ING. Lamina
PROYECTO:
ENTIDAD:
MODULO:
DESCRIPCION: DISEO DE COLUMNAS- BLOQUE 02 (AULA 03 Y VIVIENDA PARA PROFESORES)CODIGO SNIP 248940
DIAGRAMA DE INTERACCIN DE COLUMNASDATOS GEOMTRICOS : FACTOR DE REDUCCION: 80.31
0.7 para columnas estribadas 85.33
b= 25 cm. Recub. = 2.5 cm 0.75 para columnas zunchadas 0
t= 25 cm. f = 0.7 4.67f'c= 210 Kg/cm2 RESUMEN DE PUNTOS PRACTICO BALANCEADO
fy= 4200 Kg/cm2 Es= 2000000 Punto C Mu Pu Mu Pu Mu Pu
3 2.50 2.75 -7.14 1.92 -5.00 2.55 3.20
b = 25 cm. 5 7.13 5.77 25.85 4.04 18.10 6.67 44.63
Cb 11.76 6.67 44.63 4.67 31.24
# de barras Pulgadas As (cm2) 4 22.5 4.62 106.46 3.23 74.52
2.5 2 f de 5/8 3.96 1 0.00 144.83 0.00 101.38
0 f de 0 0.00
5 0 f de 0 0.00
0 f de 0 0.00
cm 20
25 5
f de 1/2 0.00
5
0 f de 0 0.00
5
2 f de 5/8 3.96
0 f de 0 0.00
0 f de 0 0.00
DATOS DEL ANLISIS: As total (cm2) = 7.92
Mu = 2.55 Tn - m SELECCIONADO As minimo 1% (cm2) = 6.25
Pu= 3.20 Tn As mximo 6% (cm2) = 37.50
CENTROIDE PLSTICO:(Con Respecto a la parte Inferior)
Yo = 12.50
PUNTO 1 P'u= 144.8265 Toneladas
PUNTO 2 Ey= 0.0021 cm.
Cb= 11.76 cm.
ESFUERZOS EN EL ACERO:
Es1= 0.00236 > Ey Fs1= 4200.00 Kg/cm2
Es2= 0.00109 < Ey Fs2= 2175.00 Kg/cm2
Es3= -0.00019 < Ey Fs3= 375.00 Kg/cm2
Es4= -0.00146 < Ey Fs4= 2925.00 Kg/cm2
Es5= -0.00274 < Ey Fs5= 4200.00 Kg/cm2
DC-02 A
MEJORAMIENTO DE LOS SERVICIOS EDUCATIVOS DE LA INSTITUCION EDUCATIVA INICIAL JESUS DE PRAGA, DISTRITO DE SANTA LUCIA - LAMPA - PUNO
01 INFRAESTRUCTUR PEDAGOGICA
MUNICIPALIDAD DISTRITAL DE SANTA LUCIA
A.M.J.HDISEO DE COLUMNAS - DIAGRAMA DE ITERACIONES
1.92; -5.00
4.04; 18.10
4.67; 31.24
3.23; 74.52
0.00; 101.38
PU maximo, 80.31
-20
0
20
40
60
80
100
120
140
160
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0
Pu
(T
n)
Mu (Tn-m)
DIAGRAMA DE INTERACCION
DIAGRAMA TEORICO
DIAGRAMA DE DISEO
SOLICITACION
BALANCEADO
PU maximo