DGs Set Tech Ani Cal Part 1

Embed Size (px)

Citation preview

Technical Part Part-1Design, Supply, testing, commissioning and guarantee of Silent type 500 kVA / 400 kW (Prime rating), 3 phase, 415 volt, 50 Hz Diesel Generator sets-4 nos.(complete with radiator, acoustic enclosure, anti-vibration mount/pad, Electronic governing system, electronic control panel, AMF control panel, with all necessary piping, power & control cable etc.)

Page 1 of 32

SPECIFICATION OF 500 kVA /400 kW DIESEL ENGINE SETS WITH ALL REQUIRED ACCESSORIES

INDEXSr. No. 01 02 03 04 05 06 07 08 09 10 Scope General Requirements for Technical Qualification Codes & standards Technical Requirements for Performance of work Training Technical Specifications Tests and inspection Engineering, Manufacturing & Maintenance facility Drawing & Data sheets Technical Data to be filled by Tenderer 29-31 of 31 26-27 of 31 28 of 31 Description Page No. 3-4 of 31 4 of 31 5 o 31 6-24 of 31 25 of 31

Page 2 of 32

1.0 SCOPE:The scope of this specification is to define the requirements of supply, installation, testing, commissioning and guarantee for intended operation of 500 kVA (Prime rating) Diesel Generator Sets with radiator, acoustic enclosure, anti-vibration mounts, diesel tanks, AMF control panel, all required accessories and its hook up with existing system in place of 310 kVA DG sets at HWPK. 1.1 Dismantling, shifting and safe deposit of existing 310 kVA indoor DG sets-4 nos. with Diesel Engine- W8V 17.5/22AMA of Kirloskar oil engine ltd. make and Alternator- 310 kVA/248 kW, YTS6 type-3 nos. and 6AX 450/2 1000- 1 nos. of Kirloskar Electric Co. Ltd. make, one-by-one after ensuring availability of emergency supply from existing location to our central store. Each DG set mainly consists of Diesel engine with governor & fly wheel arrangement, Alternator, day tank (1200 litre), fresh water tank (100 liter), existing exhaust piping (approx. 8 meters) with silencer & turbo charger, AMF panel, jacket water & lub oil heat exchanger with their connecting piping from DG set, Lube oil priming pump with motor, Engine jacket water circulating pump motor & heater, self starter with 24 volt, 200 Ah battery-4 nos. etc. 1.2 Dismantling of existing RCC foundations and structures of old DG sets, day tank, heat exchangers etc. Design & construction of new RCC (Reinforced Cement Concrete) or any other suitable foundation for 500 kVA DG sets, day tank, radiator, AMF panel, support piping & structure etc. as required for installation of new DG sets & its accessories. Vibrating isolators (AVMs) / anti vibration pad to be provided to reduce generator set vibration and noise transmission to the surrounding structure. Supply of construction materials, structural materials and all consumables items, tools & tackle etc. for foundation shall be in suppliers scope. 1.3 Design, supply of materials & construction of 3 hour rating fire resistant wall in between DG sets and in between HSD tanks. 1.4 Supply, testing, installation, commissioning and guarantee of 4 nos. of Silent type 500 kVA Diesel Generator Sets complete with their radiator (water cooled), acoustic enclosure (as per latest CPCB norms), anti vibration mount/pad, turbocharger, exhaust manifold with silencer, Electronic governing system, Electronic control panel, self starting arrangement with 24 volt battery suitable for 6 consecutive starting attempts, Flywheel arrangement, HSD day tank, AMF control panel with Power controller, electrical analyzer unit & digital automatic voltage regulator. Supply & installation of piping for hook up of cooling system & make up water from existing header, lube. Oil system, fuel system from HSD tank to DG & from existing header to HSD tank. Laying of FRLS power & control cables for connection of DGs with existing switch gear. 1.5 Supply, installation, wiring and hook up of Protection CTs (current transformer)-8 nos and measuring CTs-4 nos. for each 500 kVA DG sets in place of existing CTs of 310 kVA DG sets with relays & metering devices. Dimension & other details for design of CTs is enclosed. 1.6 Supply, commissioning and hook up of Central Monitoring System consists of PLC based centralized data logging system with redundant processor, workstation loaded with suitable SCADA/HMI software, communication network with driver software & full licenses (original version), PC with 250 GB HDD, LCD colour monitor 17, Laser B/W A4 size printer and ups (see 4.5.0 for details specifications). It needs to be communicating with individual instrument control panels/ Power controller/ energy analyzer/ PLC of respective generators to generate utility reports from the data logged during operation of DG sets as per HWPK requirements. The local instrument panels / power controller / energy analyzer have to be provided with Ethernet/ Modbus/ Other suitable communication facility in order to integrate with the central monitoring system.

Page 3 of 32

1.7 Supervision during testing & commissioning shall be taken up under control of DG sets manufacturer engineer. This supervision during installation, testing and commissioning shall be considered as included in scope of all items. The supervision during installation, testing and commissioning of DGs is in the scope of the supplier and no extra charge shall be paid for deputation of manufacturers engineer. Suppliers site engineer shall ensure that installation job is done as per good engineering practice, tender specification and approved drawings. 1.8 The Bidder shall provide necessary supporting document for seeking clearances/approvals of Pollution Control Board (PCB) / Central Electricity Authority (CEA) / Atomic Energy Regulatory Body (AERB).

2.0 GENERAL REQUIREMENTS FOR TECHANICAL QUALIFICATION:Apart from meeting technical specifications laid in subsequent pages of tender, following shall also be necessary to qualify for technical part of tender. 2.1 The bidder shall be Original Equipment Manufacturer (OEM) or Authorized dealer of Manufacturer. The offered equipment have to be designed, manufactured and tested as per relevant IS / ISO /IEC / IEEE standards with latest amendments. 2.2 DG sets manufacturer should have established manufacturing facility of similar type of Diesel Generator sets since last five (5) years and shall support for servicing and spares for minimum 20 years of operational life of DG sets. 2.3 The bidder should clearly indicate the quantity and Highest Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. 2.4 They must have executed at least three orders of supply, erection & commissioning of Diesel Generator sets of similar capacity successfully with Govt. organization, public sector or major reputed Indian private sector organization. They should submit performance certificate for their installation obtained from any two of above organization. 2.5 Independent assessment of performance of commissioned DG sets shall be done by HWPK also for qualifying technical part. 2.6 The bidder shall furnish the list of earlier installation as per requirement mentioned in Para 2.2 and 2.3 with detailed address and telephone no. etc. for independent assessment.

Page 4 of 32

3.0 CODES AND STANDARDS:The equipment shall conform to the latest issue of the relevant Indian Standard Specifications or the ISO/IEC/IEEE specifications, wherever applicable. Some of the relevant standards are listed below: IS-456 IS-2974 IS-3809 ISO-3046 ISO-8528 IS-10000 IS-10002 IS 3034 IS-12065 IS-12075 IS-8183 : : : : : : : : : : : : Plain and Reinforced concrete-code of practice Design and construction of machine foundations-code of practice Fire resistance test of structures Definition and Rating of Diesel engine Specification & definition of prime power rating, noise level, governor regulation of Diesel engine Method of tests for Internal combustion engine Specification for constant speed compression (Diesel) engine Environmental (Protection) Rules, 1986 latest amendment/ schedules for noise & emission limit of DG sets. Code of practice for fire safety of industrial buildings electrical generating and distributing stations. Permissible limits of noise levels for rotating electrical machines Limits of vibration severity of rotating electrical machines Insulating material for better attenuation

IER-1956 : Indian electricity rule-1956 IE Act The Indian Electricity Act 1910/Indian Electricity Supply Act-1948/Electricity Act: 2003. IS-4722 : Rotating Electrical Machine specification IS-4728 : Terminal marking and direction of rotation for rotating electrical machinery IS-7132 : Guide for testing synchronous machine IS-4691 : Degree of protection provided by enclosures for rotating electrical machinery IS-2165 : Guide for insulation coordination IS-3043 : Code of practice for earthing IS-2032 : Graphical symbols used in electric technology IS-13947/ Specification for Low Voltage Switchgear and Control gear : IEC-60947 IS-10118 Code of Practice for Selection, Installation and maintenance of switchgear and : control gear IS-3072 : Code of practice for installation and maintenance of switch-gear up to 1000 V. IS-2705 : Current Transformer Specification IS-3156 : Voltage Transformer Specification IS-732 : Code of practice for electrical wiring installations up to 650 volts IS-1554 Part-1 IS-7098 Part-1 IS-3842 IS-8686 IEC-60255 IS-14570/ IEC 688 : : : : : : PVC insulated (heavy duty) electric cables for working voltages up to and including 1100 volts Cross linked polyethylene insulated PVC cables for working voltages up to and including 1100 volts Application guide for Electrical relays for ac system Specification for static protection relays Testing & specification for microprocessor relay Electrical measuring transducer for converting a.c. electrical quantities to analogue or digital signals

Page 5 of 32

4.0 TECHNICAL REQUIREMENTS FOR PERFORMANCE OF WORK:4.1.0 Technical requirement of Dismantling, shifting and safe deposit

of existing 4 nos. of 310 kVA DG sets with their auxiliaries:4.1.1 The dismantling, shifting and safe deposit of the existing four nos. of diesel generator sets shall be performed one by one. 4.1.2 One by one means complete dismantling of one no. of DG set with auxiliaries and second DG set shall be dismantle only after commissioning & satisfactory operation of new 500 kVA DG set with existing switchgear at this location. After installation of two DG sets remaining two can be taken simultaneously subject to satisfactory performance of first two. 4.1.3 Each 310 kVA DG set consist of following items: a) Diesel Engine - Kirloskar oil engine ltd. make, rating of 372 BHP (at 1000 rpm), W8V 17.5/22AMA type, overall Dimension is (in mm) 2030 x 750 x 1300 (Length x Breadth x Height) , eight cylinder, four-stroke inline turbo charged engine with mechanical governor & flywheel arrangement.b) Alternator - Kirloskar Electric Co. Ltd. make, model YTS6 type- 3 nos. , overall dimension is ( in mm)1310 x 1400 x 930 (Length x Breadth x Height) and 6AX 450/2 1000- 1 no., 310 kVA 248 kW, 3 Phase, 4 wire, 50c/s, 1000 rpm. overall dimension is ( in mm)1240 x 1200 x 1130 (Length x Breadth x Height) c) Fuel Oil Tank - Approx. 1200 liter capacity MS tank. d) Fresh Water Tank - Approx. 100 liter capacity MS tank. e) AMF Panel - Consisting of Indicating meters, fuses, Power & control relays, Aux. contactors, excitation system, battery charging system etc. f) Self starting arrangement - Self Starters with Batteries (Lead Acid) - 12 volts, 200 Ah 4 Nos. with connecting cables from starter to batteries. g) Jacket water Heat exchanger - 1 no., Jacket water circulating pump with motor- 1 no., jacket water heater- 1no. & their connecting piping from heat exchanger to Diesel engine, from cooling water header to heat exchanger etc. h) Lub. Oil heat exchanger - 1 no., Lub oil priming pump with motor-1no. & their connecting piping from heat exchanger to diesel engine and vice versa etc. i) Existing exhaust piping (approx.8 mtrs) with silencer, turbo charger and supporting structures. j) All supporting structures of fuel oil tank, fresh water tank, heat exchangers, exhaust piping, lube oil & fuel oil piping.

4.1.4 At the time of dismantling of DGs fresh HSD from tank and used HSD from diesel engine shall be emptied in drums provided by purchaser. 4.1.5 At the time of dismantling of DGs used lube oil shall be emptied in drums provided by purchaser. 4.1.6 The Contractor shall install safety caps/end plugs/flanges to the fuel lines & water lines as necessary before removing/dismantling the fuel/water lines from headers.4.1.7 All types of special tools & tackles etc. required for dismantling & shifting of materials shall be arranged by party. 4.1.8 The Contractor shall remove all equipments/materials/oil etc. associated with the existing diesel generator equipment as mentioned above. The Contractor shall properly deposit all materials in our store at place assigned by HWP (K).

Page 6 of 32

4.2.0 Technical requirement of civil work: Dismantling of existing RCC foundation of 310 kVA DG sets (4nos.) and preparation of new foundation for installation of 500 kVA DG sets 4 nos.4.2.1 The dismantling and preparation of new foundation of the existing four nos. of diesel generator sets shall be performed one by one (see 4.1.2 also). 4.2.2 Each existing DG sets having RCC foundation (in cm): (a) 300x30x50 (Length x Breadth x height) 2 nos. (b) 50 x25 x 10- 2 nos. & (c) 110 x 110x 4- 1no. 4.2.3 The existing concrete pads / foundation of DG sets as mentioned above shall be fully dismantle below surface level (up to depth of 300 mm) for proper bonding of new foundation. 4.2.4 The new foundation for Diesel Generator set shall be formed in accordance with the IS-2974. Depth of foundation should be designed considering weight of 500 kVA DG set with acoustic enclosure. 4.2.5 The length and breadth of foundation should be at least 150-300 mm (6-12) more than base length and breadth of equipment. Foundation height should be about 100-150 mm above ground level to maintain cleanliness around DG set. 4.2.6 Foundation should be designed with necessary pocket for grouting of anchoring bolt/ isolators springs etc. as required for installation of Vibrating isolators (AVMs) / anti vibration pad for installation of DGs. Foundation of DG sets shall qualify for seismic zone-II with post seismic importance factor of 1.5. 4.2.7 Requirement of dimension (depth etc.), type/ design of RCC / AVMs as necessary shall be finalized during technical discussion after opening of technical bid. In case bidder offers altogether different foundation arrangement it shall also be accepted subject to meeting the vibration, noise, vibration transmission and critical speed suitability criteria as per relevant standard. 4.2.8 All areas under and adjacent to the foundation shall be well cleaned prior to pouring of concrete. The surface except the pockets for grout shall be made rough so as to secure good bond with fresh cement. Cement grout with non-shrinkable additive shall be used where structurally required. 4.2.9 All surfaces other than main foundation to be chipped/ cleaned for finishing/ recoating of the surface/floor. 4.2.10 All civil works for installation of HSD Tank, radiator, structural support for anchoring of piping, vents, exhaust chimney etc. in the bidders scope. 4.2.11 Concrete of M25 or higher grade as per IS-456 shall be used for foundation of machines. The concrete used shall be of plastic consistency without excessive water. Continuous concreting shall be done as far as possible for entire block, leaving provisions for grouting. 4.2.12 Reinforcement may be bent and fixed in accordance with the procedure indicated in IS-2502. Annealed steel wire (0.9mm dia or over) may be used for tying crossing bars. 4.2.13 Construction joints should be avoided. The finished surface of the foundation shall be leveled before installing the machine. 4.2.14 The fundamental natural frequency of foundation of DG sets shall be at least 20 percent away from the machine operating speed. Dynamic analysis, vibration analysis, static analysis, grade of concrete, reinforcement steel etc. shall be as per IS-2974.

Page 7 of 32

4.2.15 Shuttering material shall have smooth and even surface and the joint shall not permit leakage of cement grout. All surface of shuttering, in contact with concerts, shall be treated with a nonstaining mineral oil or other approved material to prevent adhesion with concrete and protect reinforcement also. 4.2.16 The required routing/ lay out for cable racks, trenches shall be worked out. Main cable trench 600 mm wide is available at both side of existing DG sets. Excavation/ digging & trenches as necessary for laying & termination of power & control cables, laying of branch piping etc. required for installation of new DG sets in the suppliers scope. 4.2.17 Checker plates / trench covers should be provided for newly make trenches. Brick works/ sand filling to be done for all excavation/ digging work. Backfilling the cable trench & making up to the ground level in the suppliers scope. 4.2.18 Supply of all construction materials (cement, concrete, reinforcement etc.), structural materials (anchoring bolt, angle, column etc.), all consumables items (nut-bolt, clamps, shims, cotton etc.) & shuttering materials etc. shall be in the suppliers scope. 4.2.19 The design, drawings and specification of foundation shall be approved from Engineer-InCharge before execution of work.

4.3.0 Technical requirement of Design, supply & construction of 3 Hour rating fire resistant wall in between DG sets & HSD day tanks.4.3.1 Fire resistant reinforced concrete wall of minimum 3 hr fire rating has to be formed in between DG sets & in between HSD tanks. 4.3.2 Concrete aggregates, thickness of reinforced concrete walls, concrete cover to the reinforcement in wall shall be calculated considering both side exposed to fire as per specification of IS-6142 & IS-456. 4.3.3 Height & length of fire resistant wall (non-load bearing) shall be finalized on the basis of overall length, height and layout of DG sets & HSD tank. 4.3.4 Fire resistant wall should have ability to shown fire stability, fire integrity/ thermal insulation or other expected duty as specified in standard fire resistance test as per IS- 3809. 4.3.5 Design and layout of the firewall shall be approved after placement of purchase order before construction of wall.

4.4.0 Technical Specification of 500 KVA Diesel generator Set- 4 nos. & its auxiliary.4.4.1 Technical requirement of foundation / base rail, unloading, shifting for installation of DG sets. 4.4.1.1 Static & dynamic load data of DG sets for foundation design shall be furnished with detail layout drawing of DG set by manufacturer for approval. 4.4.1.2 Engine & Alternator shall be coupled through a flexible coupling and mounted on a factory designed and tested sturdy steel channel base frame. The base shall be designed and built to resist deflection, maintain alignment, and minimize resonant linear vibration. 4.4.1.3 The base frame shall be free from any defects such as burrs, twists, distortions etc. The base frame shall then be painted with 2 coats each of red oxide primer and black synthetic enamel paint to prevent rusting.

Page 8 of 32

4.4.1.4 Provision for lifting (Eye bolts/ pockets) provided on base frame of the DG sets should be designed considering total weight to be handled and to maintain the centre of gravity of the DG sets while lifting. Other than this, eyebolt shall be also provided on individual major equipment of handling (Diesel engine, alternator, radiator, acoustic enclosure, tank, AMF panel etc.). 4.4.1.5 Anti-vibration mounting may be used to ensure the vibration & noise transmission of the DG sets to the surrounding structure & building within the permissible limit as per IS/ manufactures recommendation. 4.4.1.6 Sufficient no. of suitable capacity steel spring isolators/ anti vibration mountings (AVMs) dully approved shall be installed between the base and the mounting surface. The isolators shall bolt to the base, and have a waffled or ribbed pad on their bottom surface. The pads shall be resistant to heat and age, and impervious to oil, water, antifreeze, diesel fuel, and cleaning compounds. Isolators shall have minimum of 25 mm deflection and qualify for seismic zone as laid down in IS-1893. 4.4.1.7 The leveling and alignment of foundation shall be carried out carefully before placing the DG sets. The final grouting of the base frame and fixing of the mounting bolts of the panels shall be carried out only after ascertaining perfect alignment and leveling by the experienced and skilled persons and on clearance from the engineer in charge. The base frame of DG sets should be leveled using shims before grouting with foundation. 4.4.1.8 Before deployment of material handling equipments, chain pulley blocks, Hook, sling, trolley etc. for erection, shifting & installation of DG sets & its auxiliaries it is necessary to submit valid test certificates. Appropriate rating & smooth functioning of all equipment shall be ensured before start of work. Only authorized persons should be allowed to operate material handling equipments. 4.4.2.0 Technical requirement of Acoustic enclosure of Diesel Generator set. 4.4.2.1 The diesel generator sets are housed inside a high quality acoustic enclosure of compact, modular & sleek design with low noise level (75 db) at a distance of 1 meter as per latest MOEF (Ministry of Environment and forest) / CPCB (Centre pollution control board) norms. 4.4.2.2 The acoustic enclosure shall be soundproof, weatherproof, and environmental friendly consisting of acoustically treated panels from all the four sides and top. It includes hinged doors on either side for maintenance of DG set. 4.4.2.3 All the panels should be lined with fire proof acoustic material light resin rock wool as per relevant IS. The material shall have more than 48 Kg/m3 density and the layer shall be 75 mm thick covered in the fiber glass sheet and perforated powder coated sheet from inside. The outside fabrication will be made out of 2 mm GI Sheet and with ventilating louvers for both at the engine side for fresh air entry and for hot air exhaust. 4.4.2.4 Exhaust silencer should be of domestic grade type mounted outside the enclosure, exhausting to atmosphere. Exhaust pipe is to be extended up to height of approx. 8.8 meters as per CPCB norms. All joints to be sealed with fireproof neoprene gaskets to withstand temperature and pressure at site conditions. All high temperature exposed surfaces to be insulated by glass wool with aluminum cladding up to the silencer. 4.4.2.5 Adequate ventilation should be provided to meet the air requirements for combustion and heat removal. A ventilation fan/blower of adequate capacity to meet the total air requirement and air changes shall be provided. 4.4.2.6 Existing Shutter modification has to be done to accommodate the inlet & outlet ducts as necessary for air requirement for ventilation/combustion. Max allowable temp. Shall be 450 C in side the enclosure.Page 9 of 32

4.4.2.7 Enclosure and layout of the equipment have to design to facilitate easy access to all serviceable parts and having sufficient space in and around the DG set for maintenance & operation of the DG set. The fuel level gauge & engine control panel (for engine parameter) shall be visible from outside the enclosure. Drain plugs shall be provided outside the enclosure for draining lube oil. Handle type locking systems has to be provided for hinged doors. 4.4.2.8 Arrangement for illumination with 40 watt tube light type fixtures has to be make. Lights shall be arranged at both sides of DG sets inside the enclosure. In addition to this 2 nos. of panic lighting shall also provide inside the enclosure on 24 volt DC supply. Lights will be switched from individual MCBs mounted on control panel cover & have back-up HRC fuse. Two no. industrial type metallic plug socket (both side of DG). 4.4.2.9 There should be a provision of emergency shut down (by stopping solenoid) of the diesel generating set (Prime Mover) from outside the enclosure. 4.4.3.0 Technical requirement of Exhaust system of Diesel Generator set. 4.4.3.1 The engine exhaust system shall be installed to discharge combustion gases quickly and silently with minimum restriction. The exhaust system, including silencer, shall be designed for minimum restriction, and in no case backpressure shall exceed 40 mm of Hg. 4.4.3.2 Engine exhaust system shall include exhaust manifold with muffler, flexible fittings, exhaust silencer, exhaust piping, elbows, bends, heat insulating lagging/cladding, supporting dampers, spring, rain trap, thimbles etc. 4.4.3.3 A stainless steel flexible exhaust fitting shall be provided to allow for thermal expansion and engine vibration. The flexible fitting shall include a floating flange on one side to match the engine exhaust outlet port(s) and bolt pattern and a fixed flange on the opposite end to match the exhaust silencer inlet(s). 4.4.3.4 Piping shall be supported and braced to prevent weight or thermal growth being transferred to the engine. Support dampers and springs shall be included where necessary to isolate vibration. Roof height is approx. 7 mtrs. From ground level. First support shall be within 2.0 meter from exhaust flexible centre line. 4.4.3.5 The domestic type exhaust silencer shall be sized and supplied by the engine supplier. It shall be mounted near the engine at suitable location to optimize silencing & backpressure to the system. A provision for draining moisture shall be included. 4.4.3.6 The silencer shall provide extreme noise attenuation for environments with low background noise. Silencer shall be pancake style bottom inlet, end outlet style. It should meet stringent sound emission standards laid down by CPCB / MOEF notification. 4.4.3.7 Schedule B MS exhaust pipe of minimum 200 mm dia (8 inch) and long end elbows shall be used. One no. 1/ 8 inch NPT connection should be provided for measuring exhaust back pressure during commissioning. 4.4.3.8 Exhaust piping inside the DG set room should be lagged along with aluminum sheet cladding to avoid heat input to the room. A rain cap shall be provided to terminate the exhaust pipe. The distance between exhaust pipe and rain cap should be higher than diameter of pipe. Horizontal run of exhaust piping should slope downwards away from the engine to condensate trap. 4.4.3.9 Use of thimble is necessary while passing the pipe through concrete wall. The clearance around the pipe in walls shall be sufficient to allow free movement and expansion/ contraction of piping.Page 10 of 32

4.4.3.10 Emission limit (NOx level, HC, CO etc.) stack height and noise level shall comply with the guidelines laid down by MOE&F and any other stipulation of the SPCB and CPCB in this regard. 4.4.4.0 Technical requirement of HSD storage tank of Diesel Generator set. 4.4.4.1 The HSD storage tank of Diesel Generator set shall be installed outside of existing DG building as nearer as possible with DG set. 4.4.4.2 The capacity of the HSD storage tank shall be of 1000 liters capacity sufficient for 8 hours full load continuous operation. It shall be fabricated with minimum 3mm thick M.S sheet with all standard accessories, which includes breather, drain plugs for draining diesel complete with drain valve, trough arrangement to collect spill oil (individually or collectively), air vent, inlet and outlet pipe connection, and manhole with cover. 4.4.4.3 HSD tank, fuel piping, valve etc. should be free from leaks. Materials of tank, valve, pipe etc. shall be compatible with required service and shall not affect the any chemical properties of HSD (as per IS-1460). 4.4.4.4 Installation of piping for hook up the fuel system from existing header to HSD tank & from HSD tank to DG with necessary valve arrangements, non return valve between HSD tank & Diesel engine & necessary flanges/blinds etc. 4.4.4.5 Wire mesh filter screen at filling point & fill neck to allow min.5%expansion space shall be provided. Fuel water separator shall provide in between fuel tank and fuel filter, necessary mounting arrangement/drain valve etc. to be provided. 4.4.4.6 The fuel level gauge (10-95%) to be provided visible from outside the enclosure. Electronic fuel Level transmitter/switches to be installed and the digital/analog level indication have to be provided in the control panel and low & high level alarm/trip at AMF panel. The full level float arrangement has to make to avoid any spillage of oil. Each diesel engine shall be provided with on-line fuel flow metering device (calibrated in liter) to monitor fuel consumption. 4.4.4.7 Fuel tank should be placed on the level such that fuel outlet point (at bottom of fuel tank) is optimally above the engine driven booster pump inlet connection. Fuel tank location should be such that it does not obstruct free movement of service personnel. 4.4.4.8 Excavation/ digging, trenches, supports, thimbles / opening in walls as necessary for installation of fuel system shall be in the suppliers scope. 4.4.4.9 General arrangement & equipment layout drawings of HSD tank with DG, Isometric / P&I diagram for complete fuel piping arrangement shall be submitted for approval before execution of work. 4.4.5.0 Technical requirement of cooling system of Diesel Generator set. 4.4.5.1 The generator engine shall have a jacket water-cooling system with a closed circuit design with provision for filling, expansion, and de-aeration. The cooling pump shall be gear driven by the engine. Auxiliary coolant pumps if required for heat exchangers or separate circuit after cooling shall be provided. 4.4.5.2 Coolant temperature shall be internally regulated to disconnect external cooling systems until operating temperature is achieved. Cooling system should be designed considering 50 0C ambient and max temp. Rise of 5 0C is allowed inside the enclosure.

Page 11 of 32

4.4.5.3 Heat rejected to the engine jacket water shall be discharged to the atmosphere through a radiator. The radiator shall be sized to cool the engine continuously while operating at full rated load. Air shall be drawn from the underside of the radiator and discharged to the atmosphere forced by engine driven fan. The radiator shall have an expansion tank with sight glass to allow for proper expansion and filling of the cooling system. 4.4.5.4 Cross ventilation and free flow of cool, clean and fresh air to be maintained for satisfactory operation of DG set. Air should flow from alternator end to engine. Opening in front of radiator should be 1.5 times radiator core and at back 2.25-3.0 times radiator core. 4.4.5.5 Installation of piping for hook up the make up water line from existing header to radiator with necessary valve arrangements, non return valve, strainer arrangement, pressure gauge at both side of strainer & flanges/ blinds etc. 4.4.5.6 Ducting in front of radiator may be required to take out hot air from inside of acoustic enclosure to atmosphere. Extension duct to be designed and additional ventilation arrangement if required shall be incorporated by supplier. It shall be finalized during technical discussion. 4.4.5.7 Provision has to be made for low coolant level alarm, radiator water high temperature alarm & trip, cooling water circulation failure and hook up with DG control panel and AMF panel for annunciation. 4.4.6.0 Technical requirement of self-starting arrangement of Diesel Engine. 4.4.6.1 The engine starting system shall include 24-volt DC self-starting motor(s) (mounted on Diesel engine), starter relay/ magnetic switch and automatic reset circuit breaker (mounted on AMF panel) to protect against butt engagement. The engine shall be started by starter motor engaging with the fly wheel ring gear and disengaging automatically when the engine starts. 4.4.6.2 Batteries (2 x 12 V) automotive grade suitable for diesel engine cranking duty (conforming to IS 7372) shall be lead acid types mounted near the starting motor. A corrosion resistant or coated steel battery rack shall be provided with suitable rubber matting for placing batteries. The system shall be capable of starting a properly equipped engine within 10 seconds. The starting system shall be parallel to the engine starting batteries. The battery shall be capable of providing at least six consecutive starting cycles with time interval of 5 second. 4.4.6.3 Double run single core TRS insulated unsheathed circular flexible cable of 70 mm2 (2228 x 0.2) size conforming to IS: 9857 shall be used for connecting Battery to starter. 4.4.7.0 Technical specification and requirement of Diesel Engine. 4.4.7.1 The Diesel Engine shall be stationary, heavy duty, compression ignition, totally enclosed, water cooled, in line, 4 stroke, direct injection, cold battery starting, turbocharged after cooled in accordance to BS:5514 and IS:10002 complete with all accessories. 4.4.7.2 The engine shall be capable of developing brake horsepower at 1000/1500 RPM to deliver 400 kW /500 kVA alternator output equipped with all engine-mounted parasitic and external loads such as radiator fans, engine driven pumps etc. 4.4.7.3 The Engine Alternator set offered shall be continuous duty type of rating (Prime power) 400 kW /500 kVA. The set may be idle for a long period except for routine test periodically. When there is no power supply the set will be required to run continuously at rated load. The set shall be capable of taking 10% overload for one hour during a period of 12 hours.

Page 12 of 32

4.4.7.4 Diesel engine shall comply with the requirements of BS 5514 (ISO 3046). The engine shall meet all the performance requirements of the set under the specified operating conditions. 4.4.7.5 Circulation of cooling water through the engine and radiator shall be by means of engine driven pump. The water circuits shall be fitted with an easily accessible drain point. The cooling fan shall be arranged to drive directly by the engine and the hot air shall ducted to suitable openings in the generator room wall. 4.4.7.6 Lubrication of the engine shall be by means of an engine driven integral pump. The pump shall have on the suction side a coarse strainer and on the delivery side a duplex `full flow' fine filter complete with changeover cock to facilitate oil flow to the engine if filter becomes blocked. The lubricating oil system capacity shall be sufficient to enable the engine to run continuously at any load. 4.4.7.7 Lube oil priming pump with motor shall be provided when the engine is at rest. The control circuit of the lube oil pump shall be designed to run once for six minutes after every four hours or any other operating cycle suitable to engine design and cut off in case of engine running. 4.4.7.8 Lubrication shall be provided by suitable capacity gear pump to develop positive pressure for lubricating all moving parts. No moving parts shall be required lubrication by hand either prior to the starting of engine or while it is in operation. Paper filament type lube oil filter with lube oil cooler shall be provided for cooling and filtration of lube oil. A bypass filter shall be provided to bypass the lube oil in case the lube. oil is not getting hot. Temperature and pressure gauges / transmitter shall be fitted to the lubricating system. A dip stick arrangement shall be provided to check the level of lube oil in sump. 4.4.7.9 The engine shall be efficiently silenced with suitable noise attenuators provided at cooling/combustion air inlets and outlets. Bellow type flexible pipe shall be provided between Engine and M.S. Exhaust Pipe. 4.4.7.10 Diesel engine assembly should have single piece Engine block, Deep hardened crankshaft, molybdenum iron cylinder liners induction hardened, Aluminum alloy piston, Forged steel connecting rods for piston and rod assembly, intake and exhaust valves with hardened steel stem and hard faced to resist wear at high temperature, geared design flywheel, fly wheel hosing with coupling guard, vibration damper etc. 4.4.7.11 To facilitate smooth starting of engine in cold weather condition Jacket water heaters shall be provided to maintain coolant temperature of 32C while the engine is idle. Heaters of suitable rating (240 volt) with protection (fuse & contactor) and thermostatic controls shall be provided. Hoses to and from the heater shall be industrial quality, which exhibit long life in operational environments. Automatic logic shall be incorporated to isolate the heaters during operation. 4.4.7.12 Engines shall start, achieve rated voltage and frequency, and be capable of accepting load within 10 seconds. All four DG Sets should be identical in specifications; drooping characteristics and transient response of shall conform to ISO 8528 and suitable for parallel operation with grid. 4.4.7.13 the fuel system should comprise of fuel pump with Governor, fuel injectors, 24 volt DC solenoid coil, Replaceable fuel filter. Diesel fuel rates shall be based on fuel having a low heating value (LHV) of 42,780 kJ/kg when used at 29C and weighing 838.9 g/l. 4.4.7.14 The governor of the engine shall be electronic type and be capable of fine governing of speed to Class A2 of BSS 5514/1977, ISO 3046/IV.

Page 13 of 32

4.4.7.15 The governor shall be electronic besides hydraulic with manually adjustable arrangement with a over speed trip mechanism to automatically shut-off the engine or the fuel supply if the set reaches 110% of rated speed. In addition to this, an engine mounted emergency push button/lever shall be provided from outside of acoustic enclosure. This shall trip the engine when pressed. This shall be suitably protected against accidental tripping. 4.4.7.16 The engine shall run steadily and maximum change of speed because of load variation on suddenly taking off or throwing, speed variation should be as per clause 2.3.2 of IS:10000 (Part VII). 4.4.7.17 When the engine alternator is delivering 10% and 100% of the rated power output, the steady load speed band shall not exceed 1% of the rated speed. 4.4.7.18 The recovery time from temporary distribution to the steady load speed band at the new load shall not exceed 3 second after taking off or throwing on the rated load. 4.4.7.19 An electronic engine control panel shall be provided on individual Diesel Generator set visible from outside of acoustic enclosure. Following parameters/ indication shall be available on it. a) b) c) d) e) f) Engine speed (rpm) lub. oil pressure (bar) and temperature ( 0c) Radiator water temperature coolant temp( 0c) Intake air temp ( 0c) Engine runtime (hour) Controller for electronic governor

g) Multi channel Temperature scanner with digital display for exhaust gas temperature of cylinders, engine jacket water temperature, bearing & winding temperature of alternator. 4.4.7.20 Required sensors for Engine monitoring parameters as mentioned above shall be provided with analog/digital signal and additional potential free contacts for Central management system. 4.4.7.21 Calibration certificates for all the measuring and controlling instruments like fuel injection pump, thermostatic valves, tacho- generator, electronic governing system, engine monitoring sensor / devices etc. has to be furnished before supply of materials. 4.4.7.22 Engine manufacturer shall furnished the complete data / specification sheet consisting of No. of valves, Displacement, Compression ratio, Valve arrangement, firing order, cylinder bore, piston stroke length, % engine loading vs specific fuel consumption curve showing optimal engine loading with max. efficiency, max. cylinder temperature at 100% and 110 % of prime rating, specific fuel & lub. oil consumption per KWh, Engine performance data at different % load, power de-rating curves etc. 4.4.7.23 Maintenance and overhauling pattern/schedule, operating life of DG sets, service centre locations and response time for maintenance shall be furnished for evaluation of post guarantee maintenance. 4.4.7.24 Fuel consumption rate, lub oil consumption rate, Efficiency of Diesel engine shall be used for technical evaluation and depending upon operating hours during its life cost of energy shall be loaded for comparison of cost. fuel consumption rate at 75% of the rated load shall be 78 litre per hour.Page 14 of 32

4.4.8.0 Technical requirement and specification of Alternator. 4.4.8.1 The alternator shall be brushless, self excited and regulated through AVR and designed for continuous rating of 500 KVA (at 0.8 pf lagging), 415 volts, 3 phase 4 wire, 50 Hz at 1000/1500 rpm conform to IS 4722/1970 at specified site conditions. The set shall be capable of taking 10% overload for one hour during a period of 12 hours. 4.4.8.2 The alternator winding shall be star connected. The power supply terminals (3 phase) and neutral terminal shall be brought out in separate terminal box. The terminals shall be mounted in an accessible position on the alternator with necessary cable gland plates suitable for extension of the supply to the AMF control panel. 4.4.8.3 The direction of rotation of alternator, terminal marking of 3 phase with neutral and terminal marking of field winding shall be in accordance with IS-4728. The phase sequence (UVW) and direction of rotation shall be clearly marked on the alternator. 4.4.8.4 The alternator shall be directly coupled to the diesel engine through flexible coupling. The degree of protection for the generator and exciter shall be minimum IP 23. 4.4.8.5 The stator of the alternator shall be assembly of stator core, foot plates, air baffles and the stator winding. The stator core consists of low loss electrical sheet steel. The sheets are insulated to each other by coats of varnish at both sides. The skewed stator slots have to be used to reduce noise level. All windings should be double layer fractional pitch chorded lap type winding to reduce/ eliminate 5th / 7th harmonic, made of electrolytic grade copper of high purity. 4.4.8.6 The complete rotor (cylindrical / salient type construction) shall consist of single shaft, rotor field winding, damper winding, full bridge diode rectifier unit, brushless exciter winding with fan. The rotor core shall be shrunk fitted on the shaft. 4.4.8.7 The shaft shall be designed sufficiently rigid to take care of transmitting torques, minimum static deflection and natural frequency away from rated speed. The shaft should have axial grooves in middle section to accommodate leads from exciter to field winding of alternator. 4.4.8.8 The inertia of the machine shall be adequate to meet the transient stability requirements imposed by the interconnected electrical power system, to limit speed rise and shall have such a value which will not cause the machine natural frequency to be in resonance with the expected frequency of Diesel Generator sets surges. A margin of approx. 25% shall be provided. 4.4.8.9 The alternator shall be fitted with two RTDs per phase for monitoring winding temperature. The connecting leads of the temperature sensors shall be terminated in an instrument terminals box. Two nos. of space heater of rating 230 volts shall be incorporated inside the enclosures & separately wired to terminal box. 4.4.8.10 Each alternator shall be provided with its own exciter. The exciter shall have exciter winding rotating armature type and its output fed to alternator main field through full bridge diode rectifier mounted on single shaft. Stator winding of exciter should have main & regulating field winding connected to the voltage regulating system. PIV of exciter diodes must be 800v or 8 times the maximum exciter armature operating voltage, whichever is higher. 4.4.8.11 The capacity of the excitation system shall be adequate to supply continuously 1.1 times the excitation current and voltage required by the generator at 100% rated kVA and 100% rated voltage & for supplying twice the excitation current required by the machine at 100 % rated kVA and 110% rated voltage for a duration of one minute without damage.Page 15 of 32

4.4.8.12 The alternator characteristics shall be suitable for parallel operation with grid without any quadrature droop compensations. The AVRs shall be suitable for voltage regulation of +/- l % or better against all loads and prime mover drop up to 4% of the nominal speed. 4.4.8.13 The ceiling voltage shall not be less than 1.4 times the rated excitation voltage for a minimum of 10 sec. Voltage swing (Transient response) when rated load is suddenly switched on should be maximum 10 % with 0.2 to 0.7 sec (Recovery time). Automatic voltage regulation 0.5 % to 1.0 % from no load to full load. 4.4.8.14 The excitation system while operating at maximum kVA, terminal voltage, power factor & speed shall be capable of changing from rated field voltage to 90 percent of ceiling voltage within 25 ms for a sustained drop in generator terminal voltage of 5 percent. 4.4.8.15 Neutral / star point of alternator shall be solidly earthed via neutral grounding contactor in case of island mode and selectable incase of parallel running with grid. 2 nos. of earth points are to be provided of alternator for body earthing. 4.4.8.16 The alternator shall be capable to deliver 150 % of FLC and having unbalanced current carrying capacity of 20 % of FLC and Short circuit current withstand capacity is 5 times FLC for 5 sec.( S.C. rating of existing switchgear is 36 MVA). 4.4.8.17 All the performance requirements such as automatic voltage regulation (AVR), power system stabilizer (PSS) in accordance with the Authoritys connectivity regulations and standards, grid standards & regulations on grid standards shall be complied. 4.4.8.18 Insulation shall be of thermal class H for the stator and the rotor windings with temperature rises limited to that of thermal Class F. Vibration severity for the machine shall be within the limits specified in IS 12075.The rating plate information in accordance with ISIS 4722/1970. 4.4.8.19 3 phase power terminal box & terminals should be suitable for terminating 3 nos. of 3 core x 300 sq. mm FRLS insulated Aluminium cable & neutral terminal box should be suitable for 2 nos. of 150 sq.mm insulated Al. cable and glanding with double compression cable. Separate terminal boxes shall be provided for space heater, field winding & RTDs. 4.4.8.20 Generator manufacturers shall furnished the complete data / specification sheet consisting of Transient, sub transient , synchronous reactance, short circuit ratio, ceiling voltage, excitation voltage and current at no load and full load, efficiency at diff % of load, stator and field resistances etc. They will also furnish unity p.f. and S.C. characteristic curve, No load loss curve, Power-load angle characteristics, power swing curve, capability curve ( V-curve) at lagging, leading & unity pf. 4.4.9.0 Technical requirement of AMF control panel of Diesel Generator Sets 4.4.9.1 Each Diesel Generator set shall be provided with independent AMF control panel. It shall consist of components for starting, controlling and monitoring the operation of the diesel generator set. 4.4.9.2 AMF control panel shall be floor standing, cubical pattern, fabricated with 2 mm M.S. sheet painted with anticorrosive red oxide primer and powder coated with synthetic enamel paint of gray shade. It shall be supported by structural steel frame with necessary foundation / mounting arrangement and installed near the DG set. 4.4.9.3 The components of AMF control panel shall be designed, installed, wired & integrated as per IS-10118, IS-3072, IS-732 and IS-13947. The components used in the fabrication of the panel shall be of high quality/reliability and shall be of reputed make, the spares of which arePage 16 of 32

readily available in the local market. The design, drawings, layout & dimension of complete panel shall be got approved from the Engineer-In-Charge before manufacturing. 4.4.9.4 The AMF panel shall be dust, moisture & vermin proof with IP 43 enclosure. It shall have air circuit breaker of 800 amps rating. The breaker shall be electrically operated, horizontal draw out type, having three poles operated through a common shaft by operating mechanism. It shall have Service, Test and Isolate positions within the cubicle. 4.4.9.5 The circuit breaker shall be capable of rapid and smooth interruption of currents under all conditions, completely suppressing severe and persistent short circuit conditions. 4.4.9.6 The symmetrical breaking capacity of the breaker shall be more than 50 KA / 36 MVA, which shall remain constant within the limits of the rated voltages specified in this specification. For voltages lower than the rated voltage, the breaking current shall remain constant. 4.4.9.7 The circuit breaker shall be suitable for rapid closing and tripping. The breaker opening and closing operations shall be obtained from compressed spring charging mechanism. The mechanism for spring charging shall be motor operated with facility for manual charging when required. Spring operated mechanism shall be complete with opening spring, closing spring and all necessary accessories to make the mechanism a complete unit. 4.4.9.8 The auxiliary voltage of closing circuit, tripping circuit and spring charging motor shall be 110 volt dc. The closing release shall operate correctly at all values of voltage between 85% and 110% of the rated voltage. The shunt trip shall operate correctly under all conditions of the circuit breaker up to the rated breaking capacity of the circuit breaker and at all values of supply voltage between 70% and 110% of the rated voltage. 4.4.9.9 The circuit breaker shall have followings inherent safety features: i) In Test position, power contacts shall be disconnected however control contacts shall remain undisturbed and close/trip operations of the breaker should be possible without energising the power circuits. ii) Operation of close/trip should not be possible unless it is fully in Service/Test or Isolate position. Withdrawal or engagement of breaker should not be possible unless breaker is in open or tripped condition. iii) In service position it should not be possible to close unless auxiliary contacts provided for it get closed. iv) The main isolating power contacts on fixed portion should have automatically closing shutters by movement of breaker from service to test/isolate position. They should have door locking arrangement in closed position. v) Operating mechanism shall have anti pumping feature for both electrically and mechanically closing method. vi) Mechanical trip and access to it shall be provided on the front without opening of the compartment doors. 4.4.9.10 Mechanical and electrical indications shall be provided to show open & closed position of the breaker and charged/discharged condition of the spring located at a place where they are easily visible to operator, by separate indictor on the front of panel without opening compartment door. 4.4.9.11 Auto/ manual selector switch for operation of circuit breaker & C-N-T- switch for electrical close/ trip operation in test/ manual mode shall be provided. Breaker On/off, Breaker in service, spring charged, Lock out (86) operated, trip ckt healthy LED indicationPage 17 of 32

shall be provided on Breaker cubicle. 4.4.9.12 Switch fuse unit (SFU) with fuses, bimetallic relay, Power contactor, Aux. contactor etc. required for Lub. oil priming pump (see 4.4.7.7), for ventilating fans/ blowers (see 4.4.2.5), for illumination inside acoustic enclosure( see 4.4.2.8) & AMF panel, for jacket water heater (see 4.4.7.11), for space heater of alternator ( see 4.4.8.9), AMF panel etc. shall be provide in separate cubical for easy access. 4.4.9.13 A, 4 wire, 415 volt, 50 Hz Class III power supply shall be available at site for requirement of 4.4.9.12. Necessary SFU, power contactor, on/off switch, Aux. contactor, LED indication etc. shall be provided by manufacturer on AMF panel for incoming supply. 4.4.9.14 3, 415 volt, 50 Hz alternator output shall be terminated to extended bus-bar connected to incoming of breaker with necessary current transformers (CTs), potential transformer( PTs) & excitation transformer etc. for measuring, protection & AVR. 415 volt R,Y,B, LED indication for incoming supply from alternator before breaker shall be provided on Breaker cubicle. 4.4.9.15 Neutral grounding contactor (N.G.C.) shall be provided for neutral earthing of alternator (see 4.4.8.15). Control ckt to operate N.G.C shall be built up in PLC. Neutral CT for Restricted Earth fault & standby earth fault shall be provided with extended bus-bar for double earthing arrangement separately from body earthing of AMF panel. Full length copper earth bus shall be provided at the bottom of the panel. 4.4.9.16 3 terminal at outgoing of circuit breaker & neutral terminal at incoming of NGC shall be arranged horizontally with extended bus bar to terminate 3 nos. of 3 core x 300 sq. mm FRLS PVC insulated Aluminium cable. 4.4.9.17 The DG set incoming shall be provided with numerical 3 phase (microprocessor based) multifunctional generator protection relays with self supervision feature, with LCD display for parameters, LED indication for fault, RS-485 serial port for remote communication etc. suitable for electrical protection of alternator which are mentioned below: a) b) c) d) e) f) g) h) i) j) Voltage restrained over current protection (50/51V), two stage Thermal overload protection of m/c.(49) (with alarm & trip) IDMT O/C + E/F protection (51/ 51N) (selective curves) Reverse power / Low forward protection (32) Negative phase sequence protection (46), two stage Loss of excitation (40) Under / over voltage relay (27/59) two stage Under / over frequency relays (81) Restricted Earth fault (64 F) & standby earth fault (64 S) protection Lock out feature (86)

4.4.9.18 Trip circuit supervision relay, control supply failure relay, PT fuse failure relay, lockout relay, auxiliary relays etc. required for multiplication of alarm/ trip contact for tripping of breaker, alarm/ trip annunciation at AMF panel, for remote indication for synchronization & existing switchgear shall also be incorporated. 4.4.9.19 One digital Power analyzer/ energy meter/Tr-vector meter shall be provided for monitoring electrical parameter such as KWH, KW, KVA, PF, V, I. etc. of alternator. It shall have RS-485 serial port for remote communication of all parameters to central monitoringPage 18 of 32

system. 4.4.9.20 24 Volt battery for self starting of Dg sets shall be connected through Battery charging system with suitable control & protection system and electronically controlled regulating system for charging the batteries in float / boost mode with battery current limit. Battery shall be charged by 415 volt supply available at same panel. 4.4.9.21 Analog voltmeter & ammeter shall be provided for monitoring of voltage & current of battery charger & battery, for voltage & current of excitation system (field voltage & current), for Alternator O/P voltage & currents with selector switches for 3. Digital frequency meter / Analog rpm meter & pf meter shall also be provided for DG operation. 4.4.9.22 All measuring analog / digital meter/ tri-vector meter shall be of class-0.5/1 accuracy. 4.4.9.23 Following Switch / push buttons shall be provided at AMF panel for DG operation: a) Auto/ manual selector switch for auto / manual starting of DG sets. b) Local/ Remote selector switch for Local & remote operation of Dg sets. Local means from AMF panel and remote means from existing Class-III switchgear. c) Start & stop push button for starting the DG set in local & manual mode. d) Speed increase/ decrease push button for increasing frequency /speed in local and manual mode. e) Voltage raise/ lower push button in local and manual mode. f) On/ off selector switches for 24 volt DC supply, 110 volt DC supply & 415 volt 3 phase class-III supply. g) h) Float/Boost mode selector switches for battery charger. Pushbutton for emergency trip to stop the Diesel generator Set, excitation etc.

4.4.9.24 PLC based control circuitry shall be designed to start, control and monitor the operation of Diesel Generator Set. PLC shall have redundant type CPU with scan time of 10 millisec & power supply card with LED indicating type I/O cards for monitoring & controlling the parameters. It shall communicate to Central Monitoring System of DG system via communicating devices and cables. 110 volt AC, UPS supply is available at site and shall be hooked up with necessary cabling at terminals provided by you. 4.4.9.25 Lub oil pressure switch alarm & trip contacts, temp. switch alarm & trip contacts, HSD fuel level low/high alarm & trip contacts, trip ckt supervision relay alarm contact, Electrical fault lock out relay (86) trip contact, 24 volt dc source available contact, 415 volt class-III supply available contact, Alternator Bearing & winding temp. alarm / trip contact from temp. Scanner etc. shall be wired as I/Ps of PLC for logic buildup for starting & tripping of DG sets, alarm & trip annunciation on AFM panel. 4.4.9.26 The starting philosophy shall include following points: i) The present design envisages three operating & one standby DG sets and same shall be maintained. All the DG sets are designed to automatically come in line in case of failure of grid supply (Class-IV) and connect to three main Bus-Q, Bus-R, Bus-T and standby Bus-S of Class-III (emergency) switchgear. ii) If Auto/manual selector switch is selected in manual mode. DG can be started manually only from AMF panel using start push button, voltage & speed can be raise/lower using raise/lower push buttons either at AMF panel or respective Class-III switchgear panel depending upon selection of Local/ Remote switch.Page 19 of 32

iii) Auto/manual selector switch is normally kept in auto mode. When the grid voltage falls below the permissible value & after set time delay; under voltage relay of respective buses (Bus-Q, Bus-R, Bus-T) trip the respective mains breakers (Class-IV) and initiate starting signal to respective DGs & standby DG set. iv) For 500 KVA DG sets: After getting starting signal from Under voltage relays PLC shall initiate signal to start solenoid of the starter and starter motor to start the cranking of engine. PLC shall check starting of engine & the voltage buildup of alternator (80% of rated voltage). If engine does not get start & conform by PLC next start shall be initiated. v) A three attempts automatic starting sequence to be designed with total lapse time of 25 sec. After every attempts PLC shall checked the starting of the DG set and required voltage buildup .After lapse of 25 sec engine fail to start shall appear and further starting action shall be stoped. vi) PLC shall initiate the starting signal to DG sets only after conforming the following: a) If lub oil pressure is healthy. b) If Lock out relay (86) is showing healthy. c) If 24 volt dc supply is available. vii) After satisfactory starting of DG set & voltage build up to 80% of rated value PLC shall initiates the closing command to breaker of AMF panel. 4.4.9.27 PLC shall initiate the stop signal to diesel engine sets in case of following conditions: a) If lub oil pressure becomes below the trip value. b) Engine fails to start after three attempts. c) If Engine temp.is high above the trip value. d) Engine speed above 110%( set value). e) Alternator winding temp. very high. 4.4.9.28 When class IV (grid supply) power resumes & load transfer from DG set to grid without break (after synchronization) & DG supply incoming breaker on existing switchgear gets trip, PLC shall initiates trip command to trip AMF panel incoming breaker. After conforming the tripping of AMF breaker, PLC shall stop DG set after set delay in auto mode. 4.4.9.29 All DG controls, Alarm/ Trip indications, PLC aux. supply, contactor, stopping solenoid, etc. shall be designed on 24 volt DC with sufficient redundancy derived from batteries / charger. 4.4.9.30 Starting & tripping contacts shall be wired from PLC to start manually & stop automatically the HSD fuel pump as per HSD level of Individual HSD tanks of DG sets. 4.4.9.31 If Lock out relay (86) operates in case of electrical fault PLC shall trips the AMF breaker. 4.4.9.32 Digital automatic voltage regulator/ controller, excitation system, excitation transformer, metering & compounding CT, PT etc. required for voltage regulation & protection of excitation system etc. shall be provide in separate cubical at AMF panel. 4.4.9.33 The digital automatic voltage regulator shall be microprocessor based with fully programmable (user friendly with LCD display) in either auto/ manual mode or PF mode. The regulator shall be capable of sensing true RMS in three phases of alternator output voltage, or operating in single phase sensing mode. The regulator shall have over currentPage 20 of 32

protection, with under/ over current limiter. 4.4.9.34 The regulator shall not be damaged or result in unsafe operation when subjected to open or shorted input due to sensing loss, or sensing source shorted to ground. 4.4.9.35 A provision is made for field flashing arrangement for self excitation of the alternator, sensing of rotating diode by monitoring excitation current, sensing of loss of excitation, excitation voltage / current sensing for metering, for sensing of open/ short ckt/ earth fault of excitation ckt etc., contact for alarm/ trip required for annunciation shall be incorporated. 4.4.9.36 A solid state microprocessor based alarm module shall be mounted on the AMF panel including red (for trip / fail) and Amber (for status / alarm) flashing LEDs and silencable alarm hooter with acknowledge, test & reset button to annunciate alarm/ trip conditions. The hooter shall resound on subsequent alarms after silencing/acknowledgement, with the flashing LED displaying a solid light until the condition is corrected. 4.4.9.37 Annunciation window (4 x 8) shall be provided for following function:(i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) (x) (xi) (xii) (xiii) (xiv)

Local mode selected Auto mode selected Manual mode selected Remote mode selected Battery low Excitation fail Lock out relay 86 operated Generator alarm Generator alarm winding temp.

(xv)

Lub oil pressure low alarm Lub oil pressure low trip Engine temp. high alarm Engine temp. high trip Fuel oil level low alarm Engine over speed trip Lub oil priming pump overload NGC on PLC healthy Radiator temp. high Low coolant level alarm Automatic control fail(xxvii)

(xvi) (xvii) (xviii) (xix) (xx) (xxi) (xxii) (xxiii) (xxiv) (xxv) (xxvi)

Generator winding temp. trip bearing temp.

Emergency trip operated ACB trip ckt unhealthy alarm Protection & metering PT fuse failure alarm Engine fail to start

Governor solenoid

Stop

operated(xxviii) (xxix)

Rotating diode fail.

spare ( 4 windows)

4.4.9.38 A Data integrator/ converter/ mixer shall be provided on the AMF panel to integrate the data from PLC of AMF panel, from AVR, from Electronic control panel of DG set, from window annunciator and from Power analyzer/ energy meter to communicate the monitoring, alarm & fault data to Central Monitoring System consists for data logging and generate utility reports. 4.4.9.39 All doors, panels, removable covers shall have neoprene gaskets around. Pressure release diaphragms on breaker/busbar cubicle and cable termination compartments shall be provided such that hot gases discharged during release of pressure dont injure operating personnel. Page 21 of 32

Cable compartments shall be provided with removable undrilled plates of 3 mm thick for cable entries from bottom of the panel. 4.4.9.40 All Instruments, relays and control switches requiring manual intervention shall be flush mounted. 4.4.9.41 Panel doors shall be fitted with strong, heavy duty hinges and braced so as to prevent any sagging, bending or distortion. The hinged parts/doors have latches at two places. The hinges on panel doors should not deformed due to loads of relays, meters, operating switches, knobs etc. fitted on the panel doors. 4.4.9.42 All the metallic parts, enclosures, panel doors shall be earthed to a common earth busbar running along the entire length of the panel. The size of the earth busbar shall be selected for carrying the max. fault current. Two earthing terminals shall be brought out for connection to earthing grid. 4.4.9.43 Separate cable alleys shall be provided for power and control terminations. The power connectors up to 16 amps rating can be DIN rail mounting push type. The connectors above 16 amp. shall be bolted type with protective shrouds/covers. All the power terminals shall be provided with suitable rating terminals to terminate ring type lugs of power cables. The power terminals shall be properly tagged / labelled and shall be mounted separately from the control terminals. The control terminal block shall have 20 % extra terminals. 4.4.9.44 Power cable PVC FRLS (outer sheath) type- 3 nos. from alternator to existing switchgear & control cable FRLS (outer sheath) PVC insulated from AMF panel to existing switchgear shall be supply, laid, gland and terminated. 4.5.0 Technical requirement of Central Monitoring System 4.5.1 Central Monitoring System shall be designed with redundant processor, workstation loaded with suitable SCADA/HMI software, communication network with driver software, PC (LCD monitor 17) with printer and ups to be placed centralized near DG room at average distance of 20 mtrs. 4.5.2 Individual AMF panel of DG sets shall have Data integrator / mixer (see 4.4.9.38) to communicate on Ethernet/ Modbus / Other suitable communication facility with central monitoring system through separate Data converter. 4.5.3 Central Monitoring System shall monitor & store all important parameter of individual DG sets. Real time and historical data shall be shown on user friendly graphic display (mimic diagram). CMS shall have enough memory to store data for 6 month, for periodic data logging and to generate utility reports on excel sheet as per HWPK requirements. 4.5.4 CMS most show followings parameters: i) Energy Parameters- Voltage, Current, frequency, KW, KWh etc. ii) Engine parameter- Engine speed (rpm), lub. oil pressure and temperature , Intake air temp, Engine runtime (hour), temperature of cylinders, engine jacket water temperature, bearing & winding temperature of alternator etc. see(4.4.7.19). iii) Important parameter alarm/ trip/ status parameter from PLC/annunciator (see 4.4.9.37) as defined in of PLC. 4.5.5 CMC shall be supply with following components: a) PC of reputed make shall be supply with INTEL PENTIUM (core duo) processor, 2 GB RAM, 250 GB HDD, optical mouse, 17 colour LCD monitor, multimedia keyboard, Serial (RS232) port & data converter card suitable for 4 channel I/P with 20 % spare port, DVD combo drive complete with SCADA / driver software & all required accessories.Page 22 of 32

b) Latest HP Laser B/W A4 size printer complete with print technology, processor & USB port compatible with above-mentioned PC.

c) Data converter, Shielded twisted pair serial communication cable from AMF panel to CMC, hardware etc. required shall be in the scope of supplier. 4.6.0 Technical requirement of modification of existing system 4.6.1 Presently All four DG sets (three operating & one standby) are operating with existing 415 volt (Class-III) switchgear. They are designed to automatically come in line in case of failure of grid supply (Class-IV) and connected to their respective buses (three main Bus-Q, Bus-R, Bus-T and one standby Bus- S) as per existing logic and same shall be retained. 4.6.2 When class IV (grid supply) power resumes, DG sets are gets synchronized & load transfer from DG set to grid without break. We are having common synchronization system for all DGs with plug in arrangement to synchronize one by one DG with their respective buses (grid supply). We have planned to use same system for synchronization by replacing the components of synchronization panel. 4.6.3 Components Need to be supply for replacing are as follows: a) Current Transformer of Ratio- 800/5 (20/5P10) - 4nos. 800/5(15/5P10) -4nos. 800/5(20 CL1) 3 nos., 800/0.5- 1 no. (see sketch / dimension details). b) Synchronizing relay, synchronoscope, frequency meters, voltmeters etc. c) Manual freq raise lower button 4 nos., AVR manual remote potentiometer- 4 nos. 4.7.0 List of spares to be obtained for our use after guarantee period of DG sets: (i) Diesel Engine: a) b) c) d) e) f) g) h) i) j) All Engine Bearings/Bushes- 1 set Piston Assembly including piston rings, connecting rods, bolts etc. 2 nos. Piston rings(all types)- 1 set Inlet valve and exhaust valve-1 set Main lub oil pump assembly- 1 no. Main fuel oil pump assembly-1no. Fuel Injection pump-1no. Gaskets and O rings-1 set. Turbo Charger assembly-1 no. Coupling assembly complete-1no.

(ii) Lube Oil Filters: a) b) c) Filter Cartridge/Elements-1 set Cartridge Guide- 2 no. Set of filter gaskets/O rings-1 set

(iii) Fuel Oil Filters:Page 23 of 32

a) b) c)

Filter Cartridge/Elements-1 set Cartridge Guide- 2 no. Set of filter gaskets/O rings-1 set

(iv) Aux Lube Oil pump: a) b) c) d) Pump Assembly with motor & coupling 1 set Set of bearings/Sleeve- 1 set Mechanical shaft, Seal- 1 set Set of gaskets/O rings- 1 set (v) a) b) c) d) e) f) g) h) Electrical Alternator:

Set of bearings 1 set Rotating Diode assembly- 1 set Diode Fuse 20 % of total qty AVR cards 1 no. Governor Controller 1no. Potential transformer one of each type- 1 no. Current Transformer one of each type- 1 no. Control transformers one of each type- 1 no (vi) Instrumentation:

a)

10 % of spare instruments or 1 of each type 1 set

Page 24 of 32

5.0 TRAINING:Successful bidder, before erection and commissioning of Diesel Generator sets at HWPK Site will arrange for training of engineers- 2 nos. and technician-3 nos. for operation and maintenance of DG set, PLC and associated equipments at their premises/factory.

6.0 TECHNICALSPECIFICATIONS: 6.1. Guaranteed Technical Specifications of Diesel Generator Sets: Engine Specifications/ make Rated Prime rating Overload capability Type of Engine Aspiration Engine cooling system Governing System Starting Noise emission control Transient/ Governor characteristics Standard applicable Alternator specification / make Rating (kW)/ Power Factor Rated Voltage Rated speed / freq. Excitation / AVR Cooling Rated Making Capacity Rated symmetrical short circuit rating S.C. ratio Reputed make 400 kW at 1500 rpm Min. 10 % for 1 hour in every 12 hour operation In line, 4 stroke, compression ignition type. Turbocharged after cooled Radiator type Electronic besides hydraulic Self starting Acoustic enclosure As per Class A2 IS-10002, ISO-3046 / 85280 Reputed make as per IS 4722 400 kW / 0.8 p.f. 3 , 415 volt +/- 5 % 1500 rpm / 50 Hz Brushless excitation /Digital AVR with manual setting Totally enclosed fan cooled (TEFC) 110 k Ap 36 MVA / 50 kA at 415 voilt 0.5

1. a) b) c) d) e) f) g) h) i) j) 2. a) b) c) d) e) f) g) h)

Note- Equipment shall be of similar or higher rating.

Page 25 of 32

7.0 TESTS AND INSPECTION:7.1 The DG sets shall be of proven design and should have been type tested as per IS 10000 / 10002 and IS 4722 / 7132 from reputed laboratory of the country within 5 years. Copy of type test results shall be submitted for review. Type test should have been performed on at least one type of item of a group of identical items to be supplied. 7.2 Routine/ performance tests of Diesel Generator sets shall be carried out at manufacturers premises as per IS:10000 / IS:4722 / technical specifications of our tender in presence of HWPK representatives. 7.3 Provisional list of test to be performed is given below: 7.3.1 Type test: 7.3.1.1 For Diesel Machine (i) Initial performance test a) Twelve hour rating test of engine b) Fuel consumption test c) Governing test (ii) Endurance test (iii) Determination of power (iv) Mechanical efficiency determination (v) Lubricating oil consumption (vi) Test for smoke level, emission etc. 7.3.1.2 For Alternator(i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix)

Measurement of winding resistance

Measurement of leakage resistance & potier reactances Measurement of open-circuit characteristics & parameter Measurement of short-circuit characteristics & parameter Efficiency test Temperature rise-test Over speed test Dielectric test Short-circuit withstand and measurement of reactance & time const

Page 26 of 32

7.3.2 Routine Test: 7.3.2.1 For Diesel Machine(i) (ii)

Determination of power Fuel consumption test

(iii) Lubricating oil consumption

7.3.2.2 For Alternator(i) (ii)

Measurement of winding resistance of stator, field etc. Insulation resistance test

(iii) Phase sequence test (iv) Measurement of open-circuit characteristics & parameter (v)

Measurement of short-circuit characteristics & parameter

7.3 After the stand-alone test of Diesel machine and alternator is complete the bidders/ supplier shall perform functional test of PLC, AMF panel etc. and show integration of PLC, Electronic control panel, communicating devices etc. with central monitoring system. 7.4 Specification sheet & Quality Assurance plan, which shall include tests during manufacturing, routine tests, type test etc. has to be submitted for approval before supply of DG sets.

Page 27 of 32

8.0 ENGINEERING, MANUFACTURING AND MAINTENANCE FACILITY:8.1 The DG sets with all accessories shall be engineered and supply as per technical specifications and drawings shall be submitted for our approval. 8.2 The DG sets shall be tested and inspected at the DG sets manufacture factory. HWPK shall reserves the right to inspect the manufacturing facility before finalization of purchase order.

9.0 DRAWING & DATA SHEETS:9.1 The bidder shall furnish the following drawing and data along with the offer: 9.1.1 Technical particulars/catalogues for the offered system & detailed description of the system. The description should be self explanatory with required sketches/diagrams and prove the technical suitability of the item offered. 9.1.2 Complete filled in data sheet for all equipment. 9.1.3 Bill of materials and recommended list of spares for two years trouble free operation (for our future use). 9.1.4 Bidder should submit two copies of technical bid (in duplicate). 9.1.5 Bidder shall submit 4 sets of final and approved copy of all drawings, datasheet, specification sheet, manual etc. and one set of soft copy for all documents. 9.2 DATA SHEET (DEMOGRAPHIC DATA): HWP (K) is situated in village Anushakti (Rawatbhata) on the bank of Chambal River, 60 Kms. away from Kota by the side of KotaGandhi Sagar Road. Kota is a big railway junction of western railway. Site Condition a) Altitude b) Humidity c) Indoor/outdoor installation d) Climate Owner Less than 1000 M above MSL 95% non condensing Indoor, Non-AC & may have dust particles. Tropical with temperature variation 3 C to 47.5 Government of India, Department of Atomic Energy.

9.3 OTHER TECHNICAL DETAILS FOR REFERENCE:(i) (ii) (iii)

Existing Class-III switchgear arrangement single line diagram. Layout drawing of existing DG sets enclosed. Dimension details of existing current transformer.Page 28 of 32

10. TECHNICAL DATA TO BE FILLED BY TENDERER:A. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Diesel Engine Name of the Manufacturer Type / Model No. Application code / Standards Rated Prime rating (kW) Gross Engine power output (hp) Rated speed at full load (rpm) Overload capability (for 1 hr in every 12 hr) Type of Engine Aspiration No. of cylinder Bore x stroke length (mm x mm) Displacement (cc / liter) Firing order Compression ratio Air to fuel ratio Piston speed Engine cooling system (type) Coolant capacity (liter) Governing System (class) Load variations Maximum change of speed as a percentage of rated speed On suddenly taking off or Transient Change throwing on the rated load Permanent Change On change of load by any step Transient Change of 20 percent of the rated load Permanent Change at 100 % load Fuel consumption at 75 % load rate at 50 % load at 25 % load Heat rejection to ambient Heat rejection Heat rejection to coolant rate Heat rejection to exhaust Heat rejection to fuel Heat rejection to after cooler Cranking motor rating volt/kW Starting system No. of battery Battery voltage / amp-hr rating Grade of oil Lub. Oil Consumption rate / 100 hr. of running system Total system capacity Maximum Oil temperature Combustion air inlet flow rate (m3/min) Type of silencer (grade)Page 29 of 32

20

21

22

23

24 25

Exhaust system

Exhaust stack gas temperature (deg C) Exhaust gas flow rate (m3/min) Exhaust flange size (internal diameter) (mm) Exhaust system backpressure (maximum) (kPa) Type of enclosure Sound level at 1 meter (db) Sound attenuation (db) Materials used for sound attenuation

26 27 28 29 30 31 B. 1. 2 3 4 5 6 7 8 9 10

Noise emission control

11.

12 13 14 15 16 17 18 19 20 21

Dry weight ( kg) Gross weight (kg) Moment of inertia of rotating equipment with flywheel & fan (kg-m2 ) Acceleration time of engine from cold to idle speed HSD fuel tank capacity ( in liter) Alternator Name of the Manufacturer Type / Model No. / frame size Rating ( kVA / kW / p.f.) Rated Voltage (volt) Stator insulation class Rated insulation level (KVp) One minute power frequency withstand voltage Lighting impulse withstand voltage Rated Speed / Frequency (rpm / Hz) Rated full load current (Amp) Efficiency @ 100 % upf / 0.8 pf @ 75 % @ 50 % Resistance Stator resistance (ohm) Rotor resistance ( ohm ) Sub transient direct axis Reactances (x) Sub transient quadrature With time constants () Transient saturated Synchronous direct axis Synchronous quadratue axis Reactances Negative sequence (X2) Zero sequence (X0) Short circuit ratio Rated short circuit current ( kA) Rated fault MVA at 415 volt Type of cooling Over load capacity 10 % ( hr) 50 % Type of excitation Field voltage / current at rated load at u.p.f at 0.8 pf lagging Method of protection against shaft currents Rotor insulation class Exciter ceiling voltage (volt)Page 30 of 32

Rotor critical speed 22 23 24 25 rpm Temperature rise Weight of rotor / moment of inertia (kg/ kg-m2 ) Gross weight of Alternator (kg)

(rpm)

C. 1.

AMF panel Circuit breaker

2. 3. 4. 5. 6. D. 1.

2. 3. 4. 5. 6. 7. 8.

Continuous current rating Short time current rating Peak making current Power freq. withstand voltage Duty cycle Opening time Closing time Control voltage for closing / tripping/ spring charging motor Make & type of Automatic voltage regulator Make & model of power analyzer/ tri-vector meter Make & rating of indicating lamp ( rating) Window annunciation type, make & size ( no. of window/ row) Colour shade of AMF panel General Overall efficiency of at 25 % DG sets at % of rated at 50 % load at 75 % at 100 % Highest starting load permissible at % at 50 % of running load at 75% Control cable type Power cable size & type ( PVC / FRLS ) History of manufacturing and earlier installation in India for getting feed back. Enclose list Delivery period. Time period for installation & commissioning of one DG sets List of deviations, if any, from purchasers requirements. Enclose list

Rating

Note: 1. Partially filled data sheets or incomplete technical information is liable for rejection. 2. Every para of the tender should be thoroughly studied and requirement mentioned should be addressed with back up records in the technical part of the tender. 3. Each page of this document and extra sheet submit by the bidder should be signed along with its official seal. Clarification regarding site conditions and system for which the Diesel Generator sets are required can be obtained from;Page 31 of 32

General Manager, Heavy Water Plant (Kota), PO: Anushakti, Via: Kota, Rajasthan between 0900 hrs. and 1700 hrs. on any working day. Following are the contact details: Phone No. 01475# 242201, Fax No.-01475#242203

Page 32 of 32