44
Installation Manual Digital Variable Multi Air Conditioner MDS 30 70A(R) MDS 80 320B(R) 5MDS 50 500B(R)

Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Embed Size (px)

Citation preview

Page 1: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual

Digital Variable Multi Air Conditioner MDS 30 – 70A(R) MDS 80 – 320B(R) 5MDS 50 – 500B(R)

Page 2: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately
Page 3: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) i

The data and suggestions in this document are believed current and accurate at the time of publication, but they are not a substitute for trained, experienced and professional service. Individual applications and site variations can significantly affect the results and effectiveness of any information, the reader must satisfy him/herself regarding the applicability of any article and seek professional evaluation of all materials. McQuay disclaims any responsibility for actions based on this document.

This installation manual is intended for and should only be used by qualified engineers/service personnel. Installation and maintenance are to be performed only by qualified personnel who are familiar

with local codes and regulations, and experienced with this type of equipment.

Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Warning: Moving machinery and electrical power hazard. May cause severe personnel injury or death. Disconnect and lock off power before servicing equipment.

Page 4: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

ii Installation Manual IM-MDS_(i)

1.0 Safety Precautions...……………………………………………………………………………....1 1.1 Precautions before installation………………………………………………..………..1

1.2 Safety reminder on installation process...……………………………………………..1 1.3 Precautions on commissioning..………………………………………………………….1 1.4 Precautions for devices that use R410A refrigerant……………………………….....1 1.5 Other precautions……...…………………………………………………………………..2

2.0 Electrical Parameter……………………………………………………………………………..2

3.0 Installation Instruction……………………………………………………………….…………..4

4.0 Outdoor Unit Installation...………………………………………………………………………...4 4.1 Location and space of installation….…………………………………………………….4 4.2 Unit handling…………….………………………………………………………………….6 4.3 Unit installation…………..…………………………………………………………………6 4.4 Installation of master and slave unit……………………………………………………..6

5.0 Indoor Unit Installation…………………………………………………………………………7 5.1 Location and space of installation...……………………………………………………..7 5.2 Installation of MEX box………………………………….………………………………...7 5.3 Installation of MCCD series indoor unit………………………………………………….8

5.4 Installation of MCKD series indoor unit …………………………...…………………….8 5.5 Installation of MCMD series indoor unit ……………………………………………….10 5.6 Installation of MWMD series indoor unit ………………………………………………12

6.0 Piping Installation…………………………………………………………………………………13 6.1 Precautions for piping installation……………………………………………………....13 6.2 Refrigerant piping system………..………………………………………………..........14 6.3 Piping size, refnet and distributor selection….………………………………………15 6.4 Installation of refrigerant piping…………………………………………………...........18 6.5 Ball valve installation and operation.…………………………………………………19 7.0 Wiring Connection……………………………………………………………………………..…20

7.1 General wiring precautions……………………………………………………………20 7.2 Wire specification…………………………………………………………………………21 7.3 Electrical wiring connection……………………………………………………………21 7.4 Communication wiring connection……………………………………………………22 7.5 Dip switch setting……………………….………………………………………………..23 7.6 Auto restart setting……………………………………….............................................24

8.0 Air Leakage Test, Vacuum and Refrigerant Charge….…………………………………..….25

8.1 Air leakage test………………………...…………………………………………………25 8.2 Vacuum……………………………………………………………………………………25 8.3 Refrigerant charge…………..……………………………………………………………25

9.0 Commissioning………………………………………...….…………………………………..….25

9.1 Checking list before commissioning....…………………………………………………25 9.2 Commissioning record table.……………………………………………………………25 9.3 Common problems during commissioning.……………………………………………25

10.0 Unit Outlines and Dimensions….…………………………………..…………………………27

Table of Content

Page 5: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 1

1.0 Safety Precautions Please take note of the safety item stated below before and after the installation process:

1.1 Preparation before installation

Check the electrical power supply condition. Power supply shall meet the requirement of local rule and regulation.

The tolerance of voltage shall be less than ±10% based on nominal voltage. It is not allowed to share the same power cable through soldering as it will cause fluctuation of power supply.

Professional technician or engineer is needed to conduct the installation.

Follow the installation instruction in this manual. Improper installation may cause damage to the unit which will then cause other accident to happen.

A solid base shall be built on the ground before installation of outdoor unit. The base shall be strong enough to support the weight of the outdoor units. Counter measure should be taken against possible natural disaster such as earthquake and typhoon.

Installation kits and protection kits shall be used to prevent injury. 1.2 Safety reminder on installation process

Do not touch the fins of heat exchanger. It may cause injury. Besides that, any damage on the heat exchanger will reduce the heat exchange performance.

Secure the outdoor unit to avoid any vibration. The service panel and control box cover shall be closed tightly to avoid any dirt and water from damaging the components.

Only air filter and heater provided/approved by factory shall be installed on the indoor units.

Action shall be taken to avoid refrigerant leakage during the installation process.

In case of any refrigerant leakage occur, open the window and door to improve ventilation and prevent fire hazard.

Any electrical cable shall be kept away from water and humidity.

Do not change any settings of the protection devices unless instructed by factory.

Do not pull the electrical cable too tight, as it may cause the cable to break without notice.

Ensure the cable size is correct and sufficient to support the current and power consumption.

Unit must be earthed properly. Do not connect earth line with telephone line.

Indoor condensing water shall be drained away properly to avoid overflow. Insulation is needed for piping connecting to the drain pan.

All units shall be handled and carried carefully during transportation.

After installation completed, the unit should undergo leakage test. 1.3 Precautions on commissioning

Power is to be supplied to the units for 12 hours before running them for the first time. This is to prevent any damage of electrical components.

Avoid contact with power switch when hand is wet.

Do not remove the front panel or protection guard when the unit is in operation. The components running in high speed may cause injury and damage.

Do not touch the refrigerant piping when the unit is running or just stop to avoid any injury.

Do not switch off the power supply immediately after the unit is off. Please wait for 5 minutes before shutting down the power supply.

1.4 Precautions for devices that use R410A refrigerant

R410A is high pressure refrigerant. Do not use refrigerant piping of other type of refrigerant to prevent burst.

Do not use old refrigerator oil as it may contains large amount of chlorine that can cause the refrigerator oil in R410A unit to deteriorate.

Use refrigerant piping that is made of phosphorus deoxidized copper and copper alloy seamless pipe. Ensure the inner and outer surfaces of the pipes are clean and free of sulphur, oxide, dust, shaving particles, oils, moisture and other contaminant.

Store the piping properly and keep both ends sealed until it is used to prevent dust and moisture.

Ensure that only liquid refrigerant is charged into the system as the composition of refrigerant is different in gaseous phase.

Use ester oils, ether oil or small amount of alkylbenzene as the refrigerator oil to coat flares and flange connection. Do not use mineral oil.

Use a vacuum pump with a reverse flow check valve. The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.

Do not use refrigerant other than R410A.

Do not use tools such as gauge manifold, charge hose and etc which are not designed for R410A refrigerant.

Page 6: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

2 Installation Manual IM-MDS_(i)

1.5 Other precautions

Contact local distributor/manufacturer for assistance when there’s doubt on the installation process.

Do not charge in other type of refrigerant to the unit as this will damage the unit.

2.0 Electrical Parameter All values given are for reference only. They shall be checked and selected to comply with local standards and regulations. MDS-A Series Outdoor

Model MDS30-40A(R) MDS50A(R) MDS60A(R) MDS50-60A(R) MDS70A(R)

Power supply (V/Ph/Hz)

220-240/1/50 380-415/3/50

Max. Breaker Size (A)

25 30 40 15 20

Number of Wires

3 3 3 5 5

Power Cable Size (mm

2)

6 6 6 4 4

MDS-B Series Outdoor

Model MDS80B(R) MDS100-120B(R)

MDS150-180B(R)

MDS200-220B(R)

MDS240B(R)

Power supply (V/Ph/Hz)

380-415/3/50

Max. Breaker Size (A)

25 30 50 50 60

Number of Wires

5 5 5 5 5

Power Cable Size (mm

2)

6 6 10 16 16

Model MDS260B(R) MDS280B(R) MDS300B(R) MDS320B(R)

Power supply (V/Ph/Hz)

380-415/3/50

Max. Breaker Size (A)

60 70 80 80

Number of Wires

5 5 5 5

Power Cable Size (mm

2)

16 (Master) 10 (Slave)

Note: MDS 260-320B(R) is combined unit, consist of master unit and slave unit. There are two ways to connect the cable, either separate connection or serial connection. For MDS 320, only separate connection can be used. For other combined units, it is recommended to use serial connection.

5MDS-B Series Outdoor

Model 5MDS60B(R) 5MDS50B(R) 5MDS60-70B(R)

5MDS80-100B(R)

5MDS120B(R)

Power supply (V/Ph/Hz)

220-240/1/50 380-415/3/50

Max. Breaker Size (A)

40 15 20 25 30

Number of Wires

3 5 5 5 5

Power Cable Size (mm

2)

6 4 4 6 6

Page 7: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 3

Model 5MDS140-160B(R) 5MDS180-200B(R) 5MDS220B(R) 5MDS240B(R)

Power supply (V/Ph/Hz)

380-415/3/50

Max. Breaker Size (A)

40 50 60 60

Number of Wires

5 5 5 5

Power Cable Size (mm

2)

10 10 10 16

Model 5MDS260-280B(R)

5MDS300B(R) 5MDS320B(R) 5MDS340-360B(R)

Power supply (V/Ph/Hz) 380-415/3/50

Max. Breaker Size (A) 70 80 80 90

Number of Wires 5 5 5 5

Power Cable Size (mm

2)

Separate 6 (Master) 10 (Slave) 10 (Master) 10 (Slave)

Serial 16 (Master) 10 (Slave) -

Model 5MDS380B(R) 5MDS400B(R) 5MDS420-460B(R)

5MDS480-500B(R)

Power supply (V/Ph/Hz) 380-415/3/50

Max. Breaker Size (A) 100 100 125 125

Number of Wires 5 5 5 5

Power Cable Size (mm

2)

Separate 16 (Master) 10 (Slave) 16 (Master) 16 (Slave)

Serial 25 (Master) 10 (Slave) 25 (Master) 16 (Slave)

Note: 5MDS 260-500B(R) is combined unit, consist of master unit and slave unit. There are two ways to connect the cable, either separate connection or serial connection. For 5MDS 320-360B(R), only separate connection can be used. For other combined units, it is recommended to use serial connection.

MCCD/M5CCD Series Indoor

Model 10-15C 20-25C 28-30C 38-40C 50-60C

Power supply (V/Ph/Hz) 220-240/1/50

Number of Wires 3

Power Cable Size (mm2) 1.5 2.5 4.0 1.5 2.5

MCKD/M5CKD Series Indoor

Model 20-25A 30A 40A 50A 10-15C 20C

Power supply (V/Ph/Hz) 220-240/1/50

Number of Wires 3

Power Cable Size (mm2) 2.5 4.0 1.5 2.5 1.5 2.5

MCMD/M5CMD/MCMD/M5CMD Series Indoor

Model 15-25E 28E 40D 50D 62C

Power supply (V/Ph/Hz) 220-240/1/50

Number of Wires 3

Power Cable Size (mm2) 2.5 4.0 1.5 2.5 2.5

MWMD/M5WMD Series Indoor

Model 09-15G 20-25G

Power supply (V/Ph/Hz) 220-240/1/50

Number of Wires 3

Power Cable Size (mm2) 1.5 2.5

Page 8: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

4 Installation Manual IM-MDS_(i)

3.0 Installation Instruction Kindly follow the installation steps shown below:

1. Choose the installation place 2. Install the outdoor and indoor unit 3. Install the piping and cable line 4. Perform leakage test 5. Vacuum the system and charge in refrigerant 6. Test run/commissioning

4.0 Outdoor Unit Installation 4.1 Location and space of installation

Avoid the discharge air from circulating back to air inlet.

Remove any barrier to improve the air ventilation.

Ensure enough space for maintenance.

Avoid installation of unit under corrosive environment.

Avoid installation of unit at places with flammable gas.

Follow the clearance when more than one outdoor unit is installed at the same location.

Constructing on the ground

x Foundation nut installing

Many units concentrated installing

Constructing on the floor

AMDS200~240BR5

Mode

AMDS080~120BR5

AMDS140~180BR5

Drain ditch

Gradient is 1/40

x

Drain ditch

1900 2100

900

1200

A

1100

1400

B

Nut

Y Trough

UndercarriageSpring washer

Bolt mode:JA

Dimension:M12

Quantity:4

MDS 30-70A(R) 5MDS 50-70B(R)

MDS 80-320B(R) 5MDS 80-500B(R)

Page 9: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 5

≥ ≥≥45°

Front

Air Outlet Guide

≥3

00

mm

≥1

00

0m

m

FRONT

BACK

FRONT

BACK

≥450m

m≥

450m

m

BACK

FRONT

FRONT

BACK BACK

FRONT

FRONT

BACK

≥600mm

≥450m

m≥

900m

m

MDS 30-70A(R) 5MDS 50-70B(R)

MDS 80-320B(R) 5MDS 80-500B(R)

Page 10: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

6 Installation Manual IM-MDS_(i)

4.2 Unit handling

Use 4 supporting points to move the units (refer to diagram).

Avoid unstable move to prevent unit drop off.

Do use special rope to tie the units for transportation.

Do not touch the fin to avoid injury.

Keep the plastic bag from reach of children. 4.3 Unit installation

Ensure the base is solid to support the unit.

Consider the location for drainage and piping installation.

Screw bolt to secure the 4 corners of the unit.

Use rubber absorber to prevent transfer of vibration.

4.4 Installation of Master and Slave unit

Both master and slave unit must be positioned side by side and installed in the same level.

The distance between master and slave unit shall be more than 10mm.

Copper part accessories are packed with the outdoor units.

All piping should be insulated.

Gas and liquid piping should be connected paralleled to each other.

Balance piping must be installed. It should be connected through the hole of side panel, base panel or the piping connection position with the other outdoor unit.

Balance piping shall be installed horizontally and it must be lower than the access valve of balance piping.

Balance piping shall not be touching any other parts.

Page 11: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 7

5.0 Indoor Unit Installation 5.1 Location and space of installation

Ensure adequate air flow for the indoor unit and no obstacle around it.

Ensure enough space for maintenance and servicing.

Wall or ceiling shall be strong enough to support the indoor units.

Do not expose the unit under direct sunlight.

Do not install the indoor unit near to places with oil, steam or flammable gas.

Do not install the indoor unit at places with high frequency. 5.2 Installation of MEX Box

All indoor units need to connect to MEX Box.

It should be installed away from quiets such as bedroom.

Ensure the MEX box is vertical when installed. The distance between MEX box and indoor unit could not exceed the maximum length limit of the expansion valve cable. The cable needs to be plugged on the control board of indoor unit.

MEX Box can be installed in any of the method shown below.

Remove the panel

C For φ28.6mm gas pipe, directly

connect to Tri-joint; For φ34.9mm

gas pipe, add a reducer and a

transition pipe

Elbow

To units ball valve

Balance pipeLiquid pipe

Gas pipe

A

Knock-out-hole

Piping connection position

To balance pipe

access valve

Tri-jiont

φ28.6mm a transiton pipe

(only for φ34.9mm gas pipe)

Connect pipe to indoor units

D

A >10mm

B >200mm

C >500mm

D>100mmB

To units ball valve

Ball valve (gas side)

Knock-out-hole

(for connecting balance pipe)

Access valve for

balance piping (φ9.52)

Knock-out-hole

Ball valve

(liquid side)

Master and slave must be

installed in the same level

steeve

nut

washer

hole for screw

washer

nut

washer

hook

SUSPENDING BY STEEVES

SCREW SETTING ON INDOOR UNIT

SCREW

SCREW SETTING ON WALL

SCREW

Page 12: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

8 Installation Manual IM-MDS_(i)

5.3 Installation of MCCD series indoor units

Use the hanger supplied with the unit.

Install the unit horizontally and ensure the slope for drainage is sufficient.

Ensure the distance between return air inlet and heat exchanger shall be at least 1m.

Do not open the valves, connector, copper cup and cover before installation.

Install the piping and drainage properly.

Use selected air distributor or diffuser to meet the design requirement.

Connect the return air inlet of indoor units with return air inlet on the ceiling.

Both air supply and return duct shall be insulated with aluminium foil. 5.4 Installation of MCKD series indoor units

Ensure sufficient space for ventilation and no obstacle around the indoor unit.

The support shall carry weight 4 times larger than the indoor units to avoid unnecessary vibration and noise.

Keep the indoor units away from source of heat and vapour.

Use the installation template on the carton box to measure position for hanging rod. Drill the hole for the angle nut on the ceiling and fix the hanging rod.

Confirm the pitch of the hanging rod as per figure below.

MCKD/M5CKD-A MCKD/M5CKD-C

Use nut and washer to fix the indoor units securely to prevent unit falling and vibration.

Page 13: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 9

Adjust the unit height to 35mm (for MCKD-A) or 30mm (for MCKD-C) between the indoor unit bottom surface and the ceiling surface.

Confirm with a level gauge that the unit is installed horizontally.

Open the ceiling board along the outer edge of the installation template.

Drain pipe must be in downward gradient for smooth drainage to prevent reversed water flow.

When connecting the drain pipe, be careful not to exert extra force on the drain connector at indoor unit.

The outer diameter of the drain connection at the flexible drain hose is 20mm.

Ensure to apply insulation (polyethylene foam with thickness more than 8mm) on the drain piping to avoid the condensed water dripping inside the room.

Connect the main drain pipe to the flexible drain hose.

Feed water from flexible drain hose to check the piping for leakage. When the test is completed, connect the flexible drain hose to the drain connector on the indoor unit.

The front panel can only be fitted in one direction, following the piping direction. (Follow piping arrow sticker

on front panel).

Be sure to remove the installation template before installing the front panel.

Open the air intake grille by pulling back the catchers and removing it together with filter from panel.

Install the front frame panel onto the indoor unit by 4 screws and tighten it completely to prevent cool air leakage.

Connect the LED wire and air swing wire to the indoor unit.

Install the front panel firmly to prevent cool air leakage which will cause condensation and water dripping.

drain pipe

drain & leakage test

fill water

flexible pipe

Drain pipe installation

Front panel installation Wire connection between unit and panel

Drainage leak test

Page 14: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

10 Installation Manual IM-MDS_(i)

Install the air intake grille together with the air filter to the front panel.

The grille can be fit in any direction, when selecting direction, the ceiling design and grille operability should be considered.

If the unit comes with ionizer filter (optional item), make sure to fix the ionizer filter to the air filter before installing the air intake grille.

Fix the ionizer filter to the air filter with the black side on top and white side at bottom. Carefully clip on the ionizer filter frame.

Note that water pump is installed in this type of indoor unit. 5.5 Installation of MCMD series indoor units

Ensure sufficient space for ventilation and no obstacle around the indoor unit.

Install the unit horizontally and ensure the slope for drainage is sufficient.

Note that MCMD/M5CMD62C is unable to be installed in floor standing position.

MCMD/M5CMD-E Series MCMD/M5CMD-C Series

MCMD/M5CMD-D Series

Slope for drainage

Page 15: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 11

Ensure the overhead supports are strong enough to hold the weight of the unit.

Position the hanger rods and check for its alignment with the unit. Also check that the hangers are secured and the base of the indoor unit is levelled in both horizontal directions.

Provide clearance for easy serviceability and optimal air flow.

The unit must be installed a large distance away from the door to avoid direct sunlight.

The location of indoor unit should be suitable for piping and drainage installation.

The indoor unit must be installed such that there is no short circuit of cool discharge air with the warm return air.

Air return grill

Frame

Suspending

panel

Panel side

Installation of MCMD/M5CMD-C/D Series

Installation of MCMD/M5CMD-E Series

Ceiling Type Installation

Page 16: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

12 Installation Manual IM-MDS_(i)

5.6 Installation of MWMD series indoor units

Ensure sufficient space for ventilation and no obstacle around the indoor unit.

The indoor unit must be installed in such a way so as to prevent short circuit of cool discharged air with the hot return air. Please follow the installation clearance shown below.

Do not expose the indoor unit to direct sunlight and away from doors and windows.

Consider the location of piping and drainage when selecting the installation space.

The refrigerant piping can be routed to the unit in a number of ways by using the cut-out holes on the casing of the unit.

Floor Type Installation

Page 17: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 13

Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars.

Use the level gauge for horizontal mounting and fix it with 4 suitable screws.

In case the rear piping draws out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall.

The indoor drain pipe must be in a downward gradient for smooth drainage. Avoid situations that are likely to cause water to leak.

Hook the indoor unit onto the upper portion of the installation plate (engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate).

Ensure that the hooks are properly seated on the installation plate by moving it to the left and right.

6.0 Piping Installation MDS system is a “one outdoor unit coupled with many indoor units” system. For piping connection, there are gas pipe and liquid pipe connection with flare joint. 6.1 Precautions for piping installation

Check and ensure the thickness, diameter and cleanliness of the copper tube is within specification.

It is not allowed to vacuum the system with refrigerant.

Do not use any detergent to clean the refrigerant piping.

Seal the outlet of the copper tube to avoid dust, dirt or water from entering.

Do not install the copper pipe during rainy day.

Avoid bending and turning of piping. Special tools must be used to bend the piping.

Use the right equipment for brazing the copper tube.

All copper tube must be insulated to ensure heat exchange efficiency and to avoid water from condensing.

The outdoor ball valve should remain closed until the completion of leakage test and vacuum process.

Ensure the unit is properly charged with the correct amount of refrigerant.

Page 18: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

14 Installation Manual IM-MDS_(i)

6.2 Refrigerant piping system

The below 3 piping structure designs are recommended.

It is not allowed to connect any refnet after the distributor.

balance pipe

Tee jointBifurcation

Indoor unit

Distributor

Indoor unit

Balance pipe

Tee joint

Distributor

Bifucation

Balance pipe

Tee joint

Indoor unit

Distributor

Distributorbalance pipe

Tee joint

Indoor uint

Wrong connection

Bifurcation

Wrong connection

Page 19: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 15

6.3 Piping size, refnet and distributor selection

Select the piping, refnet and distributor base on the tables and diagrams below. Refrigerant piping

Page 20: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

16 Installation Manual IM-MDS_(i)

R410A Piping Materials/Radial Thickness

Type TP2M TP2Y2

Diameter (mm) 6.4 9.5 12.7 15.9 19.1 22.2 25.4 28.6 31.8 34.9 38.1 41.3

Diameter (inch) 1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/8 1-1/4 1-3/8 1-1/2 1-5/8

Minimum Thickness

(mm) 0.8 0.8 0.8 1.0 1.0 1.0 1.0 1.0 1.1 1.3 1.4 1.5

The minimum thickness of the pipe in the chart is based on the PRC Standard Specification for Drawn Tube of Copper and Copper Alloys (GB/T1527-1997), TP2M and TP2Y2 are the marks of the material brand and state. Using this table as reference, choose the pipe that meets the local standards and the maximum operation pressure reaches 4.15MPa.

If the unit is used in the environment which is eroded seriously, it should be thickened by 0.2mm.

The table shows the minimum thickness. If the pipe needs to be bent or drawn, please add the extra thickness appropriately.

Page 21: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 17

Refnet

Page 22: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

18 Installation Manual IM-MDS_(i)

Horizontal

Vertical

installation

<30°

Direction A

view

Horizontal

installation

Direction A

Outdoor

Oil trap

(every 6~8m fall of the

gas pipe set a oil trap)

Indoor

Installation of refnet and distributor should be within the allowable tolerance as shown in diagrams below.

Installation of the system should within the piping length limitation as shown below.

MDS 5MDS

Length (m) 30-50 60-70 80-320 50 60-70 80-500

Piping

Total equivalent length 100 150 350 100 150 500

Maximum length of longest branch

Actual piping length 50 70 125 50 70 150

Equivalent length 60 80 150 60 80 175

Maximum equivalent length from first branch to furthest unit

25 30 40 25 30 65

Height

Between further indoor and outdoor

outdoor above 20 30 50 20 30 50

indoor above 20 30 40 20 30 40

Maximum height between indoor unit 15

6.4 Insulation of refrigerant piping

All refrigerant piping must be insulated to ensure heat exchange efficiency and prevent water condensing.

Specification of insulation material is as below.

Insulation Material Fiberglass+Steel

Adhering material+Chloroethylene foam+adhering strip

Layer

Indoor Chloroethylene insulation strip

Bare floor Water proof flax+Bronze Pitch

outdoor Water proof flax+galvanized panel+painting

Maximum height between indoor units

Height between further indoor and outdoor

Maximum length of longest branch

Page 23: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 19

so

Close-packed

packing

Hollow

packingball valve

(gas side)

A Valve stem

B Stopper pin

C Packing(accessory)

D Connecting pipe(accessory)

E Open

F Cap, copper packing

G Service port

H Flare nut

I Liquid pipe diameter

J Gas pipe diameter

K Field piping

ball valve

(liquid side)

o s

o s

A

B

C

D

J

K

H

G

I

F

E E

dia

mete

r

The proper steps to insulate the refrigerant piping are shown below.

Pipe Specification

Diameter 6.35 - 25.4mm Diameter 28.58 - 41.3mm

Thickness Min 10mm Min 12mm

Heat resistance Min100℃

6.5 Ball valve installation and operation

Operate the gas side ball valve o Uninstall the flange connector: remove the flange connector from the piping o Stick the seal material to cover the inlet of the ball valve flange to avoid the dirt entry o Change the hollow seal pad o Fix the flange connector and hollow seal pad and fixed ball valve of gas side with screw bolt.

Liquid side ball valve connecting: expand the copper tube outlet and connect the ball valve connector

Vacuum and charge in refrigerant, ensure to open the valve completely

Calculate the additional refrigerant and charge into units accordingly

Check the looseness to avoid leakage of refrigerant

Copper tube expanded connector dimension. (unit: mm)

External Diameter Diameter

mm inch

Ф6.35 1/4” 9.0

Ф9.52 3/8” 13.0

Ф12.7 1/2” 16.2

Ф15.88 5/8” 19.4

Ф19.05 3/4” 23.3

Page 24: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

20 Installation Manual IM-MDS_(i)

diameter

Matching screw specification. (unit: mm)

Diameter Diameter

mm inch

Ф6.35 1/4” 17.0

Ф9.52 3/8” 22.0

Ф12.7 1/2” 24.0

Ф15.88 5/8” 27.0

Ф19.05 3/4” 36.0

When connecting the liquid piping and liquid ball valve, use wrench to fix tightly and ensure they are in the same axial.

Outside diameter(mm) Moment(N.m) angle (˚ )

Ф6.35 14~18 60~90

Ф9.52 35~42 60~90

Ф12.7 50~57.5 30~60

Ф15.88 75~80 30~60

Ф19.05 100~140 20~35

7.0 Wiring Connection 7.1 General wiring precautions

Power of indoor and outdoor units must be supplied simultaneously.

Cable for power and communication should be designed in parallel and maintain a distance of more than 20cm between them.

Communication cable should be screened to avoid interference of strong signal. Total wire length should be less than 1000m.

Signal wire has two poles of A and B the same pole must be connected in one connection (A to A, B to B).

Screened layer of signal wires should be earthed.

Outdoor units use either 3 phase or single phase supply (depends on model) while indoor units use only single phase power cable.

Wiring diagram can be obtained within the units. 7.2 Wire specification

For communication wire, please use below standard.

A: conducting wiring (copper, intersection surface is more than 0.5mm2 or 20AWG)

B: Insulation material

C: Screen layer (efficiency shall be higher than 95%)

D: outside layer protector (PVC)

For wiring cable, please refer to UL2547 and UL2791 standard

Wiring cable

Page 25: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 21

7.3 Electrical wiring connection

For single unit connection.

For master and slave units connection.

Fuse

Switch

Two-core cable

(power circuit) Two-core cable

(power circuit)

Switch

Fuse

Indoor unit

Fuse

Switch

L1Switch

Fuse

L2L1 L3 NPower

Outdoor unit

NL2 L3

Electrical connection for single outdoor unit (FOR AMDS080~240B(R)5)

Indoor unit

Switch

Fuse Fuse

Switch

Power

L1

L2

Fuse

Switch

L1

L2L3L2 N

Fuse

SwitchL1 L3 N

L3 N

Two-core cable

(power circuit)

Switch

Fuse

Outdoor unit

Master Slave

Two-core cable

(power circuit)

Separate electrical connection for

combined outdoor unit(FOR AMDS260~320B(R)5)

Indoor unit

Master

Outdoor unit

Two-core cable

(power circuit)

Two-core cable

(power circuit)Fuse

Switch

L1 N

Switch

Fuse

L1 N

PowerL3L1 L2

N

Fuse

Switch L2L1 L3

N

Switch

Fuse

L1 N

Slave

Series electrical connection for combined outdoor unit

(FOR AMDS260~300B(R)5, 380~500B(R)5)

Separate Connection Serial Connection

Page 26: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

22 Installation Manual IM-MDS_(i)

Indoor unit 1

To network or central

control (optional)

Communication cable

Screen

layer

Det

ail f

or

Term

inal A

pc

Outdoor unit

Control box

Main PCB

Connection

port

BpcApcAin

Bin

Bpc

Bin

Ain

Control box

A B

PCB

Control box

Indoor unit 2

B

Communication cable

Control box

A

PCB

Communication cable

JP1 of last unit on

main bus should be on

Indoor unit i

A B

PCB

JP1A

B

A

B

A

B

Connection port

com1

com

2

com

2 com1

Connection port Connection port

com

2 com1

Master unit

Outdoor unit

To network or central

control (optional)

Ain

Bin

BpcA

pc

Main PCB

Connection

port

Screen

layer

Communication cable

Connection

port

Slave unit

Main PCB

Ain

BpcA

pcB

in

Indoor unit 2

Communication cable

Indoor unit 1

Control box

PCBConnection port

A B

Control box

PCB

A B

JP1 of last unit on

main bus should be on

Indoor unit i

B

Communication cable

Control box

A

PCB

JP1A

B

A

B

A

B com

2

Connection port Connection port

com1

com

2

com

2

com1com1

PCB

BA A B

PCB

Connect A with B, wrong

A

B

A

B

co

m2

Connection port Connection port

co

m2 com1

7.4 Communication wiring connection

For single unit connection.

For master and slave units connection.

Example of wrong connection.

not bus structrue,connection cable

should be layed as bus structure

Bpc

Ain

ApcBin

Outdoor unit

Control box

Main PCB

Connection

port

Screen

layer

BAA B

PCB

Control box

Indoor unit 1 Indoor unit 2

Communication cable

Communication cable

PCB

Control box

A

B

A

B

Connection port Connection port

com1

com

2

com

2 com1

Bpc

Ain

ApcBin

Screen layer must be

grounded with outdoor unit

Control box

Connection

port

Main PCB

PCB

A B

Neglect to

connect

A

B

Connection port

com1

com

2

Page 27: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 23

7.5 Dip switch setting

Indoor unit address setting for all indoor (dip switch SW2). S2.1 S2.2 S2.3 S2.4 S2.5 S2.6 Indoor Address S2.1 S2.2 S2.3 S2.4 S2.5 S2.6 Indoor Address

0 0 0 0 0 0 0 0 1 1 0 0 0 24

0 0 0 0 0 1 1 0 1 1 0 0 1 25

0 0 0 0 1 0 2 0 1 1 0 1 0 26

0 0 0 0 1 1 3 0 1 1 0 1 1 27

0 0 0 1 0 0 4 0 1 1 1 0 0 28

0 0 0 1 0 1 5 0 1 1 1 0 1 29

0 0 0 1 1 0 6 0 1 1 1 1 0 30

0 0 0 1 1 1 7 0 1 1 1 1 1 31

0 0 1 0 0 0 8 1 0 0 0 0 0 32

0 0 1 0 0 1 9 1 0 0 0 0 1 33

0 0 1 0 1 0 10 1 0 0 0 1 0 34

0 0 1 0 1 1 11 1 0 0 0 1 1 35

0 0 1 1 0 0 12 1 0 0 1 0 0 36

0 0 1 1 0 1 13 1 0 0 1 0 1 37

0 0 1 1 1 0 14 1 0 0 1 1 0 38

0 0 1 1 1 1 15 1 0 0 1 1 1 39

0 1 0 0 0 0 16 1 0 1 0 0 0 40

0 1 0 0 0 1 17 1 0 1 0 0 1 41

0 1 0 0 1 0 18 1 0 1 0 1 0 42

0 1 0 0 1 1 19 1 0 1 0 1 1 43

0 1 0 1 0 0 20 1 0 1 1 0 0 44

0 1 0 1 0 1 21 1 0 1 1 0 1 45

0 1 0 1 1 0 22 1 0 1 1 1 0 46

0 1 0 1 1 1 23 1 0 1 1 1 1 47

Indoor unit capacity setting for all indoor (dip switch SW3).

Outdoor unit address setting for MDS30-70A(R) and 5MDS50-70B(R) (dip switch J2). J2.1 J2.2 J2.3 J2.4 J2.5 Outdoor Address

0 0 0 0 0 0

1 0 0 0 0 1

0 1 0 0 0 2

1 1 0 0 0 3

0 0 1 0 0 4

1 0 1 0 0 5

0 1 1 0 0 6

1 1 1 0 0 7

0 0 0 1 0 8

1 0 0 1 0 9

0 1 0 1 0 10

1 1 0 1 0 11

0 0 1 1 0 12

1 0 1 1 0 13

0 1 1 1 0 14

1 1 1 1 0 15

0 0 0 0 1 16

1 0 0 0 1 17

0 1 0 0 1 18

1 1 0 0 1 19

0 0 1 0 1 20

1 0 1 0 1 21

0 1 1 0 1 22

1 1 1 0 1 23

0 0 0 1 1 24

1 0 0 1 1 25

0 1 0 1 1 26

1 1 0 1 1 27

0 0 1 1 1 28

1 0 1 1 1 29

0 1 1 1 1 30

1 1 1 1 1 31

S3.1 S3.2 S3.3 S3.4 S3.5 Capacity (kW) Model Name

0 0 0 1 0 2.5 09

1 0 1 1 0 2.8 10

0 0 1 0 0 3.6 15

0 1 0 0 0 5.6 20

0 1 0 1 0 6.5 25

1 1 0 1 0 8.0 28

1 1 1 0 0 9.0 30

0 1 1 1 0 10.0 38

1 1 1 1 0 11.2 40

1 0 0 1 0 14.0 50

0 1 0 1 1 16.4 60/62

0 0 0 0 1 22.4 80

0 0 0 1 1 28.0 100

S3.6 S3.7 S3.8 Indoor Type

0 0 0 Ceiling Concealed

0 0 1 Ceiling Cassette

0 1 0 Ceiling Convertible

0 1 1 Wall Mounted

1 0 0 Ducted Blower

Page 28: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

24 Installation Manual IM-MDS_(i)

Outdoor unit address setting for MDS/5MDS80-500B(R) (dip switch S2). S2.4 S2.5 S2.6 S2.7 S2.8 Outdoor Address S2.4 S2.5 S2.6 S2.7 S2.8 Outdoor Address

0 0 0 0 0 0 1 0 0 0 0 16

0 0 0 0 1 1 1 0 0 0 1 17

0 0 0 1 0 2 1 0 0 1 0 18

0 0 0 1 1 3 1 0 0 1 1 19

0 0 1 0 0 4 1 0 1 0 0 20

0 0 1 0 1 5 1 0 1 0 1 21

0 0 1 1 0 6 1 0 1 1 0 22

0 0 1 1 1 7 1 0 1 1 1 23

0 1 0 0 0 8 1 1 0 0 0 24

0 1 0 0 1 9 1 1 0 0 1 25

0 1 0 1 0 10 1 1 0 1 0 26

0 1 0 1 1 11 1 1 0 1 1 27

0 1 1 0 0 12 1 1 1 0 0 28

0 1 1 0 1 13 1 1 1 0 1 29

0 1 1 1 0 14 1 1 1 1 0 30

0 1 1 1 1 15 1 1 1 1 1 31

Outdoor unit indoor quantity setting for MDS/5MDS80-500B(R) (dip switch S1). S1.3 S1.4 S1.5 S1.6 S1.7 S1.8 Indoor Quantity S1.3 S1.4 S1.5 S1.6 S1.7 S1.8 Indoor Quantity

0 0 0 0 0 0 1 0 1 1 0 0 0 25

0 0 0 0 0 1 2 0 1 1 0 0 1 26

0 0 0 0 1 0 3 0 1 1 0 1 0 27

0 0 0 0 1 1 4 0 1 1 0 1 1 28

0 0 0 1 0 0 5 0 1 1 1 0 0 29

0 0 0 1 0 1 6 0 1 1 1 0 1 30

0 0 0 1 1 0 7 0 1 1 1 1 0 31

0 0 0 1 1 1 8 0 1 1 1 1 1 32

0 0 1 0 0 0 9 1 0 0 0 0 0 33

0 0 1 0 0 1 10 1 0 0 0 0 1 34

0 0 1 0 1 0 11 1 0 0 0 1 0 35

0 0 1 0 1 1 12 1 0 0 0 1 1 36

0 0 1 1 0 0 13 1 0 0 1 0 0 37

0 0 1 1 0 1 14 1 0 0 1 0 1 38

0 0 1 1 1 0 15 1 0 0 1 1 0 39

0 0 1 1 1 1 16 1 0 0 1 1 1 40

0 1 0 0 0 0 17 1 0 1 0 0 0 41

0 1 0 0 0 1 18 1 0 1 0 0 1 42

0 1 0 0 1 0 19 1 0 1 0 1 0 43

0 1 0 0 1 1 20 1 0 1 0 1 1 44

0 1 0 1 0 0 21 1 0 1 1 0 0 45

0 1 0 1 0 1 22 1 0 1 1 0 1 46

0 1 0 1 1 0 23 1 0 1 1 1 0 47

0 1 0 1 1 1 24 1 0 1 1 1 1 48

For master and slave unit, set the master unit’s S2.1 as 1, and set the slave unit’s S2.1 as 0.

Address cannot be duplicated and must be continuous without skipping any address in between.

The address of first unit must be 0. Address and indoor quantity code of the slave unit need not to be set.

Start up the unit after the address setting has been completed.

1 stands for On while 0 stands for Off. 7.6 Auto restart setting To allow indoor unit to auto restart once power resume from failure, apply the setting as below.

For wireless controller, to enable auto restart, the steps are as follow: 1. Press the indoor PCB emergency ON/OFF button for 5 seconds to go into setting mode. When the unit

are in setting mode, all the LED of the indoor will be light up. 2. Use the wireless handset, select “Fan” mode. 3. Select “High Fan” speed. 4. Press the “ON/OFF” button on the wireless handset to complete the setting. Once the setting is

complete, all the indoor LED will be turned off and the unit will remain in standby mode.

To disable auto restart, the steps are as follow: 1. Press the indoor PCB emergency ON/OFF button for 5 seconds to go into setting mode. When the unit

are in setting mode, all the LED of the indoor will be light up 2. Use the wireless handset, select “Fan” mode. 3. Select “Medium Fan” speed 4. Press the “ON/OFF” button on the wireless handset to complete the setting. Once the setting is

complete, all the indoor LED will be turned off and the unit will remain in standby mode.

For wired controller, turn On dip switch 2 at the back of the controller to enable auto restart function. To disable it, turn Off dip switch 2.

Page 29: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 25

LEAKAGE TEST SKETCH

to indoor unit

to indoor unit

nitrogen LOoutdoor

unit

ball valve

ball valve

liquid pipe

gas pipe

HI

service port

pressure gauge

8.0 Air Leakage Test, Vacuum and Refrigerant Charge 8.1 Air leakage test

To conduct air leakage test, ensure the ball valve is off.

Refer to the procedure below to avoid polluting the lubricating oil during the leakage test.

Air leakage testing procedure Remark

Charging Nitrogen gas

Nitrogen gas (For R410A units: 4.15MPa, R22 units: 2.94MPa), wait for 24 hours. If the pressure is not drop, the units pass the air tightness testing; if pressure decrease, use soap water to detect the leakage point.

After charging the nitrogen gas, use soap water on the part of brazing, flange and connection position to see if there is any bubble occurred.

After air leakage testing, wipe off the bubbling agent.

Do not use oxygen and other flammable air to increase the pressure to avoid explosion

8.2 Vacuum

Ensure the ball valve is off before conducting vacuum.

Vacuum pressure is 650Pa and the time of vacuum is 24 hours.

Do not use refrigerant to vacuum.

8.3 Charging the refrigerant

Charge in additional refrigerant based on the piping length connection.

Additional charge required can be obtained from selection report or calculated manually with the steps as shown below.

Additional charge amount: = ∑ Li* Gi = (Piping Length for 15.88mm X Additional Charge Amount) + (Piping Length for 12.7mm X Additional Charge Amount) + (Piping Length for 9.52mm X Additional Charge Amount) + (Piping Length for 6.35mm X Additional Charge Amount) Caution that the additional charge amount of different pipe diameter varies base on type of refrigerant.

Pipe Diamater (mm) 6.35 9.52 12.70 15.88 19.05

R22 Additional Charge (g/m) 50 80 120 180 290

Pipe Diamater (mm) 6.35 9.52 12.70 15.88 19.05

R41A additional Charge (g/m) 45 70 120 180 260

Before charging, open the all ball valve.

vacuum

pump

check valve

service port

ball valveliquid pipe

gas pipe

ball valve

outdoor

unit

compound

pressure gauge

HILO

to indoor unit

to indoor unit

VACUUM SKETCH

Page 30: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

26 Installation Manual IM-MDS_(i)

REFRIGERANT CHARGING SKETCH

weighbridge

refrigerant

tank

compound

pressure gauge

HILO

to indoor unit

to indoor unit

service port

ball valve

liquid pipe

gas pipeball valve

outdoor

unit

refrigerant

tank

weighbridge

LO HI

compound

pressure gauge

outdoor

unit

ball valvegas pipe

liquid pipe

ball valve

service port

to indoor unit

to indoor unit

When charging R410A with cylinder which is without the siphon pipe, turn the cylinder upside down when charging to ensure only liquid refrigerant is charged into the system.

9.0 Commissioning 9.1 Checking list before commissioning

Ampere of indoor & outdoor units is normal and under protection value?

Power supply for indoor and outdoor units is normal?

Dip switch address setting up for indoor units are ok?

Indoor unit is power on?

Communication wiring is ok?

Refnet is well installed?

Condensing water drainage system is ok?

Earthing is ok?

Insulation testing (10Mega Ω)

Power supply check (220-240V/380-415V)

System has been vacuumed and charged with additional refrigerant?

How many indoor units are controlled by outdoor unit controller?

Outdoor unit ball valve is opened? 9.2 Commissioning record table

Before commissioning, power on the system 24 hours in advance to preheat the crankcase heater.

No. Suction

pressure(bar)

Discharge pressure

(bar)

Voltage (V)

Ampere (A)

Suction temperature

(℃ )

Ambient Temp.(℃ )

Checking person / Time

1

2

3

4

5

6

9.3 Common problems during commissioning

Symptoms Wiring controller Possible reason

No heating or cooling Cannot select cooling or heating When one indoors units in heating, all indoors in heating mode

Fan stop when heating Defrost Fan stop running when defrosting

Pump keep running No indication Pump keep running to drain the water

The cylinder had Syphon pipe

Syphon pipe

Page 31: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 27

10.0 Unit Outlines and Dimensions MWMD/M5WMD 009/010/015G

MWMD/M5WMD 020/025G

Page 32: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

28 Installation Manual IM-MDS_(i)

MCKD/M5CKD 020/025/030/040/050A MCKD/M5CKD 010/015/020C

MCMD 020/025/028E M5CMD 015/020/025/028E

Page 33: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 29

MCMD/M5CMD 040/050D

MCMD/M5CMD 062C

Page 34: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

30 Installation Manual IM-MDS_(i)

MCCD/M5CCD 010C

MCCD/M5CCD 015/020/025C

Page 35: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 31

MCCD/M5CCD 028C

MCCD/M5CCD 030C

Page 36: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

32 Installation Manual IM-MDS_(i)

MCCD/M5CCD 038C

MCCD/M5CCD 040C

Page 37: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 33

MCCD/M5CCD 050C

MCCD/M5CCD 060C

Page 38: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

34 Installation Manual IM-MDS_(i)

MDS 030A(R)

MDS 040/050/060/070A(R) 5MDS 050/060/070B(R)

Page 39: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 35

MDS 080/100/120/150B(R) 5MDS 080/100/120/140/160/180B(R)

MDS 180/200/220/240B(R) 5MDS 200/220/240B(R)

Page 40: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

36 Installation Manual IM-MDS_(i)

MDS 260/280/300/320B(R) 5MDS 260/280/300/320/340/360B(R)

5MDS 380/400/420B(R)

Page 41: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Installation Manual IM-MDS_(i) 37

5MDS 440/460/480/500B(R)

Page 42: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately
Page 43: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately
Page 44: Digital Variable Multi Air Conditioner - Acson International (24042007)/IM-MDS/IM-MDS... · Digital Variable Multi Air Conditioner ... Do not switch off the power supply immediately

Products manufactured in an ISO certified facility. This document contains the most current product information as of this printing. For the

most up-to-date product information, please go to www.mcquayup.com

www.mcquayup.com