Upload
margaret-murphy
View
220
Download
6
Tags:
Embed Size (px)
Citation preview
Dimensioning and Protection of PV Plants with examples
of design
Session 2
Dr. Francesco De Lia - ENEA
C.R. ENEA Casaccia
Ing. Francesco De Lia - ENEA
• Module Datasheets
• Electrical mismatch in PV array
• Electrical conduits sizing on DC and AC sides
• PV Plant protection against over currents on DC side
• Thermal sizing of electrical switchboards
• Lightning protection of PV plants
• Description of PV Plant design
Outlook
Ing. Francesco De Lia - ENEA
Calculation of Current Carrying Capacity of the
cablesIZ
Ing. Francesco De Lia - ENEA
Current carrying capacity IZ is defined as the maximum current which can be carried continuously by a conductor under specified conditions without its steady-state temperature exceeding a specified value (Tmax).
the maximum temperatures allowed are: Tmax=70 °C for cables with PVC insulation Tmax=90 °C for cables with EPR insulation
the Current carrying capacity IZ is obtained by using the formula (installation not buried in the Ground):
IZ=IZ0 * K1 * K2where:
IZ0 is the current carrying capacity of the single conductor at 30 °C reference ambient temperaturek1 is the correction factor if the ambient temperature is other than 30 °Ck2 is the correction factor for cables installed bunched or in layers or for cables installed in a layer on several supports.
Dimensioning of electrical conduitsCurrent carrying capacity (Iz)
Ing. Francesco De Lia - ENEA
Table 1 - Current carrying capacity (IZ0) at Tamb=30 °C
Dimensioning of electrical conduitsNot buried in the ground
• The table1 provides Izo for installation method indicated in the picture.
• There are a lot of other tables that provide Izo, depending on the specific installation method
For more information:http://www05.abb.com/global/scot/scot209.nsf/veritydisplay/ae2141fea4bfa9d748257a700024a579/$file/1SDC010002D0206.pdf
Ing. Francesco De Lia - ENEA
Dimensioning of electrical conduitsNot buried in the ground
Correction factor K1 for air temperature other than 30 °C
For more information:http://www05.abb.com/global/scot/scot209.nsf/veritydisplay/ae2141fea4bfa9d748257a700024a579/$file/1SDC010002D0206.pdf
Ing. Francesco De Lia - ENEA
Dimensioning of electrical conduitsCurrent carrying capacity: the factor K2
For more information:http://www05.abb.com/global/scot/scot209.nsf/veritydisplay/ae2141fea4bfa9d748257a700024a579/$file/1SDC010002D0206.pdf
Ing. Francesco De Lia - ENEA
The current carrying capacity Iz of a cable buried
in the ground, is calculated by using this formula:
IZ=IZ0 * K1 * K2 * K3where:
IZ0 is the current carrying capacity of the single conductor for installation in the ground at 20°C reference temperature
K1 is the correction factor if the temperature of the ground is other than 20°C;
K2 is the correction factor for adjacent cables
K3 = is the correction factor if the soil thermal resistivity is different from the reference value 2.5 K·m/W
Dimensioning of electrical conduitsInstallation buried in the ground
Ing. Francesco De Lia - ENEA
Dimensioning of electrical conduitsInstallation buried in the ground
Table 1 - Current carrying capacity (IZ0) at Tground=20 °C
For more information:http://www05.abb.com/global/scot/scot209.nsf/veritydisplay/ae2141fea4bfa9d748257a700024a579/$file/1SDC010002D0206.pdf
Ing. Francesco De Lia - ENEA
Dimensioning of electrical conduitsInstallation buried in the ground
Correction factors k1
For more information:http://www05.abb.com/global/scot/scot209.nsf/veritydisplay/ae2141fea4bfa9d748257a700024a579/$file/1SDC010002D0206.pdf
Ing. Francesco De Lia - ENEA
Dimensioning of electrical conduitsInstallation buried in the ground
Correction factors k2
For more information:http://www05.abb.com/global/scot/scot209.nsf/veritydisplay/ae2141fea4bfa9d748257a700024a579/$file/1SDC010002D0206.pdf
Ing. Francesco De Lia - ENEA
PV Plant protection against overcurrents on DC side
Ing. Francesco De Lia - ENEA
Protection against overcurrents on DC sideFault on string cable
Stringboxes
• Hypothesis: Short Circuit in A• from
• B to A flows an electric current equal: (m-1)*Isc
• C to B flows an electric current equal: (m-n)*Isc
• These currents could damage the cables
• ALL STRINGS supply their short circuit current to the A point.
• Single inverter: the parallel of the strings can be indifferently made in String Boxes or in the Inverter switchboard.
Ing. Francesco De Lia - ENEA
Stringboxes
• Hypothesis: Short Circuit in A• from
• B to A flows an electric current equal: n*Isc
• C to A flows an electric current equal: (m-n)*Isc
• The current from C to A could damage the cable.
• The current from B to A could NOT damage the cable.
• ALL STRINGS supply their short circuit current to the A point.
• Single inverter: the parallel of the strings can be indifferently made in String Boxes or in the Inverter switchboard.
Protection against overcurrents on DC sideFault on the cable that connects the StringBox to the inverter
Ing. Francesco De Lia - ENEA
• SC in A is sensed by string/inverter fuses
• SC in B are NOT sensed by string/inverter fuses. However, this event has low-probability to occur because it would occur inside the switchboard
Stringboxes
Protection against overcurrents on DC sideUse of fuses
Inverter switchboard
Fuse for cable string protection
Fuse for protection the cable that connects String box with the inverter.
Ing. Francesco De Lia - ENEA
Protection Devices against overcurrenton DC side
Ing. Francesco De Lia - ENEA
On the DC side of PV-Plants we can found several protecion devices:
fuses
circuit breakers
block diodes
……..
Protection devices against overcurrent on DC side
Ing. Francesco De Lia - ENEA
In Inf IfConventional
Time
In ≤ 63 A 1.25 In 1.6 In 1h
63 A < In ≤ 160 A 1.25 In 1.6 In 2h
160 A < In ≤ 400 A 1.25 In 1.6 In 3h
400 A < In 1.25 In 1.6 In 4h
for a fuse, we define following parameters:
In: is the rated current
If: is the current ensuring effective operation in the conventional time of the fuse (1h/2h/3h/4h).
Inf: is the current ensuring NO effective operation in the conventional time of the fuse
1h
If=3.2 AIn=2A
The fuses
Protection devices against overcurrent on DC side
Ing. Francesco De Lia - ENEA
The fuses dissipate power
The fuses
Protection devices against overcurrent on DC side
Ing. Francesco De Lia - ENEA
Also for a circuit breakers, we define following parameters:
In: is the rated current
If: is the current ensuring effective operation of the circuit breaker in the conventional time (1h/2h)
Inf: is the current ensuring NO effective operation of the fuse in the conventional timeCircuit breakers
Inf If Conventional time
adjustable protective
devices(CEI 17-5)
No adjustable protective
devices(CEI 23-3/1)
- In ≤ 63A 1.13 In 1.45 In 1h
- In > 63A 1.13 In 1.45 In 2h
Ir ≤ 63A - 1.05 Ir 1.3 Ir 1h
Ir > 63A - 1.05 Ir 1.3 Ir 2h
Circuit breakers
Protection devices against overcurrent on DC side
Ing. Francesco De Lia - ENEA
Dissipate Power per pole (W) 1.5…6.4 1.8 – 7.2
Also the circuit breakers dissipate power
the manufacturers provide PD,pole
Circuit breakers
Protection devices against overcurrent on DC side
Ing. Francesco De Lia - ENEA
Thermal sizing of DC switchboardsDevice derating
An example of circuit breaker derating
Ing. Francesco De Lia - ENEA
Block diodes are traditionally used in Stand Alone PV Plants
In Stand Alone PV-Plants, during the sunset, without block diodes, the current would flow into the PV-module instead of into the loads because of the presence of batteries
Diodes block are installed in series of strings
Sometimes, in grid-connected PV Plants, diodes block are installed because, in presence of shadowing phenomena's on PV array, one or more PV string could absorb current from the others PV string.
Block Diodes
Protection devices against overcurrent on DC side
Ing. Francesco De Lia - ENEA
Shadowing phenomenon on one string
V
I
Stringa 1000 W/m2
Stringa 200 W/m2
Parallelo delle stringhe
U
S
T
IU
IT
IT = absorbed current by the shadowed string in OPEN CIRCUIT conditions (I=0)
~=
Why Diodes block are used
NO SHADOWED string (1000 w/m2)
SHADOWED string (200 w/m2)
PARALLEL of two strings
Protection devices against overcurrent on DC side
Ing. Francesco De Lia - ENEA
Protection of electrical feeders
Ing. Francesco De Lia - ENEA
If in an DC cables can flow current greater than their current
carrying capacity (IZ ), the cable must be protected by an
proper protective device.
In order to protect the cable, must be satisfied the following formulas:
where:IB : is the current for which the circuit is designed (for a string cable: IB = 1.25*Isc @STC)
IN : is the rated current of the protective device; for adjustable protective devices, IN is the set current
If :is the current ensuring effective operation in the conventional time of the protective device
IZ : is the current carrying capacity
ZfZNB *I ; I I I I 45.1
Protection of electrical feeders
Ing. Francesco De Lia - ENEA
Choice of fuses
if we choose Fuses for protection of electrical feeders, they are “gG type” (that are fuses used for cable protection). Moreover:
The fuses must be compliant with DC installations
must be satisfied the formula:
Vn > 1.2* Voc
Where:
Vn : is the rated voltage of the fuse
Voc : is the PV-array voltage in open circuit condition 1.2 : is a security factor
Protection of electrical feedersHow-to choice the protective devices on DC side
Ing. Francesco De Lia - ENEA
• If shadowing phenomenon on the PV array can occur, must be evaluate the possibility of installing block diodes. If so, the diodes must:• Preferably be low drop voltage• Have max reverse voltage greater than 2*Voc,@STC • Have rated current (Id) greater than 1.25*Isc@STC.
• Be careful: block diode dissipate power (PD = VD*ID), consequently heat sink are required.
Protection of electrical feedersHow-to choice the protective devices on DC side
Choice of Block Diodes
Ing. Francesco De Lia - ENEA
• Be careful: in order to reduce loss power, choose the low-voltage version
Protection of electrical feedersHow-to choice the protective devices on DC side
Ing. Francesco De Lia - ENEA
Thank you for attention…..