Pass
V4 Ground Bedroom Room 0158 3 1 Pass
V4 Ground Bedroom Room 0160 3.3 1 Pass
V4 Ground Bedroom Room 0156 3.3 2 Pass
V4 Ground Bedroom Room 0157 3.2 1 Pass
V4 Ground Bedroom Room 159 3.2 1 Pass
V4 Ground Bedroom Room 0166 2.1 1 Pass
V4 Upper Ground Bedroom Room 0184 1.7 1 Pass
V4 Upper Ground Bedroom Room 0187 1.5 1 Pass
V4 Upper Ground Bedroom Room 0173 1.3 1 Pass
V4 Upper Ground Bedroom Room 0176 2.1 1 Pass
V4 Upper Ground Bedroom Room 0178 2.3 1 Pass
V4 Upper Ground Bedroom Room 0174 2.4 1 Pass
V4 Upper Ground Bedroom Room 0175 2.2 1 Pass
V4 Upper Ground Bedroom Room 0177 2.1 1 Pass
V4 Upper Ground Bedroom Room 0179 2.3 1 Pass
V4 Upper Ground Bedroom Room 0183 2.3 1 Pass
V4 Upper Ground Bedroom Room 0185 2.3 1 Pass
V4 Upper Ground Bedroom Room 0188 2.3 1 Pass
V4 Upper Ground Bedroom Room 0189 2.3 1 Pass
V4 Upper Ground Bedroom Room 0191 2.1 1 Pass
V4 Upper Ground Bedroom Room 0193 2.2 1 Pass
V4 Upper Ground Bedroom Room 0192 2.3 1 Pass
V4 Upper Ground Bedroom Room 0190 2 1 Pass
V4 Upper Ground Bedroom Room 0182 2.2 1 Pass
V4 Upper Ground Bedroom Room 0180 2.2 1 Pass
V4 Upper Ground Bedroom Room 0194 2.1 1 Pass
V4 Upper Ground Bedroom Room 0196 2.1 1 Pass
V4 Upper Ground Bedroom Room 0200 3.2 1 Pass
V4 Upper Ground Bedroom Room 0181 2.2 1 Pass
V4 Upper Ground Bedroom Room 0186 1.6 1 Pass
V7 Level 2 Living/Dining/Kitchen Room 0699 1.6 1.5 Pass
V7 Level 2 Living/Dining/Kitchen Room 0704 1.6 1.5 Pass
V7 Level 2 Living/Dining/Kitchen Room 0723 1.5 1.5 Pass
V7 Level 2 Living/Dining/Kitchen Room 0711 1.2 1.5 Pass
V7 Level 2 Living/Dining/Kitchen Room 0692 2.3 1.5 Pass
V7 Level 2 Living/Dining/Kitchen Room 0726 1.6 1.5 Pass
V7 Level 2 Living/Dining/Kitchen Room 0716 1.5 1.5 Pass
V7 Level 2 Bedroom Room 0700 1.6 1 Pass
V7 Level 2 Bedroom Room 0698 1.6 1 Pass
V7 Level 2 Bedroom Room 0701 1.4 1 Pass
V7 Level 2 Bedroom Room 0705 1.4 1 Pass
V7 Level 2 Bedroom Room 0719 1.7 1 Pass
V7 Level 2 Bedroom Room 0718 1.9 1 Pass
V7 Level 2 Bedroom Room 0717 1.5 1 Pass
V7 Level 2 Bedroom Room 0710 1.5 1 Pass
V7 Level 2 Bedroom Room 0709 1.9 1 Pass
V7 Level 2 Bedroom Room 0708 1.9 1 Pass
V7 Level 2 Bedroom Room 0707 2 1 Pass
V7 Level 2 Bedroom Room 0706 1.8 1 Pass
V7 Level 2 Bedroom Room 0713 1.9 1 Pass
V7 Level 2 Bedroom Room 0715 1.9 1 Pass
V7 Level 2 Bedroom Room 0714 1.3 1 Pass
V7 Level 2 Bedroom Room 0712 1.7 1 Pass
V7 Level 2 Bedroom Room 0702 0.8 1 Pass
V7 Level 2 Bedroom Room 0694 1.8 1 Pass
V7 Level 2 Bedroom Room 0696 1.4 1 Pass
V7 Level 2 Bedroom Room 0691 1.3 1 Pass
V7 Level 2 Bedroom Room 0693 1.6 1 Pass
V7 Level 2 Bedroom Room 0695 1.6 1 Pass
V7 Level 2 Bedroom Room 0697 1.3 1 Pass
V7 Level 2 Bedroom Room 0720 1.9 1 Pass
V7 Level 2 Bedroom Room 0722 1.9 1 Pass
V7 Level 2 Bedroom Room 0721 1.7 1 Pass
V7 Level 2 Bedroom Room 0724 1.9 1 Pass
V7 Level 2 Bedroom Room 0725 1.4 1 Pass
V7 Level 4 Living/Dining/Kitchen Room 0812 3 1.5 Pass
V7 Level 4 Bedroom Room 0805 1.8 1 Pass
V7 Level 4 Bedroom Room 0806 1.5 1 Pass
V7 Level 4 Bedroom Room 0807 1.9 1 Pass
V7 Level 4 Bedroom Room 0813 2 1 Pass
V7 Level 4 Bedroom Room 0815 1.4 1 Pass
V7 Level 4 Bedroom Room 0817 2 1 Pass
V7 Level 4 Bedroom Room 0814 1.6 1 Pass
V7 Level 4 Bedroom Room 0816 1.7 1 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 52 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 9-7 Average Daylight Factor for Proposed Block V6
Block Level Room type Room reference (Arch)ADF results
(Area weighted)Target Conclusion
V6 Upper Ground Living/Dining/Kitchen Room 0489 2.2 1.5 Pass
V6 Upper Ground Living/Dining/Kitchen Room 0491 2.1 1.5 Pass
V6 Upper Ground Living/Dining/Kitchen Room 0488 2.8 1.5 Pass
V6 Upper Ground Living/Dining/Kitchen Room 0486 1.9 1.5 Pass
V6 Upper Ground Living/Dining/Kitchen Room 0481 2.4 1.5 Pass
V6 Upper Ground Living/Dining/Kitchen Room 0483 2.2 1.5 Pass
V6 Upper Ground Living/Dining/Kitchen Room 0479 3.2 1.5 Pass
V6 Upper Ground Bedroom Room 0495 1.9 1 Pass
V6 Upper Ground Bedroom Room 0496 1.5 1 Pass
V6 Upper Ground Bedroom Room 0494 1.8 1 Pass
V6 Upper Ground Bedroom Room 0492 2.4 1 Pass
V6 Upper Ground Bedroom Room 0487 1.8 1 Pass
V6 Upper Ground Bedroom Room 0485 1.4 1 Pass
V6 Upper Ground Bedroom Room 0484 1.4 1 Pass
V6 Upper Ground Bedroom Room 0482 1.4 1 Pass
V6 Level 2 Bedroom Room 0520 1.4 1 Pass
V6 Level 2 Bedroom Room 0519 1.6 1 Pass
V6 Level 2 Bedroom Room 0524 1.4 1 Pass
V6 Level 2 Bedroom Room 0521 1.2 1 Pass
V6 Level 2 Bedroom Room 0523 1.2 1 Pass
V6 Level 2 Bedroom Room 0522 1.5 1 Pass
V6 Level 2 Bedroom Room 0526 1.9 1 Pass
V6 Level 2 Bedroom Room 0528 1.8 1 Pass
V6 Level 2 Bedroom Room 0530 1.8 1 Pass
V6 Level 2 Bedroom Room 0531 1.4 1 Pass
V6 Level 2 Bedroom Room 0533 1.8 1 Pass
V6 Level 2 Bedroom Room 0534 1.5 1 Pass
V6 Level 2 Bedroom Room 0536 1.4 1 Pass
V6 Level 2 Bedroom Room 0538 1.4 1 Pass
V6 Level 2 Bedroom Room 0537 1.3 1 Pass
V6 Level 2 Bedroom Room 0535 1.7 1 Pass
V6 Level 2 Bedroom Room 0527 1.6 1 Pass
V6 Level 2 Bedroom Room 0525 1.5 1 Pass
V6 Level 2 Living/Dining/Kitchen Room 0518 1.9 1.5 Pass
V6 Level 2 Living/Dining/Kitchen Room 0532 1.8 1.5 Pass
V6 Level 2 Living/Dining/Kitchen Room 0529 1.8 1.5 Pass
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 53 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Appendix A2: Average Daylight Factor for each space within the Existing Scheme
Table 9-8 Average Daylight Factor for Existing Block - Hampstead Court
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 54 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 55 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 56 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Table 9-9 Average Daylight Factor for Existing Block - College Park
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 57 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 58 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
10 Appendix B: Architectural Drawing Schedule
Table 10-1 Architectural Drawing Schedule
Drawings Revision Date Received
1909-5-DIAG-Building Height Adjustment Table-181115 15-Nov-2018
0502 - Planning - Phase 1 Basement - 13-Nov-2018
0510 - Planning - Phase 2 Ground Level - 13-Nov-2018
0511 - Planning - Phase 2 Upper Ground Level - 13-Nov-2018
0512 - Planning - Phase 2 First Level - 13-Nov-2018
0513 - Planning - Phase 2 Second Level - 13-Nov-2018
0514 - Planning - Phase 2 Third Level - 13-Nov-2018
0515 - Planning - Phase 2 Fourth Level - 13-Nov-2018
0517 - Planning - Phase 2 Sixth Level - 13-Nov-2018
0518 - Planning - Phase 2 Seventh Level - 13-Nov-2018
0519 - Planning - Phase 2 Eighth Level - 13-Nov-2018
0520 - Planning - Phase 2 Roof Level - 13-Nov-2018
1909 GLA-FCBS-XX-ZZ-DR-A-0004 Building Sections - Sheet 01 - 07-Nov-2018
1909 GLA-FCBS-XX-ZZ-DR-A-0005 Building Sections - Sheet 02 - 07-Nov-2018
1909 GLA-FCBS-XX-ZZ-DR-A-0006 Building Sections - Sheet 03 - 07-Nov-2018
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 59 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Appendix B1: Floor Layout Drawings with Room References within the Proposed Scheme
Figure 10-1 Floor Layout of Block V3 – Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 60 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-2 Floor Layout of Block V3 – Upper Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 61 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-3 Floor Layout of Block V3 – Second Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 62 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-4 Floor Layout of Block V4 – Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 63 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-5 Floor Layout of Block V4 – Upper Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 64 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-6 Floor Layout of Block V4 – Second Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 65 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-7 Floor Layout of Block V5 – Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 66 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-8 Floor Layout of Block V5 – Upper Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 67 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-9 Floor Layout of Block V5 – Third Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 68 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-10 Floor Layout of Block V1 – Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 69 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-11 Floor Layout of Block V1 – Upper Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 70 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-12 Floor Layout of Block V1 – First Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 71 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-13 Floor Layout of Block V1 – Fourth Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 72 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-14 Floor Layout of Block V6 – Upper Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 73 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-15 Floor Layout of Block V6 – Second Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 74 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-16 Floor Layout of Block V7 – Upper Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 75 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-17 Floor Layout of Block V7 – First Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 76 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-18 Floor Layout of Block V7 – Second Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 77 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-19 Floor Layout of Block V7 – Fourth Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 78 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-20 Floor Layout of Block V8 - Upper Ground Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 79 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-21 Floor Layout of Block V8 – First Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 80 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-22 Floor Layout of Block V8 – Second Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 81 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-23 Floor Layout of Block V8 – Fourth Floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 82 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Appendix B2: Floor Layout Drawings with Room References within the Existing Scheme
10.2.1 Appendix B2.1: Existing Block – Hampstead Court
Figure 10-24 Floor Layout of Hampstead Court - Ground floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 83 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-25 Floor Layout of Hampstead Court - First floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 84 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-26 Floor Layout of Hampstead Court - Second floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 85 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
10.2.2 Appendix B2.2: Window Modification in Hampstead Court
Figure 10-27 Window Modification Highlighted in Hampstead Court (East Elevation)
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 86 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
10.2.3 Appendix B2.3: Existing Block – College Park
Figure 10-28 Floor Layout of College Park - Ground floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 87 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-29 Floor Layout of College Park - First floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 88 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-30 Floor Layout of College Park - Second floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 89 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-31 Floor Layout of College Park - Third floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 90 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 10-32 Floor Layout of College Park - Fourth floor
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 91 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
10.2.4 Appendix B2.4: New Window Installation in College Park
Figure 10-33 New Window Installation Highlighted in College Park
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 92 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
11 Appendix C: 3-D Representation of the Digital Model
Figure 11-1 Plan view of Existing Buildings and Proposed Scheme
DCU Proposed Glasnevin Student Accommodation 09 September 2019
Daylight and Sunlight Assessment_v05
P a g e | 93 of 94 Geraghty Energy Consultants Ltd.
The Digital Hub, 10-13 Thomas St, Dublin 8
Figure 11-2 South aerial view of Existing Buildings (Test Rooms highlighted)
Figure 11-3 East aerial view of Existing Buildings (Test Rooms highlighted)