We are pleased to highlight some of the USP of DETECTOMAT Fire Alarm System as such,

√ DETECTOMAT, Germany is one of the most qualified manufacturer for a complete Fire Detection and Alarm System which has built over 600,000 industrial detectors, installed at many countries as because sensor alarming system and the fire-fighting system is “more sensitive, more accurate and more intelligent." √ The DETECTOMAT detectors are famous for their robust engineering design, stylish look and daily prove their quality and efficiency. It has highly touted VdS mark – and complies EN 54 Standard & LPCB approved.

√ Intelligent Detectors – Detectors with inbuilt - microprocessor √ DETECTOMAT Addressable Fire Alarm System has the capacity for 126 devices per loop with an overall loop length of 3,500 meters. √ DETECTOMAT Network devices can configure networks with up to 20 control panels. √ DETECTOMAT Detectors have Integrated T-branch and short circuit isolator √ DETECTOMAT Conventional Fire Alarm System has the capacity for 25- 30 devices per zone. √ Redundant host processor , Redundant loop card , Redundant Power Supply √ Detectors with Ambient Temperature of 60 Deg. C √ German is world known for its meteorology. √ We can provide After Sales Support as having trained man power for the Installation, Testing, Commissioning & Programming, as training is provided by DETECTOMAT. √ In house Product demonstration & training center for Programming and Installation, After sales service support. √ Product protocol matches to APOLLO protocol

Page 5: Detect Om At
Page 6: Detect Om At

DETECTOMAT Fire Alarm System & Equipments are Approved By - BHEL, NTPC- ANTA, RRVUNL, MAHAGENCO, Reliance, ADANI,

KPCL, ABB, VA Tech, DCPL, Desein, Fichtner , GSPL , NTPC- KAWAS

DETECTOMAT FIRE ALARM SYSTEM INSTALLATIONS IN INDIA

INDUSRIAL & POWER PLANT PROJECTS

• AREVA T&D LTD. - Kotambi, Baroda.

• AREVA RRVPNL- Indiranagar substation. • NTPC-Anta, Rajasthan.

• MAHAGENCO’s 1x 250 MW Paras TPS ( Unit 2)

• RRVUNL’s 1x250 MW Suratgarh Super Thermal power

Project • ADANI Power LTD - 4 x 330 MW Mundra, TPS.

• KPTCL’s 2 x 115 MW Varahi Hydroelectic Power Project

• Tata Nano Project-Sanand , Gujarat through ABB-Baroda

• MAHAGENCO’s 1X500 MW Khaperkheda TPS through BGR

-Chennai

• HI-TECH SILONG-Meghalaya State Electricity Board

Page 7: Detect Om At

COMMERCIAL PROJECT

• Reliance Industries Ltd.

Reliance PCS Center Naroda,Ahmedabad &

Reliance PCS Center Gurgoan , Delhi. • GSPL – Paguthan Terminal – Bharuch

• K. RAHEJA – Aquiline Properties – IT SEZ at KOBA , near

Gandhinagar

• NTPC-KAWAS

EXPORT PROJECTS

• Addressable Fire Alarm system for Anjelique Internation – Delhi for their Anjelique Internation – Zambia office.

• Conventional Fire Alarm system for Areva T & D – Noida for their client Kenya Electricity Board – Kenya

Page 8: Detect Om At

editing status: 2009-07-16

Properties:

� In accordance to EN 61000 - 6 - 3 class B for emissions, so suitable for the use in sensitive areas.

� Programming options for different alarm modes.

� Event log memory of up to 500 messages.

� Programming of control logics and time dependent functions for the components of series Loop 3000.

� Customized customer texts allowing up to a maximum of 20 characters.

� Simple menu structure in accordance to EN 54 - 2 A1 2006.

� Software controlled disablements for zones and individual detectors via external inputs.

� Connections for a fire brigade interface for controlling the panels outputs, key deposit and transmission units.

Product-Information Sheet

Type detect 3004plus

M GB Order No. 32551

Description:

Microprocessor controlled modular fire control panel

for the use with the Loop 3000 fire detection system

components. Approved according to EN 54 - 2 A1

2006, EN 54 - 4 A1 2002, A2 2006 and VdS for the

use according to VdE 0833.

Fire control panel detect 3004plus

, deep housing, language kit English

� Large LCD, 160 x 80 with backlight.

� Integrated display and control panel according to DIN EN 54 - 2 A1 2006.

126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.

� Option for 2 conventional interface cards for controlling up to 16 conventional zones.

� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to

EN 12094.

� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of

� Integrated interface connection for up to 63 additional network components.

� Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS.

� Incl. English language kit for control and programming.

� Different access levels with password protection.

� Integrated "one-man-revision mode" with clear protocols and a revision counter.

� Visual diagnostics and remote-control operations via the visualization software "Visual detect".

� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.

� Integrated RS 232 - interface for the dpt software and the connection of printers and other

peripheral equipment.

� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.

� Monitored power supply unit and battery charging according to EN 54-4 A1 2002 and A2 2006

via the MC 3004 monitoring card.

� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.

� 3 potential free relais for fire and fault.

� 3 inputs for collective signals.

� Ability to change and edit inspection and reaction times along with all delays.

� Emergency power supply via 2 batteries 12 V / up to 26 Ah.

� Integrated ground fault monitoring.

� Segmented front door allowing the quick assembly of LED indicator modules and printers.

� Option for customised front logos.

� Possibility for complete system redundancy with the CPU and loop interfaces.

� Up to 128 programmable detector zones.

� Up to 42 T-branches per loop possible.

� Integrated alarm buffer and 2 detector / zone dependencies.

� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.

Page 9: Detect Om At

Supply voltage

Emergency supply

Quiescent current

Alarm current

Inputs

Ambient temperature

Humidity

Protection class

Colour

Material

Dimensions (H x W x D)

Weight

VdS approval

System approval

CPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

3 inputs for collective signal

S 295054

1 x 24 V / 400 mA monitored for sounding/signalling devices

up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each

3 relais outputs 250 V / 5 A for alarm and fault

8 open collector outputs 30 V DC / 90 mA

- Subject to alterations and errors -

490 mm x 420 mm x 210 mm

230 V AC (-15%/+10%)

Technical data

LC-Display 160 x 80 points, backlight

20 LED-displays for status signal Display

400 mA

2 x 12 V / 26 Ah

250 mA

24 V DC / 72 W / 3,5 A

1 output 24 V DC / 800 mA for external devices Power supply

RS 232

Bitbus (RS 485 based)Interfaces

Outputs

-5°C bis +40°C

5 - 95 % (non-condensing)

IP 30

EN 54-2:1997 A1:2006

EN 54-4:1997 A1:2002 A2:2006Standards

light grey, RAL 7035

sheet steel

12,5 kg, without batteries

EN 12094 for 1 area extinguishing systems

international approvals on request Further approvals

Scope of delivery without loop cards, network interfaces and batteries utilization of

integrated standard extinguishing interface requires 1 optional LED indicator

module in the front to ensure the indication according to EN 54 - 2.

G 203068

General remarks

0786-CPD-20817

Page 10: Detect Om At

editing status: 2009-07-16

Properties:

� Ability to change and edit inspection and reaction times along with all delays.

� Emergency power supply via 2 batteries 12 V / up to 12 Ah.

� Integrated ground fault monitoring.

� Segmented front door allowing the quick assembly of LED indicator modules and printers.

� Option for customised front logos.

� Possibility for complete system redundancy with the CPU and loop interfaces.

� Up to 128 programmable detector zones.

� Up to 42 T-branches per loop possible.

� Integrated alarm buffer and 2 detector / zone dependencies.

� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.

via the MC 3004 monitoring card.

� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.

� 3 potential free relais for fire and fault.

� 3 inputs for collective signals.

� Integrated RS 232 - interface for the dpt software and the connection of printers and other

peripheral equipment.

� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.

� Monitored power supply unit and battery charging according to EN 54-4 A1 2002 and A2 2006

� Different access levels with password protection.

� Integrated "one-man-revision mode" with clear protocols and a revision counter.

� Visual diagnostics and remote-control operations via the visualization software "Visual detect".

� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.

� Integrated display and control panel according to DIN EN 54 - 2 A1 2006.

126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.

� Option for 2 conventional interface cards for controlling up to 16 conventional zones.

� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to

EN 12094.

� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of

� Integrated interface connection for up to 63 additional network components.

� Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS.

� incl. English language kit for control and programming.

� Connections for a fire brigade interface for controlling the panels outputs, key deposit and transmission units

Product-Information Sheet

Type detect 3004plus

S GB Order No. 32553

Description:

Microprocessor controlled modular fire control panel

for the use with the Loop 3000 fire detection system

components. Approved according to EN 54 - 2 A1

2006, EN 54 - 4 A1 2002, A2 2006 and VdS for the

use according to VdE 0833.

Fire control panel detect 3004plus

, shallow housing, language kit English

� Large LCD, 160 x 80 with backlight.

� In accordance to EN 61000 - 6 - 3 class B for emissions, so suitable for the use in sensitive areas.

� Programming options for different alarm modes.

� Event log memory of up to 500 messages.

� Programming of control logics and time dependent functions for the components of series Loop 3000.

� Customized customer texts allowing up to a maximum of 20 characters.

� Simple menu structure in accordance to EN 54 - 2 A1 2006.

� Software controlled disablements for zones and individual detectors via external inputs.

Page 11: Detect Om At

Supply voltage

Emergency supply

Quiescent current

Alarm current

Inputs

Ambient temperature

Humidity

Protection class

Colour

Material

Dimensions (H x W x D)

Weight

VdS approval

System approval

CPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

EN 12094 for 1 area extinguishing systems

international approvals on request Further approvals

Scope of delivery without loop cards, network interfaces and batteries utilization of

integrated standard extinguishing interface requires 1 optional LED indicator

module in the front to ensure the indication according to EN 54 - 2.

G 203068

0786-CPD-20817

General remarks

EN 54-2:1997 A1:2006

EN 54-4:1997 A1:2002 A2:2006Standards

light grey, RAL 7035

sheet steel

12,5 kg, without batteries

Outputs

-5°C bis +40°C

5 - 95 % (non-condensing)

IP 30

24 V DC / 72 W / 3,5 A

1 output 24 V DC / 800 mA for external devices Power supply

RS 232

Bitbus (RS 485 based)Interfaces

LC-Display 160 x 80 points

backlight

20 LED-displays for status signal

Display

400 mA

2 x 12 V / 12 Ah

250 mA

230 V AC (-15%/+10%)

Technical data

- Subject to alterations and errors -

490 mm x 420 mm x 150 mm

3 inputs for collective signal

S 295054

1 x 24 V /400 mA monitored for sounding/signalling devices

up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each

3 relais outputs 250 V / 5 A for alarm and fault

8 open collector outputs 30 V DC / 90 mA

Page 12: Detect Om At

editing status: 2009-12-15

Properties:

� Possibility for complete system redundancy with the CPU and loop interfaces.

� Up to 128 programmable detector zones.

� Up to 42 T-branches per loop possible.

� Integrated alarm buffer and 2 detector / zone dependencies.

� Emergency power supply via 2 batteries 12 V / up to 26 Ah.

� Integrated ground fault monitoring.

� Segmented front door allowing the quick assembly of LED indicator modules and printers.

� Option for customised front logos.

� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.

� 3 potential free relais for fire and fault.

� 3 inputs for collective signals.

� Integrated RS 232 - interface for the dpt software and the connection of printers and other

peripheral equipment.

� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.

� Different access levels with password protection.

� Visual diagnostics and remote-control operations via the visualization software "Visual detect".

� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.

� Integrated display and control panel according to DIN EN 54

126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.

� Option for 2 conventional interface cards for controlling up to 16 conventional zones.

� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to

EN 12094.

� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of

� Integrated interface slot for the connection for up to 63 additional network components.

� Option for control of extinguishing systems via the standard extinguishing interface in accordance to VdS.

� Incl. English language kit for control and programming.

� Connection option for a fire brigade interface for controlling the panels outputs, key deposit; transmission units.

Product-Information Sheet

Type detect 3004 M GB Order No. 32421

Description:

Microprocessor controlled modular fire control panel

for the use with the Loop 3000 fire detection system

components. Approved according to EN 54 and VdS

for the use according to VdE 0833.

Fire control panel detect 3004, deep housing, language kit English

� 4 alphanumeric lines LC-displaywith backlight

� Programming options for different alarm modes.

� Event log memory of up to 500 messages.

� Programming of control logics and time dependent functions for the components of series Loop 3000.

� Customized customer texts allowing up to a maximum of 20 characters.

� Software controlled disablements for zones and individual detectors via external inputs.

� Ability to change and edit inspection and reaction times along with all delays.

� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.

Page 13: Detect Om At

Supply voltage

Emergency supply

Quiescent current

Alarm current

Inputs

Ambient temperature

Humidity

Protection class

Colour

Material

Dimensions (H x W x D)

Weight

VdS approval

System approval

CPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

EN 12094 for 1 area extinguishing systems

international approvals on request Further approvals

Scope of delivery without loop cards, network interfaces and batteries

G 203068

General remarks

0786-CPD-20817

S 295054

EN 54-2:1997

EN 54-4:1997 Standards

light grey, RAL 7035

sheet steel

12,5 kg, without batteries

Outputs

-5°C bis +40°C

5 - 95 % (non-condensing)

IP 30

3 inputs for collective signal

1 x 24 V / 400 mA monitored for sounding/signalling devices

up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each

3 relais outputs 250 V / 5 A for alarm and fault

8 open collector outputs 30 V DC / 90 mA

24 V DC / 72 W / 3,5 A

1 output 24 V DC / 800 mA for external devices Power supply

RS 232

RS485 and Bitbus as option for networkInterfaces

4 alphanueric lined LC-Display

Backlight 7 20 LED Displays for status signal Display

146 mA

2 x 12 V / 26 Ah

86 mA

230 V AC (-15%/+10%)

Technical data

- Subject to alterations and errors -

490 mm x 420 mm x 210 mm

Page 14: Detect Om At

editing status: 2009-12-15

Properties:

� Programming options for different alarm modes.

� Event log memory of up to 500 messages.

� Programming of control logics and time dependent functions for the components of series Loop 3000.

� Customized customer texts allowing up to a maximum of 20 characters.

� Software controlled disablements for zones and individual detectors via external inputs.

� Connection option for a fire brigade interface for controlling the panels outputs, key deposit, transmission units.

Product-Information Sheet

Type detect 3004 S GB Order No. 32424

Description:

Microprocessor controlled modular fire control panel

for the use with the Loop 3000 fire detection system

components. Approved according to EN 54 and VdS

for the use according to VdE 0833.

Fire control panel detect 3004, shallow housing, language kit English

� 4 alphanumeric lines LC-display with backlight

� Integrated display and control panel according to DIN EN 54

126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.

� Option for 2 conventional interface cards for controlling up to 16 conventional zones.

� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to

EN 12094.

� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of

� Integrated interface slot for the connection for up to 63 additional network components.

� Option for control of extinguishing systems via the standard extinguishing interface in accordance to VdS.

� Incl. English language kit for control and programming.

� Different access levels with password protection.

� Visual diagnostics and remote-control operations via the visualization software "Visual detect".

� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.

� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.

� 3 potential free relais for fire and fault.

� 3 inputs for collective signals.

� Integrated RS 232 - interface for the dpt software and the connection of printers and other

peripheral equipment.

� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.

� Ability to change and edit inspection and reaction times along with all delays.

� Emergency power supply via 2 batteries 12 V / up to 12 Ah.

� Integrated ground fault monitoring.

� Segmented front door allowing the quick assembly of LED indicator modules and printers.

� Option for customised front logos.

� Possibility for complete system redundancy with the CPU and loop interfaces.

� Up to 128 programmable detector zones.

� Up to 42 T-branches per loop possible.

� Integrated alarm buffer and 2 detector / zone dependencies.

� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.

Page 15: Detect Om At

Supply voltage

Emergency supply

Quiescent current

Alarm current

Inputs

Ambient temperature

Humidity

Protection class

Colour

Material

Dimensions (H x W x D)

Weight

VdS approval

System approval

CPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

- Subject to alterations and errors -

490 mm x 420 mm x 150 mm

230 V AC (-15%/+10%)

Technical data

4 alphanumeric lined LC-Display

Backlight / 20 LED-displays for status signal Display

146 mA

2 x 12 V / 12 Ah

86 mA

24 V DC / 72 W / 3,5 A

1 output 24 V DC / 800 mA for external devices Power supply

RS 232

RS485 and Bitbus as option for networkInterfaces

Outputs

-5°C bis +40°C

5 - 95 % (non-condensing)

IP 30

3 inputs for collective signal

1 x 24 V / 400 mA monitored for sounding/signalling devices

up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each

3 relais outputs 250 V / 5 A for alarm and fault

8 open collector outputs 30 V DC / 90 mA

EN 54-2:1997

EN 54-4:1997 Standards

light grey, RAL 7035

sheet steel

12,5 kg, without batteries

EN 12094 for 1 area extinguishing systems

international approvals on request Further approvals

Scope of delivery without loop cards, network interfaces and batteries

G 203068

General remarks

0786-CPD-20817

S 295054

Page 16: Detect Om At

editing status 20.01.2010

Properties:

� Integrated display and control panel according to DIN EN 54

� Programming options for different alarm modes

� Integrated interface slot for the connection for up to 63 additional network components

� Connection option for a fire brigade interface for controlling the panels outputs, key deposit and

transmission units

� Integrated RS 232 - interface for the DPT programming software and the connection of printers and

other peripheral equipment

� Option for 8 conventional interface cards for controlling up to 64 conventional zones

Product-Information Sheet

Order No. 32422 - Type detect 3016 XL GB

Description:

Microprocessor controlled modular fire control panel for

the use with the Loop 3000 fire detection system

components approved according to EN 54 and VdS for

the use according to VdE 0833

Fire control panel detect 3016, wall mounted housing, language kit English

� 4 alphanumeric lines LC-display with backlight

� Software controlled disablements for zones and individual detectors via external inputs

� Ability to change and edit inspection and reaction times along with all delays.

� Basic version with 5 slots for 2 redundant loop-interfaces for the connection of up to 10 loops with a

maximum of 126 loop 3000 devices per loop and a maximum loop lenght of 3500m

� Option for up to 11 slots for extension boards and the connection of up to 16 loops with 126 loop 3000

devices per loop

� Extinguishing interface option for controlling extinguishing and gas suppression systems for 6

extinguishing areas in accordance to EN12094

� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes

� Customized customer texts allowing up to a maximum of 20 characters

� 1 external output 24 V / 400 mA monitored for sounding/signalling devices

� 3 potential free relais for fire and fault

� 3 inputs for collective signals

� Programming of control logics and time dependent functions for the components of series Loop 3000

� Integrated power supply 192 W according to EN 54 with 2 outputs for external devices rated

at 24V DC/ 800mA

� Emergency power supply via 2 batteries 12V / up to 45 Ah

� Segmented front door allowing the quick assembly of LED indicator Modules and printers.

� Option for customised front logos

� Possibility for complete system redundancy with redundant CPU and redundant loop interfaces

� Up to 196 programmable detector zones

� Additional up to 42 T-branches per loop possible

� Event log memory of up to 500 messages

� Integrated alarm buffer and 2 detector / zone dependencies

� Different access levels with password protection

� Visual diagnostics and remote-control operations via the visualization software "Visual detect"

� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.

� incl. English language kit for control and programming

Page 17: Detect Om At

Supply voltage

Emergency supply

Quiescent current

Alarm current

Inputs

Ambient temperature

Humidity

Protection class

Colour

Material

Dimensions (H x W x D)

Weight

VdS approval

System approval

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

General remarks

- Subject to alterations and errors -

Sheet steel

750 mm x 600 mm x 240 mm

13,5 kg, without batteries

Scope of delivery without loop cards, network interfaces and batteries

Ground fault montoring via module EM (Art.Nb. 30927)

Utilization of integrated standard extinguishing interface requires 1 optional LED

indicator module in the front to ensure the indication according

to EN 54 - 2

Technical data

230 V AC (-15%/+10%)

2 x 12 V / 45 Ah

ca. 190 mA

ca. 250 mA

G 203067

S295054

4 alphanumeric lines LC-display

Backlight

20 LED - displays for status signal

Display

3 inputs for collective signal

- 5°C up to + 40°C

1 x 24 V /400 mA monitored for sounding/signalling devices

up to 16 loops 140 mA / 3500 m for up to 126 Loop 3000 elements each

3 relais outputs 250 V / 5 A for alarm and fault

8 open collector outputs 30 V DC / 90 mA

24 V DC / 192 W / 8 A

1 output 24 V DC / 800 mA for external devicesPower supply

2 x RS 232

RS485 and Bitbus as option for networkInterfaces

Outputs

EN 54-2: 1997

EN 54-4: 1997Standards

EN 12094

EN 12094 for 1 area extinguishing systems Further approvals

IP 30

Light grey, RAL 7035

5 - 95 % (non-condensing)

Page 18: Detect Om At

editing status: 2009-08-26

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensitivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

ABS, metal mesh

42 mm x 95 mm

DIN EN 54–7

max. 93 % (+/-2%)

IP 40

15 to 30 V loop powered

silver

- Subject to alterations and errors -

5 mA

5 levels adjustable

� Detector sensitivities automatically calibrated and freely programmable.

� Periodic sensor test.

� Automatic and manual addressing on the loop 3000.

� Integrated isolator and T-branch option.

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

<20 m/s

� Disable and enable modes with individually adjustable sensitivities.

� Alarm output for the triggering of a LED indicators.

� Functions completely integrated via loop 3000 protocol.

Product-Information Sheet

Order No. 30488 - Type PL 3301 silver

Description:

Optical smoke detector for loop 3000 with 2 optical

and 1 thermal sensor for earliest fire detection and

indication and with bidirectional isolator according to

DIN EN 54-7.

Silver mesh design.

Optical smoke detector, with isolator, mesh design, silver

� Exact pollution recognition by an additional independent measuring chamber.

� Storage of last maintenance date.

max. 10 mA for LED-indicator or piezo buzzer

-10°C to +60°C

280 µA

Technical data

� Self learning modes for the ambient conditions.

� Display of the temperature environments of the fire detection system by a second temperature measurement.

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

G 205046

S 295054 and S 208123

on request

0786-CPD-20037

Page 19: Detect Om At

Date: 03.08.2010 TINr.: 0016

Description;

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg

Product information

Brief description :

Design changes to the PL 3300/3200 O outer casing, reduced 6mm in height

- Subject to change (without notice); -

The Standard design of proven PL - series was in the wake of mechanical revision to be adapted to better

accommodate today’s market. With the 6mm reduction in height, we and users alike are able to optimise the

detectors handling and storage.These advantages apply to internal production and testing along with the installation

and commissioning by the end user. The original modern design has not been affected and only a slight change is

noticeable. The following detector types are to be modified:

Part No. Description

30011 PL 3300 O

32248 PL 3300 O

30009 PL 3200 O

32519 PL 3200 O

The changes made to the outer casing, in no way effect the operation of the detector or the detector base.

The design changes have been approved by the VdS and the respective approvals for this detector series have been

amended.

All dust covers for this detector range have also been changed to fit this new design.

These changes will come into effect during the middle of August 2010.

Questions or queries

We will be happy to answer any questions you my have regarding this or any other detectomat products.

1: New PL 3300/3200 O with detector base

2 : New PL 3300/3200 O without detector base

Page 20: Detect Om At

editing status: 2009-08-25

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensitivity

Ambient Temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

� Disable and enable modes with individually adjustable sensitivities.

� Storage of last maintenance date.

� Self learning modes for the ambient conditions.

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

� Automatic and manual addressing on the loop 3000.

� Periodic sensor test.

� Alarm output for the triggering of a LED indicators.

� Functions completely integrated via loop 3000 protocol.

Product-Information Sheet

Order No. 30007 - Type PL 3200 OT

Description:

Optical and thermal multi sensor detector

for loop 3000 with 2 optical and 2 thermal

sensors for earliest fire detection and

indication in all environments with difficult

ambient conditions according to DIN EN

54-5/7 and CEA 4021.

Multi sensor detector optical - heat, without isolator

� Highest reliability by intelligent combination of thermal and optical sensor signals with via

algorithms.

< 20m/s

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

Technical data

280 µA

� Integrated temperature measurement as differential procedure and maximum value

in accordance to EN 54-5 1A.

� Exact pollution recognition by an additional independent measuring chamber.

� Detector sensitivities automatically calibrated and freely programmable.

5 mA

max. 10 mA for LED-indicator or piezo buzzer

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

5 levels adjustable

IP 40

white (similar to RAL 9003)

ABS

52 mm x 100 mm

LPCB, BOSEC, PT (GOST), UNIVERZA V LJUBLJANI, EMI, Bahrain

0786-CPD-20197

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

G 205052

15 to 30 V DC loop powered

DIN EN 54–7, EN 54-5, CEA 4021

S 295054 and S 208123

Page 21: Detect Om At

editing status: 2009-10-05

Properties:

Operation voltageQuiescent currentAlarm currentOC-outputsSensitivityAmbient temperatureHumidityAir speedProtection classColour housingMaterialDimensions (H x Ø)StandardsVdS approvalSystem approvalFurther approvalsCPD-Number

detectomat GmbHAn der Strusbek 5D-22926 Ahrensburg / Germany

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

[email protected] www.detectomat.com

on request0786-CPD-20043

15 to 30 V DC loop powered

G 203038S 295054 and S 208123

Automatic and manual addressing on the loop 3000. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date.

Delivery including protective cover for installation phase.

Product-Information Sheet

Order No. 30008 - Type PL 3200 T

Description:Heat detector with fixed and rate of rise temperature settings for loop 3000 with 1 thermal sensor for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-5.

Heat detector with fixed and rate of rise temperature settings, without isolator

Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A.

< 20m/s

Technical data

280 μA

Periodic sensor test. Detector sensitivities automatically calibrated and freely programmable.

5 mAmax. 10 mA for LED-indicator or piezo buzzer

Display of the temperature environments of the fire detection system by a second temperature measurement.

Multicolour-LED for alarm- (red) and fault (yellow).

- Subject to alterations and errors -

-10°C to +60°Cmax. 93 % (+/-2%)

5 levels adjustable

IP 40white (similar to RAL 9003)ABS52 mm x 100 mmDIN EN 54-5

Page 22: Detect Om At

Stand: 2009-10-05

Properties:

measurement.

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions ( H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD-Number

detectomat GmbH

An der Strusbek 5

D-22926 Ahrensburg / Germany

15 to 30 V DC loop powered

IP 40

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

5 levels adjustable

white (similar to RAL 9003)

ABS

� Exact pollution recognition by an additional independent measuring chamber.

< 20m/s

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

Technical data

280 µA

� Detector sensitivities automatically calibrated and freely programmable.

5 mA

max. 10 mA for LED-indicator or piezo buzzer

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

Product-Information Sheet

Order No. 30009 - Type PL 3200 O

Description:

Optical smoke detector for loop 3000 with

2 optical and 1 thermal sensor for earliest

fire detection and indication according to

DIN EN 54-7.

Optical smoke detector, without isolator

� Automatic and manual addressing on the loop 3000.

� Periodic sensor test.

� Alarm output for the triggering of LED indicators.

� Functions completely integrated via loop 3000 protocol.

� Disable and enable modes with individually adjustable sensitivities.

� Storage of last maintenance date.

� Self learning modes for the ambient conditions.

� Display of the temperature environments of the fire detection system by a second temperature

on request

0786-CPD-20677

44 mm x 100 mm

DIN EN 54–7

G 202003

S 295054 and S 208123

Tel. +49(0)4102/2114-60

Tel. +49(0)4102/2114-670

[email protected]

www.detectomat.com

Page 23: Detect Om At

Stand: 2009-08-25

Properties:

Operation voltage Quiescent currentAlarm current OC-outputs Sensivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x Ø)Standards VdS approval System approval Further approvalsCPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany

52 mm x 100 mm DIN EN 54-5G 203037

Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol.

IP 40

Multicolour-LED for alarm- (red) and fault (yellow).

Storage of last maintenance date.

Automatic and manual addressing on the loop 3000. Periodic sensor test.

Product-Information Sheet

Order No. 30010 - Type PL 3300 T

Description:Heat detector with fixed and rate of rise temperature settings for loop 3000 with 1 thermal sensor for earliest fire detection and indication in all environments with difficult ambient conditions and with bidirectional isolator according to DIN EN 54-5.

Heat detector with fixed and rate of rise temperature settings, with isolator

Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A.

< 20m/s

Technical data

280 μA

Detector sensitivities automatically calibrated and freely programmable.

5 mAmax. 10 mA for LED-indicator or piezo buzzer

Disable and enable modes with individually adjustable sensitivities.

15 to 30 V DC loop powered

Display of the temperature environments of the fire detection system by a second temperature measurement.

Delivery including protective cover for installation phase.

- Subject to alterations and errors -

-10°C to +60°Cmax. 93 % (+/-2%)

5 levels adjustable

white (similar to RAL 9003)

S 295054 and S 208123on request0786-CPD-20044

ABS

Page 24: Detect Om At

Stand: 2009-08-25

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD-Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

15 to 30 V DC loop powered

G 202002

� Disable and enable modes with individually adjustable sensitivities.

� Storage of last maintenance date.

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

IP 40

Product-Information Sheet

Order No. 30011 - Type PL 3300 O

Description:

Optical smoke detector for loop 3000 with

2 optical and 1 thermal sensor for earliest

fire detection and indication and with

bidirectional isolator according to DIN EN

54-7.

Optical smoke detector, with isolator

� Automatic and manual addressing on the loop 3000.

� Periodic sensor test.

� Integrated isolator and T-branch option.

0786-CPD-20679

ABS

� Functions completely integrated via loop 3000 protocol.

� Alarm output for the triggering of a LED indicators.

44 mm x 100 mm

DIN EN 54-7

� Delivery including protective cover for installation phase.

� Exact pollution recognition by an additional independent measuring chamber.

< 20m/s

Technical data

280 µA

� Detector sensitivities automatically calibrated and freely programmable.

5 mA

max. 10 mA for LED-indicator or piezo buzzer

� Multicolour-LED for alarm- (red) and fault (yellow).

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

� Self learning modes for the ambient conditions.

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

5 levels adjustable

white (similar to RAL 9003)

S 295054 and S 208123

on request

Page 25: Detect Om At

Stand: 2009-10-05

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD-Number

detectomat GmbH

An der Strusbek 5

D-22926 Ahrensburg / Germany

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

5 levels adjustable

white (similar to RAL 9003)

S 295054 ans S 208123

on request

0786-CPD-20198

ABS

� Highest reliability by intelligent combination of thermal and optical sensor signals with via

algorithms.

< 20m/s

Technical data

280 µA

� Exact pollution recognition by an additional independent measuring chamber.

5 mA

max. 10 mA for LED-indicator or piezo buzzer

� Disable and enable modes with individually adjustable sensitivities.

� Delivery including protective cover for installation phase.

15 to 30 V DC loop powered

Product-Information Sheet

Order No. 30021 - Type PL 3300 OT

Description:

Optical and thermal multi sensor detector

for loop 3000 with 2 optical and 2 thermal

sensors and bidirectional isolator for

earliest fire detection and indication in all

environments with difficult ambient

conditions according to DIN EN 54-5/7 and

CEA 4021.

Multi sensor detector optical - heat, with isolator

� Self lerning modes for the ambient conditions.

� Multicolour-LED for alarm- (red) and fault (yellow).

� Detector sensitivities automatically calibrated and freely programmable.

� Integrated temperature measurement as rate of rise procedure and

maximum value in accordance to EN54-5 1A.

� Fault monitoring of the measurement chamber signal and loop 3000-electonics.

� Automatic and manual addressing on the loop 3000.

� Periodic sensor test.

52 mm x 100 mm

DIN EN 54–7, EN 54-5, CEA 4021

G 205051

� Integrated Isolator and T-branch option.

� Alarm output for the triggering of LED indicators.

� Functions completely integrated via loop 3000 protocol.

IP 40

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

� Storage of last maintenance date.

Tel. +49(0)4102/2114-60

Tel. +49(0)4102/2114-670

[email protected]

www.detectomat.com

Page 26: Detect Om At

Stand: 2009-08-25

Properties:

CO-Sensor lifetime

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensitivity

Ambient temperature

Humidity

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD - Number

General remarks

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

� Alarm evaluation with professional CO-sensor technology.

CO - Alarm at 30 ppm, heat accord. to EN 54 - 5 1A

� Automatic and manual addressing on the loop 3000.

� Periodic sensor test.

� Integrated isolator and T-branch option.

� Functions completely integrated via loop 3000 protocol.

� Alarm output for the triggering of a LED indicators.

� Disable and enable modes with individually adjustable sensitivities.

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

Product-Information Sheet

Order No. 30079 - Type PL 3300 COBT

Description:

Intelligent multi sensor detector for the loop

3000 series featuring sensor technology for

carbon monoxide detection in combination

with two thermal detectors and an

integrated isolator for all environments with

difficult ambient conditions, in accordance

to EN 54-5/7.

For the earliest detection of smouldering

fires of all kinds including electrical. The PL

3300 COBT continously monitors the

temperature and the CO-concentration.

Multisensor carbon monoxide gas and heat, with isolator

max. 10 mA for LED-indicator or piezo buzzer

� Integrated acoustic indication for CO-pre alarm and CO-alarm.

� Highest reliability by intelligent combination of thermal and CO sensor via algorithm.

� Integrated temperature measurement as differential procedure and maximum value in

accordance to EN 54-5 1A.

5 mA

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

5 years

Technical data

15 to 30 V DC loop powered

� Measurement of carbon monoxid with 2 alarm thresholds:

Prealarm: 15 ppm in 15 min.

Alarm: 30 ppm in 60 min.

600 µA

G 207005

S 295054 and S 208123

ABS

IP 40

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

The Carbon Monoxide detector requires calibrating once a year to ensure the

high detection levels is maintained.

white (similar to RAL 9003)

Bulgaria

0786-CPD-20582

52 mm x 100 mm

DIN EN 54-5

Page 27: Detect Om At

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VDS-Approval

System approval

Further approvals

CPD-Number

Technical data

44 mm x 100 mm

IP 40

15 to 30 V DC loop powered

< 20m/s

max. 10 mA for LED-indicator or piezo buzzer

5 mA

280 µA

-10°C to +60°C

max. 93 % (+/-2%)

5 levels adjustable

white (similar to RAL 9003)

S 295054 and S 208123

DIN EN 54–7

G 202107

on request

0786-CPD-20036

ABS

Page 28: Detect Om At

Stand: 2009-08-27

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensitivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD - Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

max. 10 mA for LED-indicator or piezo buzzer

silver

on request

0786-CPD-20041

47 mm x 110 mm

DIN EN 54-7

� Exact pollution recognition by an additional independent measuring chamber.

IP 40

Technical data

15 to 30 V DC loop powered

� Detector sensitivities automatically calibrated and freely programmable.

280 µA

5 mA

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

Product-Information Sheet

Order No. 30568 - Type PL 3305 O silver

Description:

Optical smoke detector for loop 3000 with

2 optical and 1 thermal sensor for earliest

fire detection and indication and with

bidirectional isolator according to DIN EN

54-7.

Round glass design, silver colour.

Optical smoke detector, with isolator, round glass-design, silver

G 204089

S 295054 and S 208123

� Disable and enable modes with individually adjustable sensitivities.

� Storage of last maintenance date.

� Self learning modes for the ambient conditions.

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

<20 m/s

� Periodic sensor test.

Glass, ABS

5 levels adjustable

� Automatic and manual addressing on the loop 3000.

� Integrated isolator and T-branch option.

� Functions completely integrated via loop 3000 protocol.

� Alarm output for the triggering of a LED indicators.

Page 29: Detect Om At

Stand: 2009-08-27

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensitivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD - Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

max. 10 mA for LED-indicator or piezo buzzer

white (similar to RAL 9003)

on request

0786-CPD-20037

42 mm x 95 mm

DIN EN 54-7

� Exact pollution recognition by an additional independent measuring chamber.

IP 40

Technical data

15 to 30 V DC loop powered

� Detector sensitivities automatically calibrated and freely programmable.

280 µA

5 mA

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

Product-Information Sheet

Order No. 30956 - Type PL 3301 O white

Description:

Optical smoke detector for loop 3000 with

2 optical and 1 thermal sensor for earliest

fire detection and indication and with

bidirectional isolator according to DIN EN

54-7.

White mesh design.

Optical smoke detector, with isolator, mesh design, white

G 205046

S 295054 and S 208123

� Disable and enable modes with individually adjustable sensitivities.

� Storage of last maintenance date.

� Self learning modes for the ambient conditions.

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

<20 m/s

� Periodic sensor test.

ABS, metal mesh

5 levels adjustable

� Automatic and manual addressing on the loop 3000.

� Integrated isolator and T-branch option.

� Functions completely integrated via loop 3000 protocol.

� Alarm output for the triggering of a LED indicators.

Page 30: Detect Om At

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

further apporvals

CPD-number

Sensivity

detectomat GmbH [email protected]

An der Strusbek 5 www.detectomat.com

D-22926 Ahrensburg / Germany

G 208095

on request

52 mm x 100 mm

< 20m/sIP 40white (similar to RAL 9003)ABS

� Functions completely integrated via loop 3000 protocol

5 levels adjustble -10°C to +60°Cmax. 93% (+/-2%)

0786-CPD-20580

Tel. +49(0)4102/2114-670

� Integrated temperature measurement as rate of rise procedure and max. value in accordance to EN54-5 1A

250 µA5mAmax. 10 mA for LED-indicator or piezo buzzer

� Detector sensitivities automatically calibrated and freely programmable � Fault monitoring of the measurement chamber signal and loop 3000-electronics

� Integrated Isolator and T-branch option � Alarm output for the triggering of LED indicators

Product-Information Sheet

Order No. 32149 - Typ PL 3300 OTi Fusion

Description:

Intelligent optical and thermal multi sensor detector for loop 3000 with 2

optical and 2 thermal sensors and a bidirectional Isolator for earliest fire

detection and indication in all enviroments with difficult ambient conditions,

according to EN 54-5/7 and CEA 4021. Fusion®-Technology for the

detection of the smallest smoke particles and fires in the early stage by

using the wavelengthsof the wide-band white light spectrum.

Multi sensor optical - heat - intelligent Fusion

editing status: 2009-10-05

� Integrated measurement-System and algorithm for condensation recognition (Humitec®)

� Automatic and manual adressing on the loop 3000

- Subject to alterations and errors -

DIN 54-7, EN 54-5, CEA 4021

S 295054 and S 208123

� Intelligent analysis and disruption mode für the elimination of false alarm (e.g. cigarette smoke)

� Exact pollution recognition by an additional independent measuring chamber � Highest reliability by intelligent combination of thermal and optical sensor signals via algorithms

� Periodic sensor test

Tel. +49(0)4102/2114-60

� Disable and enable modes with individually adjustable sensitivities � Storage of last maintenance date � Self learning modes for the ambient conditions � Display of the temperature envirements of the fire detection system by a second temperature measurement � Multicolour-LED for alarm- (red) and fault (yellow) � Delivery including protective cover for installation phase

15 to 30 V DC loop powered Technical data

Page 31: Detect Om At

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensitivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material ABS

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD-Number

Sensitivity

detectomat GmbH [email protected]

An der Strusbek 5 www.detectomat.comD-22926 Ahrensburg / Germany

� Functions completely integrated via loop 3000 protocol.

� Disable and enable modes with individually adjustable sensitivities.

� Storage of last maintenance date.

� Self learning modes for the ambient conditions.

� Periodic sensor test.

� Automatic and manual adressing on the loop 3000.

� Integrated isolator and T-branch option.

� Alarm output for the triggering of LED indicators.

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2 %)

max. 10 mA for LED-indicator or piezzo buzzer5 levels adjustable

on request0786-CPD-20578

IP 40

white (similar to RAL 9003)

Tel. +49(0)4102/2114-60

� Exact pollution recognition by an additional independent measuring chamber.

� Integrated temperature measurement as rate of rise procedure and maximum value in

accordance to EN 54-5 1A.

� Detector sensitivities automatically calibrated and freely programmable.

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

� Highest reliability by intelligent combination of thermal and optical sensor signals with via

algorithms.

Product-Information Sheet

Order No. 32150 - Type PL 3300 OTi

Description:

Intelligent optical and thermal multi sensor detector for loop 3000

with 2 optical and 2 thermal sensors and a bidirectional isolator for

earliest fire detection and indication in all environments with difficult

ambient conditions, according to EN 54-5/7.

Multi sensor detector optical - heat - intelligent

� Integrated measurement-system and algorithm for condensation recognition (Humitec®).

� Intelligent analysis and disruption mode for the elimination of false alarms (e.g. cigarette smoke).

Stand: 2009-10-05

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

<20 m/s

250 µA

5 mA

Technical data

15 to 30 V DC loop powered

Tel. +49(0)4102/2114-670

S 295054 and S 208123

52 mm x 100 mm)

DIN EN 54-7, EN 54-5, CEA 4021

G 208096

Page 32: Detect Om At

Stand: 2009-08-26

Properties:

Operation voltage

Quiescent current

Alarm current

OC-outputs

Sensitivity

Ambient temperature

Humidity

Air speed

Protection class

Colour housing

Material

Dimensions (H x Ø)

Standards

VdS approval

System approval

Further approvals

CPD - Number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

� Periodic sensor test.

ABS, metal mesh

5 levels adjustable

� Automatic and manual addressing on the loop 3000.

� Integrated isolator and T-branch option.

� Functions completely integrated via loop 3000 protocol.

� Alarm output for the triggering of a LED indicators.

G 205046

S 295054 and S 208123

� Disable and enable modes with individually adjustable sensitivities.

� Storage of last maintenance date.

� Self learning modes for the ambient conditions.

� Display of the temperature environments of the fire detection system by a second temperature

measurement.

<20 m/s

Product-Information Sheet

Order No. 30525 - Type PL 3301 O black

Description:

Optical smoke detector for loop 3000 with

2 optical and 1 thermal sensor for earliest

fire detection and indication and with

bidirectional isolator according to DIN EN

54-7.

Optical smoke detector, with isolator, mesh design, black

� Exact pollution recognition by an additional independent measuring chamber.

IP 40

Technical data

15 to 30 V DC loop powered

� Detector sensitivities automatically calibrated and freely programmable.

280 µA

5 mA

� Multicolour-LED for alarm- (red) and fault (yellow).

� Delivery including protective cover for installation phase.

� Fault monitoring of the measurement chamber signal and loop 3000-electronics.

- Subject to alterations and errors -

-10°C to +60°C

max. 93 % (+/-2%)

max. 10 mA for LED-indicator or piezo buzzer

black

on request

0786-CPD-20037

42 mm x 95 mm

DIN EN 54-7

Page 33: Detect Om At

editing status 13.04.2010

Properties:

Supply voltage Power supplyEmergency supplyQuiescent current Alarm current Short circuitConventional line broken wire/ fault

Ambient temperature Humidity Stock temperature Protection class Colour MaterialDimensions (H x W x D) Weight

Further approvals

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany

Standards

21 LEDs for status display, thereof 11 LEDs masked6 keys for operation2 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC /3A for alarm and fault

2 to 10 mA 10 to 110 mA ≥110 mA0 to 2 mA

-20°C to +60°C

Grey (similar to RAL 7035)

-5°C to +40°C

ABS

2,30 kg, without batteryEN 54-2:1997/A1:2006EN 54-4:1997/A2:2006

Connection possibility for 2 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone

230 V AC ±10 %24 V DC/300 mA1 x 12 V/7 Ah

2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 7 Ah

Product-Information Sheet

Order No. 32638 - Type DCC 2

Description:Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1 2006 and EN 54-4:1997/A2:2006.

Fire Control Panel, 2 Zones, Conventional, English

Clear display and easy operation with LED displays and operation keys

Integrated "one-man-revision mode"

- Subject to alterations and errors -

0 - 95 % (non condensing)

IP 30

Integrated power supply accord. to EN 54-4:1997/A2:2006 with 1 output for external devices rated at 24V DC 2 monitored outputs with 300 mA each for signalling devices

288 mm x 340 mm x 98 mm

Independent connection of detector and signalling device zones

1293-CPD-0132

2 access levels via key switch

Display

Outputs

Manual control of signalling devices via seperate input Internal selftest for 8 potential faults Incl. programming option, e.g. alarm delay, fast modus

Technical data

Page 34: Detect Om At

editing status 13.04.2010

Properties:

Supply voltage Power supplyEmergency supplyQuiescent current Alarm current Short circuitConventional line broken wire/ fault

Ambient temperature Humidity Stock temperature Protection class Colour MaterialDimensions (H x W x D) Weight

Further approvals

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany

2 access levels via key switch

Display

Outputs

Manual control of signalling devices via seperate input Internal selftest for 8 potential faults

Technical data

Clear display and easy operation with LED displays and operation keys

Integrated "one-man-revision mode"

- Subject to alterations and errors -

0 - 95% (non condensing)

IP 30

Integrated power supply accord. to EN 54-4:1997/A2:2006 with 1 output for external devices rated at 24 V DC 2 monitored outputs with 300 mA each for signalling devices

288 mm x 340 mm x 98 mm

Independent connection of detector and signalling device zones

1293-CPD-0132

Product-Information Sheet

Order No. 32639 - Type DCC 4

Description:Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1:2006 and EN 54-4:1997/A2:2006.

Fire Control Panel, 4 Zones, Conventional, English

ABS

2,30 kg, without batteryEN 54-2:1997/A1:2006EN 54-4:1997/A2:2006

Connection possibility for 4 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone

230 V AC ±10 %24 V DC/300 mA1 x 12 V/7 Ah

2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 7 Ah

Standards

25 LEDs for status display, thereof 11 LEDs masked6 keys for operation2 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC /3A for alarm and fault

2 to 10 mA 10 to 110 mA ≥110 mA0 to 2 mA

-20°C to +60°C

Grey (similar to RAL 7035)

-5°C to +40°C

Page 35: Detect Om At

editing status 28.04.2010

Properties:

Supply voltage Power supplyEmergency supplyQuiescent current / ZoneAlarm current / Zone Short circuitConventional line broken wire/ fault

Ambient temperature Humidity Stock temperature Protection class Colour MaterialDimensions (H x W x D) Weight

Further approvals

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany

Standards

16 LED-displays for status display (+ 8 LEDs in case of extension)6 keys for operation and programming4 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC/3A for alarm and fault

2 to 10 mA 10 to 110 mA ≥110 mA0 to 2 mA

-20°C to +60°C

Grey (similar to RAL 7035)

-5°C to +40°C

Connection possibility for 8 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone

230 V AC ±10 %24 V DC/1 A1 x 12 V/18 Ah

2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 18 Ah

32654 - 4 alarm zones extension Type SE 4 32655 - Relay-module, 8 Relays 1 A/12 V Type RM 8

Technical data

1293-CPD-0133

ABS

4,26 kg, without batteryEN 54-2:1997/A1:2006EN 54-4:1997/A2:2006

Product-Information Sheet

Order No. 32640 - Type DCC 8 plus

Description:Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1:2006 and EN 54-4:1997/A2:2006.

Fire Control Panel, 8 - 16 Zones, Conventional, English

Clear display and easy operation with LED displays and operation keys

Integrated "one-man-revision mode"

- Subject to alterations and errors -

0 - 93% (non condensing)

IP 30

Extension option via 4 zone modules for up to 16 conventional zones for CT 3000 fire detection components Integrated power supply accord. to EN 54-4:1997/A2:2006 4 monitored outputs with 300 mA each for signalling devices

Outer dimensions 345 mm x 455 mm x 128 mm

Independent connection of detector and signalling device zones

Display

Outputs

Manual control of signalling devices via seperate input Internal selftest for 8 potential faults Incl. programming option, e.g. alarm delay, fast modus Panel network of max. two fire control panels

Accessories: 32653 - 4 zone extension module Type GE 4

Page 36: Detect Om At

www.detectomat.com

39

8. Conventional System

Multisensor detector optical/thermal CT 3000 OTNo. 30022

Conventional multisensor detector optical/thermal according to EN 54-7:

• intelligent analysis of the thermal sensor• intelligent analysis of the measuring chamber signal

Technical data

operating voltage 9 up to 33 V DCquiescent current 100 µAalarm current 20 mAopen collector output 15 mA for LED indicatorssensitivity < 0,15 dB/m 60°C rate of riseoperation temperature -10°C up to +60°Chumidity max. 95 %/RH/40°Cprotection class IP 30colour housing whitematerial ABSEN 54-7approvals further on request

Heat detector CT 3000 TNo. 30014

Conventional heat detector according to EN 54-7:

• highly functional detection-system• intelligent analysis of the thermal sensor

Technical data

operating voltage 9 up to 33 V DCquiescent current 80 µAalarm current 20 mAopen collector output 15 mA for LED indicatorssensitivity 60°C rate of riseoperation temperature -10°C up to +60°Chumidity max. 95 %/RH/40°Cprotection class IP 30colour housing whitematerial ABSEN 54-7approvals further on request

Detector base standard SDB 3000 whiteNo. 30301

Standard base for all conventional:

• including LED indicator connection• space for additional modules

Technical data

operation temperature -10°C up to +60°Cmaterial ABScolour whitedimensions (H x ø) 20 mm x 95 mm

Page 37: Detect Om At

www.detectomat.com

38

8. Conventional System

Fire control panel FCP 6No. 30941

Fire control panel FCP 4No. 32143

Conventional fire control panel with (FCP 4) 4 detector zones:

• 2 monitored outputs for signalling devices (300 mA)• 1 programmable output for telephone operators• 4 quiescent current monitored detector zones• max. 30 automatic detectors each zone• 4 relay outputs for alarm and fault• space for battery (1 x 12 V/7 Ah)

Conventional fire control panel with 4 or 6 detector zones:

• 2 monitored outputs for signalling devices (250 mA)• max. 30 automatic detectors each zone• 6 quiescent current monitored detector zones• 6 relay outputs for alarm and fault• space for battery (1 x 12 V/7 Ah)

Technical data

system voltage 220 up to 240 V ACoperating voltage 24 V DCquiescent current 190 mAalarm current 160 mAfrequency 50/60 Hzemergency power 12 V/7 Ahoperation temperature 0°C up to +60°Coutput relay 1 relay per zonesounder output 2 x 24 V/300 mA monitoreddisplay LCD displayhumidity max. 95 %protection class IP 20colour housing greymaterial ABS

EN:FCP 54-2, 54-4

dimensions (H x D x W) 240 mm x 325 mm x 80 mmweight 2 kg without battery

Optical smoke detector CT 3000 O VdS G203036No. 30015

Conventional optical smoke detector according to EN 54-7:

• highly functional detection-system• intelligent analysis of the measuring chamber signal

Technical data

operating voltage 9 up to 33 V DCquiescent current 40 mAalarm current 20 mAopen collector output 15 mA for LED indicatorssensitivity < 0,15 dB/moperation temperature -10°C up to +60°Chumidity max. 95 %/RH/40°Cprotection class IP 30colour housing whitematerial ABSDIN EN 54-7dimensions (H x Ø ) 44 mm x 100 mmapprovals further on request

Page 38: Detect Om At

editing status: 2009-08-27

Properties:

Colour housing

Material

Dimensions (H x Ø)

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

white (similar RAL 9003)

Technical data

- Subject to alterations and errors -

21 mm x 95 mm

ABS

� Integrated connectors for LED indicator (Art. 31193) or piezo buzzer (Art. 32091).

� Space for additional connectors Type WAGO 243.

� Mounting space for the piezo buzzer (Art 32091) and the detector labelling clip (Art 30479).

� Including transparent seal cover to protect the base against contaminents.

� Integrated connectors for the connection of one spur for the loop extension (T-branch).

Product-Information Sheet

Order No.32242 Type SDB 3000

Description:

Detector Base for all detectors of series CT and loop

3000.

Detector standard base, white

Page 39: Detect Om At

editing status 20.01.2010

Properties:

Operation voltage

Current consumption

Input

Ambient temperature

Humidity

Weight

Protection class

Colour housing

Material

Dimensions (H x W x D)

Standards

VdS approval

System approval

CPD - number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

Approx.20g

Technical data

Low active monitored

-10°C to +60°C

max. 93% (+/-2%)

� Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel

� Completely encapsulated module for the integration in special applications with control by the loop 3000

- Subject to alterations and errors -

Blue

27 mm x 73 mm x 15 mm

� Programming of different switching variants of input and output also with time control

� Monitoring of the operating status via Loop 3000

� Independent programming of Input and Output

S 295054 and S 208123

� Functions completely integrated via loop 3000 protocol

Product-Information Sheet

Order No. 31640 - Type OMS 3301 mini

Description:

Intelligent Input- / Output module mini for the Loop 3000

for the control of external optical and acoustic signalling

devices with bidirectional isolator for the integration in

externally connected modules according to DIN EN 54-

18 including one monitored fault input and one open

collector output for signalling devices

Input- / Output module, single I/O, signalling devices,with isolator

ABS

DIN EN 54-18, 17

IP 30

G 206047

0786-CPD-20530

� Connecting module with one freely programmable fault input and one output for the connection of

signalling devices

15 to 30 V DC loop powered

380 µA

1 Open Collector 500 mA

1 10 mAparallelfor LED-status indicationOutput

� Automatic and manual addressing on the loop 3000

� Integrated Isolator

Page 40: Detect Om At

editing status 20.01.2010

Properties:

Operation voltage

Quiescent current

Alarm current

Output

Input

Ambient temperature

Humidity

Weight

Protection class

Colour housing

Material

Dimensions (H x W x D)

Standards

VdS approval

System approval

CPD - number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

-10°C to +60°C

460 µA

460 µA, 5 mA if alarm-LED is active

Relay 1 change over contact 30 V DC/ 1A

Low active monitored

Accessories:

� Possibility for monitoring of the output with UBW 3311 (Order No. 32073)

15 to 30 V DC loop powered

Technical data

- Subject to alterations and errors -

ABS

DIN EN 54-18, 17

� Programming of different switching variants of input and output also with time control

� Independent programming of Input and Output

� Automatic and manual addressing on the loop 3000

� Integrated Isolator and T-branch option

� Monitoring of the operating status via Loop 3000

0786 - CPD-20459

� Aestethical robust wall mounted housing according with IP 54

� Functions completely integrated via loop 3000 protocol

� Multicolour-LED for alarm (red) and fault (yelow)

Product-Information Sheet

Order No. 30200 - Type IOM 3311

Description:

Intelligent Input- / Output Module for the Loop 3000 with

bidirectional isolator according to DIN EN 54-18 with one

monitored input and one potentialfree relay output

Input- / Output module, single I/O, Relay, with Isolator

� Connecting module with one freely programmable Input and one freely programmable output

G 205029

grey (similar to RAL 7035)

S 295054 and S 208123

max. 93% (+/-2%)

Approx. 185 g

IP 54

93 mm x 93 mm x 55 mm

Page 41: Detect Om At

editing status 16.12.2009

Properties:

Quiescent current

Alarm current

Input

Ambient temperature

Humidity

Weight

Portection class

Colour housing

Material

Dimensions (H x W x D)

Standards

VdS approval

System approval

CPD-Nummer

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

max. 93% (+/-2%)

Approx. 190g

IP 54

� Voltage selection for the detector zone supply via "jumper" on the module board

- Subject to alterations and errors -

grey (similarto RAL 7035)

93 mm x 93 mm x 55 mm

� Possibility for parametrization of short-circuit, wire break, prealarm and alarm thresholds

� Automatic and manual adressing on the loop 3000

� Integrated Isolator and T-branch option

S 295054 and S 208123

� Aesthetical robust wall mounted housing according with IP 54

Technical data

Product-Information Sheet

Order No. 30205 - Type TCM 3300

Description:

Intelligent Input module for the connection of one

conventional detector zone to the loop 3000 with

vidirectional isolator according to DIN EN 54-18 and for

the connection of conventional detectors with 12V or 24V

technology

Input module, 1 conventional zone,with Isolator

-10°C to +60°C

� Functions completely integrated via loop 3000 protocol

� Multicolour-LED for alarm (red) and fault (yellow)

ABS

DIN EN 54-18, 17

G 206048

0786-CPD-20373

� External supply of conventional detector zones for the flexible use of different current consumptions

and operation voltages

560 µA

560 µA ; 5 mA if alarm-LED is active

1 monitored detector zone with up to 65 mA

15 to 30 V DC loop powered

External supply output 12V or 24V DCOperation voltage

Page 42: Detect Om At

editing status 20.01.2010

Properties:

Operation voltage

Current consumption

Input

Output

Ambient temperature

Humidity

Weight

Protection class

Colour housing

Material

Dimensions (H x W x D)

Standards

VdS approval

System approval

CPD - number

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

Low active monitored

-10°C to 60°C

� Aestethical robust wall mounted housing according with IP 54

General remarks

� The fault input can be used for the monitoring module UBW 3311

Accessories:

� Possibility for monitoring of the output with UBW 3311 (Art.Nb. 32073)

� Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel

� Programming of different switching variants ofa input and output also with time control

- Subject to alterations and errors -

93 mm x 93 mm x 55 mm

G 205030

� Monitoring of the operating status via Loop 3000

� Independent programming of Input and Output

� Automatic and manual addressing on the loop 3000

� Multicolour-LED for alarm (red) and fault (yellow)

Product-Information Sheet

Order No. 30211 - Type OMS 3301

Description:

Intelligent Input- / Output module for the Loop 3000 for

the control of external optical and acoustic signalling

devices with bidirectional isolator according to DIN EN

54-18 including one monitored fault input and one

potentialfree relay output for signalling devices

Input- / Output module, single I/O, signalling devices, with isolator

DIN EN 54-18, 17

S 295054 and S 208123

ABS

07786-CPD-20460

� Connecting module with one freely programmable fault input and one output for the connection of

signalling devices

15 to 30 V DC loop powered

460 µA

Relay 1 change over contact 30 V DC / 1A

� Integrated Isolator and T-branch option

� Functions completely integrated via loop 3000 protocol

Technical data

max. 93% (+/-2%)

Approx. 190 g

IP 54

Grey (similar to RAL 7035)

Page 43: Detect Om At

editing status 14.12.2009

Properties:

Operation voltage

Quiescent current

Alarm Current

Input

Ambient temperature

Humidity

Weight

Protecting class

Colour Housing

Material

Dimensions (H x W x D)

Standards

VdS approval

System approval

CPD-Nummer

detectomat GmbH [email protected] Tel. +49(0)4102/2114-60

An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670

D-22926 Ahrensburg / Germany

DIN EN 54-1, 18

380 µA

G 206047

076-CPD-20530

max. 93% (+/-2%)

� Functions completely integrated via loop 3000 protocol

Product-Information Sheet

Order No. 30513 - Type AMD 3311

Description:

Intelligent Input- / Output module mini for the Loop 3000

with bidirectional isolator for the integration in special

detectors and externally connected modules according

to DIN EN 54-18 including one monitored input and one

open collector output

Input- / Output module, single I/O, Open Collector with Isolator

� Connecting module with one freely programmable Input and one freely programmable output

- Subject to alterations and errors -

Blue

� Additional parallel alarm output (blinking) for the control of a status indicator (without series resistor)

� Monitoring of the operating status via Loop 3000

� Independent programming of Input and Output

� Automatic and manual addressing on the loop 3000

� Programming of different switching variants of input and output also with time control

S 295054 and S 208123

� Completely encapsulated module for the integration in special applications with control by the loop 3000

� Integrated Isolator

15 to 30 V DC loop powered

Technical data

380 µA ; 5 mA if alarm-LED is active

27 mm x 73 mm x 15 mm

low active monitored

-10°C to +60°C

ABS

Approx. 20g

IP 30

Output 1 Open Collector 500 mA

1 10 mA parallel for LED-Status indication