TracTion inverTer / Dc energy recovery2

GENERAL INFORMATIONanswering increasing energy efficiency requirements of rail transportation, Sécheron has developed a range of flexible solutions to recover the excess braking energy present in the system.

allowing a reduction of the total energy consumption, these systems have been designed following the strictest requirements of sustainability, maintainability and durability.

MAIN BENEFITSMAIN BENEFITS D cost savings through recovery of the excess braking electrical energy.

D reduction of heat in tunnels and substations 4 reduction of cooling requirements 4 Further cost savings.

D compatible with existing systems.

D Minimisation of co2 footprint.

D Harmonization and integration with SePcoS (Sécheron’s control and protection relay) and Sécheron Dc switchgear for protection, diagnostics and control.

MV Network

Braking / Regenerating train

TractionInverter

TractionRectifier

750

0 1 2 3 4

1500

3000

UN [VDC]

P [MW]

Thyristor Inverter

IGBT Inverter

Page 3: DC energy recovery · Braking / Regenerating train Traction Inverter Traction Rectifier 750 0 1 2 3 ... The inverter includes a SePcoS system, ... This document is not contractual

TracTion inverTer / Dc energy recovery 3

INVERTER RANGE

Sécheron provides engineering support to ensure an optimized investment in fixed installation assets based on customer specifications.

OPTIMIZED INVESTMENT

IGBT Inverter Thyristor Inverter

750 v 1500 v 750 v 1500 v 3000 v

Standard inverter range

rated Dc voltage [v] 750-1000 1500-2000 750-1000 1500-2000 3000-3900

rated power [MW] 0.5-1.5 1-3 0.5-1.5 1-3 4

Maximum power [MW] Up to 4.5 Up to 9 Up to 4.5 Up to 9 Up to 12

overload capacity class vi per en 50328 / iec 60146

ac frequency [Hz] 50/60

efficiency > 97.5 %

Power factor 1 (fully controlable) 1 (with optional filter)

THDi < 5 % < 5 % (with optional filter)

cooling Forced air natural air

Max. ambient temperature [°c] 40 (without derating)

Maximum altitude [m] < 1000 (without derating)

iP degree Up to iP32

noise level [dB] < 65

insulation levels Tested for cat 3 Power Frequency Withstand voltage Levels according to iec 61992-1 *

Standards iec 61000, en 50328, ieee 519, en 50121-5, iec 61992-1

/// TRANSFORMER-INVERTER GROUP

Depending on requirements, connection with cheaper autotransformers or direct connection to rectifier transformer secondaries can be achieved. consulting and support for transformer specification, manufacturing, FaT and combined tests is provided.

/// SEMICONDUCTOR TECHNOLOGY

requirements such as harmonics, reactive power, maintenance, overload, type of cooling, and efficiency will be carefully considered to offer the most suitable technology for the application.

/// PROTECTION AND RELIABILITY

Based on Sécheron’s ample experience, the protective devices present in the inverter and the complete substation are carefully coordinated to ensure optimal protection. Breakers, brake choppers and other protective devices are configured to ensure safety and to preserve the acquired assets.

/// REMOTE CONTROL, MONITORING AND DIAGNOSTICS

The inverter includes a SePcoS system, allowing connection to all types of communication bus and protocols.

* Other insulation levels upon request.

Page 4: DC energy recovery · Braking / Regenerating train Traction Inverter Traction Rectifier 750 0 1 2 3 ... The inverter includes a SePcoS system, ... This document is not contractual

Sécheron SA

Rue du Pré-Bouvier 251242 Satigny - Geneva

CH-Switzerland

www.secheron.com

Tel: +41 (0)22 739 41 11Fax: +41 (0)22 739 48 [email protected]

This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product, whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser’s responsibility to inform himself, no matter what the circumstances, of

the product’s maintenance conditions and requirements. Sécheron reserves all rights, especially those arising from our “General Delivery Conditions”.

Copyright© 2016 Sécheron SA

Sg825865Ben_c00-09.16