discrimination curve

Embed Size (px)

Citation preview

  • 8/13/2019 discrimination curve

    1/6

    TrustedTM

    AN-T80008

    Issue 2 Feb 07 AN-T80008 1

    Application Note

    MCB Discrimination

    In a radial feeder layout, as shown in Figure 1 overleaf, the purpose of discrimination is to disconnectonly the faulty load or feeder from the network and no others, thus ensuring maximum continuity ofservice. If discrimination studies are not or are incorrectly carried out, an electrical fault may causeseveral protective devices to trip, thus provoking an interruption in the supply of power to a large part ofthe network. That constitutes an abnormal loss in the availability of electrical power for those parts of

    the network where no fault occurred.

    Issue Record

    Issue

    Number

    Date Revised by Technical

    Check

    Authorised by Modification

    1 Jun 06 Julia Bourn Initial Issue

    2 Feb 07 Nick Owens Ray Brown Pete Stock Format

  • 8/13/2019 discrimination curve

    2/6

    TrustedTM

    AN-T80008 MCB Discrimination

    Issue 2 Feb 07 AN-T80008 2

    Figure 1 Several circuit-breakers are concerned by the fault If

    Several types of over currents may be encountered in an installation:

    overloads, short-circuits, inrush currents, as well as:

    earth faults, transient currents due to voltage dips or momentary loss of supply.

    The MCB characteristic curves must be checked against the power supply overload graph to ensurethat the MCB trips before the power supply in an overload situation.

  • 8/13/2019 discrimination curve

    3/6

    TrustedTM

    AN-T80008 MCB Discrimination

    Issue 2 Feb 07 AN-T80008 3

    Trusted Power supplies T824X

    The trend for increasing power in an ever decreasing package requires a higher level of sophisticationof the internal electronics and self protection circuitry. Improved self protection however, means that anMCB discrimination study becomes an important part of the power distribution design.

    Tests carried out on the power units under severe overload situations produced the following results.(Maximum rating is 31 amps per unit at 24V, i.e. 750W.)

    Figure 2 Power unit(s) severe overload Current v Time

    The graph above shows the response of a single power unit to severe overloads. As the load is

    increased, the power supply protection mechanism operates and shuts down the output. It can beseen that for a period of just in excess of 200ms the power unit can provide currents up to 115 amps or380% of its stated maximum(115/31 = 3.8). This 200ms/380% can be extrapolated for additionalpower units in order to perform MCB discrimination studies.

    Power Unit(s) Overload Current Vs Time

    0

    50

    100

    150

    200

    250

    300

    0 20 40 60 80 100 120 140

    Current / Amps

    Time/ms

    1 Power Unit

    2 Power Units

  • 8/13/2019 discrimination curve

    4/6

    TrustedTM

    AN-T80008 MCB Discrimination

    Issue 2 Feb 07 AN-T80008 4

    Example analysis

    If the circuit breakers used were ETA 2210-S2 (fast acting) 10A (see Figure 3)then at two times theMCB rating i.e. 20A, it would take 10 seconds to trip the MCB.

    If one of the MCBs in the example above were subjected to an overload, resulting in a load of 20A inone branch, then the power pack total load is increased to 40A. At 40A the power pack goes intoprotective shutdown after 700mS and hence will shutdown before the branch MCB has opened. Alarger overload will result in protective shutdown after 200ms (see Figure 2)

    Figure 3 Characteristics of ETA Thermal-magnetic circuit breaker 2210-S2 (fast acting)

    Power unit

    10A

    10A

    10A

  • 8/13/2019 discrimination curve

    5/6

    TrustedTM

    AN-T80008 MCB Discrimination

    Issue 2 Feb 07 AN-T80008 5

    Conclusion

    The internal self-protection of T824x power units may cause them to trip before the MCBs. Ensure thatMCBs and other circuit protection devices are rated to ensure that any one short will not overload thesupply. Low current ratings are therefore recommended, to ensure that the protection device trips first,due to its time/current curve.

  • 8/13/2019 discrimination curve

    6/6

    ICS Triplex technologies and services are available worldwide.

    Regional Headquarters:

    Americas:

    4325 West Sam Houston

    Parkway North, Suite 100

    Houston

    Texas 77043-1219

    USA

    Tel: +1 713 353 2400

    Fax: +1 713 353 2401

    Europe, ME & Africa:

    Hall Road

    Maldon Essex

    CM9 4LA

    UK

    Tel: +44 1621 854444

    Fax: +44 1621 851531

    Asia Pacific:

    Unit 2/12 Keegan Street

    OConnor

    Western Australia

    Tel: +61 89 314 7787

    Fax: +61 89 314 7786

    www.icstriplex.com

    For technical support email: [email protected]

    Sales enquiries: [email protected]

    Technology Driven Customer Led