BMS-IFDD02E2
INSTALLATION MANUAL
DIGITAL INPUT/OUTPUTRELAY INTERFACE
Thank you very much for purchasing this TOSHIBA Digital Input/Output Relay Interface.
Please read this manual carefully beforehand for proper installation of the relay interface.
CONTENTSPrecautions for Safety.................................................................................................................... 1
Introduction ..................................................................................................................................... 2
Before Installation .......................................................................................................................... 3
1 Installation.................................................................................................................................... 42 Conection of Power cables/Earth wires/Singl wires ............................................................... 5
3 Setting .......................................................................................................................................... 8
4 Trial Operation Check ................................................................................................................. 9
7/27/2019 Di-do Relay Interface
2/12
1
Precautions for Safety
Read these Precautions for Safety carefully before installation.
The precautions described below include important items regarding safety. Observe them without fail.
After the installation work, perform a trial operation to check for any problem. Follow the Owner's
Manual to explain how to use and maintain the unit to the customer. Ask the customer to keep this
Installation Manual together with the Owners Manual.
Ask an authorized dealer or qualified installation professional to install or reinstall the relayinterface.
Improper installation may result in electric shock or fire.
Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
Perform installation work properly according to this Installation Manual.
Improper installation may result in electric shock or fire.
Do not modify the unit.
Any modification may cause a malfunction, resulting in overheating or fire.
WARNING
Perform wiring correctly in accordance with specified the current capacity.
Failure to do so may result in short-circuiting, overheating, or fire.
Connect the specified cables for the terminals securely to prevent external forces fromaffecting them.
Failure to do so may result in disconnection, overheating, or fire.
CAUTION
7/27/2019 Di-do Relay Interface
3/12
2
Introduction
nApplications/Functions/Specifications
Power supply
Power consumption
Operating temperature/
humidityStorage temperature
Chassis material
Dimensions
Mass
220 - 240 V, AC 50/60 Hz
6.5 W
0 to 40 C, 10 to 90% RH
-20 to +60 C
Galvanized sheet metal 0.8t(no coating)
66(H) x 193(W) x 246(D) mm
1.65 kg
234
18
18
(193)
92.5
64.5
18
18
53.5
103.5
63
.6
6
6
220
246
Grommet forpower input
Grommet forDigital Inputs
Grommet forRS485
Grommet forDigital Outputs
Applications/Functions/Specifications
Applications
The Digital Input/Output Relay Interface is used to control air conditioners by interlocking them withelectric lock signals and fire alarm signals, and to transmit air conditioner failures to other devices.
Functions
The Digital Input/Output Relay Interface connects non-voltage contact signals, transmits their input
status to the Touch Screen Controller, and outputs signals from the contacts (open collector) according
to the command from the Touch Screen Controller.
Specifications
External View
Digitalinput
Digitaloutput
Input type
Input points
Input registance
Input "ON" currentOutput type
Output points
Output current
Output voltage
Photo-coupler insulation
8 points
9 k ohm
1 mAOpen collector
4 points
Max. 35 mA (per point)
Less than DC 24V
DC 12 V, 120 mAExternal power supply forInput/Output
7/27/2019 Di-do Relay Interface
4/12
3
Before Installation
Check the following package contents.
Use the following wiring materials to connect signal lines and power lines. (Procured on site.)
No.
1
2
3
4
Quantity
1
1
4
2
Item
DIGITAL INPUT/OUTPUT RELAY INTERFACE
Installation Manual
Screw
Pin terminal
Remarks
M4 x 12mm tapping screws
No.
1
2
3
Type
Wire size
Length
Type
Wire size
LengthType
Wire size
Line
For RS-485
For digital Input/Outputconnection
For power
Description
2-core shield wire
1.25mm2, 500m max. (total length)
2-core wire, 0.3mm2, 100m max.
H07 RN-F or 245IEC660.75mm2, 50 m max.
7/27/2019 Di-do Relay Interface
5/12
4
1 Installation
Do not install the unit in any of the following places.
Humid or wet place Dusty place Place exposed to direct sunlight Place where there is a TV set or radio within one meter Place exposed to rain (outdoors, under eaves, etc.)
REQUIREMENT
100mm
100mm
100mm
Digital Input/Output Relay Interface Installation Method and Orientation
There are five installation methods for this relay interface as shown below, surface mount or wall mount.
Use the attached screws.
Installation Space and Maintenance Space
A side space for connecting through cable inlets and an upper space for maintenance must be reservedbefore installation.
The other sides can be adjacent to surrounding objects.
No good
7/27/2019 Di-do Relay Interface
6/12
5
Disconnect the appliance from the main power supply.
This appliance must be connected to the main power supply by a circuit breaker or switch with acontact separation of at least 3mm.
REQUIREMENT
ON
SW1
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
FG
B
DO1
DO2
DO3
DO4
GND
+12V
A
SW2SW3
S W4 S W7
1 2 3 4
N
3535 35 66
10
55 10
RS-485
L
Secure eachcable with a cableclamp.
Power cable
Secure eachcable with acable clamp.
Digital inputcontacts
Touch ScreenController
Digital outputload
Length of strippedpower cable
Length of strippedcommunication wire
Length of stripped digitalInput/Output connector wire
Insert the wire by pushing thelever with a screwdriver. Checkthat the wire is inserted securely.
When inserting two RS-485communication cables into asingle terminal for connection toanother interface, crimp themusing the attached pin terminal.
Power cables/Earth wires/Signal wires
Connection of Power cables/Earth wires/2 Signal wires
Connect power cables, earth wires, and signal wires to the specified terminals on the terminal block.
The RS-485 signal wire has polarity. Connect A to A, and B to B. If connected with incorrect polarity,the unit will not work.
CAUTION
Connect the earthwire to the earthterminal on thechassis.
7/27/2019 Di-do Relay Interface
7/12
6
If an inductive load (relay coil) or a bulb is connected, a surge voltage or rush current will begenerated. Take adequate measures against surge voltage or rush current.
CAUTION
Wiring Connection
The following describes wiring connections of the Digital Input/Output Relay Interface when it is used in
the air conditioner control system.
Terminator resistor setting
Set the RS-485 terminator resistor by the TCS-NET Relay Interface.
Do not set it by the Digital Input/Output Relay Interface.
Shield earthingThe shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the TouchScreen Controller.
Other shield lines should be closed, and the terminal end should be open and insulated.
Connection of external digital inputs
Input circuit examples are shown below (electrically isolated using a photo-coupler).
(1) Example of contact input connection
12V 12V
(2) Example of current sink connection
Connection of external digital outputs
Output circuit examples are shown below (open collector output electrically isolated using a photo-
coupler).
(1) Example of load connection (2) Example of load connection
12V
GND
12V+12V
Connection of Power cables/Earth wires/2 Signal wires (continued)
Contact
Input terminal
DI-1 to DI-8 Current sink
Input terminal
DI-1 to DI-8
Output terminalDO1 to DO4 Load
Externalpowersupply Output terminal
DO1 to DO4
7/27/2019 Di-do Relay Interface
8/12
7
A
A
B
FG
U1
U2
TCC-LINK
RS-485
B
4
SW1
ADDRESS
A
B
RS-485
A
B
RS-485
DI8
+12V
GND
DO4
DO3
DO2
DO1
+12V
GNDDO4
DO3
DO2
DO1
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
1
SW1
ADDRESS
A
B
L
N
L
N
L
N
Connection diagram
The shield earth of the RS-485signal wires should be single-pointearth. Earth the wires on the TouchScreen Controller.
Set the Digital Input/Output RelayInterface address with SW1. Assign1 to 4 to each address to avoidduplication. You can set the digitalInput/Output Relay Interface addressindependently from the TCC-LINKRelay Interface address or theEnergy Monitoring Relay Interface
address.CAUTION: The SW1 setting is readwhen the power is turned on. Pushthe reset switch (SW7) afterchanging the address.
TCS-NET RELAYINTERFACE
CAUTION: Set the RS-485terminator resistor on the TCS-NETRelay Interface. No terminator
resistor setting switch is providedon the Digital Input/Output RelayInterface.
The RS-485 signal wire haspolarity A and B. Be careful whenconnecting the wire.
Red/O
range
Brown/Yellow
Powersupply
Input contact 1
Input contact 2
Input contact 3
Input contact 4
Input contact 5
Input contact 6
Input contact 7
Input contact 8
Load 1
Load 2
Load 3
Load 4
Input contact 1
Input contact 2
Input contact 3
Input contact 4
Input contact 5
Input contact 6
Input contact 7
Input contact 8
Load 1
Load 2
Load 3
Load 4
Red
Orange
Yell
ow
Brown
Crimp3wireswith
aclosedendwirejo
int.
Connect theshield wire of thetwo wires
Connection of Power cables/Earth wires/2 Signal wires (continued)
Powe
rsupply
Powersupply
TOUCH
SCREEN
CONTROLLER
DIGITAL I/OINTERFACE
DIGITAL I/OINTERFACE
7/27/2019 Di-do Relay Interface
9/12
8
3 Setting
ON
SW1 SW2SW3
LED2
LED3
LED4
LED5
LED1
LED17
LED16
LED15
LED14
SW4 SW7
1 2 3 4
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
N
L
B
DO1
DO2
DO3
DO4
GND
+12V
ARS-485
SW1
SW2SW3
SW4
SW7
LED1
LED2
LED3
LED4
LED5
LED14 -LED17
Address set switch
1 - 4 Address
0,5 - F Not used
Operating mode set switch (0 usually)Test switch (all OFF usually)
Test switch
Reset switch
Power indicator
RS-485 communication status indicator
Not used
Test indicator
Test indicator
Digital output indicator
Set relay interface addresses according to the air conditioner address table. When the SW1 setting has been changed, push the reset switch SW7. The new address
setting is read.
CAUTION
The following settings are necessary to use Digital Input/Output Relay Interfaces. SW1 Address set switch
When two or more Digital Input/Output Relay Interfaces are used, set a different address for each
unit to avoid address duplication.
Assign addresses in ascending order.
SW2 Operation mode set switch
SW3 Test switch
SW4 Test switch
SW7 Reset switch
When performing address setting with SW1, push this reset switch after address setting to read
the set value.
These switches are not used during normal
operation. Set zero (0) or all OFF.
7/27/2019 Di-do Relay Interface
10/12
9
4 Trial Operation CheckBefore starting trial operation
Turn on the power of the Digital Input/Output Relay Interface after all cable connections and settings are
completed. Turn on power of the air conditioning control system.
Trial operation
Confirming external input connection
In the test mode, when the external inputs connected to the input terminals DI-1 to DI-8 are ON, the
respective LEDs will goes on so you can confirm the connection.
Confirming procedure:
Set the operation mode switch SW2 to 3, and push the reset switch SW7 to enter the test mode.
Unless SW4 is pushed, the respective input status of DI-1 to DI-4 is indicated by LED2 to LED5.
When SW4 is pushed, the respective input status of DI-5 to DI-8 is indicated by LED2 to LED5.
(*) To return to the normal operation, reset SW2 to zero (0) and push SW7.
SW4 OFF
SW4 ON
LED2
Displays DI-1 inputstatus.
Displays DI-5 inputstatus.
LED3
Displays DI-2 inputstatus.
Displays DI-6 inputstatus.
LED4
Displays DI-3 inputstatus.
Displays DI-7 inputstatus.
LED5
Displays DI-4 inputstatus.
Displays DI-8 inputstatus.
Input ON: LED lightsInput OFF: LED turns off
Checking external output connection
In the test mode, you can set output terminals DO1 to DO4 to ON or OFF with the test switch. Their
output status is indicated by each LED.
Checking procedure:Set the operation mode switch SW2 to 3 in the same way as the external input check, and then
push the reset switch SW7 to enter the test mode.
When the bit of the test switch SW3 is set to ON, the external output turns ON; when set to OFF,
the external output turns OFF.
Bits 1 to 4 of SW3 correspond to output terminals DO1 to DO4.
The respective output status of output terminals DO1 to DO4 is indicated by LED14 to LED17.
The LEDs light with the output ON, and goes off with the output OFF.
(*)To return to normal operation, reset SW2 to zero (0) and push SW7.
LED14
Displays DO1 output
status.
LED15
Displays DO2 output
status.
LED16
Displays DO3 output
status.
LED17
Displays DO4 output
status.Output ON: LED lightsOutput OFF: LED turns off
Checking the RS-485 communication status
Use LED2 for checking the RS-485 communication status.
When RS-485 communication with Touch Screen Controller is normal, LED2 will blink.
LED1
LED2
LED3LED4
LED5
Power indicator
RS-485 communicationstatus indicator
Not usedTest indicator
Test indicator
Normal
ON
Blinking
OFFOFF
OFF
Abnormal
OFF
OFF