Dkg-329 User Manual

Embed Size (px)

Citation preview

  • 8/13/2019 Dkg-329 User Manual

    1/43

    DKG-329 User Manual V-12 (09.10.2012)

    DKG-329 AUTOMATIC

    TRANSFER SWITCH

    CONTROLLER

    WITH UNINTERRUPTED TRANSFER AND MULTIPLE GENSET SUPPORT

    The DKG-329 is designed to monitor 3-phase

    mains voltages, send remote start command to

    generating sets and control the changeover of both

    generator and mains contactors.

    The unit offers an internal synchroscope for

    uninterrupted transfer in both directions. The

    number of gensets to run before transfer is

    selectable, allowing multiple genset support.

    If a fault condition occurs, the unit disables the

    remote starting automatically and indicates the

    failure with the corresponding led lamp and text.

    The unit provides a comprehensive set of digitallyadjustable program parameters. The unauthorizedaccess to program parameters is prevented by a 3level password system. All programs may bemodified via front panel pushbuttons and do notrequire any external unit.

    Last 100 faults are stored in the event log file. The

    event log includes not only the date-time

    information, but also a comprehensive list of

    measured parameters at the time that the fault has

    occurred.

    The WINDOWS based RAINBOW programallows remote monitoring and control.

    The unit supports MODBUS protocol enablingcommunication with PLCs and buildingmanagement systems. The MODBUS protocol isalso supported through GSM and PSTNmodems.

    True RMS measurements

    Synchroscope & check synch

    No break transfer& no b reak load test

    Automat ic con tac tor con t ro l

    Mul t iple genset system sup portLoad shedding, dummy load

    Event logging with t ime stamp and measurements

    Battery backed-up real t ime clock

    Bui l t in d ai ly / weekly / monthly exerciser

    Weekly operation schedule programs

    Field adjustable parameters

    RS-232 serial port

    Free MS-Window s Remote mon itor ing SW

    GSM and PSTN modem sup port

    GSM SMS message sending on faul t

    MODBUS comm unicat ions

    Mult iple language supp ort

    Custom er logo disp lay capabi l i ty

    16 Am p contactor outputs

    1 Amp DC semiconductor cont ro l outpu ts

    Configurable digi tal inputs: 7

    Configurable digi tal outputs: 3

    Total digi tal outputs: 6

    I/O expansion capabi l i ty

    Plug- in conn ect ion system

    Sealed fron t panel

    FEATURESDESCRIPTION

  • 8/13/2019 Dkg-329 User Manual

    2/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 2 -

    Section1. INSTALLATION

    1.1. Introduction to the Control Panel1.2. Mounting the Unit1.3. Wiring the Unit

    2. INPUTS AND OUTPUTS3. DISPLAYS

    3.1. Led Displays3.2. Language Selection3.3. Digital Display

    4. ALARMS AND WARNINGS5. MODES OF OPERATION6. LOAD TRANSFER MODES

    6.1. Transfer with Interruption6.2. No Break Transfer7.OTHER FEATURES

    7.1. Remote start operation7.2. Mains Simulation (Disable Start)7.3. Delayed Mains Simulation, Battery Charging7.4. Service Request Display7.5. Engine Hours Meter7.6. Date-Time Display7.7. Display of Software Version7.8. Modem connection

    7.9. SMS message sending7.10. Remote Monitoring and Programming7.11. External Control of the Unit7.12. Automatic Exerciser7.13. Resuming to factory set parameters7.14. Load Shedding / Dummy Load7.15. Firmware Update7.16. Pre-Transfer Signal

    8. MODBUS COMMUNICATION9. WEEKLY OPERATION SCHEDULE10. EVENT LOGGING

    11. STATISTICAL COUNTERS12. MAINTENANCE13. PROGRAMMING14. TROUBLESHOOTING15. DECLARATION OF CONFORMITY16. TECHNICAL SPECIFICATIONS17. CONNECTION DIAGRAM

    TABLE OF CONTENTS

  • 8/13/2019 Dkg-329 User Manual

    3/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 3 -

    The unit is a control and protection panel designed to monitor the 3-phase mains voltages, send remote

    start command to the generating set and make changeover of both generator and mains contactors. The genset is

    supposed to be controlled by a Remote Start type control unit.It shows the measured values on its display. The

    unit is designed to provide user friendliness for both the installer and the user. Programming is usually

    unnecessary, as the factory settings have been carefully selected to fit most applications. However

    programmable parameters allow the complete control over the load transfer. Programmed parameters are

    stored in a Non Volatile Memory and thus all information is retained even in the event of complete loss of

    power.

    Measured parameters are:

    Mains voltage phase L1 to neutral

    Mains voltage phase L2 to neutralMains voltage phase L3 to neutralMains voltage phase L1-L2Mains voltage phase L2-L3Mains voltage phase L3-L1Mains frequencyBattery voltageGen voltage phase L1 to neutralGen voltage phase L2 to neutralGen voltage phase L3 to neutralGen voltage phase L1-L2Gen voltage phase L2-L3Gen voltage phase L3-L1

    Load current phase L1Load current phase L2Load current phase L3

    Gen frequency

    Load total kWLoad total cos

    Load L1 kW

    Load L2 kW

    Load L3 kW

    Load L1 kVAr

    Load L2 kVAr

    Load L3 kVAr

    Load L1 cos

    Load L2 cos

    Load L3 cosSynchroscope phase angle

    The unit is designed for panel mounting. The user should not be able to access parts of the unit

    other than the front panel.

    Mount the unit on a flat, vertical surface. Before mounting, remove the mounting brackets and

    connectors from the unit, then pass the unit through the mounting opening. The unit will be maintained in its

    position by the mounting brackets spring.

    The output of the current transformers shall be 5 Amperes. The input current rating of the current

    transformers may be selected as needed (between 10/5 and 9000/5 amps). Current transformer outputs

    shall be connected by separate cable pairs from each transformer, to related inputs. Never use common

    terminals or grounding. The power rating of the transformer should be at least 5 VA. It is recommended to

    use 1% precision transformers.Programmable digital inputs are compatible with both normally open and normally closed

    contacts, switching either to BAT-or BAT+.

    Engine body must be grounded for correct operationof the unit, otherwise incorrect voltage andfrequency measurements may occur.

    1.2 Mounting the Unit

    1.1 Introduction to the Control Panel1. INSTALLATION

  • 8/13/2019 Dkg-329 User Manual

    4/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 4 -

    WARNING: ELECTRICITY CAN KILLALWAYS disconnect the power BEFORE

    connecting the unit.The fuse rating should be 6

    Amps.1) ALWAYS remove the plug connectors when inser t ing wires with

    a screwdriver.

    2) An appropr iate and readi ly accessib le set of disconn ect ion

    devices (e.g. automatic fu ses) MUST be prov ided as p art of the

    instal lat ion.

    3) The bui ld ing mains supply MUST incorporate appropr iate shor t -

    circu it backup prot ection (e.g. a fuse or circ uit breaker) of High

    Breaking Capacity (HBC, at least 1500A).

    Use cables of adequate current carrying capacity (at least2

    WARNING: THE UNIT IS NOT FUSED.

    Use external fuses for Mains phases: L1,L2,L3,Generator phase: L1,L2,L3, Battery positive: BAT(+).Install the fuses as nearly as possible to the unit in a

    lace easil accessible for the user.

    1.3 Wiring the Unit

  • 8/13/2019 Dkg-329 User Manual

    5/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 5 -

    RS-232 SERIAL PORT: This connector provides serial data input and output for various purposes like

    remote monitoring and remote programming.

    EXTENSION CONNECTOR: This connector is intended for the connection to output extension modules.

    The optional relay extension module provides 8 programmable 16A relay outputs. The unit allows the use of

    up to 2 I/O extension modules.

    Term Function Technical data Description

    1 GENERATOR CONTACTOR Relay output, 16A-AC This output provides energy to the generator

    contactor. If the generator phases do not have

    acceptable voltage or frequency values, the

    generator contactor will be de-energized. In

    order to provide extra security, the normally

    closed contact of the mains contactor should

    be serially connected to this output.

    2 GEN-L1 Generator phaseinputs, 0-300V-AC Connect the generator phases to these inputs.The generator phase voltages upper and

    lower limits are programmable.

    3 GEN-L2

    4 GEN-L3

    5 GENERATOR NEUTRAL Input, 0-300V-AC Neutral terminal for the generator phases.

    6 MAINS NEUTRAL Input, 0-300V-AC Neutral terminal for the mains phases.

    7 MAINS-L3 Mains phase inputs,

    0-300V-AC

    Connect the mains phases to these inputs.

    The mains voltages upper and lower limits are

    programmable.8 MAINS-L2

    9 MAINS-L1

    10 MAINS CONTACTOR Relay output, 16A-AC This output provides energy to the mains

    contactor. If the mains phases do not have

    acceptable voltages, the mains contactor will

    be de-energized. In order to provide extra

    security, the normally closed contact of thegenerator contactor should be serially

    connected to this output.

    11 GROUND O VDC Power supply negative connection.

    12 BATTERY POSITIVE +12 or 24VDC The positive terminal of the DC Supply shall

    be connected to this terminal. The unit

    operates on both 12V and 24V battery

    systems.

    13 NC

    14 NC

    15 NC

    16 NC

    2. INPUTS AND OUTPUTS

  • 8/13/2019 Dkg-329 User Manual

    6/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 6 -

    Term Function Technical data Description

    17 RELAY-1 Output 1A/28VDC This relay has programmable function,

    selectable from a list.

    18 RELAY-2 Output 1A/28VDC This relay has programmable function,

    selectable from a list.19 HORN RELAY OUTPUT Output 1A/28VDC This relay controls the horn

    20 REMOTE START OUTPUT Output 1A/28VDC This relay is used for remote start signal.

    21 DIGITAL INPUT - 1:

    EMERGENCY STOP

    Digital inputs These inputs have programmable

    characteristics selected via the program

    menu. Each input may be driven by a

    normally closed or normally open contact,

    switching either battery+ or battery-. The effect

    of the switch is also selectable from a list. See

    PROGRAMMING section for more details.

    22 DIGITAL INPUT - 2:

    SPARE-1

    23 PROGRAM LOCK

    24 DIGITAL INPUT - 3:

    SPARE-2

    25 DIGITAL INPUT - 4:

    SPARE-3

    26 DIGITAL INPUT - 5:

    FAULT RESET

    27 DIGITAL INPUT - 6:

    ALARM MUTE

    28 DIGITAL INPUT - 7:

    PANEL LOCK

    29 CURR_1+ Current transformer

    inputs, 5A-AC

    Connect the load current transformerterminals to these inputs. Do not connect thesame current transformer to other instrumentsotherwise a unit fault will occur. Connect eachterminal of the transformer to the units relatedterminal. Do not use common terminals. Donot use grounding. Correct polarity of

    connection is vital. If the measured power isnegative, then change the polarity of each 3current transformers. The rating of thetransformers should be the same for each ofthe 3 phases. The secondary winding ratingshall be 5 Amperes. (For ex. 200/5 Amps).

    30 CURR_1-

    31 CURR_2+

    32 CURR_2-

    33 CURR_3+

    34 CURR_3-

  • 8/13/2019 Dkg-329 User Manual

    7/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 7 -

    The unit has 12 LEDs, divided in 3 groups:-Group_1: Operating mode: This group indicates the genset function.

    -Group_2:Mimic diagram: This group indicates the current status of the mains and genset

    voltages and contactors.

    -Group_3:Warnings and alarms: This group indicates the existence of abnormal conditions

    encountered during operation.

    Function Color Description

    MAINS ON Green The LED will turn on when all 3 mains phase voltages

    are within the limits.

    MAINS OFF Red The LED will turn on when at least one of the mains

    phase voltages is outside limits.

    LOAD MAINS Green It turns on when the mains contactor is activated.LOAD GENERATOR Yellow It turns on when the generator contactor is activated.

    GENERATOR Yellow The LED will flash when the engine is running. It will

    turn on steadily when all 3 generator phase voltages

    are within the programmed limits.

    LOAD TEST Yellow It turns on when the related operation mode is

    selected. One of these LEDs is always on and

    indicates which operation mode is selected.

    If the operation of the genset is disabled by the

    weekly operation schedule, then the AUTO led will

    flash.

    TEST Yellow

    OFF Yellow

    AUTO Green

    ALARM Red If a fault condition resulting to the engine shutdown

    has occurred, the alarm led turns on steadily. If a

    loaddump condition occurs, this led will flash. Alarms

    work on a first occurring basis. The occurrence of a

    fault will disable other faults of lower or equal priority.

    WARNING Red If a warning condition has occurred, this led turns on

    steadily. The warnings work on a first occurring basis.

    The occurrence of a warning will disable other

    warnings, however shutdown and loaddump alarms

    are still allowed.

    SERVICE REQUEST Red Engine periodic maintenance request indicator. It

    turns on when the preset engine hours or time

    duration after previous service has elapsed.

    3.1 Led Displays3. DISPLAYS

  • 8/13/2019 Dkg-329 User Manual

    8/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 8 -

    The unit is able to display information in 3 languages. Language selection is made through program

    parameter CONTROLLER CONFIGURATION > LANGUAGE SELECTION. Below selections are available:

    0: English language

    1: Turkish language

    2: Chinese language

    3: ask selection at power-up

    If language is set to 3, below screen will come at power on:

    Left / Up / Down arrow pushbuttons will select the screen language. The language will be asked

    everytime power is turned on.

    With selections of 0,1,2 this screen will not appear and the selected language is enabled.

    The unit has a graphical 128x64 pixel LCD display. It shows:-Measured parameters,-The company logo,-The alarm list-Software version and date-time information,-Statistical counters,-Event records,-Program parameters.

    Navigation between different screens s made with the MENU and MENU buttons. Eachdepression of the MENU button switches the display to the next screen. Each depression of theMENUbutton switches the display to the previous screen.

    During operation, the unit will switch automatically between different screens, displaying alwaysthe most important parameters for the current operating status.

    If an alarm or warning occurs during operation, in other then programming mode, the display willautomatically switch to ALARM LISTposition. The MENU or MENUbuttons will not function. Toenable display navigation and mute the internal buzzer, press ALARM MUTE button first. If there ismore than one alarm, the next alarm is displayed by pressing the button. Thus all existing alarms canbe scanned. END OF ALARM LIST will be displayed when there is no more alarm to display.

    The display has a backlight illumination feature. The backlightturns on with the depression ofany button or when the genset runs. It turns off after 4 hours to allow power economy.

    3.3 Digital Display

    3.2 Language Selection

  • 8/13/2019 Dkg-329 User Manual

    9/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 9 -

    Screen Description Contents

    1 Mains parameters(phase to neutral)

    Genset statusMains Volts L1, Mains FrequencyMains Volts L2 , Battery VoltageMains Volts L3,

    2 Mains parameters(phase to phase)

    Genset statusMains Volts L1-L2, Mains FrequencyMains Volts L2-L3, Battery VoltageMains Volts L3-L1,

    3 Genset parameters(phase to neutral)

    Genset statusGenset Volts L1, Genset FrequencyGenset Volts L2, Battery VoltageGenset Volts L3,

    4 Genset parameters(phase to phase)

    Genset statusGenset Volts L1-L2, Genset FrequencyGenset Volts L2-L3, Battery VoltageGenset Volts L3-L1,

    5 Load parameters(currents)

    Genset statusLoad Current L1, Load FrequencyLoad Current L2, Load Active Power (kW)Load Current L3, Load Power Factor

    6 Load Phase Powerparameters

    Genset statusGenset Phase L1 : Active Power(kW) / Power FactorGenset Phase L2 : Active Power(kW) / Power FactorGenset Phase L3 : Active Power(kW) / Power Factor

    7 Load Phase Powerparameters

    Genset statusGenset Phase L1 : Reactive Power(kVAr)Genset Phase L2 : Reactive Power(kVAr)Genset Phase L3 : Reactive Power(kVAr)

    8 Synchroscope Phase Angle

    Voltage difference mains_L1gen_L1Frequency difference mains-genAngle difference mains-gen

    9 Company Logo

    10 Alarm List If no alarm exists, END OF ALARM LIST will be displayed.Existing alarms, load_dumps and warnings will be displayedas one screen for each entry. Switching to the next entry willbe made with the button.

    11 Date-Time,Software Version

    Date and time.Operating software version.

    12 Statistical Counters 1 / 2 Engine Hours Run

    Total Genset Active Power (kW-h)13 Statistical Counters 2/ 2 Engine Hours to Service

    Time to Service

    14 Event Records The unit provides information about last 100 events, startingfrom the most recent one.Please review chapter 10 for detailed information about eventlogging.

  • 8/13/2019 Dkg-329 User Manual

    10/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 10 -

    Alarms indicate an abnormal situation in the generating set are divided into 3 priority levels:

    1- ALARMS:These are the most important fault conditions and cause:

    - The ALARMled to be on steadily,

    - The genset contactor to be released immediately,

    - The engine to be stopped immediately,

    - The Horn, Alarm,Alarm+Load_dumpand Alarm+Load_dump+Warningdigital

    outputs to operate, (if selected via programming menu)

    2- LOAD_DUMPS:These fault conditions cause:

    - The ALARM led to flash,

    - The genset contactor to be released immediately,

    - The engine to be stopped after Cooldown period,

    - The Horn, Alarm+Load_dumpand Alarm+Load_dump+Warningdigital outputs to

    operate, (if selected via programming menu)

    3- WARNINGS: These conditions cause:

    - The WARNING led to be on steadily,

    - The Hornand Alarm+Load_dump+Warningdigital outputs to operate, (if selected

    via programming menu)

    If the ALARM MUTE button is pressed, the Horn output will be deactivated; however the

    existing alarms will persist and disable the operation of the genset.

    Alarms operate in a first occurring basis:

    -If an alarm is present, following alarms, load_dumps and warnings will not be accepted,

    -If a load_dump is present, following load_dumps and warnings will not be accepted,-If a warning is present, following warnings will not be accepted.

    Alarms may be of LATCHING type following programming. For latching alarms, even if the alarm

    condition is removed, the alarms will stay on and disable the operation of the genset. The existing alarms

    may be canceledby pressing one of the operating mode buttons (LOAD TEST / TEST / OFF / AUTO).

    Most of the alarms have programmable trip levels. See the programming chapter for adjustable

    alarm limits.

    EMERGENCY STOP:Set if a signal is detected at the emergency stop input.

    SPARE-1 / SPARE-2:Set if a signal is detected from the related spare fault input.

    MAINS CB FAIL TO CLOSE (warning): Set if the mains contactor feed back input is not active at the end

    of mains contactor timeout when mains contactor is activated. Enabled if one of digital inputs assigned as

    mains contactor feed back input.MAINS CB FAIL TO OPEN (load_dump): Set if the mains contactor feed back input is still active at the

    end of mains contactor timeout when mains contactor is deactivated. Enabled if one of digital inputs

    assigned as mains contactor feed back input.

    GENSET CB FAIL TO CLOSE (warning):Set if the genset contactor feed back input is not active at the

    end of genset contactor timeout when genset contactor is activated. Enabled if one of digital inputs

    assigned as genset contactor feed back input.

    GENSET CB FAIL TO OPEN (warning):Set if the genset contactor feed back input is still active at the

    end of genset contactor timeout when genset contactor is deactivated. Enabled if one of digital inputs

    assigned as genset contactor feed back input. The mains contactor cannot operate when this warning is

    up.

    LOW SPEED / HIGH SPEED: Set if the generator frequency is outside programmed limits. These faults

    will be monitored with Holdoff Timerdelay after the engine is running. Low and high limits for warning andalarm are separately programmable. Another high frequency shutdown limit which is 12% above the high

    limit is always monitored and stops the engine immediately.

    4. ALARMS AND WARNINGS

  • 8/13/2019 Dkg-329 User Manual

    11/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 11 -

    STOP FAIL (warning):Set if the engine has not stopped before the expiration of the Stop Timer.

    OVERLOAD (load_dump):Set if at least one of the genset phase currents goes over the Overcurrent

    Limit for Overload Timer. If currents goes below the limit before expiration of the timer then no alarm will

    be set.

    EXCESS POWER (load_dump):Set if the genset power (kW) supplied to the load goes over the Excess

    Power limit for Overload Timer. If the power goes below the limit before expiration of the timer then no

    alarm will be set.GENSET LOW VOLTAGE:Set if any of the generator phase voltages goes outside programmed limits for

    Overload Timer. This fault will be monitored with holdoff timerdelay after the engine is running.

    GENSET HIGH VOLTAGE:Set if any of the generator phase voltages goes outside programmed limits for

    Overload Timer. This fault will be monitored with holdoff timerdelay after the engine is running.

    LOW BATTERY VOLTAGE (warning):Set if the battery voltage goes below the programmed limit.

    HIGH BATTERY VOLTAGE:Set if the battery voltage goes above programmed limits. Both warning and

    alarm levels for high battery voltage are programmable.MAINS PHASE ORDER FAIL (warning):Set if the mains phase order checking is enabled, mains phasesare present and mains phase order is reversed. This fault prevents the Mains Contactor to close.

    The modes of operation are selected by pushing the front panel keys. Changing the operation

    mode while the genset is running will result to a behavior suitable for the new operating mode. For example,

    if the LOAD TEST mode is selected when genset is running at TEST mode, then the load will be transferred

    to the genset.

    OFF: In this mode, the mains contactor will be energized if mains phase voltages are within the

    programmed limits. The engine will be stopped.

    AUTO:It is used for genset and mains automatic transfer. If at least one of the mains phase voltages is

    outside limits, the mains contactor will be deactivated and the REMOTE START output will be activated atthe end of the start wait period. The engine will run without load during engine heating period. After this, if

    alternator phase voltages and frequency are within limits, then the unit will wait for the generator contactor

    period and the generator contactor will be energized.

    When all the mains phase voltages are within the limits, the engine will continue to run for the mains waiting

    period. At the end of this period the generator contactor is deactivated and the mains contactor will be

    energized. If a cooling period is given, the REMOTE START output will be active during the cooling period.

    At the end of the period, the REMOTE START output will be de-energized and the diesel will stop. The unit

    will be ready for the next mains failure. If the operation of the genset is disabled by the weekly schedule,

    then the AUTOled will flash, and the operation of the genset will be as in the OFFmode.

    TEST: It is used to test the generator when the mains are on, or keep the generator running in the

    emergency backup mode. The operation of the generator is similar to the AUTO mode, but the mains

    contactor will not be deactivated if the mains are not off. If the mains are off, mains contactor will bedeactivated and the generator contactor will be activated. When the mains are on again, a changeover to

    the mains will be made, but the engine will be kept running unless another mode is selected. To stop the

    engine, select AUTOor OFFmode.

    LOAD TEST:It is used to test the genset under load. Once this mode is selected, the engine will run and

    the load will be transferred to the genset. The genset will feed the load indefinitely unless another mode is

    selected.

    5. MODES OF OPERATION

  • 8/13/2019 Dkg-329 User Manual

    12/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 12 -

    The unit has two ways of transferring the load from genset to mains and vice versa.

    These modes are:

    -transfer with interruption.-no break transfer.

    This is the most conventional way of transferring the load between the genset and mains. Therewill be a power interruption period duration during the transfer. Note that the program parameters MainsContactor Timerand Genset Contactor Timerdefine the power interruption period.

    Transfer from genset to mains:-The generator contactor releases,-The unit waits for Mains Contactor Timer-The mains contactor is energized.

    Transfer from mains to genset:-The mains contactor releases,-The unit waits for Genset Contactor Timer

    -The generator contactor is energized.

    In this mode, the transfer will be made without power interruption. This implies that both ofthe mains and generator contactors will be active during transfer.

    The maximum duration that both contactors will be activated is programmable. However thisprocess may be quicker with the use of one auxiliary contact at each contactor. Thus the changeoverwill be quite instantaneous, preventing any excess or reverse power condition. Any digital input can beprogrammed for genset contactor auxiliary contact and mains contactor auxiliary contact.

    To prevent a phase to phase short circuit below criteria must be met:

    -The mains and generator voltages must be equal,-The mains and generator voltages must have the same phase,-The mains and generator voltages must have the same phase sequence order.

    The unit will allow a No Break Transferonly if all of the below conditions are fulfilled:

    -Mains phase voltages within the programmed limits,-Mains frequency within the programmed limits,-Genset phase voltages within the programmed limits,-Genset frequency within the programmed limits,-Mains phase order correct (or phase order check must be disabled),-Genset phase order correct (or phase order check must be disabled),-The difference between mains and genset frequencies not more than programmed limit,-The voltage difference between mains_L1 and genset_L1 not more than programmed limit,

    -The phase angle between mains_L1 and genset_L1 not more than programmed limit,

    If this transfer method is used, it is advised to make an electricalinterlock between contactors to prevent a phase to phase shortcircuit.

    6.1 No Break Transfer

    6.1 Transfer with Interruption

    6. LOAD TRANSFER MODES

  • 8/13/2019 Dkg-329 User Manual

    13/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 13 -

    When a No Break Transfer cycleis initiated, the unit checks all the above criteria to besatisfied as long as the Synchronization Fail Timeout is not expired.

    Normally with frequencies matching at +/- 2Hz and voltages matching at +/-10 volts anuncontrolled No Break Transferwill be successfull.

    If synchronization conditions are not met at the expiration of the Synchronization Fail

    Timeout, then the unit reverts to a Transfer with Interruption.

    If matching is found before the expiration of the Synchronization Fail Timeout,then both

    contactors will be activated. If contactor auxiliary contacts are used, the other contactor will releaseimmediately. If contactor auxiliary contacts are not used, the other contactor will release after contactortimeout.

    The unit has a set of programmable parameters to define the No Break Transfer operation.These parameters are:

    Mains Voltage Low Limit (Electrical Parameters):Each of the mains phase voltages must be overthis limit.

    Mains Voltage High Limit (Electrical Parameters):Each of the mains phase voltages must be belowthis limit.

    Mains Frequency Low Limit (Electrical Parameters):The mains frequency must be over this limit.

    Mains Frequency High Limit (Electrical Parameters):The mains frequency must be below this limit.

    Genset Voltage Low Limit (Electrical Parameters):Each of the genset phase voltages must be overthis limit.

    Genset Voltage High Limit (Electrical Parameters):Each of the genset phase voltages must bebelow this limit.

    Low Frequency Shutdown (Engine Parameters):The genset frequency must be over this limit.

    Low Frequency Warning (Engine Parameters):The genset frequency must be over this limit.

    High Frequency Shutdown (Engine Parameters):The genset frequency must be below this limit.

    High Frequency Warning (Engine Parameters):The genset frequency must be below this limit.

    Genset Phase Order Enable(Electrical Parameters):If set , this parameter will enable the phaseorder check for genset. The phase order check should be disabled only in single phase gensets.

    Mains Phase Order Enable(Electrical Parameters):If set, this parameter will enable the phase ordercheck for mains.

    No Break Transfer(Controller Config Parameters):This parameter enables/disables the No BreakTransfer feature.

    Max Frequency Difference(Controller Config Parameters): This is the maximum difference betweenmains and genset frequencies to enable a NO Break Transfer.

    Max Voltage Difference(Controller Config Parameters): This is the maximum difference between the

    mains_L1 and genset_L1 voltages to enable a NO Break Transfer.

    Max Phase Difference(Controller Config Parameters):This is the maximum phase differencebetween the mains_L1 and genset_L1 to enable a No Break Transfer.

    Synchronization Fail Timeout (Controller Config Parameters):If the phase and voltagesynchronization is not successful before the expiration of this timer, then the unit terminates the NoBreak Transferand makes a Transfer with Interruption.

    Contactor Timeout (Controller Config Parameters):This is the maximum time duration in which bothcontactors are active in case of No Break Transfer.

    Any digital input may be assigned as mains and genset contactor feedback input for faster transfer.For this, digital input function select parameter groupis used to select the function and inputconfiguration parameter groupis used to configure digital inputs. The action parameter should be

    set to 3and always active option should be selected for both contactor feedback inputs. NCtypemust be selected for mains contactor feedback input.(Pls refer to programming chapter for moredetailed explanation)

  • 8/13/2019 Dkg-329 User Manual

    14/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 14 -

    The unit offers the possibility of REMOTE STARTmode of operation. Any digital input may beassigned as Remote Start Inputusing Input Function Selectprogram parameters.

    The REMOTE START signal may be a NO or NC contact, switching to either battery positive orbattery negative. These selections are made using programming menu.

    It is also necessary to set the ACTIONprogram parameter of the related input to 3in order toprevent any alarm from this input.

    In this mode the mains phases are not monitored. If the REMOTE START signal is present thenthe mains will be supposed to fail, inversely if the REMOTE START signal is absent, then mainsvoltages will be supposed to be present. The front panels mimic diagrams mains LEDs will reflect the

    status of the REMOTE START input.

    The unit offers an optional SIMULATE MAINSsignal input. Any digital input may be assignedas Simulate Mainsusing Input Function Selectprogram parameters.

    It is also necessary to set the ACTIONprogram parameter of the related input to 3in order toprevent any alarms generated from this input.

    The SIMULATE MAINS signal may be a NO or NC contact, switching to either battery positive orbattery negative. These selections are made using the programming menu.

    If the Simulate Mainsinput is defined and the input signal is active, the mains phases are notmonitored and supposed to be inside limits. This will prevent the genset from starting even in case of amains failure. If the genset is running when the signal is applied, then usual Mains Waiting andCooldown cycles will be performed before engine stop. When the SIMULATE MAINS signal is present,the front panels mimic diagrams mains LEDs will reflect the mains voltages as present.

    When the signal is passive, the unit will revert to normal operation and monitor the mainsvoltage status.

    The REMOTE START operation overrides SIMULATE MAINS andFORCE TO START operations.

    7.2 Mains Simulation (Disable Start)

    7.1 Remote Start Operation

    7. OTHER FEATURES

  • 8/13/2019 Dkg-329 User Manual

    15/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 15 -

    The Delayed Mains Simulation feature is used in battery backed up telecom systems wherebatteries are able to supply the load during a certain period. The genset is requested to run only whenbattery voltage drops below the critical level. Once the engine runs, the rectifier system starts chargingthe batteries and the battery voltage goes up immediately. Thus the engine should continue to run aprogrammed period for effective charging. The critical battery voltage level will be detected by anexternal unit which provides the digital Simulate Mains signal for the genset control unit.

    The unit offers an optional SIMULATE MAINSsignal input. Any digital input may be assignedas Simulate Mainsusing Input Function Selectprogram parameters.

    It is also necessary to set the ACTIONprogram parameter of the related input to 3in order toprevent any alarms generated from this input.

    The SIMULATE MAINS signal may be a NO or NC contact, switching to either battery positive or

    battery negative. These selections are made using the programming menu.

    If the Delayed Simulate Mains program parameter is set to 1 and the input signal is active

    when the genset is not feeding the load, the mains phases are not monitored and supposed to be insidelimits. This will prevent the genset from starting when the simulate mains signal is present (batteriescharged). The genset will start when mains voltages are out of limits and the simulate mains signal notpresent.

    If the genset is running when the signal is applied, then MAINS SIMULATION will be preventedduring Flashing Relay Timer program parameter. After this, usual Mains Waiting and Cooldown cycleswill be performed before engine stop. When the SIMULATE MAINS signal is present, the front panelsmimic diagrams mains LEDs will reflect the mains voltages as present.

    When the signal is passive, the unit will revert to normal operation and monitor the mainsvoltage status.

    The REMOTE START operation overrides DELAYED SIMULATEMAINS operation. When both parameters Remote StartOperation and Delayed Simulate Mains are set then REMOTESTART operation mode is performed.

    7.3 Delayed Mains Simulation, Battery Charging

  • 8/13/2019 Dkg-329 User Manual

    16/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 16 -

    This led is designed to help the periodic maintenance of the genset to be made consistently.

    The periodic maintenance is basically carried out after a given engine hours (for example 200

    hours), but even if this amount of engine hours is not fulfilled, it is performed after a given time limit (for

    example 12 months).

    The unit has both programmable engine hours and maintenance time limit. The engine hours is

    programmable with 50-hour steps, the time limit is programmable with 1 month steps. If any of the

    programmed values is zero, this means that the parameter will not be used. For example a maintenance

    period of 0 months indicates that the unit will request maintenance only based on engine hours, there will

    be no time limit. If the engine hours is also selected as 0 hours this will mean that the SERVICE REQUEST

    display will be inoperative.

    When the engine hours OR the time limit is over, the SERVICE REQUEST led (red) will start to

    flash and the service request relay function will be active.

    The service request relay function may be assigned to spare relays using Relay Definition

    program parameters. Also relays on an extension module may be assigned to this function.

    The remaining engine hours and the remaining time limit are kept stored in a non-volatile memory

    and are not affected from power supply failures.

    The time and engine hours to service are displayed in the STATISTICAL COUNTERS menu.

    The unit features a non-erasable incremental engine hour meter. The hour meter information is

    kept in a non-volatile memory and is not affected from power supply failures.

    The engine hours may be displayed STATISTICAL COUNTERS menu.

    The date & time display is provided for verification.

    To turn off the SERVICE REQUEST led, and reset the

    service period, press together the ALARM MUTE andLAMP TEST keys for 5 seconds.

    The SERVICE REQUEST led has no effect on the gensetoperation.

    7.6 Date & Time Display

    7.5 Engine Hour Meter

    7.4 Service Request Display

  • 8/13/2019 Dkg-329 User Manual

    17/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 17 -

    Some additional features are installed within consecutive software releases. In order to be sure

    of the validity of the status of the unit, the software version needs to be known.

    The software version of the unit is displayed together with the datatime information.

    The software version consists of 2 numbers. The first number represent the operating software

    version of the unit.

    The unit is capable of making modem calls in case of alarm, as well as answering modem callsmade from a remote location. GSMmodems and classic cable network (PSTN) modems areacceptable.

    If the modem is connected to the unit, the Modem Enableprogram parameter should be set to1, otherwise faulty operation may occur.

    A maximum of 2 telephone numbers can be defined for outgoing modem calls. In case of alarm,the unit will attempt to reach control centers associated with each number. In case of modemconnection failure, the call will be repeated up to 30 times with 2 minute intervals.

    When the modem call is in progress, a telephone icon ( ) will appear at the upper rightcorner of the screen.

    Advised modems are DATAKOM types which are powered up from the same DC batteryvoltage than the unit. Most of other desktop modems with standard AT commands are also usable, but itis the users responsibility to provide an uninterrupted AC supply source to the modem. The necessarymodem cable will be supplied by DATAKOM.

    Modem calls are always terminated by the central RAINBOW software. However the unit doesnot allow connection durations exceeding 2 minutes, and hangs up the modem when this periodexpires.

    The PC program used for remote monitoring and programming is the same RAINBOW softwareused for RS-232 connection.

    Please note that the modem operation is also compatible with the MODBUS communication.

    Thus the unit can iniate and receive calls to/from a MODBUS master station. Please review chapter_8for more details on MODBUS communication.

    If Modem Enableor SMS Enableor MODBUS Addressparametersare different from zero, the local PC connection will not work.

    7.8 Modem Connection

    7.7 Software Version Display

  • 8/13/2019 Dkg-329 User Manual

    18/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 18 -

    The GSM SMS sending is activated by setting the SMS Enableprogram parameter to 1.

    When a fault condition occurs, the unit will compose an SMS message and will send it to up to 6phone numbers. If modem is enabled, only 4 telephone numbers are available for SMS sending.

    The unit is also able to send SMS messages in below conditions, without creating a visible alarm orwarning:Mains Fail, Mains Restored(enabled via SMS on Mains Changeprogram parameter)

    If both modem and SMS are enabled, the unit will send SMS messages first and attempt modemconnection afterwards.

    When SMS sending is in progress, an (SMS) icon will appear at the upper right corner of thescreen.

    The maximum number of alarms transmitted in a SMS message is 4. This limitation is due to themaximum length of an SMS message which is 160 characters.

    A sample GSM SMS message is given below:

    DKGxxx STOP : EMERGENCY STOP.END OF ALARM LIST

    The first line of the message carries information about the unit type and the site identity string. Thisline is intended for the identification of the genset sending the SMS message.

    Each following line will give one fault information. The message will always be terminated by theEND OF ALARM LIST string.

    When the message is sent, the existing alarms will be masked, causing the audible alarm relay torelease and preventing consecutive GSM SMS messages. Any new upcoming alarm will result in a newGSM SMS message. The new message will indicate all existing alarms, even masked ones.

    The necessary GSM modem cable will be supplied by DATAKOM. This is the same cable asPSTN (land) modems.

    If Modem Enableor SMS Enableor MODBUS Addressparametersare different from zero, the local PC connection will not work.

    7.9 SMS Message Sending

  • 8/13/2019 Dkg-329 User Manual

    19/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 19 -

    Thanks to its standard serial RS-232 port, the unit offers the remote monitoring and

    programming feature.

    The remote monitoring and programming PC software is called RAINBOW and may be

    downloaded from www.datakom.com.trinternet site with password login.The modem, SMS and Modbus modes are not compatible with the local PC connection. Modem

    Enable, SMS Enableand MODBUS Addressprogram parameters should be set to 0 before connection.

    The RAINBOW software allows the visualization and recording of all measured parameters. The

    recorded parameters may then be analyzed graphically and printed. The software also allows the

    programming of the unit and the storage of the program parameters to PC or the downloading of stored

    parameters from PC to the unit.

    For PCs without a serial port, below USB to serial adapters are tested and approved :

    DIGITUS USB 2.0 TO RS-232 ADAPTER (PRODUCT CODE: DA70146 REV 1.1)DIGITUS USB 1.1 TO RS-232 ADAPTER (PRODUCT CODE: DA70145 REV 1.1)FLEXY USB 1.1 TO SERIAL ADAPTER (PRODUCT CODE BF-810)CASECOM USB TO SERIAL CONVERTER (MODEL: RS-01)

    The necessary PC connection cable will be supplied by DATAKOM.

    The unit offers total external control through programmable digital inputs. Each digital input may be

    programmed for below external control functions:

    - Force OFF mode

    - Force AUTO mode

    - Force TEST mode

    - Force LOAD TEST mode

    - Disable Auto Start

    - Force to Start

    - Fault Reset

    - Alarm Mute

    - Panel Lock

    External mode select signals have priority on mode buttons of the unit. If the mode is selected by

    external signal, it is impossible to change this mode with front panel keys. However if the external mode

    select signal is removed, the unit will revert to the last selected mode via pushbuttons.

    It is also possible to lock the front panel completely for remote command.

    7.11 External Control of the Unit

    7.10 Remote Monitoring and Programming

  • 8/13/2019 Dkg-329 User Manual

    20/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 20 -

    The unit offers automatic exerciser operation. The exercise operation may be done on a daily,weekly or monthly basis.

    The start day and time of the exercise is programmable as well as its duration. The exercisemay be done with or without load following programming.

    Program parameters related to the exerciser are:Exercise start day and hourExercise durationExercise off_load/on_loadExerciser Period (Daily / Weekly / Monthly)

    Please refer to the programming section for a more detailed description of the aboveparameters.

    When the start day and hour of exercise has come, the unit will automatically switch to eitherTESTor LOAD TEST mode. The engine will run and if the on_load exercise is selected then the load

    will be transferred to the genset.

    If a mains failure occurs during the off-load exercise, the load will not be transferred to thegenset unless the Emergency Backup Operationis allowed by setting the related program parameterto 1. Thus it is highly recommended that the Emergency Backup mode enabled with off-load exerciser.

    At the end of the exercise duration, the unit will switch back to the initial mode of operation.

    If any of the mode selection keys are pressed during exercise, then the exercise will beterminated.

    Using the daily exercise mode, the unit may feed the load from the genset during predefinedhours of the day. This operation may be used in high tariff periods of the day.

    In order to resume to the factory set parameter values:

    -hold pressed the OFF, LAMP TEST and ALARM MUTEbuttons for 5 seconds,-RETURN TO FACTORY SET will be displayed-immediately press and hold pressed the ALARM MUTEbutton for 5 seconds

    -factory set values will be reprogrammed to the parameter memory.

    It is not possible to restore user parameters.

    7.13. Resuming to factory set parameters

    7.12 Exerciser

  • 8/13/2019 Dkg-329 User Manual

    21/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 21 -

    The load shedding feature consists on the disconnection of the least crucial loads when thegenset power approaches to its limits. These loads will be supplied again when the genset power falls

    below the programmed limit. The internal Load Shedding function is always active. Any of the auxiliaryrelays may be used as the load shedding output.

    The dummy load function consists on the connection of a dummy load if the total genset load isbelow a limit and to disconnection of the dummy load when the total power exceeds another limit. Thedummy load function is the inverse of the load shedding function, thus the same output may be used forboth purposes.

    The parameters used in Load Shedding feature are in the Electrical Parameters Group:Load Shedding Low Limit:If the genset active power output goes below this limit, then the LoadShedding relay will be deactivated.Load Shedding High Limit:If the genset active power output goes above this limit, then the LoadShedding relay will be activated.

    The unit offers possibility of updating the firmware in the field. The firmware is updated throughthe RS-232 serial port using Rainbow or a special DOS program.

    The unit will go to firmware download mode with a special command from the PC program. Indownload mode, the display of the unit will show DL-V1.00

    During firmware update process, the progress is visible through a completion bar on the screen.

    The firmware update operation will take around 3 minutes.

    After completion of the update a special command will set back the unit to normal operationmode.

    The controller is able to provide a pre-transfer digital output function.

    This function is designed for elevator systems, in order to bring the cabin to a floor and open cabindoors before transfer.

    The duration where this output is active is adjusted with the Pre-Transfer Delayparameter.

    The Pre-Transfer signal may be assigned to any digital output.

    If the Pre-transfer Delay parameter is not zero, this will delaytransfers by the same amount.

    7.16. Pre-Transfer Signal

    7.15. Firmware Update

    7.14. Load Shedding / Dummy Load

  • 8/13/2019 Dkg-329 User Manual

    22/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 22 -

    The unit offers the possibility of MODBUS communication via its RS232 serial port.The connection to the MODBUS master may be done in 3 ways:

    1) RS232 connection using directly the RS232 port provided.2) RS422/485 connection using external RS422/485 converter.3) Modem connection using external modem.

    The MODBUS mode is activated by assigning a controller address to the unit using MODBUSAddressprogram parameter. The possible address range is 1 to 144. Setting the address to 0 willdisablethe MODBUS mode and allow communication under RAINBOW protocol.

    The MODBUS properties of the unit are:-Data transfer mode: RTU-Serial data: 9600 bps, 8 bit data, no parity, 1 bit stop-Supported functions:

    -Function 3 (Read multiple registers)-Function 6 (Write single register)

    Detailed description about the MODBUS protocol is found in the document Modicon Modbus

    Protocol Reference Guide.The web address is:www.modbus.org/docs/PI_MBUS_300.pdfBelow is a limited shortlist of readable registers. For the detailed Modbus Application Manual

    and a complete list of registers please contact DATAKOM.

    ADDRESS(hex)

    R /W

    DATASIZE

    COEFFICIENT DESCRIPTION

    0000 R 16bit x1 Mains Phase L1 voltage

    0001 R 16bit x1 Mains Phase L2 voltage

    0002 R 16bit x1 Mains Phase L3 voltage

    0003 R 16bit x1 Genset Phase L1 voltage

    0004 R 16bit x1 Genset Phase L2 voltage

    0005 R 16bit x1 Genset Phase L3 voltage

    0006 R 16bit x1 Genset Phase L1 current

    0007 R 16bit x1 Genset Phase L2 current

    0008 R 16bit x1 Genset Phase L3 current

    000C R 16bit x1 Mains Phase L12 voltage

    000D R 16bit x1 Mains Phase L23 voltage

    000E R 16bit x1 Mains Phase L31 voltage

    000F R 16bit x1 Genset Phase L12 voltage

    0010 R 16bit x1 Genset Phase L23 voltage

    0011 R 16bit x1 Genset Phase L31 voltage

    0012 R 16bit x10 Mains frequency

    0013 R 16bit x10 Genset frequency

    0016-0017 R 32bit x256 Genset active power: this 24 bit signed register holds thegenset active power multiplied by 256. Least significant

    16 bits are in the register 0016h. Most significant 8 bitsare in the LSB of the register 0017h.

    0018 R 8bit x100 Power factor multiplied by 100 (signed byte). Negativevalues indicate a capacitive power factor.

    002F R 16bit x10 Battery voltage

    003D R 8bit - Operating modebit_3: manual modebit_4: auto modebit_5: off modebit_6: test modebit_7: load test mode

    8. MODBUS COMMUNICATION

    http://localhost/var/www/apps/conversion/tmp/www.modbus.org/docs/PI_MBUS_300.pdfhttp://localhost/var/www/apps/conversion/tmp/www.modbus.org/docs/PI_MBUS_300.pdfhttp://localhost/var/www/apps/conversion/tmp/www.modbus.org/docs/PI_MBUS_300.pdf
  • 8/13/2019 Dkg-329 User Manual

    23/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 23 -

    In most applications, the genset is requested to operate only in working hours. Thanks to theweekly program feature unwanted operation of the genset may be prohibited.

    The unit has one programmable turn-on/turn-off time pairs for each day of week. Theseprogrammable parameters allow the genset to operate automatically only in allowed time limits.

    The weekly operation schedule is only active in AUTOmode. In other modes it will not affectthe genset operation.

    In AUTOmode, if the operation of the genset is disabled by the weekly schedule, then theAUTO led will flash(instead of a steady on state).

    Each turn-on/turn-off time is defined in 10 minute steps.

    Unused programs should be set to 24:00.

    An example setup may be as follows:

    Monday Turn_on 07:00

    Monday Turn_off 18:00Tuesday Turn_on 07:00Tuesday Turn_off 18:00Wednesday Turn_on 07:00Wednesday Turn_off 18:00Thursday Turn_on 07:00Thursday Turn_off 18:00Friday Turn_on 07:00Friday Turn_off 18:00

    Saturday Turn_on 07:00Saturday Turn_off 13:00

    Sunday Turn_on 24:00 (Sunday no turn on time, last operation mode continues)

    Sunday Turn_off 24:00 (Sunday no turn off time, last operation mode continues)

    If the same time is used for turn on and turn off, then it will be considered as a turn-on time.

    The unit has a battery backed-up precision real time clock circuit. The real time clock circuit willcontinue its operation even in power failures. The real time clock is precisely trimmed using the RealTime Clock Adjustprogram parameter. For more details check the programming section.

    9. WEEKLY OPERATION SCHEDULE

  • 8/13/2019 Dkg-329 User Manual

    24/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 24 -

    The unit keeps record of the last 100 events in order to supply information for the service personal.

    The genset status information and a comprehensive set of measured values are stored within the eventmemory. The events are recorded with a time stamp which comes from the internal real time clockcircuit of the unit.

    The events are stored in a circular memory. This means that a new coming event will erase the oldestrecorded event. The events are always displayed starting from the most recent one.

    Events are kept in a non-volatile memory and are not affected from power failures.

    Switching from one menu screen to another is made with the MENU andMENUbuttons.

    When the EVENT RECORD screen is displayed, each depression on the MENU button makes thedisplay switch to the previous event and MENUbutton makes the display switch to the next event.

    Each event is displayed in 4 pages. Event and page numbers are shown at the top right corner of the

    display. Events are numbered starting from 1, number 1 being the latest one. Pages are listed from A to

    D. Navigation between different pages of the same event is done with andbuttons.

    Event sources are:-Shutdown alarms, Load dump alarms, Warnings

    -Operating mode change (OFF, AUTO, etc)-Periodic records.

    Event record contents are:Event type (alarms, mode change, periodic, etc)Date and timeGenset operating mode (AUTO, MANUAL,OFF,TEST, LOAD TEST)Genset operation status (mains ok, running, cooldown etc)Genset phase voltages L1-L2-L3Genset frequencyLoad phase currents L1-L2-L3Load active power (kW)Load power factor

    Battery voltageMains phase voltages L1-L2-L3Mains frequencyDigital input statuses

    To exit event record pages please hold pressed MENUorMENUbuttons.

    10. EVENT LOGGING

  • 8/13/2019 Dkg-329 User Manual

    25/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 25 -

    The unit provides a set of non resettable incremental counters for statistical purposes.

    The counters consist on:-total engine hours-total genset kWh-engine hours to service-time to service

    These counters are kept in a non-volatile memory and are not affected from power failures.

    Wipe the unit, if necessary with a soft damp cloth. Do not use chemical agents

    12. MAINTENANCE

    11. STATISTICAL COUNTERS

    DO NOT OPEN THE UNIT

    There are NO serviceable parts inside the unit.

  • 8/13/2019 Dkg-329 User Manual

    26/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 26 -

    The program mode is used to program timers, operational limits and the configuration of the unit.

    To enter the program mode, press together MENU andMENUbuttons for 1 second. Theprogram mode is only allowed if the PROGRAM LOCK input is left open. If this input is tied toGROUND, the program value modification will be disabled to prevent unauthorized intervention. It is

    advised to keep the PROGRAM LOCKinput tied to GROUND.

    When the program mode is entered, below password entry screen will be displayed.

    A 4 digit password must be entered using , , MENUandMENU buttons.

    The unit stores 3 different passwords. Each password allows access to a different level of

    program parameters.

    The password level-1 allows access to field adjusted parameters. The level-2 allows access to

    factory setup. The password level-3 is reserved to Datakom and allows access to calibration

    parameters.

    The password level-1 is factory set to 1234 and the password level-2 is factory set to 9876.

    Passwords can only be modified through Rainbow program.

    The program mode will not affect the operation of the unit. Thus programs may be modified

    anytime, even while the genset is running.

    The program mode is driven with a two level menu system. The top menu consists on program

    groups and each group consists of various program parameters.

    When program mode is entered, a list of available groups will be displayed. Navigation between

    different groups are made with andbuttons. Selected group is shown in reverse video (blue onwhite). In order to enter inside a group, please press MENUbutton. In order to exit from the group to

    the main list please press MENU button.Navigation inside a group is made also with andbuttons. A list of available parameters will

    be displayed. Selected parameter is shown in reverse video (blue on white). In order display/change the

    value of this parameter, please press MENUbutton. Parameter value may be increased anddecreased with and buttons. If these keys are hold pressed, the program value will beincreased/decreased by steps of 10. When a program parameter is modified, it is automatically saved in

    memory. If MENUbutton is pressed, next parameter will be displayed. If MENU button is pressed,then the list of parameters in this group will be displayed.

    Program parameters are kept in a non-volatile memory and are not affected from power failures.

    To exit the program modepress one of the mode selection keys. If no button is pressed during

    1 minute the program mode will be cancelled automatically.

    13. PROGRAMMING

  • 8/13/2019 Dkg-329 User Manual

    27/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 27 -

    Program Group: Controller Configuration

    Parameter Definition,(Password Level)

    Unit FactorySet

    Description

    (1)LCD Contrast - 22This parameter is used to set LCD contrast. Adjust forthe best viewing angle.

    (2)Language - 0

    0:English language selected.1: Turkish language selected. This language maydepend on the country where the unit is intended tobe used.2:Chinese language selected3:The unit will ask for manual language selection atpower-on.

    (2)Line-to-Line Voltages - 00:Display Line to Neutral voltages as default1:Display Line to Line voltages as default

    (1)Genset Default Display - 0

    This parameter selects the screen which is displayedduring genset on load operation.

    0:screen 3 (or 4) electrical, large characters1:screen 5 engine parameters, large characters2:screen 6 (or 7) maximum information, smallcharacters3: screen 8 (or 9)Details of each screen are explained in chapter 3.2

    (2)Fault Holdoff Timer sec 12This parameter defines the delay after the engineruns and before the fault monitoring is enabled.

    (1)Alarm Relay Timer sec 60This is the period during which the ALARMrelay isactive. If the period is set to 0, this will mean that theperiod is unlimited.

    (1)Intermittent Alarm Relay - 00:continuous1:intermittent (turns on and off every second)

    (1)Emergency BackupOperation

    - 0

    0:In TEST mode, the load will not be transferred tothe genset even if the mains fail.1:In TEST mode, the load will be transferred to thegenset if the mains fail.

    (1)Exercise Day and Time - 168

    This parameter defines the start day and hour of theexerciser.Values higher or equal to 168 mean that the exerciseris off.The exercise may be selected to start at thebeginning of the any hour of the week. The parametervalue is the hour count of the start time.Examples:

    0 = exercise starts at Monday 00:00

    8 = exercise starts at Monday 08:0024 = exercise starts at Tuesday 00:00

    167 = exercise starts at Sunday 23:00168 = exerciser offIf a daily exercise is selected, then the dayinformation is dont care and the exercise will beperformed every day regardless of the day selection.If the monthly exerciser is selected, then the exercisewill be performed during the first 7 days of eachmonth at the programmed day and hour.

  • 8/13/2019 Dkg-329 User Manual

    28/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 28 -

    Program Group: Controller Configuration (continued)

    Parameter Definition,(Password Level)

    Unit FactorySet

    Description

    (1)Exercise Duration min 10This parameter defines the exercise duration and

    programmed in 10 minute steps up to 24 hours.

    (1)Exercise Off/On Load - 00:Exercise at TESTmode1:Exercise at LOAD TESTmode

    (1)Exercise Period - 1

    0:exercise every day (the exercise will be performedevery day regardless of the day selection of ExerciseDat and Time parameter).1:exercise once per week2:exercise once per month (the exercise will beperformed during the first 7 days of each month atthe programmed day and hour).

    (2)Delayed Simulate Mains - 0

    0:The SPARE-2input has normal function1:The SPARE-2 input has delayed simulate mainsfunction. See chapter 7.3for more info.

    (2)Modem Enable - 00: No modem connection, the serial port is connectedto PC1: Modem connected.

    (2)SMS Enable - 00:SMS not enabled1:SMS enabled

    (2)MODBUS Address - 00:RAINBOW communication protocol.1-144:MODBUS communication. This parameter isalso the MODBUS controller address of the unit.

    (1)Real Time Clock Adjust - 117

    This parameter trims precisely the real time clockcircuit.Values from 0 to 63 speed up the clock with0.25sec/day steps.Values from 127 to 64 slow down the clock with0.25sec/day steps.

    (2) Hysteresis Voltage V 8

    This parameter provides the mains and gensetvoltage limits with a hysteresis feature in order toprevent faulty decisions.For example, when the mains are present, the mainsvoltage low limit will be used as the programmed lowlimit. When the mains fail, the low limit will beincremented by this value. It is advised to set thisvalue to 8 volts.

    (2) SMS on Mains Change - 0

    This parameter controls SMS sending when mainsvoltages status is changed. No warning is generated.0: no SMS when mains failed or restored1: SMS sent when mains failed or restored

  • 8/13/2019 Dkg-329 User Manual

    29/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 29 -

    Program Group: Controller Configuration (continued)

    Parameter Definition,(Password Level)

    Unit FactorySet

    Description

    (2) Minimum ready inputnumber for transfer - 0

    This parameter defines minimum activated input

    number required to start transfer the load from mainsto genset.

    (2) Ready bypass timeout - 0

    0: The unit will wait undefinitely until the minimumnumber of gensets (defined in above parameter) areready before transfer.1 to 255: The unit will transfer the load at theexpiration of this timer, even if the minimum numberof ready gensets is not reached.

    (3)No Break Transfer Enable - 00: No break transfer disabled.1: No break transfer enabled.

    (3)Max Voltage Difference V 10This is the maximum difference between the mainsphase-L1 and the genset phase-L1 voltages toenable a NO Break Transfer.

    (3)Max FrequencyDifference

    Hz 2.0 This is the maximum difference between mains andgenset frequencies to enable a NO Break Transfer.

    (3)Max Phase AngleDifference

    Deg 10This is the maximum phase difference between themains phase-L1 and the genset phase-L1 to enable aNO Break Transfer.

    (3)Synchronization failTimeout

    Sec 30

    If the phase and voltage synchronization is notsuccessful before the expiration of this timer, then aSynchronization Fail Warningis given and the unitreverts to No Break Transfermaking a conventionalchangeover.

    (3)Contactor Timeout Sec 1This is the maximum time duration in which bothcontactors are active in case of No Break Transfer.It is advised to set this timer to 1sec maximum.

    (2)CT Location - 00: CTs at genset side1: CTs at load side2:CTs at mains side

    (2) Pre-Transfer Delay Sec 0

    If this parameter is not zero, the unit will activate thePre-Transferoutput function during this timer, beforeinitiating a load transfer.This function is designed for elevator systems, inorder to bring the cabin to a floor and open doorsbefore transfer.

  • 8/13/2019 Dkg-329 User Manual

    30/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 30 -

    Program Group: Electrical Parameters

    Parameter Definition,(Password Level)

    Unit FactorySet

    Description

    (2)Current TransformerRatio A 500

    This is the rated value of current transformers.

    All transformers must have the same rating.The secondary of the transformer will be 5 Amps.

    (2)Overcurrent Limit A 0

    If the current goes above this limit, during the perioddefined in Overload Timeoutthen a Overcurrent LoadDumpalarm will be generated.If this parameter is 0 then Overcurrent check is disabled.

    (2)Excess Power Limit kW 0

    If the active power goes above this limit, during theperiod defined in Overload Timeout then an ExcessPower Load Dump alarm will be generated.If this parameter is 0 then Excess Power check isdisabled.

    (2)Overload Timeout sec 5

    This is the period between the current or active power goover the limits and OVERCURRENT orEXCESS

    POWERLoad Dump alarms occur.This is also the period between the frequency goes outof the limits and OVERSPEED orUNDERSPEED alarmsoccur.This is also the period between the genset voltage goesout of the limits and HIGH VOLTAGE orLOWVOLTAGE alarms occur.

    (2) Multi Genset Fault Delay sec 30

    If the minimum ready input numberfor transferparameter is set to more than 1, (multi genset system)this parameter is used for voltage or frequencyshutdown fault delay instead of Overload Timeout,inorder to allow the system survive in case of failure onone genset. If another genset can start and feed the

    load before the expiration of this timer then no alarmcondition will be generated.

    (1)Mains Voltage Low Limit V 170If one of the mains phases goes under this limit, itmeans that the mains are off and it starts the transferto the genset in AUTOmode.

    (1)Mains Voltage High Limit V 270If one of the mains phases goes over this limit, itmeans that the mains are off and it starts the transferto the genset in AUTOmode.

    (2)Genset Low VoltageShutdown Limit

    V 170

    If one of the generator phase voltages goes under thislimit when feeding the load, this will generate a GENSETLOW VOLTAGEshutdown alarmand the engine willstop.

    (2)Genset Low VoltageWarning Limit

    V 180If one of the generator phase voltages goes under thislimit when feeding the load, this will generate a GENSETLOW VOLTAGEwarning.

    (2)Genset High VoltageWarning Limit

    V 260If one of the generator phase voltages goes above thislimit when feeding the load, this will generate a GENSETHIGH VOLTAGEwarning.

    (2)Genset High VoltageShutdown Limit

    V 270If one of the generator phase voltages goes over thislimit when feeding the load, this will generate a GENSETHIGH VOLTAGE alarm and the engine will stop.

  • 8/13/2019 Dkg-329 User Manual

    31/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 31 -

    Program Group: Electrical Parameters (continued)

    Parameter Definition,(Password Level)

    UnitFactorySet

    Description

    (2)Low Battery Voltage

    WarningV 9.0

    If the battery voltage falls below this limit, this will

    generate a LOW BATTERY warning.(2)High Battery Voltage

    WarningV 31.0

    If the battery voltage goes over this limit, this willgenerate a HIGH BATTERY warning.

    (2)High Battery VoltageShutdown

    V 33.0If the battery voltage goes over this limit, this willgenerate a HIGH BATTERY shutdownalarm and theengine will stop.

    (1)Mains Waiting Timer min 0.5This is the time between the mains voltages enteredwithin the limits and the generator contactor isdeactivated.

    (2)Genset Contactor Timer sec 1This is the period after the mains contactor has beendeactivated and before the generator contactor hasbeen activated.

    (2)Mains Contactor Timer sec 1

    This is the period after the generator contactor has

    been deactivated and before the mains contactor hasbeen activated.

    (2)Mains Phase Order

    Enable- 0

    0:mains phase order checking disabled1:if mains phase order is faulty, then a warning isgiven and mains contactor deenergized.

    (2)Reverse power warninglimit

    kW 0If the genset power is negative and goes above thislimit then a REVERSE POWERwarning will begenerated.

    (2)Reverse powerloaddumpg limit

    kW 0If the genset power is negative and goes above thislimit then a REVERSE POWERloaddump will begenerated.

    (2)Load Shedding Low Limit kW 0If the genset power goes below this limit then theload shedding relay will be deactivated.

    (2)Load Shedding HighLimit

    kW 0If the genset power goes above this limit then theload shedding relay will be activated.

    (2)Genset Phase Order

    Enable- 0

    0:genset phase order checking disabled1:if genset phase order is faulty, then a loaddump isgenerated and the genset stops after cooldown.

  • 8/13/2019 Dkg-329 User Manual

    32/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 32 -

    Program Group: Engine Parameters

    Parameter Definition,(Password Level)

    UnitFactorySet

    Description

    (2)Low Frequency

    ShutdownHz 30

    If the genset frequency goes under this limit, a GENSET

    LOW SPEED alarm is generated and the engine stops.

    (1)Low Frequency Warning Hz 35If the genset frequency goes under this limit, a GENSETLOW SPEED warning is generated.

    (1)High Frequency Warning Hz 54If the genset frequency goes over this limit, a GENSETHIGH SPEED warning is generated.

    (2)High FrequencyShutdown

    Hz 55If the genset frequency goes over this limit, a GENSETHIGH SPEED alarm is generated and the engine stops.

    (2)Engine Start Delay sec 0

    This is the time between the mains fails and the fuelsolenoid turns on before starting the genset. Itprevents unwanted genset operation in batterybacked-up loads.

    (1) Engine Heating Timer sec 4This is the period used for engine heating followingthe program parameter.

    (1) Cooldown Timer min 1.0 This is the period that the generator runs for coolingpurpose after the load is transferred to mains.

    (1)Stop Solenoid Timer sec 10

    This is the maximum time duration for the engine tostop. During this period the STOP relay output isenergized (if assigned by Relay Definitions). If thegenset has not stopped after this period, a FAIL TOSTOPwarning occurs.

    (1) Service Engine Hours hour 50

    The SERVICE REQUEST led indicator will turn onafter this quantity of engine hours from the lastservice. If the period is set to 0 no SERVICEREQUEST will be generated depending on enginehours.

    (1) Service Period month 6

    The SERVICE REQUEST led indicator will turn onafter this amount of time from the last service. If theperiod is set to 0 no SERVICE REQUEST will beindicated depending on time.

    Program Group: Adjust Date and Time (password level-2)

    Parameter Definition Unit FactorySet

    Description

    Date - 01-31 Current day of the month.

    Month - 01-12 Current month.

    Year - 00-99 Last two digits of the current year.

    Hours - 00-23 Current hour of the day.Minutes - 00-59 Current minute of the hour.

    Seconds - 00-59 Current second of the minute.

  • 8/13/2019 Dkg-329 User Manual

    33/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 33 -

    Program Group: Weekly Schedule (password level-2)

    Parameter Definition Unit FactorySet

    Description

    Monday Turn_on - 24:00

    Please review chapter 9 for a detailed description ofweekly programming schedule operation.

    Monday Turn_off - 24:00Tuesday Turn_on - 24:00

    Tuesday Turn_off - 24:00

    Wednesday Turn_on - 24:00

    Wednesday Turn_off - 24:00

    Thursday Turn_on - 24:00

    Thursday Turn_off - 24:00

    Friday Turn_on - 24:00

    Friday Turn_off - 24:00

    Saturday Turn_on - 24:00

    Saturday Turn_off - 24:00

    Sunday Turn_on - 24:00

    Sunday Turn_off - 24:00

    Program Group: Input Configuration (Emergency Stop)

    (password level-2)

    Parameter Definition Unit Fac.Set Description

    Action 0

    0:Shutdown (the engine stops immediately)1: Load Dump (the engine stops after cooldown)2:Warning (the horn relay operates)3:No operation

    Sampling 0

    0:Always

    1:After holdoff timer2:When mains present

    Latching 00:Non latching1:Latching

    Contact type 00:Normally open1:Normally closed

    Switching 00:Battery negative1:Battery positive

    Response delay 00:No delay1:Delayed (4sec)

  • 8/13/2019 Dkg-329 User Manual

    34/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 34 -

    Program Group: Input Configuration (Spare -1 Input)

    (password level-2)

    Parameter Definition Unit Fac.Set Description

    Action 30:Shutdown (the engine stops immediately)1: Load Dump (the engine stops after cooldown)2:Warning (the horn relay operates)3:No operation

    Sampling 0

    0:Always1:After holdoff timer2:When mains present

    Latching 00:Non latching1:Latching

    Contact type 00:Normally open1:Normally closed

    Switching 00:Battery negative1:Battery positive

    Response delay 0 0:No delay1:Delayed (4sec)

    Program Group: Input Configuration (Spare -2 Input)

    (password level-2)

    Parameter Definition Unit Fac.Set Description

    Action 3

    0:Shutdown (the engine stops immediately)1: Load Dump (the engine stops after cooldown)2:Warning (the horn relay operates)3:No operation

    Sampling 00:Always1:After holdoff timer2:When mains present

    Latching 00:Non latching1:Latching

    Contact type 00:Normally open1:Normally closed

    Switching 00:Battery negative1:Battery positive

    Response delay 00:No delay1:Delayed (4sec)

  • 8/13/2019 Dkg-329 User Manual

    35/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 35 -

    Program Group: Input Configuration (Spare -3 Input)

    (password level-2)

    Parameter Definition Unit Fac.Set Description

    Action 30:Shutdown (the engine stops immediately)1: Load Dump (the engine stops after cooldown)2:Warning (the horn relay operates)3:No operation

    Sampling 0

    0:Always1:After holdoff timer2:When mains present

    Latching 00:Non latching1:Latching

    Contact type 00:Normally open1:Normally closed

    Switching 00:Battery negative1:Battery positive

    Response delay 0 0:No delay1:Delayed (4sec)

    Program Group: Input Configuration (Fault Reset)

    (password level-2)

    Parameter Definition Unit Fac.Set Description

    Action 3

    0:Shutdown (the engine stops immediately)1: Load Dump (the engine stops after cooldown)2:Warning (the horn relay operates)3:No operation

    Sampling 00:Always1:After holdoff timer2:When mains present

    Latching 00:Non latching1:Latching

    Contact type 00:Normally open1:Normally closed

    Switching 00:Battery negative1:Battery positive

    Response delay 00:No delay1:Delayed (4sec)

  • 8/13/2019 Dkg-329 User Manual

    36/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 36 -

    Program Group: Input Configuration (Alarm Mute)

    (password level-2)

    Parameter Definition Unit Fac.Set Description

    Action 30:Shutdown (the engine stops immediately)1: Load Dump (the engine stops after cooldown)2:Warning (the horn relay operates)3:No operation

    Sampling 0

    0:Always1:After holdoff timer2:When mains present

    Latching 00:Non latching1:Latching

    Contact type 00:Normally open1:Normally closed

    Switching 00:Battery negative1:Battery positive

    Response delay 0 0:No delay1:Delayed (4sec)

    Program Group: Input Configuration (Panel Lock)

    (password level-2)

    Parameter Definition Unit Fac.Set Description

    Action 3

    0:Shutdown (the engine stops immediately)1: Load Dump (the engine stops after cooldown)2:Warning (the horn relay operates)3:No operation

    Sampling 00:Always1:After holdoff timer2:When mains present

    Latching 00:Non latching1:Latching

    Contact type 00:Normally open1:Normally closed

    Switching 00:Battery negative1:Battery positive

    Response delay 00:No delay1:Delayed (4sec)

    The parameters below define the functions of relay outputs. The unit has 6 relay outputs. Thefixed function relays are Remote Start, Alarm (Horn), Mains Contactor and Generator Contactor.RELAY-1 and RELAY-2 have programmable functions, selected from a list.

    The relays may be extended up to 22 using Relay Extension Modules. Other relays are in the

    optional Extension Modules.

  • 8/13/2019 Dkg-329 User Manual

    37/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 37 -

    Program Group: Relay Definitions (password level-2)

    Parameter Definition Unit Fac.Set Description

    Relay 01 Definition 11 RELAY-1 function selected from list

    Relay 02 Definition 16 RELAY-2 function selected from listRelay 03 Definition 0 RELAY-3 function (expansion module) selected from list

    Relay 04 Definition 2 RELAY-4 function (expansion module-1) selected from list

    Relay 05 Definition 4 RELAY-5 function (expansion module-1) selected from list

    Relay 06 Definition 5 RELAY-6 function (expansion module-1) selected from list

    Relay 07 Definition 0 RELAY-7 function (expansion module-1) selected from list

    Relay 08 Definition 2 RELAY-8 function (expansion module-1) selected from list

    Relay 09 Definition 4 RELAY-9 function (expansion module-1) selected from list

    Relay 10 Definition 5 RELAY-10 function (expansion module-1) selected from list

    Relay 11 Definition 0 RELAY-11 function (expansion module-2) selected from list

    Relay 12 Definition 2 RELAY-12 function (expansion module-2) selected from list

    Relay 13 Definition 4 RELAY-13 function (expansion module-2) selected from list

    Relay 14 Definition 5 RELAY-14 function (expansion module-2) selected from list

    Relay 15 Definition 0 RELAY-15 function (expansion module-2) selected from list

    Relay 16 Definition 2 RELAY-16 function (expansion module-2) selected from list

    Relay 17 Definition 4 RELAY-17 function (expansion module-2) selected from list

    Relay 18 Definition 5 RELAY-18 function (expansion module-2) selected from list

  • 8/13/2019 Dkg-329 User Manual

    38/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 38 -

    The function of a programmable relay output may be selected from the below list.

    00 Remote Start

    01 Alarm

    02 -

    03 -

    04 Gen. Contactor05 Mains Contactor

    06 -

    07 -

    08 Shutdown alarm

    09 Shutdown orload_dump alarm

    10 Shutdown orload_dump or warning

    11 Automatic ready

    12 Week. on time

    13 Exerciser on

    14 Load_dump alarm15 Pre-Transfer signal

    16 Mains Fail

    17 -

    18 Service Request

    19 -

    20 Load Shedding Relay

    21 -

    22 -

    23 -

    24 Mains Phase OrderFail

    25 Genset Phase Order

    Fail26 -

    27 -

    28 Alternate Volt/FreqEnabled

    29 -

    30 -

    31 -

    32 -

    33 -

    34 -

    35 -

    36 Emerg.Stop alarm37 Spare-1 Alarm

    38 Spare-2 Alarm

    39 -

    40 -

    41 -

    42 Low speed alarm

    43 High speed alarm

    44 Low voltage alarm

    45 High voltagealarm

    46 -

    47 -

    48 -49 -

    50 -

    51 High battery voltagealarm

    52 -

    53 -

    54 -

    55 -

    56 -

    57 -

    58 -

    59 -

    60 Emerg.Stop load_dump61 Spare-1 load_dump

    62 Spare-2 load_dump

    63 -

    64 -

    65 -

    66 -

    67 -

    68 -

    69 -

    70 -

    71 -

    72 Overcurrent load_dump73 Excess power ldd

    74 Reverse power ldd

    75 -

    76 -

    77 Mains CB Fail To Close

    78 Mains CB Fail To Open

    79 Genset Phase OrderFail Loaddump

    80 -

    81 -

    82 -

    83 -

    84 Emerg Stop warn.85 Spare-1 warning

    86 Spare-2 warning

    87 -

    88 -

    89 -

    90 Low speed warning

    91 High speed warning

    92 -

    93 -

    94 Fail to stop warning

    95 -

    96 Service requestwarning

    97 Mains Phase OrderFail

    98 Low battery warning

    99 High battery warning

    100 -

    101 -

    102 -

    103 Synchronization Fail

    104 -

    105 Gen Low voltge warn.

    106 Gen High voltge warn.

    107 Reverse Power warn.108 -

    109 -

    110 Gen CB Fail To Close

    111 Gen CB Fail To Open

    112 -

    113 -

    114 -

    115 -

    116 -

    117 -

    118 -

    119 -120 -

    The parameters below define the functions of digital inputs, selected from a list.Functions from 12 to 23 activate also the related operating sequence.

    The related input configuration parameters apply for each input, thus any signal can beprogrammed for NO or NC contact, closing to BAT+ or BAT-.

  • 8/13/2019 Dkg-329 User Manual

    39/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 39 -

    Program Group: Input Function Select (password level-2)

    Parameter DefinitionFact.Set

    Description

    Input 01 Function Select 4 Emergency Stop

    Input 02 Function Select 2 Spare-1Input 03 Function Select 3 Spare-2

    Input 04 Function Select 4 Spare -3

    Input 05 Function Select 21 Fault Reset

    Input 06 Function Select 22 Alarm Mute

    Input 07 Function Select 23 Panel Lock

    Input Function Select List

    Number Description

    0 Genset Contactor Sw.

    1 Mains Contactor Sw.2 Spare-1 Input

    3 Spare-2 Input

    4 Emergency Stop

    5 Door Open

    6 Earthquake Detector

    7 Genset-1 Ready

    8 Genset-2 Ready

    9 Genset-3 Ready

    10 Genset-4 Ready

    11 Genset-5 Ready

    12 Force AUTO Mode

    13 Force OFF Mode

    14 Force TEST Mode

    15 Force LOAD TEST Mode

    16 Spare-3 Input

    17 Spare-4 Input

    18 Remote Start Input

    19 Disable Auto Start

    20 Force to Start

    21 Fault Reset

    22 Alarm Mute

    23 Panel Lock

  • 8/13/2019 Dkg-329 User Manual

    40/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 40 -

    Program Group: Site Id (password level-2)

    Parameter Definition Factory Set Description

    Site Id StringDATAKOM SITE

    ID

    This is the site Id string sent at the beginning of anSMS message for the identification of the genset

    sending the SMS message. Any 20 character longstring may be entered.

    Program Group: Modem-1/SMS-1 Telephone Number(password level-2)

    Parameter Definition Factory Set Description

    Modem-1 / SMS-1

    telephone number----------------

    This telephone number buffer accepts up to 16digits, including the wait charater (,) in order toenable dialing through a pabx.If Modem Enabled: This is the first telephonenumber used for modem calls.If Modem Disabled: This is the first SMS telephonenumber.

    Program Group: Modem-2 / SMS-2 Telephone Number (passwordlevel-2)

    Parameter Definition Factory Set Description

    Modem-2 / SMS-2

    telephone number----------------

    This telephone number buffer accepts up to 16 digits,including the wait charater (,) in order to enabledialing through a pabx.If Modem Enabled: This is the second telephonenumber used for modem calls.If Modem Disabled: This is the second SMS

    telephone number.

    Program Group: SMS-3 Telephone Number (password level-2)

    Parameter Definition Factory Set Description

    SMS-3 telephone number ---------------- This SMS telephone number accepts up to 16 digits.

    Program Group: SMS-4 Telephone Number (password level-2)

    Parameter Definition Factory Set Description

    SMS-3 telephone number ---------------- This SMS telephone number accepts up to 16 digits.

    Program Group: SMS-5 Telephone Number (password level-2)Parameter Definition Factory Set Description

    SMS-3 telephone number ---------------- This SMS telephone number accepts up to 16 digits.

    Program Group: SMS-6 Telephone Number (password level-2)

    Parameter Definition Factory Set Description

    SMS-3 telephone number ---------------- This SMS telephone number accepts up to 16 digits.

  • 8/13/2019 Dkg-329 User Manual

    41/43

    DKG-329 User Manual V-12 (09.10.2012)

    - 41 -

    The genset operates while AC mains are OK or continues to operate after AC mains are OK:

    -Check engine body grounding.-AC mains voltages may be outside programmed limits, measure the phase voltages.-Check the AC voltage readings by pressing the MENU button.-Upper and lower limits of the mains voltages may be too tight. Check the parameters Mains VoltageLow Limitand Mains Voltage High Limit. Standard values are 170/270 volts.-The hysteresis voltage may be given to excessive. The standard value is 8 volts.

    AC voltages or frequency displayed on the unit are not correct:

    -Check engine body grounding, it is necessary.-The error margin of the unit is +/- 3 volts.

    -If there are faulty measurements only when the engine is running, there may be a faulty chargingalternator or voltage regulator on the engine. Disconnect the charging alternator connection of theengine and check if the error is removed.-If there are faulty measurements only when mains are present, then the battery charger may be failed.Turn off the rectifier fuse and check again.

    kW and cos readings are faulty although the Amp readings are correct:

    -Current transformers are not connected to the correct inputs or some of the CTs are connected withreverse polarity. Determine the correct connections of each individual CT in order to obtain correct kWand cos for the related phase, and then connect all CTs.

    Short circuit the outputs of unused Current Transformers.

    AUTO led flashes and the genset does not run when mains fail:

    The unit is in Weekly Schedule OFF time. Please check date and time setting of the unit. Please checkalso Weekly Schedule program parameters.

    The unit is inoperative:

    Measure the DC-supply voltage between Bat+ and Bat- terrminals at the rear of the unit. If OK, turn allfuses off, then turn all fuses on, starting from the DC supply fuse. Then test the unit again.

    Programming mode can not be entered:

    The program lock input disables programming mode entry. Disconnect the program lock input frombattery negative before modification. Do not forget to make this connection again to preventunauthorized program modifications.

    Some program parameters cannot be modified:

    These parameters are reserved for factory setting and require a higher level password.

    14. TROUBLESHOOTING

  • 8/13/2019 Dkg-329 User Manual

    42/43

  • 8/13/2019 Dkg-329 User Manual

    43/43

    DKG-329 User Manual V-12 (09.10.2012)

    17. CONNECTION DIAGRAM