33
DER/Load behaviour during disturbances & dynamic model development NERC SPIDERWG October 2019 Jenny Riesz Principal, Operational Analysis & Engineering

DER/Load behaviour during disturbances & dynamic model

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

DER/Load behaviour during disturbances & dynamic model developmentNERC SPIDERWGOctober 2019

Jenny Riesz

Principal, Operational Analysis & Engineering

About AEMOAEMO operates Australia's National Electricity Market and power grid in Australia’s eastern and south-eastern seaboard, and the Wholesale Electricity Market and power grid in south-west WA.

Both markets supply more than 220 terawatt hours of electricity each year.

We also operate retail and wholesale gas markets across south-eastern Australia and Victoria’s gas pipeline grid.

Collectively NEM & WEM traded over A$20 billion in the last financial year.

Ownership

Marketparticipants

40%Governments of Australia

60%

2

Context

Rooftop PV

Minimum demand in South Australia:

3

DER generation could soon match entire demand in some regions.

• What will this mean for the power system?

• How do we affordably maintain security and reliability for customers throughout this transition?

• What actions do we need to take?

Technical challenges

This presentation will focus on:• DER behaviour during disturbances• Development of accurate dynamic

models

Many technical challenges have been identified and a program of work has been established

Outline DER & load behaviour• Bench testing• Interval data• Load tripping• High-speed measurements

Development of load/DER model• Load composition• Composite load model (CMPLD)• DER_A model

Next steps• Short/medium term

Bench testing

• Collaboration with UNSW to understand PV inverter behaviour• 18 inverters now tested (represents ~10% of NEM installed capacity)• Unexpected behaviours:

• Short duration voltage sags• Half the inverters tested curtail or disconnect (100ms, 0.78pu voltage sag)

• Voltage phase angle jump• RoCoF

• 1 single make of inverter disconnected at 1Hz/s• Equivalent to 240MW of installed capacity in the NEM

• Next steps• Testing more inverters• Incorporating findings into revisions to AS4777

2005 inverters

2015 inverters

Interval data• 30s/60s data for individual PV inverters• Provided by Solar Analytics as part of a collaboration

• Funded by Australian Renewable Energy Agency (ARENA)• Solar Analytics monitors individual PV systems and provides customers with analytics on system performance

• Example: NSW bushfires, 15/04/2018, 07:52-13:00, 13 incidents• 1725 PV systems in Solar Analytics sample, post cleaning

Presenter
Presentation Notes
On this day there were 13 faults were seen throughout a morning, all occurring in relatively close proximity. The graph shows the aggregated PV output based on the sample of systems in NSW that are monitored by solar analytics Initial inspection showed that PV systems exhibited responses to the faults (see highlighted green which show fault times) On this day it’s estimated PV generation ranged from 12% capacity factor -> 30% -> 36% with a relatively smooth profile, making this event a strong candidate for analysis.

0930 - 0943 hrs

0.90 p.u.

0.95 p.u.

0.93 p.u.

0.78 p.u.0.87 p.u.

0.59 p.u.0.71 p.u.

Frequency events• 10 frequency disturbances analysed, most mild.• No response from DER for ±0.5Hz• One severe frequency event observed:

• PV disconnections• Installed prior to Oct 2015: Consistent with expectations, confirms survey results• Installed post Oct 2016: 4-7% disconnected, inconsistent with AS4777.2:2015

• Frequency-Watt behaviour• AS4777.2:2015 requires droop response to over-frequency exceeding 50.25Hz• At least 15-30% of systems did not respond

• Need for improved auditing and encouragement of compliance with standards

AEMO (10 January 2019), “Final Report – Queensland and South Australia system separation on 25 August 2018 – An operating incident report for the National Electricity Market”. Available at: https://www.aemo.com.au/-/media/Files/Electricity/NEM/Market_Notices_and_Events/Power_System_Incident_Reports/2018/Qld---SA-Separation-25-August-2018-Incident-Report.pdf

AEMO (April 2016), “Response of Existing PV Inverters to Frequency Disturbances”. Available at: https://aemo.com.au/-/media/Files/PDF/Response-of-Existing-PV-Inverters-to-Frequency-Disturbances-V20 pdf

Calculate response in zones (distance from fault location)

Voltage events• Analysis of PV

disconnecting in daytime voltage disturbances 2016-2018 for which high speed data is available

• n=x indicates number of PV systems in sample

<50km

50-150km 150-250km

Load TrippingQuantify load tripping from 4s SCADA data

Energy Queensland dataset• High speed data provided from locations in the Queensland distribution

network (11kV)• 2016-2018• Locations:

• Brendale 11A – Primarily residential• Brendale 14B – Primarily small commercial/industrial• Currimundi – Primarily residential

Typical load response (BRD11A)

Some load loss for deeper faults

Load behaviour• All “normal” events

with distributed PV generation estimated <10%

Commercial shows

significantly more load loss

-3% for -0.35pu

-3% for -0.35pu-8% for -0.5pu

-15% for -0.35pu-35% for -0.5pu

Typical response with high DER operating (BRD11A)

Transient response (<1s)

“steady state” response (>1s)

Load + PV response combined

DER behaviour

• Estimated likely PV generation and underlying load for each event

• Estimated likely loss of load due to voltage dip (based upon trends from overnight data), to add to ΔP observed, and calculate likely change in PV generation.

• BRD11A consistent with disconnection findings from Solar Analytics datasets (<50km)

• May not be adequate data on deep faults at Currimundi for suitable comparison

10-15%For -0.3pu

30-40%For -0.14pu

Model development

• Need to incorporate behaviour into dynamic models (PSSE/PSCAD)

• CMPLD + DER_A• Assistance from PEACE

Consulting• Load model first

• Essential foundation for developing a DER model

1:TMotor A

ElectronicLoad

Static Load

Bss

Bf1 Bf2

Rfdr + j Xfdr

jXxf

DER

Motor B

Motor C

Motor D

Load composition

Motor A Motor B Motor C Motor D Power Elec Constant Current Constant ImpedanceQLD 12% 14% 10% 3% 27% 16% 18%NSW 12% 10% 9% 6% 24% 14% 25%VIC 12% 10% 6% 6% 26% 16% 24%SA 9% 13% 11% 5% 35% 7% 20%TAS 14% 12% 13% 3% 15% 27% 16%

Motor A Motor B Motor C Motor D Power Elec Constant Current Constant ImpedanceQLD 6% 12% 11% 3% 19% 19% 30%NSW 4% 8% 8% 6% 20% 17% 37%VIC 4% 8% 7% 6% 20% 20% 35%SA 5% 12% 11% 6% 26% 8% 32%TAS 8% 11% 11% 4% 15% 25% 26%

Summer evening peak:

Winter evening peak:

State-wide average values:References:

Playback of distribution events

• Selected events that are relatively balanced• Value in comparison against positive-sequence simulation tool

• Play the positive sequence component of recorded 3-phase voltage into CMLD, and compare measured and simulated P & Q

11 kV

Load Model(CMLD or AEMO’s original ZIP model)

Playback Voltage Source

Small Impedancej0.01 pu

Validation: Distribution events

BRD11A: Comparison of playback simulation using “residential” QLD CMLD composition numbers:

• CMLD is significantly better at replicating reactive power response

• Slightly better at replicating real power response

• Active power spike likely related to motor parameters

Tuning:Tripping Parameters

22

• 17 Events• PV generation <10%• Optimisation using an

open-source Sequential Quadratic Programming Solver

• Aim for best fit parameters across all events

• ZIP model doesn’t capture load tripping at all

BRD14B – 4 Jan 2018

Presenter
Presentation Notes
Some good examples, shows load tripping Reactive power is pretty good Active power spikes not so good Delay reset, can’t with CMPLD, updated in future

Validation: System-wide disturbances

15/10/2019 23

NSW 4th Feb 2019, Canberra – Upper Tumut 330kV

Voltage at Lower Tumut NSW Area Load

• CMPLD shows slower recovery, more similar to HSM• Load tripping represented accurately• Voltage overshoot in both models

Presenter
Presentation Notes
Event without load tripping Accurate voltage response of CMPLD Snap back of ZIP Limited by PMUs – Filtering, 20ms resolution, good for frequency, maybe not voltage

Validation: System-wide disturbances

15/10/2019Example footer text 24

SA 11th April 2018, Cherry – TIPS B – 275kV

Voltage at Para SA Area Load

• CMPLD shows slower recovery, more similar to HSM• Load tripping represented accurately• Voltage overshoot in both models

Presenter
Presentation Notes
Example of load tripping. More voltage overshoot than ZIP Still slower voltage recovery Voltage overshoot influenced by load trip, related to real/reactive power spikes of motor loads Great representation of load tripping, band is +- 20%

Validation: System-wide disturbances

15/10/2019 25

SA 17th April 2019, TIPS – Magill 275kV

Voltage at TIPS A 275kV SA Area Load

• CMPLD shows slower recovery, more similar to HSM• Load tripping represented more accurately• Voltage overshoot in both models

Presenter
Presentation Notes
Example where we didn’t exactly hit load tripping Still better than ZIP Underestimate vs overestimate Voltage overshoot similar for both ZIP and CMPLD

Summary of Results

15/10/2019 26

Event Voltage Recovery speed Load Loss Voltage Overshoot

ZIP CMPLD ZIP CMPLD Observed ZIP CMPLD

NSW 4th February 2019 Faster Faster Accurate Accurate 0MW High Moderate

VIC 8th March 2018 Faster Slower None 23% of Observed 276 MW Moderate Moderate

VIC 9th December 2018 Faster Slower Accurate Accurate 0MW Moderate High

SA 11th April 2018 Faster Faster None Accurate 117 MW Moderate High

VIC 15th February 2019 Faster Faster Accurate Accurate 0MW High Moderate

NSW 15th August 2019 Faster Slower Accurate Accurate 0MW Moderate Moderate

SA 17th April 2019 Faster Faster None 59% of Observed 118 MW Moderate High

VIC 18th February 2019 Faster Slower None Accurate 69 MW High High

Presenter
Presentation Notes
Voltage overshoot is poor for both models Not much/no improvement with CMPLD Better motor parameters would probably improve this

HSM Load Monitors

15/10/2019 27

9th Dec 2018, Hazelwood – Rowville 220kV

Templestowe 66kV

Voltage

Active Power

Reactive Power

Active/Reactive power spikes also

visible in HSM data

Presenter
Presentation Notes
HSM Load monitors in Rowville Real Reactive power spikes. Much larger for CMPLD than ZIP This is based on load fraction estimated from james G./ Dist companies, probably not so accurate, not worth tuning off?

DER_A model

DER_A model testing

Motor load composition reduced, majority of load moved to electronic load

DER_A model testing

Trip levels for power electronic load and trip time for first trip setting of DER_A adjusted.

DER_A adjustments (UNSW)• DER_A can’t capture some

important behaviours observed

• Introduce aggregate partial frequency tripping model

• Survey of 2005 tripping frequencies/pick-up times

• Introduce RoCoF tripping• Incorporate proportion of

2015/2015 standards in the model

• Voltage phase angle jump response?

Next Steps

• Load tripping analysis, assessment of operational implications of DER tripping• DER_A model – refine parameters, incorporate new features• Operationalise the model• Load composition

• Motor D composition (motor drive small air conditioning)• Commercial load composition• Update of Residential Baseline Study• Large Industrial Loads

• Improve high resolution monitoring systems (more load data)• Dx parameters• Solar Analytics ARENA collaboration

DERWorkstream

Networkincentives

Datavisibility

System & Marketframework

Technical standards& connections

Operationalprocess

Industry-widecollaboration

Workstreamobjectives

Networkregulation &pricing facilitate DER andbetter customer serviceofferings.

Visibility of DER foroperational, forecasting,planning, and market(incl settlement) functions.

A consistent access regime for all market participants within the confines of customer consent and privacy.

Integrate DER into energy,ancillary and reserve markets.

Market arrangements recognise non-retailer models, including third-party/aggregator concepts.

Evolve market arrangement to a distributed market model.

Where appropriate,a nationally consistentapproach to DERconnections anddevelop DERtechnical standards.

To better understandoperational challenges and DER capabilities to inform operationalprocesses and tools.

Enablers Pilot programs

Cyber security

Digital & Technology Strategies

Integrating DER to maximise consumer value

Industry working together to deliver outcomes for consumers

33