Design of Residential Building

Embed Size (px)

DESCRIPTION

design of slab, beam and column is given in this design. for more design go on sitewww.hammadjatt.weebly.com

Citation preview

Page 1: Design of Residential Building

DESIGN OF SIMPLE RESIDENTIAL BUILDING SLAB, BEAM, COLUMN ♀♀♀♀

2016

HAMMAD BASHIR BSC CIVIL ENGINEER

Page 2: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Page 3: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

DESIGN OF RESIDENTIAL BUILDING

EXAMPLE:

DESIGN TYPICAL HOUSE WITH TWO ROOMS AND VERANDAH….

Solution:

In this house, we will Design

1. two-way slab

2. one-way slab, Beam and column

DESIGN

1) SLAB

2) BEAM

3) COLUMN

Page 4: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

SLAB:

THICKNESS: According to ACI 318 the minimum thickness of slab should be 5 inch.

Load calculation:

Service dead loads:

Material THICKNESS (INCH)

THICKNESS (FEET)

DENSITY LOAD CALCULATION KSF

SLAB 5” 5”/12 0.15 0.0625 MUD 4” 4”/12 0.12 0.04 TILE 2” 2”/12 0.12 0.02

TOTAL DEAD LOADS= 0.1225 KSF

Page 5: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

FACTORED DEAD LOAD 1.2 0.1225 0.147 Ksf

Service dead loads: FOR RESIDENTIAL BUILDING LIVE LOAD WILL BE ACCORDING TO LOADING

CRITERIA……

Sr.no

Occupancy or use

Live load

Kgs/m2 Pascal N/m2

lb/ft2

1 Private rooms, school class rooms.

200 1900 40

2 Offices. 250 to 425 2400 to 4000

50 to 85

3 Fixed-seats, assembly halls, library reading rooms.

300 2900 60

4 Corridors in public building 400 3800 80 5 Movable seats assembly hall 500 4800 100 6 Wholesales stores, light storage

warehouses. 610 6000 125

7 Library stack rooms 730 7200 150 8 Heavy manufacturing, heavy storage

warehouses, side walks and driveways subject to truckling

1200 12000 250

9 Stairs, general 500 4800 100 10 Stairs, upto two-family residences,

50% more than specifications. 300 2900 60

WE USE 40 Psf = 0.040 Ksf

FACTORED LIVE LOAD 1.6 0.04 0.064 Ksf

TOTAL FACTORED LOAD= FACTORED LIVE LOAD + FACTORED DEAD LOAD

= 0.1225 + 0.064 = 0.211 Ksf

Page 6: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

BENDING MOMENT CALCULATION

ASPECT RATIO:

m= la/lb

la= shorter length…. lb= longer length

BENDING MOMENT Co-efficients

Page 7: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Page 8: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

TWO WAY SLAB DESIGN…..

m = la/lb = 12/16 = 0.75

Ca,neg = 0.076 Cb,neg = 0.024

Ca,pos DL = 0.043 Cb,pos DL = 0.013

Ca,pos LL = 0.052 Cb,pos LL = 0.016

Calculating moments using ACI Coefficients:

Ma, neg = Ca, neg wula2

Mb, neg = Cb, neg wulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll

= Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll

= Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

2

a,neg = 2.31 ft-kip

b,neg = 1.29 ft-kip

a,pos = 1.39 ft-kip

b,pos = 0.76 ft-kip

Page 9: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Design of Two-Way Slab

First determining capacity of min. reinforcement:

As,min = 0.002bhf = 0.12 in2

Using #3 bars: Spacing for As,min = 0.12 in2 = (0.11/0.12) × 12 = 11″ c/c

However ACI max spacing for two way slab = 2h = 2(5) = 10″ or 18″ = 10″ c/c

Hence using #3 bars @ 10″ c/c

For #3 bars @ 10″ c/c: As,min = (0.11/10) × 12 = 0.132 in2

Capacity for As,min: a = (0.132 × 40)/(0.85 × 3 × 12) = 0.17″

ΦMn = ΦAsminfy(d – a/2) = 0.9 × 0.132 × 40(4 – (0.17/2)) = 18.60 in-kip

Therefore, for Mu values ≤ 18.60 in-k/ft,

use As,min (#3 @ 10″ c/c) & for Mu values > 18.6 in-kip/ft, calculate steel area using trial & error

procedure.

For Ma,neg = 2.31 ft-kip = 27.71 in-kip > 18.60 in-kip: As = 0.20 in2 (#3 @ 6.6″ c/c)

Using #3 @ 6″ c/c

For Mb,neg = 1.29 ft-kip = 15.56 in-kip < 18.60 in-kip: Using #3 @ 10 “c/c

For Ma,pos = 1.39 ft-kip = 16.67 in-kip < 18.60 in-kip: Using #3 @ 10” c/c

For Mb,pos = 0.76 ft-kip = 9.02 in-kip < 18.60 in-kip: Using #3 @ 10″ c/c

Page 10: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Design of One-Way Slab

Main Reinforcement:

Mver (+ve) = 14.73 in-kip

As,min = 0.002bhf = 0.002(12)(5) = 0.12 in2

Using #3 bars, spacing = (0.11/0.12) × 12 = 11″ c/c

For one-way slabs, max spacing by ACI = 3h = 3(5) = 15″ or 18″ = 15″ c/c

For #3 bars @ 15″ c/c,

As = (0.11/15) × 12 = 0.09 in2.

Hence using As,min = 0.12 in2

a = (0.12 × 40)/(0.85 × 3 × 12) = 0.16″

ΦMn = ΦAsminfy(d – a/2)

= 0.9 × 0.12 × 40(4 – (0.16/2)) = 16.94 in-kip > Mver (+ve)

Therefore, using #3 @ 11″ c/c

However, for facilitating field work, we will use #3 @ 10″ c/c

Shrinkage Reinforcement:

Ast = 0.002bhf = 0.12 in2 (#3 @ 11″ c/c)

However, for facilitating field work, we will use #3 @ 10″ c/c

Page 11: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Verandah Beam Design

Step 01: Sizes

Let depth of beam = 18″

ln + depth of beam = 15.875′ + (18/12) = 17.375′

c/c distance between beam supports

= 16.375 + (4.5/12) = 16.75′

Therefore l = 16.75′

Depth (h) = (16.75/18.5) × (0.4 + 40000/100000) × 12

= 8.69″ (Minimum requirement of ACI 9.5.2.2).

Take h = 1.5′ = 18″

d = h – 3 = 15″

b = 12″

Page 12: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Step 02: Loads

Load on beam will be equal to

Factored load on beam from slab + factored self weight of beam web

Factored load on slab = 0. 211 ksf

Load on beam from slab = 0. 211 ksf x 5 = 1.055 k/ft

Factored Self load of beam web =

= 1.2 x (13 × 12/144) × 0.15 = 0.195 k/ft

Total load on beam = 1.055 + 0.195

= 1.25 kip/ft

Page 13: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

BENDING MOMENT COEFFIENTS

Page 14: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Page 15: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

COLUMN DESIGN

Sizes:

Column size = 12″ × 12″

Loads:

Pu = 11.41 × 2 = 22.82 kip

Page 16: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Main Reinforcement Design:

Nominal strength (ΦPn) of axially loaded column is:

ΦPn = 0.80Φ {0.85fc′ (Ag – Ast) + Astfy} {for tied column, ACI 10.3.6}

Let Ast = 1% of Ag (Ast is the main steel reinforcement area)

ΦPn = 0.80 × 0.65 × {0.85 × 3 × (144 – 0.01 × 144) + 0.01 × 144 × 40}

= 218.98 kip > Pu = 22.82 kip, O.K.

Ast =0.01 × 144 =1.44 in2

Using 3/4″ Φ (#6) with bar area Ab = 0.44 in2

No. of bars = 1.44/0.44 = 3.27 ≈ 4 bars

Use 4 #6 bars (or 8 #4 bars) and #3 ties @ 9″ c/c

Page 17: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

DRAFTING DETAILS

FRONT VIEW

Page 18: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

3D VIEW

SLAB DRAFTING DETAILS

Page 19: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

SLAB DRAFTING DETAILS

Page 20: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

Page 21: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

BEAM DETAILS

Page 22: Design of Residential Building

HAMMAD BASHIR GONDAL (JUTT) (B.SC CIVIL ENGINEER) +923430817733

http://hammadjatt.weebly.com/ OR www.hammadjatt.weebly.com or www.hammadjutt.weebly.com

COLUMN DESIGN DETAIL

Reference

I. Design of concrete structure by NIlson

II. Notes of PROF. ZIAAUDDIN MIAN UET LAHORE PAKISTAN