Upload
apb56
View
565
Download
8
Tags:
Embed Size (px)
DESCRIPTION
Sample street lighting calculation report from dialux
Citation preview
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
PHILIPS SGP551 T-POT A FG / Luminaire Data Sheet
See our luminaire catalog for an image of the luminaire.
Luminous emittance 1:
Luminaire classification according to CIE: 100CIE flux code: 38 75 97 100 81
Due to missing symmetry properties, no UGR table can be displayed for this luminaire.
Page 1
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
PHILIPS SGP551 T-POT M GB / Luminaire Data Sheet
See our luminaire catalog for an image of the luminaire.
Luminous emittance 1:
Luminaire classification according to CIE: 100CIE flux code: 37 71 96 100 82
Due to missing symmetry properties, no UGR table can be displayed for this luminaire.
Page 2
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
PHILIPS SGP551 T-POT M GB / Luminaire Data Sheet
See our luminaire catalog for an image of the luminaire.
Luminous emittance 1:
Luminaire classification according to CIE: 100CIE flux code: 37 71 96 100 85
Due to missing symmetry properties, no UGR table can be displayed for this luminaire.
Page 3
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
10m Corridor - Local Urban Access (Residential) / Planning data
Street Profile
Maintenance factor: 0.70
Cycle Lane (Width: 2.000 m)
Carriageway (Width: 3.650 m, Number of lanes: 1, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Foot Path (Width: 1.850 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 42.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.196 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 4
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
10m Corridor - Local Urban Access (Residential) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:344
Grid: 14 x 3 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.17 0.56 0.57 12 0.78Required values according to class: 0.75 0.40 0.50 30 0.50
Fulfilled/Not fulfilled:
Assigned Observer (1 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.825, 1.500) 1.17 0.56 0.57 12
Page 5
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
10m Corridor - Local Urban Access (Residential) / Cycle Lane / Results overview
Maintenance factor: 0.70 Scale 1:344
Grid: 14 x 3 Points Accompanying Street Elements: Cycle Lane.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] Emin [lx]
Calculated values: 11.73 6.17Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 6
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
10m Corridor - Local Urban Access (Residential) / Foot Path / Results overview
Maintenance factor: 0.70 Scale 1:344
Grid: 14 x 3 Points Accompanying Street Elements: Foot Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] Emin [lx]
Calculated values: 10.50 3.07Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 7
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
12m Corridor - Local Urban Access (Residential) / Planning data
Street Profile
Maintenance factor: 0.70
Shared Use Path (Width: 2.500 m)
Roadway 1 (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Lay-by 1 (Width: 2.200 m)
Sidewalk 1 (Width: 1.300 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 40.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): 0.004 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 8
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
12m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /
Results overview
Maintenance factor: 0.70 Scale 1:329
Grid: 14 x 6 Points Accompanying Street Elements: Roadway 1.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.29 0.48 0.52 15 0.58Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.500, 1.500) 1.40 0.49 0.63 10
2 Observer 3 (-60.000, 4.500, 1.500) 1.29 0.48 0.52 15
Page 9
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
12m Corridor - Local Urban Access (Residential) / Valuation Field Sidewalk 1 /
Results overview
Maintenance factor: 0.70 Scale 1:329
Grid: 14 x 3 Points Accompanying Street Elements: Sidewalk 1.Selected Lighting Class: S3 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 8.18 5.74Required values according to class: 7.50 1.50
Fulfilled/Not fulfilled:
Page 10
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
12m Corridor - Local Urban Access (Residential) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:329
Grid: 14 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 11.03 3.38Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 11
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
16m Corridor - Local Urban Access (Residential) / Planning data
Street Profile
Maintenance factor: 0.70
Shared Use Path (Width: 2.500 m)
Parking Bay (Width: 2.500 m)
Roadway 1 (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Shared Use Path (Width: 2.500 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 58.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.196 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 12
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
16m Corridor - Local Urban Access (Residential) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 58.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.196 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 13
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
16m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /
Results overview
Maintenance factor: 0.70 Scale 1:458
Grid: 3 x 3 Points Accompanying Street Elements: Roadway 1.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.41 0.66 0.62 13 0.69Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.500, 1.500) 1.41 0.66 0.65 9
2 Observer 3 (-60.000, 4.500, 1.500) 1.43 0.69 0.62 13
Page 14
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
16m Corridor - Local Urban Access (Residential) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:458
Grid: 20 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 10.10 3.49Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 15
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Residential) / Planning data
Street Profile
Maintenance factor: 0.70
Shared Use Path (Width: 4.500 m)
Parking Bay (Width: 2.500 m)
Roadway 1 (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Shared Use Path (Width: 4.500 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 50.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.496 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 16
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Residential) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 50.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.496 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 17
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Residential) / Valuation Field Roadway 1 /
Results overview
Maintenance factor: 0.70 Scale 1:401
Grid: 3 x 3 Points Accompanying Street Elements: Roadway 1.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav
[cd/m] U0 Ul TI [%] SR
Calculated values: 1.51 0.73 0.66 12 0.74Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.500, 1.500) 1.51 0.73 0.66 9
2 Observer 3 (-60.000, 4.500, 1.500) 1.53 0.82 0.71 12
Page 18
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Residential) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:401
Grid: 17 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav
[lx] Emin
[lx]
Calculated values: 10.15 3.20Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 19
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Residential) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:401
Grid: 17 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav
[lx] Emin
[lx]
Calculated values: 10.13 3.24Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 20
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Commercial) / Planning data
Street Profile
Maintenance factor: 0.70
Shared Use Path (Width: 3.500 m)
Buffer (Width: 0.700 m)
Parking Bay (Width: 2.500 m)
Carriageway (Width: 6.600 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Buffer (Width: 0.700 m)
Shared Use Path (Width: 3.500 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 46.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.696 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 21
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Commercial) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 46.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.696 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 22
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Commercial) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:372
Grid: 3 x 3 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav
[cd/m] U0 Ul TI [%] SR
Calculated values: 1.50 0.77 0.70 12 0.75Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.650, 1.500) 1.50 0.77 0.70 9
2 Observer 3 (-60.000, 4.950, 1.500) 1.51 0.83 0.70 12
Page 23
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Commercial) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:372
Grid: 16 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav
[lx] Emin
[lx]
Calculated values: 10.31 3.33Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 24
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
20m Corridor - Local Urban Access (Commercial) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:372
Grid: 16 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav
[lx] Emin
[lx]
Calculated values: 10.31 3.33Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 25
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Planning data
Street Profile
Maintenance factor: 0.70
Shared Use Path (Width: 4.000 m)
Buffer (Width: 2.500 m)
Parking Bay (Width: 2.500 m)
Carriageway (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Buffer (Width: 2.500 m)
Shared Use Path (Width: 4.000 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 38.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -3.796 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 26
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 38.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -3.796 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 27
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Residential) /
Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:315
Grid: 3 x 3 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav
[cd/m] U0 Ul TI [%] SR
Calculated values: 1.52 0.81 0.75 10 0.95Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.500, 1.500) 1.52 0.81 0.75 9
2 Observer 3 (-60.000, 4.500, 1.500) 1.53 0.81 0.89 10
Page 28
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Shared Use
Path / Results overview
Maintenance factor: 0.70 Scale 1:315
Grid: 13 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav
[lx] Emin
[lx]
Calculated values: 10.14 3.47Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 29
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Residential) / Shared Use
Path / Results overview
Maintenance factor: 0.70 Scale 1:315
Grid: 13 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav
[lx] Emin
[lx]
Calculated values: 10.11 3.44Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 30
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Planning data
Street Profile
Maintenance factor: 0.70
Footpath (Width: 2.350 m)
Buffer (Width: 0.850 m)
Cycle Track (Width: 1.500 m)
Grass Strip 1 (Width: 1.500 m)
Parking Bay (Width: 2.500 m)
Roadway 1 (Width: 6.000 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Grass Strip 2 (Width: 1.500 m)
Cycle Track (Width: 1.500 m)
Buffer (Width: 0.850 m)
Footpath (Width: 2.350 m)
Page 31
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 45.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -3.921 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, topPole Distance: 45.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -3.921 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 32
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Valuation
Field Roadway 1 / Results overview
Maintenance factor: 0.70 Scale 1:365
Grid: 15 x 6 Points Accompanying Street Elements: Roadway 1.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.26 0.76 0.70 11 0.97Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.500, 1.500) 1.26 0.76 0.70 10
2 Observer 4 (-60.000, 4.500, 1.500) 1.26 0.78 0.70 11
Page 33
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Footpath /
Results overview
Maintenance factor: 0.70 Scale 1:365
Grid: 15 x 3 Points Accompanying Street Elements: Footpath.Selected Lighting Class: S3 (All lighting performance requirements are met.)
Eav
[lx] Emin
[lx]
Calculated values: 7.91 2.21Required values according to class: 7.50 1.50
Fulfilled/Not fulfilled:
Page 34
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Footpath /
Results overview
Maintenance factor: 0.70 Scale 1:365
Grid: 15 x 3 Points Accompanying Street Elements: Footpath.Selected Lighting Class: S3 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 7.90 2.16Required values according to class: 7.50 1.50
Fulfilled/Not fulfilled:
Page 35
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Cycle
Track / Results overview
Maintenance factor: 0.70 Scale 1:365
Grid: 15 x 3 Points Accompanying Street Elements: Cycle Track.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 12.25 5.02Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 36
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
24m Corridor - Local Urban Access & Minor Urban Collector (Commercial) / Cycle
Track / Results overview
Maintenance factor: 0.70 Scale 1:365
Grid: 15 x 3 Points Accompanying Street Elements: Cycle Track.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 12.23 5.04Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 37
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Minor Urban Collector (Residential) / Planning data
Street Profile
Maintenance factor: 0.70
Shared Use Path (Width: 4.500 m)
Buffer (Width: 3.500 m)
Parking Bay & Hard Strip (Width: 3.000 m)
Carriageway (Width: 3.000 m, Number of lanes: 1, tarmac: R3, q0: 0.070)
Hatched Median (Width: 4.000 m, Height: 0.000 m)
Carriageway (Width: 3.000 m, Number of lanes: 1, tarmac: R3, q0: 0.070)
Parking Bay & Hard Strip (Width: 3.000 m)
Buffer (Width: 3.500 m)
Shared Use Path (Width: 4.500 m)
Page 38
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Minor Urban Collector (Residential) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 27015 lm Maximum luminous intensities
at 70: 457 cd/klmat 80: 127 cd/klmat 90: 3.74 cd/klmAny direction forming the specified angle from the downward vertical, with
the luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 33200 lmLuminaire Wattage: 519.0 WArrangement: Double row, with offsetPole Distance: 53.000 mMounting Height (1): 10.000 mHeight: 9.955 mOverhang (2): -4.996 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 39
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Minor Urban Collector (Residential) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:422
Grid: 18 x 3 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.38 0.71 0.67 14 0.96Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (1 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.500, 1.500) 1.38 0.71 0.67 14
Page 40
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Minor Urban Collector (Residential) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:422
Grid: 18 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 10.82 3.10Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 41
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Minor Urban Collector (Residential) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:422
Grid: 18 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 10.82 3.10Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 42
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Minor Urban Collector (Residential) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:422
Grid: 18 x 3 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.38 0.71 0.67 14 0.96Required values according to class: 1.25 0.40 0.50 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (1 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 4 (-60.000, 8.500, 1.500) 1.38 0.71 0.67 14
Page 43
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Major Urban Collector (Commercial) / Planning data
Street Profile
Maintenance factor: 0.70
Shared Use Path (Width: 3.500 m)
Buffer (Width: 1.400 m)
Parking Bay & Hard Strip (Width: 3.000 m)
Carriageway (Width: 6.600 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Median with hardstrips (Width: 3.000 m, Height: 0.000 m)
Carriageway (Width: 6.600 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Parking Bay & Hard Strip (Width: 3.000 m)
Buffer (Width: 1.400 m)
Shared Use Path (Width: 3.500 m)
Page 44
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Major Urban Collector (Commercial) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 27015 lm Maximum luminous intensities
at 70: 457 cd/klmat 80: 127 cd/klmat 90: 3.74 cd/klmAny direction forming the specified angle from the downward vertical, with the luminaire
installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 33200 lmLuminaire Wattage: 519.0 WArrangement: on MedianPole Distance: 44.000 mMounting Height (1): 10.000 mHeight: 9.955 mOverhang (2): 0.504 mBoom Angle (3): 5.0 Boom Length (4): 2.000 m
Page 45
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Major Urban Collector (Commercial) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:358
Grid: 15 x 6 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 2.09 0.57 0.70 13 0.80Required values according to class: 2.00 0.40 0.70 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.650, 1.500) 2.28 0.59 0.70 11
2 (-60.000, 4.950, 1.500) 2.09 0.57 0.73 13
Page 46
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Major Urban Collector (Commercial) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:358
Grid: 15 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 10.56 6.37Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 47
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Major Urban Collector (Commercial) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:358
Grid: 15 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 10.56 6.37Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 48
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
32m Corridor - Major Urban Collector (Commercial) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:358
Grid: 15 x 6 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 2.09 0.57 0.70 13 0.80Required values according to class: 2.00 0.40 0.70 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 4 (-60.000, 11.250, 1.500) 2.09 0.57 0.73 13
2 (-60.000, 14.550, 1.500) 2.28 0.59 0.70 11
Page 49
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Carriageway) / Planning data
Street Profile
Maintenance factor: 0.70
Median with Hard Strip (Width: 8.000 m)
Carriageway (Width: 10.950 m, Number of lanes: 3, tarmac: R3, q0: 0.070)
Landscape with hardstrip (Width: 2.500 m)
Cycle Track (Width: 2.000 m)
Buffer (Width: 1.550 m)
Service Road (Width: 4.000 m)
Parking Bay (Width: 2.500 m)
Buffer (Width: 1.500 m)
Footway (Width: 3.000 m)
Page 50
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Carriageway) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT A FGLuminous flux (Luminaire): 45526 lm Maximum luminous intensities
at 70: 286 cd/klmat 80: 54 cd/klmat 90: 1.14 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G3. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 56500 lmLuminaire Wattage: 831.0 WArrangement: Single row, topPole Distance: 40.000 mMounting Height (1): 12.000 mHeight: 12.000 mOverhang (2): -1.496 mBoom Angle (3): 5.0 Boom Length (4): 2.500 m
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 40.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -15.846 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 51
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Carriageway) / Footway / Results overview
Maintenance factor: 0.70 Scale 1:334
Grid: 14 x 3 Points Accompanying Street Elements: Footway.Selected Lighting Class: S1 (All lighting performance requirements are met.)
Eav [lx] Emin [lx]
Calculated values: 17.09 6.80Required values according to class: 15.00 5.00
Fulfilled/Not fulfilled:
Page 52
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Carriageway) / Cycle Track / Results overview
Maintenance factor: 0.70 Scale 1:334
Grid: 14 x 3 Points Accompanying Street Elements: Cycle Track.Selected Lighting Class: S1 (All lighting performance requirements are met.)Additional EV Lighting Class: EV5 (Not all lighting performance requirements are met.)
Eav [lx] E
min [lx] E
min (vertical) [lx]
Calculated values: 17.54 14.87 5.85Required values according to class: 15.00 5.00 5.00
Fulfilled/Not fulfilled:
Page 53
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Carriageway) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:334
Grid: 14 x 9 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 2.20 0.43 0.85 10 0.78Required values according to class: 2.00 0.40 0.70 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (3 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.825, 1.500) 2.57 0.43 0.91 5
2 Observer 2 (-60.000, 5.475, 1.500) 2.39 0.45 0.87 8
3 (-60.000, 9.125, 1.500) 2.20 0.48 0.85 10
Page 54
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Service Road) / Planning data
Street Profile
Maintenance factor: 0.70
Median with Hard Strip (Width: 8.000 m)
Carriageway (Width: 10.950 m)
Landscape with hardstrip (Width: 2.500 m)
Cycle Track (Width: 2.000 m)
Buffer (Width: 1.550 m)
Service Road (Width: 4.000 m, Number of lanes: 1, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Buffer (Width: 1.500 m)
Footway (Width: 3.000 m)
Page 55
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Service Road) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT A FGLuminous flux (Luminaire): 45526 lm Maximum luminous intensities
at 70: 286 cd/klmat 80: 54 cd/klmat 90: 1.14 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G3. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 56500 lmLuminaire Wattage: 831.0 WArrangement: Single row, topPole Distance: 40.000 mMounting Height (1): 12.000 mHeight: 12.000 mOverhang (2): -18.500 mBoom Angle (3): 5.0 Boom Length (4): 2.500 m
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 40.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -5.796 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 56
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
64m Corridor - Major Urban Arterial(Service Road) / Valuation Field Service Road /
Results overview
Maintenance factor: 0.70 Scale 1:334
Grid: 14 x 3 Points Accompanying Street Elements: Service Road.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 0.86 0.81 0.74 9 1.14Required values according to class: 0.75 0.40 0.50 30 0.50
Fulfilled/Not fulfilled:
Assigned Observer (1 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 3 (-60.000, 2.000, 1.500) 0.86 0.81 0.74 9
Page 57
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
40m Corridor - Major Urban Collector (Residential & Commercial) / Planning data
Street Profile
Maintenance factor: 0.70
Median and hardstrip (Width: 4.000 m)
Carriageway (Width: 7.300 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Median 1 (Width: 1.500 m, Height: 0.000 m)
Service Road (Width: 3.500 m, Number of lanes: 1, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Shared Use Path (Width: 3.500 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT A FGLuminous flux (Luminaire): 45526 lm Maximum luminous intensities
at 70: 286 cd/klmat 80: 54 cd/klmat 90: 1.14 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G3. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 56500 lmLuminaire Wattage: 831.0 WArrangement: Single row, topPole Distance: 49.000 mMounting Height (1): 12.000 mHeight: 12.000 mOverhang (2): 0.500 mBoom Angle (3): 5.0 Boom Length (4): 2.500 m
Page 58
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
40m Corridor - Major Urban Collector (Residential & Commercial) / Shared Use Path /
Results overview
Maintenance factor: 0.70 Scale 1:394
Grid: 17 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 11.20 7.48Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 59
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
40m Corridor - Major Urban Collector (Residential & Commercial) / Service Road /
Results overview
Maintenance factor: 0.70 Scale 1:394
Grid: 17 x 3 Points Accompanying Street Elements: Service Road.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.20 0.76 0.84 9 1.01Required values according to class: 0.75 0.40 0.50 30 0.50
Fulfilled/Not fulfilled:
Assigned Observer (1 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.750, 1.500) 1.20 0.76 0.84 9
Page 60
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
40m Corridor - Major Urban Collector (Residential & Commercial) / Carriageway /
Results overview
Maintenance factor: 0.70 Scale 1:394
Grid: 17 x 6 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 2.42 0.60 0.70 10 0.84Required values according to class: 2.00 0.40 0.70 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 3 (-60.000, 6.825, 1.500) 2.61 0.60 0.70 8
2 Observer 4 (-60.000, 10.475, 1.500) 2.42 0.60 0.70 10
Page 61
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
50m Corridor - Major Urban Collector (Residential) / Planning data
Street Profile
Maintenance factor: 0.70
Median and hardstrip (Width: 8.000 m)
Carriageway (Width: 7.300 m, Number of lanes: 2, tarmac: R3, q0: 0.070)
Median 1 (Width: 4.150 m, Height: 0.000 m)
Service Road (Width: 3.400 m, Number of lanes: 1, tarmac: R3, q0: 0.070)
Parking Bay (Width: 2.500 m)
Shared Use Path (Width: 3.650 m)
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT A FGLuminous flux (Luminaire): 45526 lm Maximum luminous intensities
at 70: 286 cd/klmat 80: 54 cd/klmat 90: 1.14 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G3. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 56500 lmLuminaire Wattage: 831.0 WArrangement: Single row, topPole Distance: 48.000 mMounting Height (1): 12.000 mHeight: 12.000 mOverhang (2): -1.500 mBoom Angle (3): 5.0 Boom Length (4): 2.500 m
Page 62
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
50m Corridor - Major Urban Collector (Residential) / Planning data
Luminaire Arrangements
Luminaire: PHILIPS SGP551 T-POT M GBLuminous flux (Luminaire): 14787 lm Maximum luminous intensities
at 70: 453 cd/klmat 80: 115 cd/klmat 90: 3.00 cd/klmAny direction forming the specified angle from the downward vertical, with the
luminaire installed for use.
Arrangement complies with luminous intensity class G2. Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 17500 lmLuminaire Wattage: 319.0 WArrangement: Single row, bottomPole Distance: 48.000 mMounting Height (1): 8.000 mHeight: 7.955 mOverhang (2): -2.196 mBoom Angle (3): 5.0 Boom Length (4): 1.000 m
Page 63
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
50m Corridor - Major Urban Collector (Residential) / Shared Use Path / Results overview
Maintenance factor: 0.70 Scale 1:387
Grid: 16 x 3 Points Accompanying Street Elements: Shared Use Path.Selected Lighting Class: S2 (All lighting performance requirements are met.)
Eav [lx] E
min [lx]
Calculated values: 13.54 5.92Required values according to class: 10.00 3.00
Fulfilled/Not fulfilled:
Page 64
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
50m Corridor - Major Urban Collector (Residential) / Service Road / Results overview
Maintenance factor: 0.70 Scale 1:387
Grid: 16 x 3 Points Accompanying Street Elements: Service Road.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 1.69 0.75 0.59 11 0.91Required values according to class: 0.75 0.40 0.50 30 0.50
Fulfilled/Not fulfilled:
Assigned Observer (1 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 1 (-60.000, 1.700, 1.500) 1.69 0.75 0.59 11
Page 65
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
50m Corridor - Major Urban Collector (Residential) / Service Road / Observer 1 /
Isolines (L)
Values in Candela/m, Scale 1 : 387
Grid: 16 x 3 Points Observer Position: (-60.000 m, 1.700 m, 1.500 m) tarmac: R3, q0: 0.070
Lav [cd/m] U0 Ul TI [%]
Calculated values: 1.69 0.75 0.59 11
Required values according to class ME4a: 0.75 0.40 0.50 30
Fulfilled/Not fulfilled:
Page 66
Project 1
22.03.2013
OperatorTelephone
Faxe-Mail
50m Corridor - Major Urban Collector (Residential) / Carriageway / Results overview
Maintenance factor: 0.70 Scale 1:387
Grid: 16 x 6 Points Accompanying Street Elements: Carriageway.tarmac: R3, q0: 0.070Selected Lighting Class: ME4a (All lighting performance requirements are met.)
Lav [cd/m] U0 Ul TI [%] SR
Calculated values: 2.32 0.62 0.70 10 0.86Required values according to class: 2.00 0.40 0.70 20 0.50
Fulfilled/Not fulfilled:
Assigned Observer (2 Pieces):
No. Observer Position [m] Lav [cd/m] U0 Ul TI [%]
1 Observer 3 (-60.000, 9.375, 1.500) 2.52 0.62 0.76 7
2 Observer 4 (-60.000, 13.025, 1.500) 2.32 0.64 0.70 10
Page 67