Diagnostics facilities for PROFINET
IO-Device
IO-Controller
1
IO-Supervisor
23
1The supervisor requests the device status from the controller
2 The Controller interrogates the deviceand makes the info available
3 The supervisor interrogates directlythe IO device
Overview of diagnostics facilities for PN
LEDs on the device/controller
Engineering Diagnostics
Standard tools
Diagnostics with the Topology Editor
Integrated WEB Servers
Diagnostics with additional user program
Network management – Using LEDs
Port LED- Green: Link, no data- Yellow: Link + data- Dark: not connected
Power line indicators- Yellow: one line powered- Green: both lines powered- Dark: no power
Fault LED- Link down on a monitored port.- Failure of one redundant PS- C-PLUG error- Device startup (approx. 20 sec) - RM connected through.
If Device is in PROFINET mode:– no connection to the controller– connection but diagnostic available
Set/select Button
Using LEDs on the modules you can see some basic information
RM LED-Green: RM enabled-Green flashing: RM swapped-Dark: RM disabled
Network management – Using wires
Events that could be signaledEvents that could be signaled Power down on a
redundant power line
Link down on a monitored port
Signal on a digital input port
Signalingcontact
Signalingcontact
LEDs on the device/controller
LINK: Physical connection to the switch/controllerRX/TX: Data are sent/receivedSF / F: Diagnosis pendingBF: Device/controller cannot be reachedEXTF: Diagnosis pending or device cannot be reached
LEDs on the module provide the initial informationabout the status of the devices/controller
Overview of the diagnostics facilities for PN
LEDs on the device/controller
Engineering Diagnostics
Standard tools
Diagnostics with the Topology Editor
Integrated WEB Servers
Diagnostics with additional user program
STEP7 Online - Hardware Diagnostics
Missing node
STEP7 Online - Hardware Diagnostics
Wrong Name assigned:
STEP7 Online - Hardware Diagnostics
Wrong Module:
Station (device) diagnose
STEP7 Online - Hardware Diagnostics
Wrong Module:
Module diagnose
STEP7 Online - Hardware Diagnostics
Wrong Module:
STEP7 Online - Hardware Diagnostics
Missing Module:
STEP7 Online - Hardware Diagnostics
Port status of switches – Scalance X200:
Online statistics:
STEP7 Online - Hardware Diagnostics
Diagnostics facilities for PROFINET
LEDs on the device/controller
Engineering Diagnostics
Standard tools
Diagnostics with the Topology Editor
Integrated WEB Servers
Diagnostics with additional user program
Web-diagnosticsDiagnostics whenever required
Via an integrated PROFINET interface
Read access via the Internet browser
Display optimized for PCs, Multi Panels, PDAs
Web contentsModule identification(MLFB, FW version, etc.)
Operating status, diagnostics buffer
Display of messages (Alarm S)
Ethernet parameters and statistics
Topology information
Variable table (VAT) from STEP7 andmonitoring of variables
Pages are stored on MMC of the CPU use a MCC of at least 512 kB.
Easy access to diagnostics data at any location
Increased plant availability
Internet
Security
Basic interfaceIf you have
only small bandwidth
Full interface
suitable web browsers:● Internet Explorer (version 6.0 and higher)● Mozilla Firefox (V1.5 and higher)● Opera (version 9.0 and higher)● Netscape Navigator (version 8.1 and higher)
Web-diagnostics
Entering the IP-address of the module
Select your
language
Select a menu point
Automatic update on/off(refresh time set in STEP7)
Web-diagnostics
Settings
CPU status
CPU status
Web-diagnostics
CPU-status
Details of an entry
Download as csv
Web-diagnostics
Diagnostic buffer
Remember, PNIO requires 100 Mbps, full duplex
Web-diagnostics
Communication parameters
possibleformats
Automatic updateOn/off
(frequency see HWconfig)
Web-diagnostics
Tag-status
Select table
Web-diagnostics
VAT-tables
Localization of cable breakages (copper)
Efficient error localization and removal through Web-Browser !
Web-diagnostics
POF/PCF Line diagnostics integrated on the Scalance X WEB-interface Long-term diagnostics pro port is also possible Port diagnostics & quality-status of the POF/PCF cable Detailed port diagnostics using LED’s, SNMP & PROFINET messages
Web-diagnostics
FO diagnostics
Diagnostics facilities for PROFINET
LEDs on the device/controller
Engineering Diagnostics
Diagnostics with additional user program
Other tools
Diagnostics with the Topology Editor
Integrated WEB Servers
PROFINET Topology editor
What is PROFINET Topology
Zoom in/out
Place boxes as desired
Possibility of a background
picture
Drag and drop,to create a link
PROFINET Topology editor
PROFINET Topology (Drawing)
PROFINET Topology editor
PROFINET Topology (Drawing)
Maintenance Damping reserve
PROFINET Topology editor
PROFINET Topology (Search & Find)
PROFINET Topology editor
PROFINET Topology (Online)
Cable disconnected
Save
PROFINET Topology editor
PROFINET Topology (Web)
Saved topology: A saved actual topology can be adopted as setpoint topology, makingit easier to diagnose changes in the actual topology.
ET200son Port 5
ET200s on Port5,as configured
ET200s on Port6,=>error
PROFINET Topology editor
PROFINET Topology (Web)
Overview of diagnostics facilities for PN
LEDs on the device/controller
Engineering Diagnostics
Diagnostics with additional user program
Other tools
Diagnostics with the Topology Editor
Integrated WEB Servers
Diagnostics in the user program: (OBs)
Organization blocks (OBs) form the interface between the operating system and the user program
CPU startupExample.: OB100 (warm restart), OB101 (restart), OB102
(cold restart) Cyclical or clocked
Example.: OB30-OB35 (timed interrupts), OB10-OB17 (time interrupts) When process interrupts occur
Example.: OB40-OB47 (process interrupts)
When faults occurOB82: channel diagnostic
OB83: insert/remove moduleOB85: program execution error
OB86: Rack fault, Station error
Organization blocks are executed in accordance with their configured priority
Reading out diagnostic interrupts from I/O modules or PN devices with SFB 54
Report System Error
Report System Error
Report System Error (Web)
Click and surf through the information
Here is the problem
Further information
LEDs on the device/controller
Engineering Diagnostics
Diagnostics in the user program:error OBs, SSLs
Other tools
Diagnostics with the Topology Editor
Integrated Web Servers
Networkmanagement Tools
Network monitoring 24x7 via Web-interface
Detailed diagnostics of PROFINET network incl. ring redundancy and even WLAN
Standard diagnostics of third-party devices
Automatic device detection and network topology
Personalized Web diagnostics
Standard network reports
Alarming
Integration HMI/SCADA
Simple operation
Wireshark
Wireshark is a freeware for recording data traffic Is able to record traffic between controller and device.