  • 7/22/2019 Dimmer Schneider

    1/492029E.fm/2 Schneider Electric

    Control and remote control Remote control dimmersand dimmerTV700, TVe700, TVo1000, TVBoand Vo1000

    FunctionThe (remote control) dimmers modulate lighting brightness for unit powers from 50to 1000 VA from one or more switch-on points.Products in the range whose terminology includes an "o" are fitted-out with an opticallink enabling them to communicate with one another without wiring to allow:extensions to powers greater than 1000 VAb additional functions (brightness regulation, indication, lighting level override, timedelayed scale, etc.) by combining auxiliariesb a three-phase distributionb a distribution on different types of lamps with centralised control.Optical transmission runs from left to right: the device furthest to the left controls theother devices.

    DescriptionA (remote control) dimmer is chosen according to:b the type of lighting, the control and variation range requiredb the auxiliary function required (maintaining a constant level of br ightness,overriding a pre-set level of brightness, time delayed scale, etc.).

    The dimmers and remote control dimmers comply with standards: IEC 669-2.1,NF EN 60669-2.1, EN 55-014, NF EN 55-014 (disturbance suppression).

    The dimmers and remote control dimmers are designed to operate from -5 Cto +50 C. However, between 30 C and 50 C, a 30 % reduction in acceptable powermust be anticipated:b for small unventilated enclosures or cubicles housing many power switchgearitems (circuit-breakers, contactors, solid state contactors, remote control dimmers,etc.)b for ambient temperature in room likely to be greater than 30 C (allow for annualtemperature variations). Inserts (catalogue number 27062) are then necessary toseparate remote control dimmers from devices with high losses.

    Choice according to lighting type

    Technical data Autonomousremote controldimmers

    Lighting fluctuationsystems

    TV700 TVe700 TVo1000 Vo1000 TVBo Type of transformer Precharge

    Controlled lighting

    Incandescent lamp b b b bLV halogen (230 V) b b b bELV halogen (12 or 24 V) with: PTV1 (1)

    electronic transformer buniversal electronic transformer b b b TFu70-TFu105-TFu150 PTV1 (1)

    ferromagnetic transformer b b b b TFt50 PTV1 (1)

    Fluorescent tube with electronic ballast 1-10 V controllable b

    Dischargelamp

    ferromagnetic ballast+ starter with electronic supply

    no variation possiblewith this load type

    (1)For TVo1000 and Vo1000, PTV1 required in ELV in thefollowing cases:b if the transformer is charged with a power less than 80% ofthe rated powerb if the load consists of a single transformer and a single lampb if the total load is less than 100 VA.

    Choosing auxiliary functions

    Function Auxiliary TVo1000 TV700Vo1000 TVe700

    TVBo

    Maintaining constant brightness RGo b no optical link andassociationpossible

    Load control (on/off) or remote indication ISo bOverride a lighting level NTVo b

    Progressive lighting on/off (adjustable time) TTVo b

    Optical repeater RPo b

    Remark on the Vo1000Associated with the TVo1000, the Vo1000 is recommended as a power extension(knob and ON/OFF control de-activated).

    Comment on the lighting supplied by a backed-up networkOperation on backed-up power supply (by generating set) may cause disturbances inlighting.

  • 7/22/2019 Dimmer Schneider

    2/492029E.fm/3Schneider Electric

    Control and remote control Remote control dimmersand dimmerTV700, TVe700, TVo1000, TVBoand Vo1000

    Characteristics

    Technical data Autonomousremote controldimmers

    Lighting fluctuationsystems

    TV700 TVe700 TVo1000 Vo1000 TVBo

    Characteristics

    Local control on front face

    by pushbutton (1) b b

    by knob bRemote control

    by pushbutton (1)

    non illuminated b b b b

    illuminated (max. 2.5 mA) b b b

    by switch (2) bControl by optical link b b b

    Memorisation of setting b b b bSetting the minimum lighting threshold b b

    Power extension by association b b bEnergisation delay

    3 s 3 s 3 sProtection

    Preservation, on brownout < 0.2 s,of the lighting level setting

    b b b knob b

    Short-circuit (by 5 x 20 mm rapid fuse)(A): spare fuse in a rack on the frontface

    3,2 5 5

    Short-circuit(electronic protection)

    b

    Fuse out of operation: lighting switch-off red indicator light permanently on

    b b

    Overload (electronic protection):- progressive reduction of lighting leveluntil stabilised

    b b b

    - total switch-off of lighting bOperation indication on front panel

    Variation, faults, OFF b b bVariation, OFF b

    Power supply230 V power supply (50 Hz 10 %) 10 % 10 % 10 % 10 % -10...+6 %Consumption (VA) 5 2,5 5 5 5Power loss (W) 10 10 15 15 15Connection

    Tunnel terminals (2 x 2,5 mm2) b b b b b

    (1): control order using pushbutton:b ON/OFF by impulse (duration: 100...300 ms)b variation by pressing for a min. of 390 ms(reversal of variation direction between twoactions).

    (2): control order using switch: ON/OFF.

  • 7/22/2019 Dimmer Schneider

    3/492029E.fm/4 Schneider Electric

    Control and remote control Remote control dimmersand dimmerTV700, TVe700, TVo1000, TVBoand Vo1000

    Specific technical data

    Acceptable power according to luminous load Watt

    TV700Incandescent-LV halogen (230 V) 60 - 700

    TVe700

    Incandescent-LV halogen (230 V) 50 - 700

    ELV halogen (12/24 V):

    with ferromagnetic transformer 50 - 550

    with electronic and universal electronic transformer 50 - 650

    TVo1000/Vo1000

    Incandescente-halogne BT (230 V) 60 - 1000

    ELV halogen (12/24 V):

    with ferromagnetic transformer 60 - 800

    with electronic and universal electronic transformer 60 - 900

    Vo1000b alone, used as a dimmer controlled from its front face by knob and/or optionalremote ON/OFFb associated with a remote control dimmer, it is recommended as a power extension(knob and ON/OFF control de-activated).

    TVBob maximum number of acceptable tubes (1-10 V ballast):

    Tube type Nbr of tubes

    18 W single-corrected 50

    dual-corrected 40

    36 W single-corrected 40

    dual-corrected 20

    58 W single-corrected 30

    dual-corrected 15

  • 7/22/2019 Dimmer Schneider

    4/492029E.fm/5Schneider Electric

    Control and remote control Remote control dimmersand dimmerTV700, TVe700, TVo1000, TVBoand Vo1000

    Catalogue numbersType Power Cat. No. Width in mod. of 9 mm

    TV700 60...700 W 15287 6

    15287

    Type Power Cat. No. Width in mod. of 9 mm

    TVe700 50...700 VA 15285 6

    15285

    Type Power Cat. No. Width in mod. of 9 mm

    TVo1000 60...1000 VA 15289 10

    15289

    Type Power Cat. No. Width in mod. of 9 mm

    Vo1000 60...1000 VA 15290 10

    15290

    Type Power Cat. No. Width in mod. of 9 mm

    TVBo 1500 VA maxi 15297 6

    15297

    Additionalinformations

    Auxiliaries:page 92039/2