  • 7/27/2019 Di-do Relay Interface

    1/12

    BMS-IFDD02E2

    INSTALLATION MANUAL

    DIGITAL INPUT/OUTPUTRELAY INTERFACE

    Thank you very much for purchasing this TOSHIBA Digital Input/Output Relay Interface.

    Please read this manual carefully beforehand for proper installation of the relay interface.

    CONTENTSPrecautions for Safety.................................................................................................................... 1

    Introduction ..................................................................................................................................... 2

    Before Installation .......................................................................................................................... 3

    1 Installation.................................................................................................................................... 42 Conection of Power cables/Earth wires/Singl wires ............................................................... 5

    3 Setting .......................................................................................................................................... 8

    4 Trial Operation Check ................................................................................................................. 9

  • 7/27/2019 Di-do Relay Interface

    2/12

    1

    Precautions for Safety

    Read these Precautions for Safety carefully before installation.

    The precautions described below include important items regarding safety. Observe them without fail.

    After the installation work, perform a trial operation to check for any problem. Follow the Owner's

    Manual to explain how to use and maintain the unit to the customer. Ask the customer to keep this

    Installation Manual together with the Owners Manual.

    Ask an authorized dealer or qualified installation professional to install or reinstall the relayinterface.

    Improper installation may result in electric shock or fire.

    Turn off the main power supply switch or breaker before attempting any electrical work.

    Make sure all power switches are off. Failure to do so may cause electric shock.

    Perform installation work properly according to this Installation Manual.

    Improper installation may result in electric shock or fire.

    Do not modify the unit.

    Any modification may cause a malfunction, resulting in overheating or fire.

    WARNING

    Perform wiring correctly in accordance with specified the current capacity.

    Failure to do so may result in short-circuiting, overheating, or fire.

    Connect the specified cables for the terminals securely to prevent external forces fromaffecting them.

    Failure to do so may result in disconnection, overheating, or fire.

    CAUTION

  • 7/27/2019 Di-do Relay Interface

    3/12

    2

    Introduction

    nApplications/Functions/Specifications

    Power supply

    Power consumption

    Operating temperature/

    humidityStorage temperature

    Chassis material

    Dimensions

    Mass

    220 - 240 V, AC 50/60 Hz

    6.5 W

    0 to 40 C, 10 to 90% RH

    -20 to +60 C

    Galvanized sheet metal 0.8t(no coating)

    66(H) x 193(W) x 246(D) mm

    1.65 kg

    234

    18

    18

    (193)

    92.5

    64.5

    18

    18

    53.5

    103.5

    63

    .6

    6

    6

    220

    246

    Grommet forpower input

    Grommet forDigital Inputs

    Grommet forRS485

    Grommet forDigital Outputs

    Applications/Functions/Specifications

    Applications

    The Digital Input/Output Relay Interface is used to control air conditioners by interlocking them withelectric lock signals and fire alarm signals, and to transmit air conditioner failures to other devices.

    Functions

    The Digital Input/Output Relay Interface connects non-voltage contact signals, transmits their input

    status to the Touch Screen Controller, and outputs signals from the contacts (open collector) according

    to the command from the Touch Screen Controller.

    Specifications

    External View

    Digitalinput

    Digitaloutput

    Input type

    Input points

    Input registance

    Input "ON" currentOutput type

    Output points

    Output current

    Output voltage

    Photo-coupler insulation

    8 points

    9 k ohm

    1 mAOpen collector

    4 points

    Max. 35 mA (per point)

    Less than DC 24V

    DC 12 V, 120 mAExternal power supply forInput/Output

  • 7/27/2019 Di-do Relay Interface

    4/12

    3

    Before Installation

    Check the following package contents.

    Use the following wiring materials to connect signal lines and power lines. (Procured on site.)

    No.

    1

    2

    3

    4

    Quantity

    1

    1

    4

    2

    Item

    DIGITAL INPUT/OUTPUT RELAY INTERFACE

    Installation Manual

    Screw

    Pin terminal

    Remarks

    M4 x 12mm tapping screws

    No.

    1

    2

    3

    Type

    Wire size

    Length

    Type

    Wire size

    LengthType

    Wire size

    Line

    For RS-485

    For digital Input/Outputconnection

    For power

    Description

    2-core shield wire

    1.25mm2, 500m max. (total length)

    2-core wire, 0.3mm2, 100m max.

    H07 RN-F or 245IEC660.75mm2, 50 m max.

  • 7/27/2019 Di-do Relay Interface

    5/12

    4

    1 Installation

    Do not install the unit in any of the following places.

    Humid or wet place Dusty place Place exposed to direct sunlight Place where there is a TV set or radio within one meter Place exposed to rain (outdoors, under eaves, etc.)

    REQUIREMENT

    100mm

    100mm

    100mm

    Digital Input/Output Relay Interface Installation Method and Orientation

    There are five installation methods for this relay interface as shown below, surface mount or wall mount.

    Use the attached screws.

    Installation Space and Maintenance Space

    A side space for connecting through cable inlets and an upper space for maintenance must be reservedbefore installation.

    The other sides can be adjacent to surrounding objects.

    No good

  • 7/27/2019 Di-do Relay Interface

    6/12

    5

    Disconnect the appliance from the main power supply.

    This appliance must be connected to the main power supply by a circuit breaker or switch with acontact separation of at least 3mm.

    REQUIREMENT

    ON

    SW1

    DI1

    DI2

    DI3

    DI4

    DI5

    DI6

    DI7

    DI8

    FG

    B

    DO1

    DO2

    DO3

    DO4

    GND

    +12V

    A

    SW2SW3

    S W4 S W7

    1 2 3 4

    N

    3535 35 66

    10

    55 10

    RS-485

    L

    Secure eachcable with a cableclamp.

    Power cable

    Secure eachcable with acable clamp.

    Digital inputcontacts

    Touch ScreenController

    Digital outputload

    Length of strippedpower cable

    Length of strippedcommunication wire

    Length of stripped digitalInput/Output connector wire

    Insert the wire by pushing thelever with a screwdriver. Checkthat the wire is inserted securely.

    When inserting two RS-485communication cables into asingle terminal for connection toanother interface, crimp themusing the attached pin terminal.

    Power cables/Earth wires/Signal wires

    Connection of Power cables/Earth wires/2 Signal wires

    Connect power cables, earth wires, and signal wires to the specified terminals on the terminal block.

    The RS-485 signal wire has polarity. Connect A to A, and B to B. If connected with incorrect polarity,the unit will not work.

    CAUTION

    Connect the earthwire to the earthterminal on thechassis.

  • 7/27/2019 Di-do Relay Interface

    7/12

    6

    If an inductive load (relay coil) or a bulb is connected, a surge voltage or rush current will begenerated. Take adequate measures against surge voltage or rush current.

    CAUTION

    Wiring Connection

    The following describes wiring connections of the Digital Input/Output Relay Interface when it is used in

    the air conditioner control system.

    Terminator resistor setting

    Set the RS-485 terminator resistor by the TCS-NET Relay Interface.

    Do not set it by the Digital Input/Output Relay Interface.

    Shield earthingThe shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the TouchScreen Controller.

    Other shield lines should be closed, and the terminal end should be open and insulated.

    Connection of external digital inputs

    Input circuit examples are shown below (electrically isolated using a photo-coupler).

    (1) Example of contact input connection

    12V 12V

    (2) Example of current sink connection

    Connection of external digital outputs

    Output circuit examples are shown below (open collector output electrically isolated using a photo-

    coupler).

    (1) Example of load connection (2) Example of load connection

    12V

    GND

    12V+12V

    Connection of Power cables/Earth wires/2 Signal wires (continued)

    Contact

    Input terminal

    DI-1 to DI-8 Current sink

    Input terminal

    DI-1 to DI-8

    Output terminalDO1 to DO4 Load

    Externalpowersupply Output terminal

    DO1 to DO4

  • 7/27/2019 Di-do Relay Interface

    8/12

    7

    A

    A

    B

    FG

    U1

    U2

    TCC-LINK

    RS-485

    B

    4

    SW1

    ADDRESS

    A

    B

    RS-485

    A

    B

    RS-485

    DI8

    +12V

    GND

    DO4

    DO3

    DO2

    DO1

    +12V

    GNDDO4

    DO3

    DO2

    DO1

    DI7

    DI6

    DI5

    DI4

    DI3

    DI2

    DI1

    DI8

    DI7

    DI6

    DI5

    DI4

    DI3

    DI2

    DI1

    1

    SW1

    ADDRESS

    A

    B

    L

    N

    L

    N

    L

    N

    Connection diagram

    The shield earth of the RS-485signal wires should be single-pointearth. Earth the wires on the TouchScreen Controller.

    Set the Digital Input/Output RelayInterface address with SW1. Assign1 to 4 to each address to avoidduplication. You can set the digitalInput/Output Relay Interface addressindependently from the TCC-LINKRelay Interface address or theEnergy Monitoring Relay Interface

    address.CAUTION: The SW1 setting is readwhen the power is turned on. Pushthe reset switch (SW7) afterchanging the address.

    TCS-NET RELAYINTERFACE

    CAUTION: Set the RS-485terminator resistor on the TCS-NETRelay Interface. No terminator

    resistor setting switch is providedon the Digital Input/Output RelayInterface.

    The RS-485 signal wire haspolarity A and B. Be careful whenconnecting the wire.

    Red/O

    range

    Brown/Yellow

    Powersupply

    Input contact 1

    Input contact 2

    Input contact 3

    Input contact 4

    Input contact 5

    Input contact 6

    Input contact 7

    Input contact 8

    Load 1

    Load 2

    Load 3

    Load 4

    Input contact 1

    Input contact 2

    Input contact 3

    Input contact 4

    Input contact 5

    Input contact 6

    Input contact 7

    Input contact 8

    Load 1

    Load 2

    Load 3

    Load 4

    Red

    Orange

    Yell

    ow

    Brown

    Crimp3wireswith

    aclosedendwirejo

    int.

    Connect theshield wire of thetwo wires

    Connection of Power cables/Earth wires/2 Signal wires (continued)

    Powe

    rsupply

    Powersupply

    TOUCH

    SCREEN

    CONTROLLER

    DIGITAL I/OINTERFACE

    DIGITAL I/OINTERFACE

  • 7/27/2019 Di-do Relay Interface

    9/12

    8

    3 Setting

    ON

    SW1 SW2SW3

    LED2

    LED3

    LED4

    LED5

    LED1

    LED17

    LED16

    LED15

    LED14

    SW4 SW7

    1 2 3 4

    DI1

    DI2

    DI3

    DI4

    DI5

    DI6

    DI7

    DI8

    N

    L

    B

    DO1

    DO2

    DO3

    DO4

    GND

    +12V

    ARS-485

    SW1

    SW2SW3

    SW4

    SW7

    LED1

    LED2

    LED3

    LED4

    LED5

    LED14 -LED17

    Address set switch

    1 - 4 Address

    0,5 - F Not used

    Operating mode set switch (0 usually)Test switch (all OFF usually)

    Test switch

    Reset switch

    Power indicator

    RS-485 communication status indicator

    Not used

    Test indicator

    Test indicator

    Digital output indicator

    Set relay interface addresses according to the air conditioner address table. When the SW1 setting has been changed, push the reset switch SW7. The new address

    setting is read.

    CAUTION

    The following settings are necessary to use Digital Input/Output Relay Interfaces. SW1 Address set switch

    When two or more Digital Input/Output Relay Interfaces are used, set a different address for each

    unit to avoid address duplication.

    Assign addresses in ascending order.

    SW2 Operation mode set switch

    SW3 Test switch

    SW4 Test switch

    SW7 Reset switch

    When performing address setting with SW1, push this reset switch after address setting to read

    the set value.

    These switches are not used during normal

    operation. Set zero (0) or all OFF.

  • 7/27/2019 Di-do Relay Interface

    10/12

    9

    4 Trial Operation CheckBefore starting trial operation

    Turn on the power of the Digital Input/Output Relay Interface after all cable connections and settings are

    completed. Turn on power of the air conditioning control system.

    Trial operation

    Confirming external input connection

    In the test mode, when the external inputs connected to the input terminals DI-1 to DI-8 are ON, the

    respective LEDs will goes on so you can confirm the connection.

    Confirming procedure:

    Set the operation mode switch SW2 to 3, and push the reset switch SW7 to enter the test mode.

    Unless SW4 is pushed, the respective input status of DI-1 to DI-4 is indicated by LED2 to LED5.

    When SW4 is pushed, the respective input status of DI-5 to DI-8 is indicated by LED2 to LED5.

    (*) To return to the normal operation, reset SW2 to zero (0) and push SW7.

    SW4 OFF

    SW4 ON

    LED2

    Displays DI-1 inputstatus.

    Displays DI-5 inputstatus.

    LED3

    Displays DI-2 inputstatus.

    Displays DI-6 inputstatus.

    LED4

    Displays DI-3 inputstatus.

    Displays DI-7 inputstatus.

    LED5

    Displays DI-4 inputstatus.

    Displays DI-8 inputstatus.

    Input ON: LED lightsInput OFF: LED turns off

    Checking external output connection

    In the test mode, you can set output terminals DO1 to DO4 to ON or OFF with the test switch. Their

    output status is indicated by each LED.

    Checking procedure:Set the operation mode switch SW2 to 3 in the same way as the external input check, and then

    push the reset switch SW7 to enter the test mode.

    When the bit of the test switch SW3 is set to ON, the external output turns ON; when set to OFF,

    the external output turns OFF.

    Bits 1 to 4 of SW3 correspond to output terminals DO1 to DO4.

    The respective output status of output terminals DO1 to DO4 is indicated by LED14 to LED17.

    The LEDs light with the output ON, and goes off with the output OFF.

    (*)To return to normal operation, reset SW2 to zero (0) and push SW7.

    LED14

    Displays DO1 output

    status.

    LED15

    Displays DO2 output

    status.

    LED16

    Displays DO3 output

    status.

    LED17

    Displays DO4 output

    status.Output ON: LED lightsOutput OFF: LED turns off

    Checking the RS-485 communication status

    Use LED2 for checking the RS-485 communication status.

    When RS-485 communication with Touch Screen Controller is normal, LED2 will blink.

    LED1

    LED2

    LED3LED4

    LED5

    Power indicator

    RS-485 communicationstatus indicator

    Not usedTest indicator

    Test indicator

    Normal

    ON

    Blinking

    OFFOFF

    OFF

    Abnormal

    OFF

    OFF

  • 7/27/2019 Di-do Relay Interface

    11/12

    10

    Memo

  • 7/27/2019 Di-do Relay Interface

    12/12

    DH69409102