DOCKETED
Docket Number: 17-BSTD-01
Project Title: 2019 Building Energy Efficiency Standards PreRulemaking
TN #: 217286
Document Title: 4-20-2017 Staff Workshop - 2019 Building Energy Efficiency Standards ZNE Strategy
Description: Zero net energy strategy presentation by Mazi Shirakh.
Filer: Adrian Ownby
Organization: California Energy Commission
Submitter Role: Commission Staff
Submission Date:
4/24/2017 4:21:08 PM
Docketed Date: 4/24/2017
file:///C:/Users/svc_SP_Admin/AppData/Local/Temp/fd06961b-30cf-4866-9605-fa7408245d51
Building Energy Efficiency Standards
2019 Building Energy Efficiency Standards ZNE Strategy Building Standards Office: Mazi Shirakh, PE ZNE Lead and Advisor for Building Energy Standards Standards Christopher Meyer Manager, Building Standards Office Bill Pennington Senior Technical and Program Advisor to the Energy Efficiency Division Countdown to 2020
April 20, 2017
2019 ZNE Strategy
Content 1. ZNE Strategy – What is it and how we arrived there; explaining EDR
2. Cost Effectiveness for Prescriptive PV Requirements and NEM rules
3. Strategies for Reach Codes
4. CBECC-Res Software Tools for ZNE
2
ZNE Strategy: the 2015 IPER Vision A decade ago when the ZNE goal was first set it was a simple idea: All newly constructed residential buildings by the year 2020 must be ZNE as defined by the IEPR:
“…the value of the net amount of energy produced by on-site renewable energy resources is equal to the value of the energy consumed annually by the building, at the level of a single “project” …. using the California Energy Commission’s Time Dependent Valuation metric.”
Improving building energy efficiency and deploying PVs were identified as the primary tools to achieve the ZNE goals
3
4
ZNE Goals – Lessons Learned Reality turns out to be more nuanced - Since ZNE policy was first set we have learned about the impact of
• 50% RPS and large scale PV deployment on the grid
• large scale deployment of building-based PVs which lowers the value of additional electricity around midday, coincident with utility solar production
• Net energy metering (NEM) and Time-Of-Use (TOU) on compensation for residential customer-owned generation and cost effectiveness of PVs
Also, we have learned that as the electric grid becomes greener in the future, rooftop PVs will have diminished carbon reduction benefits
5
ZNE Goals – Lessons Learned - Continued • The current NEM rules treat the grid as “virtual storage” (or a bank), where the
overgenerated kWhs can be “stored” and retrieved later in the day, or even as if summer kWhs could be stored until winter
• In reality, the grid as it is now has very little capability to store and effectively use overgenerated kWhs from PVs
• Electrification of homes, which results in a larger PV array, must be coupled with grid harmonization strategies to avoid aggravating the duck curve issues and to realize the expected environmental benefits
• Currently, customer-owned storage at about $450/kWh is still too expensive to be cost effective using the LCC for the 2019 Standards, but this is a fast evolving technology which can become cost effective under a future cycle of the Standards
6
ZNE Goals – Lessons Learned - Continued The most important lesson is that grid harmonization strategies (GHS) must be coupled with customer owned PV systems to bring maximum benefits to the grid, environment, and the home owner
GHSs are strategies that maximize self-utilization of the PV array output and minimizes uneconomic exports to the grid, examples of GHS include but not limited to battery storage, demand response, thermal storage, and EV integration.
the 2019 Standards approach must consider these issues
7
ZNE Goals – 2019 Standards Goals The 2019 Standards should be structured to send the right signal to the market to pave the way for achieving full ZNE in a later cycle of Standards by encouraging:
1. Envelope efficiency, 2. Appropriately sized PVs, and 3. Grid harmonization strategies that maximize self-utilization of the PV output and limit exports to the grid
Further, the standards must be framed in a way to encourage competition, innovation, and flexibility to foster new solutions as the grid and technologies evolve.
A possible structure is proposed later in the presentation.
8
The ZNE Challenge: Grid Harmonization The value of midday PV generated kWhs decrease as we approach the 50% Renewable Portfolio Standard (RPS) by 2030 and increasing customer-owned renewables; this necessitates developing GHS strategies that prevent the so called “Duck Curve” Issues – Curtailment is already happening in California
However, Hawaii and Australia that have already encountered these problems, are adopting grid integration/harmonization strategies to maximize self-utilizations and minimize exports to the grid
Recent News Article April 10, 2017
http://www.utilitydive.com/news/california-solar-spike-leads-to-negative-caiso-real-time-prices-in-march/440114/
http://www.utilitydive.com/news/california-solar-spike-leads-to-negative-caiso-real-time-prices-in-march/440114/http://www.utilitydive.com/news/california-solar-spike-leads-to-negative-caiso-real-time-prices-in-march/440114/http://www.utilitydive.com/news/california-solar-spike-leads-to-negative-caiso-real-time-prices-in-march/440114/
Oversupply and ramping: A new challenge as more renewables are integrated into the grid
Typical Spring Day
Net Load 11,663 MW on May 15, 2016
Actual 3-hour ramp 10,892 MW on
February 1, 2016
Page 9 CAISO Public
Solutions
Target energy efficiency
Increase storage and demand response
Enable economic dispatch of renewables
Decarbonize transportation fuels
Retrofit existing power plants
Align time-of-use rates with system conditions
Diversify resource portfolio
Deepen regional coordination
Oversupply is here already and is increasingly managed using renewable resource’s economic bids
Page 10 CAISO Public
11
PV Cost Effectiveness - Findings
All Standards measures , whether efficiency or renewables, must be cost effective in each CZ, using life cycle costing
Using the 2019 TDVs which captures the impact of 50% RPS by 2030, the LCC finds:
Appropriately sized PVs that displace the site kWh are found to be cost effective in all climate zones, even if the NEM2 rules are changed to compensate hourly exported kWhs at avoided cost, and assuming no Federal ITC
12
Proposed Prescriptive 2019 Standards PV Size
Prescriptively, the PV size will be sized to displace the annual site kWhs of the home
The prescriptive PV size will be calculated as follows:
PVs = Wsf X CFA X Aaj X CZaj Where PVs is the DC size of the PV system Wsf is the PV size per square foot of the CFAfor a dwelling of 1200 sf or less CFA is the conditioned floor area Aaj is the area adjuster CZaj is the climate zone adjuster There will be look up tables for the area and CZ Adjusters For performance compliance, we’ll use the Energy Design Rating (EDR) Tool
13
Builds on Commission’s Energy Design Rating Tool
• Energy Design Rating (EDR) score show how close a home is to the ZNE target
Aligned with RESNET
Reference home is a 2006 IECC compliant home, EDR=100
A score of zero means the house is a ZNE building
• CEC’s CBECC-Res software has the capability to calculate EDR scores for EE and PV
• Builders can use a combination of envelope energy efficiency features, better appliances, PVs, and other strategies to get to the target EDR
Download CBECC-Res here for free: http://www.bwilcox.com/BEES/BEES.html
http://www.bwilcox.com/BEES/BEES.htmlhttp://www.bwilcox.com/BEES/BEES.html
14
Proposed 2019 Standards Approach
Energy Design Rating (EDR) targets for each climate zone: 1. An EDR level for energy efficiency features based on 2019 prescriptive
measures – This EDR target can only be met using energy efficiency measures
2. An EDR Contribution for PV array that is sized to displace the annual site kWhs (no more PV tradeoff)
3. Combine the energy efficiency EDR with the PV EDR for one final target EDR
15
Proposed 2019 Standards Approach 1. Maximize envelope efficiency as allowed by LCC and calculate EE EDR
i. HPA to R19 in severe CZs – Currently R13
ii. HPW to 0.043 ~ 0.046 U-factor in severe CZs – Currently 0.051
iii. Windows U-factor of 0.30 and SHGC of 0.23 – Currently 0.32 and 0.25
iv. QII as a prescriptive requirement
2. Establish an Energy Design Rating (EDR) for energy efficiency in each CZ that can only be met with efficiency measures (no PV tradeoff against EE)
3. Calculate EDR of PV array as follows:
i. Calculate the PV size required to displace the site kWh in each CZ
ii. Calculate the EDR contribution of the PV array
4. Combine the EDR contribution of EE to the EDR contribution of PV and establish a Target EDR in each CZ that the building must meet to comply
Note: Examples are presented in later slides
16
Target EDR’s Many Advantages 1. A target EDR establishes a performance benchmark that the building must meet to comply; the
concept is similar to performance standards consistent with the Warren-Alquist Act expectation to provide builders with compliance flexibility
2. As shown by the 2016 HPA and HPW approach, builders appreciated having many options to comply, leading to a flurry of innovation in attics and walls, which continues to date
3. Target EDR can send the right signals to the market about EE, PV sizing, storage, demand response and flexibility, and other grid harmonization strategies that can achieve ZNE in the future
4. Target EDR allows the builder to use more efficiency and less PV to get to the target; the builder can also use high performance glazing or appliances that are higher than minimum efficiency levels that we are prevented to require because of preemption
5. Target EDR is fully compatible with the reach codes, local jurisdiction simply identify a lower target EDR (or zero) that can be met with a combination of additional EE, PV, demand response/flexibility, EV integration, or storage
6. Target EDR works well with varying building sizes – static PV size does not
17
Target EDR Advantages - Example Here is an example of how CBECC-Res calculates the Target EDR for both EE and PV in CZ12 for the 2,700 sf house:
18
All-Electric Home Option What should be the EE EDR and Target EDR for All-Electric Homes (AEH)? Staff proposes the same EDRs used for mixed fuel homes be used for the AEH:
1. Requiring a much larger PV system on AEH to displace the larger annual kWh will disincentivize the AEH approach
2. The larger PV needed to displace the AEH kWh, without grid harmonization strategies, will aggravate duck curve issues
Large number of AEHs, due to higher winter kWh usage than summer, can cause a winter peak that may be as large or larger than the summer peak with limited solar resources in the winter to help.
CZ
Summer Cooling kWh
Winter Heating kWh
1 0 4,686 2 30 2,367 3 3 932 4 52 2,128 5 - 2,339 6 37 909 7 9 139 8 302 307 9 632 845
10 839 1,020 11 1,577 2,179 12 543 2,208 13 1,757 1,868 14 1,578 2,266 15 5,282 119 16 105 5,596
Total 12,746 29,908
All-Electric Challenge
Base 2100-CZ2-16
Basic 2100 sf, 2016 Compliant Buildings
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ11CZ13CZ15
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating158184.317.8Space Heating136158.815.5Space Heating22.60.1
Space Cooling1,38936.2Space Cooling1,57439.8Space Cooling5,04690.6
IAQ1121.2IAQ1121.2IAQ1121.1
Water Heating116.79.3Water Heating115.09.2Water Heating93.37.5
Total Regulated Loads1,659301.064.5Total Regulated Loads1,822273.865.6Total Regulated Loads5,16095.999.3
Inside Lighting1,04511.4Inside Lighting1,04511.4Inside Lighting1,04510.9
Appliances95852.514.2Appliances95852.514.2Appliances95852.513.8
Plug Loads2,20623.3Plug Loads2,20623.3Plug Loads2,20622.3
Exterior1171.1Exterior1171.2Exterior1171.1
Total Non-regulates Loads4,32652.550.1Total Non-regulates Loads4,32652.550.1Total Non-regulates Loads4,32652.548.2
Total Building5,985353.5114.5Total Building6,148326.3115.7Total Building9,486148.4147.5
TDV Kbtu and Delta kWh/year240,471TDV Kbtu and Delta kWh/year242,886TDV Kbtu and Delta kWh/year309,708
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1806.25.49,739PV Cal 1806.75.810,098PV Cal 1808.47.713,638
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ12CZ14
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating167194.118.8Space Heating153178.117.3
Space Cooling31211.8Space Cooling1,35133.5
IAQ1121.2IAQ1121.1
Water Heating121.29.6Water Heating117.79.5
Total Regulated Loads591315.341.4Total Regulated Loads1,616295.861.4
Inside Lighting1,04511.5Inside Lighting1,04510.9
Appliances95852.514.2Appliances95852.513.8
Plug Loads2,20623.4Plug Loads2,20622.3
Exterior1171.2Exterior1171.1
Total Non-regulates Loads4,32652.550.3Total Non-regulates Loads4,32652.548.0
Total Building4,917367.891.7Total Building5,942348.3109.4
TDV Kbtu and Delta kWh/year192,549TDV Kbtu and Delta kWh/year229,719
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DR
PV Cal 1805.34.58,061PV Cal 1805.54.39,898
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ2CZ7CZ16
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating188202.821.0Space Heating1416.51.6Space Heating388453.142.7
Space Cooling80.5Space Cooling90.7Space Cooling521.9
IAQ1121.2IAQ1121.2IAQ1121.1
Water Heating128.210.1Water Heating118.19.2Water Heating138.611.1
Total Regulated Loads308331.032.8Total Regulated Loads135134.612.6Total Regulated Loads552591.756.8
Inside Lighting1,04511.3Inside Lighting1,04511.5Inside Lighting1,04510.8
Appliances95852.514.2Appliances95852.514.2Appliances95852.513.8
Plug Loads2,20623.2Plug Loads2,20623.5Plug Loads2,20622.2
Exterior1171.1Exterior1171.2Exterior1171.1
Total Non-regulates Loads4,32652.549.8Total Non-regulates Loads4,32652.550.3Total Non-regulates Loads4,32652.547.8
Total Building4,634383.582.6Total Building4,461187.163.0Total Building4,878644.2104.6
TDV Kbtu and Delta kWh/year173,460TDV Kbtu and Delta kWh/year132,216TDV Kbtu and Delta kWh/year219,639
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1804.63.96,976PV Cal 1803.42.95,460PV Cal 1805.34.59,017
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ3CZ8
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating108125.512.2Space Heating2326.92.6
Space Cooling- 0- 0Space Cooling2587.4
IAQ1121.2IAQ1121.1
Water Heating128.610.2Water Heating115.89.2
Total Regulated Loads220254.123.5Total Regulated Loads393142.720.3
Inside Lighting1,04511.2Inside Lighting1,04511.0
Appliances95852.514.2Appliances95852.513.9
Plug Loads2,20623.2Plug Loads2,20622.6
Exterior1171.1Exterior1171.2
Total Non-regulates Loads4,32652.549.7Total Non-regulates Loads4,32652.548.7
Total Building4,546306.673.2Total Building4,719.0195.269.0
TDV Kbtu and Delta kWh/year153,741TDV Kbtu and Delta kWh/year144,900
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DR
PV Cal 1803.83.35,942PV Cal 1803.83.35,943
NG 2100-CZ2-16
2100 sf - HPA:R19, QII, 0.29U and 0.23 SH, and 50% Lighting Reduction
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1Storage Factor0.8
CZ11-Red BluffCZ13-FresnoCZ15-Palm Springs
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating137159.415.4Space Heating118137.113.4Space Heating11.00.1
Space Cooling1,10828.6Space Cooling1,25631.8Space Cooling4,39977.5
IAQ1121.2IAQ1121.2IAQ1121.1PV Annula kWh generation per one kW1,500
Water Heating116.79.3Water Heating115.09.2Water Heating93.37.5
Zero Carbon:
Total Regulated Loads1,357276.154.5Total Regulated Loads1,486252.155.5Total Regulated Loads4,51294.386.3Eletricity, lb/kWh0.69
NG, lb/therm11.7
Inside Lighting5916.6Inside Lighting5916.6Inside Lighting5916.2
Appliances95852.514.2Appliances95852.514.2Appliances95852.513.8
Plug Loads2,20623.2Plug Loads2,20623.2Plug Loads2,20622.3
Exterior600.6Exterior600.6Exterior600.5
Total Non-regulates Loads3,81552.544.6Total Non-regulates Loads3,81552.544.6Total Non-regulates Loads3,81552.542.8
Total Building5,172328.699.1Total Building5,301304.6100.1Total Building8,327146.8129.0
TDV Kbtu/year149,945.1208,068TDV Kbtu/year156,411.3210,273TDV Kbtu/year247,172.2270,984
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1805.58,616PV Cal 1805.88,658PV Cal 1807.312,090
PV 180 with Storage4.46,893PV 180 with Storage4.66,926PV 180 with Storage5.99,672
TDV Electric Only at 1803.86,001TDV Electric Only at 1804.36,492TDV Electric Only at 1806.71,094
kWh Electric Only at 1803.45,276kWh Electric Only at 1803.65,327kWh Electric Only at 1805.08,292
Zero Carbon, PV 1807.2Zero Carbon, PV 1807.0Zero Carbon, PV 1807.2
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ12-SacramentoCZ14-PalmdaleTDV Ratios
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating146169.516.4Space Heating128149.314.50.00847
Space Cooling2026.8Space Cooling1,14428.3
IAQ1121.2IAQ1121.1
Water Heating121.29.6Water Heating117.79.5
Total Regulated Loads460290.734.0Total Regulated Loads1,384267.053.4
Inside Lighting5916.6Inside Lighting5916.2
Appliances95852.514.2Appliances95852.513.80.01052
Plug Loads2,20623.2Plug Loads2,20622.3
Exterior600.6Exterior600.5
Total Non-regulates Loads3,81552.544.6Total Non-regulates Loads3,81552.542.8
Total Building4,275343.278.6Total Building5,199319.596.1
TDV Kbtu/year104,262.1165,081TDV Kbtu/year146,068.1201,894
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR
PV Cal 1804.56,957PV Cal 1804.88,607
PV 180 with Storage3.65,566PV 180 with Storage3.96,886
TDV Electric Only at 1802.94,426TDV Electric Only at 1803.66,475
kWh Electric Only at 1802.74,200kWh Electric Only at 1802.95,201
Zero Carbon, PV 1806.7Zero Carbon, PV 1807.1
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ2-Santa RosaCZ7-San DiegoCZ16-Blue Canyon
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating160186.017.9Space Heating1011.71.1Space Heating344402.137.8
Space CoolingSpace Cooling30.3Space Cooling140.5
IAQ1121.2IAQ1121.2IAQ1121.1
Water Heating128.210.1Water Heating118.19.2Water Heating138.611.1
Total Regulated Loads272314.229.2Total Regulated Loads125129.811.8Total Regulated Loads470540.750.5
Inside Lighting5916.6Inside Lighting5916.6Inside Lighting5916.2
Appliances95852.514.2Appliances95852.514.2Appliances95852.513.9
Plug Loads2,20623.2Plug Loads2,20623.2Plug Loads2,20622.6
Exterior600.6Exterior600.6Exterior600.6
Total Non-regulates Loads3,81552.544.6Total Non-regulates Loads3,81552.544.6Total Non-regulates Loads3,81552.543.3
Total Building4,087366.773.8Total Building3,940182.356.4Total Building4,285593.293.8
TDV Kbtu/year90,336.0154,938TDV Kbtu/year88,215.2118,377TDV Kbtu/year92,326.3196,938
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1804.16,245PV Cal 1803.04,696PV Cal 1804.88,189
PV 180 with Storage3.34,996PV 180 with Storage2.43,757PV 180 with Storage3.86,551
TDV Electric Only at 1802.43,656TDV Electric Only at 1802.33,499TDV Electric Only at 1802.23,839
kWh Electric Only at 1802.64,073kWh Electric Only at 1802.63,940kWh Electric Only at 1802.54,285
Zero Carbon, PV 1806.9Zero Carbon, PV 1804.7Zero Carbon, PV 1809.6
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ3-San FranCZ8-Fulerton
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating8498.39.6Space Heating1821.52.1
Space Cooling- 0- 0Space Cooling1804.4
IAQ1121.2IAQ1121.1
Water Heating128.610.2Water Heating115.89.2
Total Regulated Loads196226.920.9Total Regulated Loads310137.316.9
Inside Lighting5916.3Inside Lighting5916.2
Appliances95852.514.2Appliances95852.513.9
Plug Loads2,20623.2Plug Loads2,20622.6
Exterior600.6Exterior600.6
Total Non-regulates Loads3,81552.544.3Total Non-regulates Loads3,81552.543.3
Total Building4,011279.465.2Total Building4,125189.860.2
TDV Kbtu/year88,270.9136,941TDV Kbtu/year94,825.5126,357
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR
PV Cal 1803.45,216PV Cal 1803.35,215
PV 180 with Storage2.74,173PV 180 with Storage2.74,172
TDV Electric Only at 1802.23,362TDV Electric Only at 1802.53,914
kWh Electric Only at 1802.64,011kWh Electric Only at 1802.64,125
Zero Carbon, PV 1805.8Zero Carbon, PV 1804.9
Elect 2100-CZ2-16
2100 sf - HPA:R19, QII, 0.29U and 0.23 SH, and 50% Lighting Reduction
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1Storage Factor0.8
CZ11CZ13CZ15
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating1,76114.8Space Heating1,45112.2Space Heating330.1
Space Cooling1,07331.4Space Cooling1,22233.1Space Cooling4,39882.6
IAQ1121.2IAQ1121.2IAQ1121.1
Water Heating1,46814.9Water Heating1,45414.8Water Heating1,27812.4
Total Regulated Loads4,414- 062.3Total Regulated Loads4,239- 061.4Total Regulated Loads5,821- 096.2
Inside Lighting5916.5Inside Lighting5916.4Inside Lighting5916.2
Appliances2,497- 026.3Appliances2,497- 026.3Appliances2,497- 025.2
Plug Loads2,20623.3Plug Loads2,20623.3Plug Loads2,20623.3
Exterior600.6Exterior600.6Exterior600.6
Total Non-regulates Loads5,354- 056.6Total Non-regulates Loads5,354- 056.6Total Non-regulates Loads5,354- 055.2
Total Building9,768- 0118.9Total Building9,593- 0117.9Total Building11,175- 0151.5
TDV Kbtu and Delta kWh/year249,732TDV Kbtu and Delta kWh/year247,674TDV Kbtu and Delta kWh/year318,045
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1806.4- 010,341PV Cal 1806.8- 010,198PV Cal 1808.6- 014,190
PV 180 with Storage5.28,273PV 180 with Storage5.58,158PV 180 with Storage6.911,352
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ12CZ14TDV Ratio
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating1,70814.5Space Heating1,79114.10.0085
Space Cooling1946.3Space Cooling1,11730.4
IAQ1121.2IAQ1121.1
Water Heating1,75018.0Water Heating1,66816.2
Total Regulated Loads3,764- 040.0Total Regulated Loads4,688- 061.7All of these need to be changed
Inside Lighting5916.5Inside Lighting5916.2
Appliances2,497- 026.3Appliances2,497- 025.10.0105
Plug Loads2,20623.3Plug Loads2,20622.3
Exterior600.6Exterior600.6
Total Non-regulates Loads5,354- 056.6Total Non-regulates Loads5,354- 054.1
Total Building9,118- 096.5Total Building10,042- 0115.8
TDV Kbtu and Delta kWh/year202,734TDV Kbtu and Delta kWh/year243,222
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DR
PV Cal 1805.6- 08,544PV Cal 1805.8- 010,369
PV 180 with Storage4.56,835PV 180 with Storage4.78,295
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ2CZ7CZ16
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating1,93916.2Space Heating1150.9Space Heating4,74138.1
Space Cooling0.4Space Cooling30.2Space Cooling110.4
IAQ1121.2IAQ1121.2IAQ1121.1
Water Heating1,68017.3Water Heating1,48315.4Water Heating2,67426.0
Total Regulated Loads3,731- 035.1Total Regulated Loads1,713- 017.7Total Regulated Loads7,538- 065.6
Inside Lighting5916.4Inside Lighting5916.5Inside Lighting5916.1
Appliances2,49726.2Appliances2,497- 026.4Appliances2,497- 025.1
Plug Loads2,20623.2Plug Loads2,20623.5Plug Loads2,20622.2
Exterior600.6Exterior600.6Exterior600.6
Total Non-regulates Loads5,354- 056.4Total Non-regulates Loads5,354- 056.9Total Non-regulates Loads5,354- 053.9
Total Building9,085- 091.5Total Building7,067- 074.6Total Building12,892- 0119.5
TDV Kbtu and Delta kWh/year192,087TDV Kbtu and Delta kWh/year156,702TDV Kbtu and Delta kWh/year251,013
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1805.1- 07,742PV Cal 1804.0- 06,216PV Cal 1806.1- 010,438
PV 180 with Storage4.16,194PV 180 with Storage3.24,973PV 180 with Storage4.88,350
2100 sf2016 Standards - Scenario 12100 sf2016 Standards - Scenario 1
CZ3CZ8
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating967- 08.1Space Heating2341.8
Space Cooling- 0- 0Space Cooling1744.0
IAQ1121.2IAQ1121.1
Water Heating1,683- 017.4Water Heating1,46314.6
Total Regulated Loads2,762- 026.6Total Regulated Loads1,983- 021.5
Inside Lighting5916.3Inside Lighting5916.2
Appliances2,497- 026.2Appliances2,497- 025.5
Plug Loads2,20623.2Plug Loads2,20622.6
Exterior600.6Exterior600.6
Total Non-regulates Loads5,354- 056.3Total Non-regulates Loads5,354- 054.9
Total Building8,116- 082.9Total Building7,337- 076.4
TDV Kbtu and Delta kWh/year174,090TDV Kbtu and Delta kWh/year160,335
PV System Nominal SizeDCACKWhPV System Nominal SizeDCACKWh
CBECC, DRCBECC, DR
PV Cal 1804.3- 06,631PV Cal 1804.2- 06,617
PV 180 with Storage3.45,305PV 180 with Storage3.45,294
Base 2700-CZ2-16
Basic 2700 sf, 2016 Compliant Buildings
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ11CZ13CZ15
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating189220.216.6Space Heating169196.714.9Space Heating1012.00.9
Space Cooling1,90237.7Space Cooling2,11240.7Space Cooling6,08184.5
IAQ1411.2IAQ1411.2IAQ1411.1
Water Heating129.28.0Water Heating127.47.9Water Heating103.36.5
Total Regulated Loads2,232349.463.5Total Regulated Loads2,422324.164.7Total Regulated Loads6,232115.393.0
Inside Lighting1,30011.0Inside Lighting1,30011.0Inside Lighting1,30010.6
Appliances1,02360.412.1Appliances1,02360.412.1Appliances1,02360.411.7
Plug Loads2,63021.6Plug Loads2,63021.6Plug Loads2,63020.6
Exterior1611.2Exterior1611.2Exterior1611.2
Total Non-regulates Loads5,11460.445.9Total Non-regulates Loads5,11460.445.9Total Non-regulates Loads5,11460.444.1
Total Building7,346409.8109.4Total Building7,536384.5110.5Total Building11,346175.7137.1
TDV Kbtu295,326TDV Kbtu298,377TDV Kbtu and Delta kWh/year370,089
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DR10CBECC, DR10.1CBECC, DR12.7
PV Calc 1109.313,060PV Calc 1109.813,508PV Calc 11012.317,600
PV Cal 1807.812,252PV Cal 1808.312,472PV Cal 18010.316,532
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ12CZ14
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating192224.116.9Space Heating181211.116.0
Space Cooling54916.2Space Cooling1,87335.4
IAQ1411.2IAQ1411.1
Water Heating134.28.3Water Heating130.48.1
Total Regulated Loads882358.342.6Total Regulated Loads2,195341.560.6
Inside Lighting61611.1Inside Lighting1,30010.5
Appliances1,04260.412.1Appliances1,02360.411.7
Plug Loads2,37121.7Plug Loads2,63020.6
Exterior1521.2Exterior1611.2
Total Non-regulates Loads4,18160.446.1Total Non-regulates Loads5,11460.444.1
Total Building5,063418.788.6Total Building7,309401.9104.7
TDV Kbtu and Delta kWh/year239,247TDV Kbtu and Delta kWh/year282,555
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DR8.2CBECC, DR8.9
PV Calc 1107.910,960PV Calc 1108.313,643
PV Cal 1806.49,748PV Cal 1806.912,328
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ2CZ7CZ16
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating208242.218.2Space Heating1517.91.3Space Heating447522.038.2
Space Cooling592.3Space Cooling231.3Space Cooling1674.8
IAQ1411.2IAQ1411.2IAQ1411.1
Water Heating141.98.7Water Heating130.87.9Water Heating153.59.5
Total Regulated Loads408384.130.3Total Regulated Loads179148.711.7Total Regulated Loads755675.553.7
Inside Lighting1,30010.9Inside Lighting1,30011.7Inside Lighting1,30010.4
Appliances1,02360.412.1Appliances1,02360.412.1Appliances1,02360.411.7
Plug Loads2,63021.5Plug Loads2,63021.8Plug Loads2,63020.6
Exterior1611.2Exterior1611.2Exterior1611.2
Total Non-regulates Loads5,11460.445.7Total Non-regulates Loads5,11460.446.7Total Non-regulates Loads5,11460.443.9
Total Building5,522444.576.0Total Building5,293209.158.4Total Building5,869735.997.6
TDV Kbtu and Delta kWh/year205,173TDV Kbtu and Delta kWh/year157,653TDV Kbtu and Delta kWh/year263,493
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1805.38,122PV Cal 1803.96,255PV Cal 1806.511,121
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ3CZ8
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating101117.48.9Space Heating2933.92.6
Space Cooling40.2Space Cooling4109.4
IAQ1411.2IAQ1411.1
Water Heating142.48.7Water Heating128.27.9
Total Regulated Loads246259.819.0Total Regulated Loads580162.121.1
Inside Lighting1,30010.8Inside Lighting1,30010.6
Appliances1,02360.412.1Appliances1,02360.411.9
Plug Loads2,63021.5Plug Loads2,63021.0
Exterior1611.2Exterior1611.2
Total Non-regulates Loads5,11460.445.6Total Non-regulates Loads5,11460.444.6
Total Building5,360320.264.6Total Building5,694222.565.7
TDV Kbtu and Delta kWh/year174,528TDV Kbtu and Delta kWh/year177,363
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR
PV Cal 1804.36,714PV Cal 1804.87,459
NG2700-CZ2-16
2700 sf - HPA:R19, QII, 0.29U-Factor and 0.23 SHGC, and 50% Lighting Reduction
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1Storage to PV TDV Ratio0.8
CZ11-Red BluffCZ13-FresnoCZ15-Palm Springs
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrDOE Imported and Exported Etricity Conversion Factor10,751
Space Heating167194.614.7Space Heating151175.613.3Space Heating88.80.7DOE NG Conversion Factor1.09109,000
Space Cooling1,57830.9Space Cooling1,78334.1Space Cooling5,24472.2Therms to BTU100,000
IAQ1411.2IAQ1411.2IAQ1411.1PV Annual kWh generation per one kW1,500
Water Heating129.27.8Water Heating127.47.9Water Heating103.36.5
Zero Carbon:
Total Regulated Loads1,886323.854.5Total Regulated Loads2,075303.056.5Total Regulated Loads5,393112.180.5Eletricity, lb/kWh0.69
NG, lb/therm11.7
Inside Lighting7356.2Inside Lighting7356.2Inside Lighting7356.0
Appliances1,02360.412.1Appliances1,02360.412.1Appliances1,02360.411.8
Plug Loads2,63021.6Plug Loads2,63021.6Plug Loads2,63020.7
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads4,470.060.440.5Total Non-regulates Loads4,47060.440.5Total Non-regulates Loads4,47060.439.1
Total Building6,356.0384.295.1Total Building6,545363.497.0Total Building9,863172.5119.5
TDV Kbtu/year189,172256,689TDV Kbtu/year197,361261,873TDV Kbtu/year294,439322,677
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DR8.7CBECC, DR8.9CBECC, DR11.1
PV Calc 1108.111,351PV Calc 1108.611,741PV Calc 11010.715,297
PV Cal 1806.86.810,543PV Cal 1807.210,875PV Cal 1808.68.614,10714107
TDV Electric Only at 1805.05.07,907TDV Electric Only at 1805.37,979TDV Electric Only at 1807.97.912,93512935
kWh Electric Only at 1804.04.06,405kWh Electric Only at 1804.36,528kWh Electric Only at 1806.06.09,8119811
PV 180 with storage5.48,434PV 180 with storage5.88,700PV 180 with storage6.911,286
Elect Only & Storage at 1804.2Elect Only & Storage at 1804.5Elect Only & Storage at 1806.5
DOE Definition6.8DOE Definition6.8DOE Definition7.7
Zero Carbon, PV 1808.6Zero Carbon, PV 1808.5Zero Carbon, PV 1808.5
EHPA-R23, EHPW-R23 QII, 0.29U and 0.23 SH, and 50% Lighting Reduction
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ12-SacramentoCZ14-PalmdaleCZ15TDV Ratios
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating180189.115.9Space Heating160186.414.1Space Heating77.60.60.0067
Space Cooling53617.5Space Cooling1,57429.4Space Cooling5,12770.4
IAQ1411.2IAQ1411.1IAQ1411.1
Water Heating134.28.3Water Heating130.48.1Water Heating103.36.5
Total Regulated Loads857323.342.8Total Regulated Loads1,875316.852.7Total Regulated Loads5,275110.978.5
Inside Lighting7356.3Inside Lighting7356.0Inside Lighting7356.0
Appliances1,02360.412.1Appliances1,02360.411.7Appliances1,02360.411.80.0082
Plug Loads2,63021.6Plug Loads2,63020.6Plug Loads2,63020.7
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads4,47060.440.6Total Non-regulates Loads4,47060.438.9Total Non-regulates Loads4,47060.439.1
Total Building5,327383.783.4Total Building6,345377.291.7Total Building9,745171.3117.6
TDV Kbtu/year153,253.1225,153TDV Kbtu/year181,323.4247,509TDV Kbtu/year289,506.8317,493
0
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DR7.7CBECC, DR7.8CBECC, DR10.9
PV Calc 1107.410314PV Calc 1107.312,839PV Calc 11010.615,052
PV Cal 1805.88663PV Cal 1806.010,814PV Cal 1808.614,107
TDV Electric Only at 1804.06,033TDV Electric Only at 1804.37,788TDV Electric Only at 1807.912,935
kWh Electric Only at 1803.45,296kWh Electric Only at 1803.66,388kWh Electric Only at 1806.09,811
PV 180 with storage4.66,930PV 180 with storage4.88,651PV 180 with storage6.811,104
Elect Only & Storage at 1803.3Elect Only & Storage at 1803.6Elect Only & Storage at 1806.4
DOE Definition6.1DOE Definition6.8DOE Definition7.7
Zero Carbon, PV 1807.9Zero Carbon, PV 1808.5Zero Carbon, PV 1808.4
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ2-Santa RosaCZ7-San DiegoCZ16-Blue Canyon
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating188219.416.4Space Heating1214.21.0Space Heating401467.734.2
Space Cooling321.2Space Cooling100.5Space Cooling1103.0
IAQ1411.2IAQ1411.2IAQ1411.1
Water Heating141.98.7Water Heating130.87.9Water Heating153.59.5
Total Regulated Loads361361.327.5Total Regulated Loads163145.010.6Total Regulated Loads652621.247.8
Inside Lighting7356.2Inside Lighting7356.3Inside Lighting7355.9
Appliances1,02360.412.1Appliances1,02360.412.1Appliances1,02360.411.7
Plug Loads2,63021.6Plug Loads2,63021.6Plug Loads2,63020.6
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads4,47060.440.4Total Non-regulates Loads4,47060.440.6Total Non-regulates Loads4,47060.438.8
Total Building4,831421.768.0Total Building4,633205.451.2Total Building5,122681.686.6
TDV Kbtu/year109,063183,519TDV Kbtu/year104,377138,213TDV Kbtu/year114,066233,955
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR3.4CBECC, DR5.8
PV Calc 110PV Calc 110PV Calc 110
PV Cal 1804.87382PV Cal 1803.45,490PV Cal 1805.59,479
TDV Electric Only at 1802.94,461TDV Electric Only at 1802.64,330TDV Electric Only at 1802.64,567
kWh Electric Only at 1803.14,825kWh Electric Only at 1802.94,721kWh Electric Only at 1803.15,286
PV 180 with storage3.85,906PV 180 with storage2.74,392PV 180 with storage4.47,583
Elect Only & Storage at 1802.4Elect Only & Storage at 1802.2Elect Only & Storage at 1802.2
DOE Definition6.1DOE Definition4.5DOE Definition8.0
Zero Carbon, PV 1808.0Zero Carbon, PV 1805.4Zero Carbon, PV 18011.1
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ3-San FranCZ8-Fulerton
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating7890.86.9Space Heating2428.42.2
Space Cooling30.1Space Cooling3046.5
IAQ1411.2IAQ1411.1
Water Heating142.48.7Water Heating128.27.9
Total Regulated Loads222233.217.0Total Regulated Loads469156.617.7
Inside Lighting7356.1Inside Lighting7356.0
Appliances1,02360.412.1Appliances1,02360.411.9
Plug Loads2,63021.6Plug Loads2,63021.0
Exterior820.6Exterior820.6
Total Non-regulates Loads4,47060.440.4Total Non-regulates Loads4,47060.439.4
Total Building4,692293.657.4Total Building4,939217.057.2
TDV Kbtu/year104,055154,872TDV Kbtu/year118,174154,332
0
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR7.8
PV Calc 110PV Calc 110
PV Cal 1804.16261PV Cal 1804.16,339
TDV Electric Only at 1802.64,136TDV Electric Only at 1803.14,877
kWh Electric Only at 1803.14,734kWh Electric Only at 1803.14,877
PV 180 with storage3.35,009PV 180 with storage3.35,071
Elect Only & Storage at 1802.4Elect Only & Storage at 1802.7
DOE Definition5.1DOE Definition4.8
Zero Carbon, PV 1806.4Zero Carbon, PV 1805.7
Elect 2700-CZ2-16
All Elect, 2700 sf - HPA:R19, QII, 0.29U and 0.23 SH, and 50% Lighting Reduction
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1Storage to PV TDV Ratio0.8
CZ11-Red BluffCZ13-FresnoCZ15-Palm Springs
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrDOE Imported and Exported Etricity Conversion Factor10,751
Space Heating2,17914.4Space Heating1,86812.4Space Heating1190.6DOE NG Conversion Factor1.09109,000
Space Cooling1,57735.1Space Cooling1,75736.8Space Cooling5,28276.2Therms to BTU100,000
IAQ1411.2IAQ1411.2IAQ1411.1PV Annual kWh generation per one kW1,500
Water Heating1,571- 012.5Water Heating1,55112.3Water Heating1,35910.2
Zero Carbon:
Total Regulated Loads5,468- 063.2Total Regulated Loads5,317- 062.6Total Regulated Loads6,901- 088.2Eletricity, lb/kWh0.69
NG, lb/therm11.7
Inside Lighting7356.2Inside Lighting7356.2Inside Lighting7356.0
Appliances2,79222.9Appliances2,79222.9Appliances2,79221.9
Plug Loads2,63021.6Plug Loads2,63021.6Plug Loads2,63020.7
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads6,239- 051.3Total Non-regulates Loads6,239- 051.3Total Non-regulates Loads6,239- 049.2
Total Building11,707- 0114.5Total Building11,556- 0113.9Total Building13,140- 0137.4
TDV Kbtu and Delta kWh/year309,123TDV Kbtu and Delta kWh/year307,611TDV Kbtu and Delta kWh/year370,872
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1808.212,788PV Cal 1808.412,677PV Cal 18010.016,391
PV 180 with storage6.610,230PV 180 with storage6.710,142PV 180 with storage8.013,113
kWh Electric Only at 1807.411,663kWh Electric Only at 1807.711,564kWh Electric Only at 1808.213,322
DOE Definition7.8DOE Definition7.7DOE Definition8.8
Zero Carbon, PV 1807.8Zero Carbon, PV 1807.7Zero Carbon, PV 1808.8
EHPA-R23, EHPW-R23 QII, 0.29U and 0.23 SH, and 50% Lighting Reduction
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ12-SacramentoCZ14-PalmdaleCZ15TDV Ratio
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating2,20814.8Space Heating2,26614.0Space Heating1060.60.0067
Space Cooling54318.6Space Cooling1,57832.8Space Cooling5,17074.9
IAQ1411.2IAQ1411.1IAQ1411.1
Water Heating1,86814.9Water Heating1,78013.4Water Heating1,35910.2
Total Regulated Loads4,760- 049.5Total Regulated Loads5,765- 061.3Total Regulated Loads6,776- 086.7
Inside Lighting7356.3Inside Lighting7356.0Inside Lighting7356.0
Appliances2,79222.9Appliances2,79221.9Appliances2,79221.90.0082
Plug Loads2,63021.7Plug Loads2,63020.6Plug Loads2,63020.7
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads6,239- 051.5Total Non-regulates Loads6,239- 049.0Total Non-regulates Loads6,239- 049.2
Total Building10,999- 0100.9Total Building12,004- 0110.4Total Building13,015- 0135.9
TDV Kbtu and Delta kWh/year272,538TDV Kbtu and Delta kWh/year297,972TDV Kbtu and Delta kWh/year366,930
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DRCBECC, DR
PV Cal 1807.211,127PV Cal 1807.212,962PV Cal 1809.916,027
PV 180 with storage5.88,902PV 180 with storage5.810,370PV 180 with storage7.912,813
kWh Electric Only at 1807.111,040kWh Electric Only at 1806.712,106kWh Electric Only at 1807.912,935
DOE Definition7.3DOE Definition8.0DOE Definition8.7
Zero Carbon, PV 1807.3Zero Carbon, PV 1808.0Zero Carbon, PV 1808.7
Note: Because TDV approach values therms less than source energy, therms domonated CZs will endup with a smaller PV array using TDV than the ones using source energy.
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ2 - Santa RosaCZ7-San DiegoCZ16-Blue Canyon
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating2,36715.6Space Heating1390.9Space Heating5,59635.20.0066
Space Cooling301.1Space Cooling90.4Space Cooling1053.2
IAQ1411.2IAQ1411.2IAQ1411.1
Water Heating1,79314.4Water Heating1,58212.8Water Heating2,85921.7
Total Regulated Loads4,331- 032.3Total Regulated Loads1,871- 015.3Total Regulated Loads8,701- 061.2
Inside Lighting7356.2Inside Lighting7356.3Inside Lighting7355.9
Appliances2,79222.8Appliances2,79223.0Appliances2,79221.80.0082
Plug Loads2,63021.5Plug Loads2,63021.5Plug Loads2,63020.6
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads6,239- 051.1Total Non-regulates Loads6,239- 051.4Total Non-regulates Loads6,239- 048.9
Total Building10,570- 083.4Total Building8,110- 066.7Total Building14,940- 0110.1
TDV Kbtu and Delta kWh/year225,072TDV Kbtu and Delta kWh/year180,009TDV Kbtu and Delta kWh/year297,162
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR4.5CBECC, DR7.3
PV Cal 1805.88,952PV Cal 1804.67,500PV Cal 1807.212,631
PV 180 with storage4.77,269PV 180 with storage3.55,776PV 180 with storage5.69,804
Elect Only & Storage at 1803.0Elect Only & Storage at 1802.8Elect Only & Storage at 1802.7
kWh Electric Only at 1806.510,440kWh Electric Only at 1805.08,289kWh Electric Only at 1808.414,710
DOE Definition7.0DOE Definition5.4DOE Definition10.0
Zero Carbon, PV 1807.0Zero Carbon, PV 1805.4Zero Carbon, PV 18010.0
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ3-San FranCZ8-Fulerton
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating9326.1Space Heating3071.90.0065
Space Cooling30.1Space Cooling3026.3
IAQ1411.2IAQ1411.1
Water Heating1,79814.5Water Heating1,56112.1
Total Regulated Loads2,874- 021.8Total Regulated Loads2,311- 021.4
Inside Lighting7356.1Inside Lighting7356.0
Appliances2,79222.8Appliances2,79222.20.0082
Plug Loads2,63021.5Plug Loads2,63021.0
Exterior820.6Exterior820.6
Total Non-regulates Loads6,239- 051.1Total Non-regulates Loads6,239- 049.7
Total Building9,113- 072.8Total Building8,550- 071.1
TDV Kbtu and Delta kWh/year196,641TDV Kbtu and Delta kWh/year192,051
0
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR7.8
PV Cal 1804.87565PV Cal 1805.07,891
PV 180 with storage3.96,052PV 180 with storage4.06,313
Elect Only & Storage at 1802.8Elect Only & Storage at 1803.2
kWh Electric Only at 1805.89,051kWh Electric Only at 1805.58,664
DOE Definition6.1DOE Definition5.7
Zero Carbon, PV 1806.1Zero Carbon, PV 1805.7
NG2700-Ultra
2700 sf - HPA:R19, HPW: U 0.040, QII, 0.29U-Factor and 0.23 SHGC, and 50% Lighting Reduction; WH: 0.92 EF, Furn: 0.90, AC: SEER 17 EER 15
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1Storage to PV TDV Ratio0.8
CZ11-Red BluffCZ13-FresnoCZ15-Palm Springs
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrDOE Imported and Exported Etricity Conversion Factor10,751
Space Heating152177.013.3Space Heating136158.812.1Space Heating55.90.5DOE NG Conversion Factor1.09109,000
Space Cooling1,24023.8Space Cooling1,38025.9Space Cooling4,14156.5Therms to BTU100,000
IAQ1411.2IAQ1411.2IAQ1411.1PV Annual kWh generation per one kW1,500
Water Heating114.67.1Water Heating112.97.0Water Heating91.65.7
Zero Carbon:
Total Regulated Loads1,533291.645.4Total Regulated Loads1,657271.746.1Total Regulated Loads4,28797.563.8Eletricity, lb/kWh0.69
NG, lb/therm11.7
Inside Lighting7356.2Inside Lighting7356.2Inside Lighting7356.0
Appliances1,02360.412.1Appliances1,02360.412.1Appliances1,02360.411.8
Plug Loads2,63021.6Plug Loads2,63021.6Plug Loads2,63020.7
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads4,470.060.440.5Total Non-regulates Loads4,47060.440.5Total Non-regulates Loads4,47060.439.1
Total Building6,003.0352.086.0Total Building6,127332.186.7Total Building8,757157.9102.9
TDV Kbtu/year144,288232,092TDV Kbtu/year149,958233,982TDV Kbtu/year229,230277,695
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DR7.9CBECC, DR7.9CBECC, DR9.5
PV Calc 1107.310,264PV Calc 1107.710,616PV Calc 1109.213,832
PV Cal 1806.1PV Cal 1806.4PV Cal 1807.4
TDV Electric Only at 180TDV Electric Only at 180TDV Electric Only at 180
kWh Electric Only at 1803.8kWh Electric Only at 1804.0kWh Electric Only at 1805.3
PV 180 with storage4.9PV 180 with storage5.1PV 180 with storage5.9
Elect Only & Storage at 1803.7Elect Only & Storage at 1804.0Elect Only & Storage at 1805.6
DOE Definition6.4DOE Definition6.3DOE Definition6.9
Zero Carbon, PV 1808.0Zero Carbon, PV 1807.8Zero Carbon, PV 1807.6
EHPA-R23, EHPW-R23 QII, 0.29U and 0.23 SH, and 50% Lighting Reduction
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ12-SacramentoCZ14-PalmdaleCZ15
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating156182.113.8Space Heating145168.712.8Space Heating77.60.6
Space Cooling3208.4Space Cooling1,24422.8Space Cooling5,12770.4
IAQ1411.2IAQ1411.1IAQ1411.1
Water Heating119.07.4Water Heating115.67.2Water Heating103.36.5
Total Regulated Loads617301.130.7Total Regulated Loads1,530284.343.9Total Regulated Loads5,275110.978.5
Inside Lighting7356.3Inside Lighting7356.0Inside Lighting7356.0
Appliances1,02360.412.1Appliances1,02360.411.7Appliances1,02360.411.8
Plug Loads2,63021.6Plug Loads2,63020.6Plug Loads2,63020.7
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads4,47060.440.6Total Non-regulates Loads4,47060.438.9Total Non-regulates Loads4,47060.439.1
Total Building5,087361.571.3Total Building6,000344.782.8Total Building9,745171.3117.6
TDV Kbtu/year102,816.0192,429TDV Kbtu/year137,970.0223,641TDV Kbtu/year266,706.0317,493
0
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DR6.6CBECC, DR7.0CBECC, DR10.9
PV Calc 1106.48815PV Calc 1106.610,973PV Calc 11010.615,814
PV Cal 1805.0PV Cal 1805.4PV Cal 1808.614,107
TDV Electric Only at 180TDV Electric Only at 180TDV Electric Only at 1807.912,935
kWh Electric Only at 1803.2kWh Electric Only at 1803.4kWh Electric Only at 1806.09,811
PV 180 with storage4.0PV 180 with storage4.3PV 180 with storage6.811,104
Elect Only & Storage at 1802.8Elect Only & Storage at 1803.3Elect Only & Storage at 1806.4
DOE Definition5.8DOE Definition6.3DOE Definition7.7
Zero Carbon, PV 1807.5Zero Carbon, PV 1807.9Zero Carbon, PV 1808.4
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ2-Santa RosaCZ7-San DiegoCZ16-Blue Canyon
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating188219.416.4Space Heating1214.21.0Space Heating406401.429.8
Space Cooling321.2Space Cooling100.5Space Cooling1482.0
IAQ1411.2IAQ1411.2IAQ1411.1
Water Heating141.98.7Water Heating130.87.9Water Heating153.58.5
Total Regulated Loads361361.327.5Total Regulated Loads163145.010.6Total Regulated Loads695554.941.4
Inside Lighting7356.2Inside Lighting7356.3Inside Lighting7355.9
Appliances1,02360.412.1Appliances1,02360.412.1Appliances1,02360.411.7
Plug Loads2,63021.6Plug Loads2,63021.6Plug Loads2,63020.6
Exterior820.6Exterior820.6Exterior820.6
Total Non-regulates Loads4,47060.440.4Total Non-regulates Loads4,47060.440.6Total Non-regulates Loads4,47060.438.8
Total Building4,831421.768.0Total Building4,633205.451.2Total Building5,165615.380.1
TDV Kbtu/year82,998183,519TDV Kbtu/year81,486138,213TDV Kbtu/year81,486216,351
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR3.4CBECC, DR5.3
PV Calc 110PV Calc 110PV Calc 110
PV Cal 1804.87382PV Cal 1803.45,490PV Cal 1805.1
TDV Electric Only at 1802.94,461TDV Electric Only at 1802.64,330TDV Electric Only at 180
kWh Electric Only at 1803.14,825kWh Electric Only at 1802.94,721kWh Electric Only at 1803.1
PV 180 with storage3.85,906PV 180 with storage2.74,392PV 180 with storage4.1
Elect Only & Storage at 1802.4Elect Only & Storage at 1802.2Elect Only & Storage at 1802.1
DOE Definition6.1DOE Definition4.5DOE Definition7.6
Zero Carbon, PV 1808.0Zero Carbon, PV 1805.4Zero Carbon, PV 18010.4
2700 sf2016 Standards - Scenario 12700 sf2016 Standards - Scenario 1
CZ3-San FranCZ8-Fulerton
Site Energy, KWHThermskTDV.sf-yrSite Energy, KWHThermskTDV.sf-yr
Space Heating7890.86.9Space Heating2428.42.2
Space Cooling30.1Space Cooling3046.5
IAQ1411.2IAQ1411.1
Water Heating142.48.7Water Heating128.27.9
Total Regulated Loads222233.217.0Total Regulated Loads469156.617.7
Inside Lighting7356.1Inside Lighting7356.0
Appliances1,02360.412.1Appliances1,02360.411.9
Plug Loads2,63021.6Plug Loads2,63021.0
Exterior820.6Exterior820.6
Total Non-regulates Loads4,47060.440.4Total Non-regulates Loads4,47060.439.4
Total Building4,692293.657.4Total Building4,939217.057.2
TDV Kbtu/year79,974154,872TDV Kbtu/year95,067154,332
0
PV System Nominal SizeDCKWhPV System Nominal SizeDCKWh
CBECC, DRCBECC, DR7.8
PV Calc 110PV Calc 110
PV Cal 1804.16261PV Cal 1804.16,339
TDV Electric Only at 1802.64,136TDV Electric Only at 1803.14,877
kWh Electric Only at 1803.14,734kWh Electric Only at 1803.14,877
PV 180 with storage3.35,009PV 180 with storage3.35,071
Elect Only & Storage at 1802.4Elect Only & Storage at 1802.7
DOE Definition5.1DOE Definition4.8
Zero Carbon, PV 1806.4Zero Carbon, PV 1805.7
Sumarry PV Size
2100 SF Prototype - Nominal PV Size at 180o (kW)
2019 Improved HPA: R19, QII, & Windows: U 0.29, S 0.23
123456789101112
CZ2016 Standards Compliant, 180 Degrees2019 Package TDV Displacing Elect & NGTDV With Storage Displacing Elect & NGTDV Displacing Only ElectrickWh Displacing Only ElectricDesign Rating Score for Displacing TDV Elect (w/o PV)Design Rating Score for Displacing TDV Elect (w PV)DOE Source Energy Displacing Elect & NGZero Carbon Displacing Elect & NGAll Eletric Homes - TDV
24.64.13.32.42.667.741.46.95.1
33.83.42.72.22.666.036.05.84.3
73.43.02.42.32.677.537.44.74.0
83.83.32.72.52.661.032.74.94.0
116.25.54.43.83.450.929.17.26.4
125.34.53.62.92.751.231.26.75.6
136.75.84.64.33.650.826.57.06.8
145.54.83.93.62.952.330.27.15.8
158.47.35.96.75.050.121.67.28.6
165.34.83.82.22.573.550.29.66.1
2016 TDVs2700 SF Prototype - Nominal PV Size at 180o (kW)
2019 Improved HPA: R19, QII, & Windows: U 0.29, S 0.23
123456789101112
CZ2016 Standards Compliant, 180 Degrees2019 Package TDV Displacing Elect & NG2019 Pacakge TDV With Storage Displacing Elect & NG2019 Ultra Efficiency Package2019 Ultra Efficiency Package With StorageTDV Displacing Only ElectrickWh Displacing Only ElectricDesign Rating Score for Displacing TDV Elect (w/o PV)Design Rating Score for Displacing TDV Elect (w PV)DOE Source Energy Displacing Elect & NGZero Carbon Displacing Elect & NGAll Eletric Homes - TDV
25.34.83.82.93.164.235.86.18.05.8
34.34.13.32.63.162.831.25.16.44.8
73.93.42.72.62.975.631.24.55.44.6
84.84.13.33.13.160.723.94.85.75.0
117.86.85.46.14.95.04.050.321.86.88.68.2
126.45.84.65.04.04.03.452.224.86.17.97.2
138.37.25.86.45.15.34.350.819.86.88.58.4
146.96.04.85.44.34.33.650.922.96.88.57.2
1510.38.66.97.45.97.96.048.311.97.78.510.0
166.55.54.45.14.12.63.170.546.38.011.17.2
27.0
Note: Ultra Efficiency Pacakge includes:
HPA:R19, HPW: U 0.040, QII, 0.29U-Factor and 0.23 SHGC, and 50% Lighting Reduction; WH: 0.92 EF, Furn: 0.90, AC: SEER 17 EER 15
2019 TDVs2700 SF Prototype - Nominal PV Size at 180o (kW)
2019 Improved HPA: R19, HPW: 0.041, QII, & Windows: U 0.29, S 0.23
123456789101112
CZ2016 Package TDV Displacing Elect & NG2019 Package TDV Displacing Elect & NG2019 Pacakge TDV With 10 kWh Storage Displacing Elect & NG2019 Ultra Efficiency Package2019 Ultra Efficiency Package With StorageDesign Rating Score for Displacing TDV Elect (w PV)PV Array Size (kW) for DR Scores in Col 6, Based On Col 2All Eletric Homes - TDVAll Electric Homes with a Target EDR of 27Regulated Loads Plus AppliancesRegulated Loads OnlyReglated LoadsPplus I/O Lighting
25.65.22.530.02.06.93.63.02.12.6
35.55.12.431.22.26.83.82.81.92.5
74.03.91.225.02.04.92.71.80.91.4
84.84.51.823.92.45.62.92.41.52.0
118.27.54.86.74.021.84.69.85.35.34.34.9
127.16.53.86.03.324.83.68.54.64.33.33.9
138.88.05.37.24.519.85.410.35.55.64.65.2
147.16.43.75.83.122.93.98.34.54.53.74.2
1510.49.16.48.05.311.97.810.85.77.06.06.6
167.97.24.56.84.146.32.111.67.74.94.04.6
Sheet1
Mazi PV Output, July 6 2015
HourskWhHourskWhHourskWh20200.3300.017
"10-110.6120210.347
0.6420220.364
0.6820230.381
0.720240.398
"11-120.7320250.415
0.7520260.432
0.7720270.449
0.7820280.466
"12-130.7920290.483
0.7920300.50.17
0.8020310.5
0.8320320.5
13-140.8220330.5
0.8220340.5
0.8220350.5
0.8120360.5
14-150.8120370.5
0.7520380.5
0.7620390.5
0.7920400.5
"15-160.7520410.5
0.7420420.5
0.7120430.5
0.6820440.5
20450.5
20460.5
Total6.486.144.8320470.5
20480.5
2 Hours6.4820490.5
4 Hours12.6220500.5
6 Hours17.45
0.490.16
PV Size, kW DCAll-Electric Challenge
CZ2019 Package TDV Displacing Elect & NGAll Eletric Homes - TDVSummer Cooling kWhWinter Heating kWhCZTarget Design Rating Score for Displacing kWh ElectkW PV Size for Displacing kWh Electric Only kW PV Size for Displacing kWh Electric Only
104,686
24.85.8302,367213.52.9
34.14.83932313.53.1
4522,128
5- 02,339
637909
73.44.6913978.22.7
84.15.030230789.42.9
9632845
108391,020
116.88.21,5772,1791116.43.8
125.87.25432,2081215.53.1
137.28.41,7571,8681317.14.0
1467.21,5782,2661418.23.3
158.610.05,2821191514.75.7
165.57.21055,5961623.32.8
Total12,74629,908
2,700 sf Prototype2,700 sf Prototype2,100 sf Prototype
PV Size: 3.1 kW DCPV Size: 5.3 kW DCPV Size: 2.6 kW DC
CZ: 12CZ: 12CZ: 12
Storage SizeTarget EDRDeltaStorage SizeTarget EDRDeltaStorage SizeTarget EDRDelta
022.2007.40023.40
221.60.625.91.5221.22.2
419.12.543.12.8418.13.1
616.72.462.01.1617.11.0
815.71.081.20.8816.60.5
1015.00.7100.70.51016.40.2
1215.00.0120.40.31215.90.5
1414.90.1140.20.21415.70.2
1614.90.0160.20.01615.60.1
Total7.3Total7.2Total7.8
2,700 sf Prototype2,700 sf Prototype2,100 sf Prototype
PV Size: 5.7 kW DCPV Size: 8.0 kW DCPV Size: 8.0 kW DC
CZ: 12CZ: 12CZ: 12
Storage SizeTarget EDRDeltaStorage SizeTarget EDRDeltaStorage SizeTarget EDRDelta
04.700-10.700-21.90
22.91.82-13.32.62-25.13.2
40.32.64-14.81.54-26.11.0
6-0.60.96-15.60.86-26.60.5
8-1.40.88-16.20.68-27.00.4
10-1.90.510-16.50.310-27.20.2
12-2.10.212-16.70.212-27.20.0
14-2.30.214-16.70.014-27.20.0
16-2.30.016-16.70.016-27.20.0
Total7.0Total6.0Total5.3
Delta EDR per 1 kW of PV6.7Delta EDR per 1 kW of PV6.7Delta EDR per 1 kW of PV8.4
EDR Credit By Measures
2700 sf Prototype, CZ12
Building ScenarioEE EDR ScoreDifferenceTotal HPA+HPW
Base 2019 Standards43.2
No HPA46.5-3.3
No HPW45.5-2.3-5.6
HPG 0.2040.92.3Note: Furnace and SEER credits have interactive effects with envelope measures
HPG 0.1539.93.3
0.95 Furn41.81.4
SEER 16, EER 1441.91.3
Tankless 0.9542.70.5
HPG 0.20, 0.95 Furn. 0.95 WH, SEER 16385.2
HPG 0.15, 0.95 Furn. 0.95 WH, SEER 1637.26.0
EmbeddedFile1.xls
19
All-Electric - Summer Duck vs Christmas Turkey All-Electric homes use more kWhs in the winter than summer that may result in
higher peak and demand in winter – Grid harmonization becomes more important – Like a broken clock, a dumb PV systems is correct twice a YEAR
Chart1
13743.453912.34753.351927.8
10732.056690.63962.73294.9
8646.759216.94022.554536
7793.110577.73764.255203.8
6835.511484.93783.155651.1
6196.0511973.153934.355893.65
7169.411992.055087.255903.1
6753.611604.64778.555710.95
7011.910196.554863.65017.95
6659.18908.24139.14381.65
9777.65663.74299.752784.6
14360.854180.054819.52056.95
Elect Use - All Elct
PV Gen - All Elct
Elect Use - Mixed
PV Gen - Mixed
Months
kBTU/Year
2,700 sf Mixed Fuel vs All-Elect, CZ12, Source Energy, 3.1 & 6.3 kW PV Sized to Displace Annual kWh
Sheet1
2,700 sf, CZ12, 3.1 kW PV - Mixed Fuel, kBTU Site Energy2,700 sf, CZ12, 3.1 kW PV - All Elect, kBTU Site Energy
3.1 Kw PV sized to offset annual kWh6.3 Kw PV sized to offset annual kWh
Total Elect-MFTotal Solar-MFTotal Elect-Solar-MFTotal GasTotal Elect-AETotal Solar-AETotal Elect-Solar-AETotal Gas
Jan1,5096128977,543Jan4,3631,2423121
Feb1,2581,0462124,893Feb3,4072,1241283
Mar1,2771,440(163)3,330Mar2,7452,926-181
Apr1,1951,652(457)2,654Apr2,4743,358-884
May1,2011,794(593)1,702May2,1703,646-1476
Jun1,2491,871(622)1,331Jun1,9673,801-1834
Jul1,6151,874(259)1,192Jul2,2763,807-1531
Aug1,5171,813(296)1,160Aug2,1443,684-1540
Sep1,5441,593(49)1,256Sep2,2263,237-1011
Oct1,3141,391(77)1,321Oct2,1142,828-714
Nov1,3658844814,080Nov3,1041,7981306
Dec1,5306538777,359Dec4,5591,3273232
Total16,57416,623(49)37,821Total33,54933,778(229)- 0
2,700 sf, CZ12, 3.1 kW PV - Mixed Fuel, kBTU Source Energy2,700 sf, CZ12, 3.1 kW PV - All Elect, kBTU Source Energy
3.1 Kw PV sized to offset annual kWh6.3 Kw PV sized to offset annual kWh
Total Elect-MFTotal Solar-MFTotal Elect-Solar-MFTotal Gas-MFTotal Elect-AETotal Solar-AETotal Elect-Solar-AETotal Gas
Jan4,7531,9282,8268,222Jan13,7433,9129,831
Feb3,9633,2956685,333Feb10,7326,6914,041
Mar4,0234,536(513)3,630Mar8,6479,217(570)
Apr3,7645,204(1,440)2,893Apr7,79310,578(2,785)
May3,7835,651(1,868)1,855May6,83611,485(4,649)
Jun3,9345,894(1,959)1,451Jun6,19611,973(5,777)
Jul5,0875,903(816)1,299Jul7,16911,992(4,823)
Aug4,7795,711(932)1,264Aug6,75411,605(4,851)
Sep4,8645,018(154)1,369Sep7,01210,197(3,185)
Oct4,1394,382(243)1,440Oct6,6598,908(2,249)
Nov4,3002,7851,5154,447Nov9,7785,6644,114
Dec4,8202,0572,7638,021Dec14,3614,18010,181
Total52,20852,362(154)41,225Total105,679106,401(721)
Delta Between AE and MF UsageDelta Between AE and MF PV Gen
Conversion Factors:8,9901,984
Elect3.156,7693,396
NG1.094,6244,681
4,0295,374
3,0525,834
2,2626,080
2,0826,089
1,9755,894
2,1485,179
2,5204,527
5,4782,879
9,5412,123
53,47154,038
Sheet1
Total Electric
Total Solar
Electric-Solar
Total Gas
Months
kBTU/Year
2,700 sf Mixed Fuel, CZ12, Source Energy, 3.1 kW PV Sized to Displace Annual kWh
Sheet2
Total Electric
Total Solar
Electric-Solar
Months
kBTU/Year
2,700 sf All-Elect, CZ12, Source Energy, 6.3 kW PV Sized to Displace Annual kWh
Sheet3
Elect Use - All Elct
PV Gen - All Elct
Elect Use - Mixed
PV Gen - Mixed
Months
kBTU/Year
2,700 sf Mixed Fuel vs All-Elect, CZ12, Source Energy, 3.1 & 6.3 kW PV Sized to Displace Annual kWh
Delta AE vs MF Elect Usage
Delats AE vs MF PV Gen
NG
Months
kBTU/Year
2,700 sf, Net Gen and Usage Between Mixed Fuel & All-Elect, CZ12, Source Energy, 3.1 & 6.3 kW PV Sized to Displace Annual kWh
EmbeddedFile2.xls
20
Target EDR Examples by Climate Zone Here is are examples of how Target EDRs might look for different scenarios in different CZs for the 2,700 sf Mixed Fuel Homes: Note: At this time these numbers are examples only and may change as our tools evolve
NEM = Net Energy Metering; GH = Grid Harmonization
1 2 3 4 5 6 7 8 9 10 11
CZ
Efficiency EDR without PV, based on
2019 Efficiency Measures
Target Design Rating Score
for Displacing kWh Elect
with PV from Col 4
kW PV Size for Displacing kWh Electric Only –
Cool with NEM, not so Cool with
GH
Standalone PV Sized to Zero EDR (Dumb
PV) – Violates NEM, Not Cool
with GH
PV Size for Zero EDR with Basic
Battery Controls – May Violate NEM,
OK with GH
PV Size for Zero EDR with
Optimum Battery Controls – Cool with NEM and
GH
Similar to Col 7 But With 95 Furn, 0.95 WH
– Real Cool with NEM and
GH
Col 6 to 4
Ratio
Col 7 to 4
Ratio
Col 8 to 4
Ratio
1 48.0 26.5 3.4 7.7 6.9 4.6 4.1 2.0 1.4 1.2
2 41.2 18.0 2.9 6.1 5.5 3.1 2.8 1.9 1.1 1.0
3 46.9 22.7 2.8 5.8 5.3 3.2 2.9 1.9 1.1 1.0
6 48.0 20.9 2.9 5.3 4.5 2.9 2.8 1.6 1.0 1.0
7 48.0 14.9 2.7 4.6 3.9 2.4 2.3 1.4 0.9 0.9
8 43.0 14.6 2.9 5.3 4.3 2.7 2.6 1.5 0.9 0.9
11 43.3 23.4 3.8 8.5 6.5 4.4 4.2 1.7 1.2 1.1
12 43.1 24.5 3.1 7.0 5.8 3.8 3.5 1.9 1.2 1.1
13 44.8 22.1 4.0 9.0 6.2 4.9 4.6 1.6 1.2 1.2
14 44.6 21.3 3.4 7.4 5.4 4.4 4.1 1.6 1.3 1.2
15 48.0 17.9 5.7 10.5 8.1 6.9 6.8 1.4 1.2 1.2
16 46.3 27.5 3.0 7.6 6.5 4.8 4.3 2.2 1.6 1.4
21
Target EDR Examples by Climate Zone Here is are examples of how Target EDRs might look for different scenarios in different CZs for the 2,700 sf All-Electric Homes: Note: At this time these numbers are examples only and may change as our tools evolve
NEM = Net Energy Metering; GH = Grid Harmonization
1 2 3 4 5 6 7 8 9 10 11
CZ
Target Design Rating Score
for Displacing kWh Elect
with PV Size from Col 3
kW PV Size for Displacing kWh Electric Only in
Mixed Fuel Homes–Cool
with NEM
Standalone PV Size Needed to Displace Annual kWh – Cool with NEM, not Cool
with GH
Standalone PV Sized for Zero
EDR (Dumb PV) – Violates
NEM, Not Cool with GH
PV Sized for Zero EDR with Basic Battery
Controls – May Violate NEM,
OK for GH
PV Sized for Zero EDR with
Optimum Battery Controls
– Cool with NEM and GH
Similar to Col 7 But With 14 EER HP, 3.5
COP HPWH – Real Cool with NEM and GH
Col 6 to 4
Ratio
Col 7 to 4 Ratio
Col 8 to 4 Ratio
1 33.9 3.4 7.7 9.4 8.4 5.6 5.3 1.1 0.8 0.7
2 29.6 2.9 5.9 7.2 6.5 3.9 3.7 1.1 0.7 0.6
3 32.1 2.8 5.4 7.0 6.0 3.8 3.6 1.1 0.7 0.7
6 26.6 2.9 4.6 5.9 4.9 3.2 3.0 1.1 0.7 0.7
7 26.0 2.7 4.1 5.3 4.4 2.7 2.6 1.1 0.7 0.6
8 26.0 2.9 4.6 6.1 4.8 3.1 2.9 1.0 0.7 0.6
11 31.4 3.8 6.6 9.9 7.6 5.9 5.3 1.2 0.9 0.8
12 30.0 3.1 5.9 8.4 6.7 4.8 4.4 1.1 0.8 0.7
13 30.8 4.0 6.7 10.3 8.0 6.5 5.8 1.2 1.0 0.9
14 33.3 3.4 5.9 8.6 6.7 5.8 5.3 1.1 1.0 0.9
15 26.2 5.7 7.0 11.5 9.2 8.0 7.0 1.3 1.1 1.0
16 48.3 3.0 7.7 10.2 8.9 7.0 6.9 1.3 1.0 1.0
22
2 – Life Cycle Costing
Life Cycle Costing for Prescriptive PV Requirement
E3 Life Cycle Costing Analysis Finds:
1. PV systems sized to displace site annual kWh cost effective in all climate zones
2. Even if NEM2 rules are changed to compensate exported kWhs at avoided cost
3. With no federal ITC
The followings are a partial representation of E3 analysis and findings (E3’s greatest hits) – The full report will be available online
Solar production occurs during low TDV hours, and households demand energy during high TDV hours
• PV must be sized larger to reach TDV ZNE vs. Site ZNE (which doesn’t account for the changing value of kWh)
For a 2,100 ft2 home with 180° PV orientation, TDV ZNE requires 7% - 44% larger PV capacity than Site ZNE (average: 21%)
Because PV interconnection rules limit sizing to electric kWh, this presentation focuses on that size
TDV ZNE requires a larger PV system than Site ZNE
23
-
2
4
6
8
10
CZ1
CZ2
CZ3
CZ4
CZ5
CZ6
CZ7
CZ8
CZ9
CZ10
CZ11
CZ12
CZ13
CZ14
CZ15
CZ16
PV S
yste
m C
apac
ity (k
W)
Mixed Fuel Home PV System Capacity (kW)2100 sf mixed fuel home, 180° orientation
Sizing PV to Offset Electric kWhSizing PV to Offset Electric TDVSizing PV to Offset Electric + Gas TDV (Current Definition of ZNE)
-
2
4
6
8
10
CZ1
CZ2
CZ3
CZ4
CZ5
CZ6
CZ7
CZ8
CZ9
CZ10
CZ11
CZ12
CZ13
CZ14
CZ15
CZ16
PV s
yste
m c
apac
ity
(kW
)
All-Electric Home PV system capacity (kW)(2,100 sq ft all-electric home, 180°PV orientation)
Sizing PV to Offset Electric kWh Sizing PV to Offset Electric TDV
PV Costs
No ITC Assumed - The ITC is scheduled to step down throughout the 2020-2022 building standard cycle (26%, 22%, 20%) and then to 0% for residential systems beginning in 2023
All costs assume a 30-yr panel life and inverter replacements after 10 and 20 years (comprises ~$0.40/W in the costs)
$2.61 $2.99
$3.55
$0.00$0.50$1.00$1.50$2.00$2.50$3.00$3.50$4.00
Low Cost Med Cost High Cost
$/W
($2
019)
PV Costs
Price based on NREL 2016 Installer Price
• Low cost case: • 30% cost reduction 2016 – 2020 (GreenTech Media)
• Medium cost case: • 18% cost reduction 2016 – 2020 (Bloomberg)
• High cost case: • No cost reduction 2016 - 2020
Three solar compensation policies
25
0
1
2
3
4
5
6
NEM 2.0 AC for Exports AC for All
30-y
r NPV
PV
Prod
uctio
n Va
lue
($20
19)
Average per-kWh compensated value (TDV) of rooftop PV(Mixed fuel home, solar PV sized to electric kWh, 2,100 sq ft home, 180°PV orientation)
Behind-the-meter Generation Non-Surplus Export Generation
AC = Avoided Costs
Non-surplus Export Generation are the hourly exports
Offsetting electric kWh with solar PV is cost-effective except under the most aggressive NEM reform scenarios
Cost-Effectiveness of Offsetting Elec kWh in a Mixed Fuel Home
26
CZ PV kW1 2.89 2 2.46 3 2.38 4 2.36 5 2.22 6 2.38 7 2.26 8 2.46 9 2.51
10 2.58 11 3.10 12 2.58 13 3.28 14 2.73 15 4.83 16 2.37
$(10,000)
$(5,000)
$-
$5,000
$10,000
$15,000
$20,000
$25,000
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Net
Ben
efit
($20
19 N
PV)
Climate Zone
Net Benefit of Offsetting Electric kWh in a Mixed Fuel Home2700 sf - PV 180°
Low Cost PV NEM 2.0
Med Cost PV NEM 2.0
High Cost PV NEM 2.0
Low Cost PV Avoided Cost forExportsMed Cost PV Avoided Cost forExportsHigh Cost PV Avoided Cost forExportsLow Cost PV Avoided Cost for All
3 - Strategies for Reach Codes
NEM Rules and Oversizing PV –
DRAFT
March 2, 2017
Snuller Price, Zachary Ming, Brian Conlon
PV Sizing Methods
Electric kWh
• PV scaled such that annual generation = annual electric load
Maximize Net Benefits
• PV scaled to maximize net TDV benefit to customer • Practically, this is the same capacity as sizing to kWh, i.e., further generation will only
receive Net Surplus Compensation (NSC)
Electric TDV
• PV scaled such that annual TDVs generated = annual TDV of electric load
Zero Net Benefits (Breakeven Point)
• PV scaled to point at which a larger system will not be cost-effective
• Cost of PV system = Revenue from PV generation 28
Sizes no longer follow predictable order
02468
101214161820
CZ01 CZ02 CZ03 CZ04 CZ05 CZ06 CZ07 CZ08 CZ09 CZ10 CZ11 CZ12 CZ13 CZ14 CZ15 CZ16
Syst
em Si
ze (k
W)
2700 sqft, PV180, NEM 2.0, Mid Cost PV
PV Sized to Electric kWh PV Sized to Maximize Net Benefits
PV Sized to Electric TDV PV Sized to Zero Net Benefits
CZ1 1.98 CZ2 2.51 CZ3 2.49 CZ4 2.62 CZ5 2.76 CZ6 2.42 CZ7 2.61 CZ8 2.49 CZ9 2.55
CZ10 2.43 CZ11 2.65 CZ12 2.59 CZ13 2.43 CZ14 2.96 CZ15 2.55 CZ16 2.61
PV sized to max net benefits is smaller than sized to electric TDV
• Sizing to TDV does not reflect lower compensation for exports from NEM 2.0
At sizes beyond max net benefits, incremental kW only receive NSC
• Large net benefit and small marginal net cost (PV cost – NSC) at the point of maximum net benefits require much larger systems to zero out net benefits
• NEM2 for self-use and exports, NSC for net surplus
Sizing Comparison NEM 2.0, Mid Cost PV
29
Ratio of PV Sized to Zero Net Benefits
PV Sized to Electric kWh
02468
101214161820
CZ01 CZ02 CZ03 CZ04 CZ05 CZ06 CZ07 CZ08 CZ09 CZ10 CZ11 CZ12 CZ13 CZ14 CZ15 CZ16
Syst
em Si
ze (k
W)
2700 sqft, PV180, Avoided Cost for Exported Energy, Mid Cost PV
PV Sized to Electric kWh PV Sized to Maximize Net Benefits
PV Sized to Electric TDV PV Sized to Zero Net Benefits
CZ01 1.21 CZ02 1.57 CZ03 1.52 CZ04 1.64 CZ05 1.71 CZ06 1.58 CZ07 1.67 CZ08 1.67 CZ09 1.69 CZ10 1.57 CZ11 1.65 CZ12 1.64 CZ13 1.45 CZ14 1.91 CZ15 1.55 CZ16 1.60
Valuing export PV generation at avoided cost reduces cost-effectiveness of PV sized to offset kWh
• Smaller net benefits for systems sized to offset kWh means less kW at marginal net cost are needed to zero out net benefits
• Retail for self-use, AC for exports, NSC for net surplus
Sizing Comparison AC for Exports, Mid Cost PV
30
Ratio of PV Sized to Zero Net Benefits
PV Sized to Electric kWh
- 2 4 6 8
10 12 14 16 18 20
CZ01 CZ02 CZ03 CZ04 CZ05 CZ06 CZ07 CZ08 CZ09 CZ10 CZ11 CZ12 CZ13 CZ14 CZ15 CZ16
Syst
em Si
ze (k
W)
2700 sqft, PV180, BTM TDV, Mid Cost PV
PV Sized to Electric kWh PV Sized to Maximize Net Benefits
PV Sized to Electric TDV PV Sized to Zero Net Benefits
Sizing Comparison BTM TDV, Mid Cost PV
31
Ratio of PV Sized to Zero Net Benefits
PV Sized to Electric kWh
BTM TDV means
• All PV production consumed behind-the-meter (BTM) receives full TDV value
• All PV production exported to the grid as well as all net surplus above a system sized to annual kWh receives net surplus compensation (NSC)
PV sized to electric kWh and electric TDV are unchanged from previous rate structures
PV sized to maximize net benefits and PV sized to zero net benefits are substantially reduced
Retail for self-use, NSC for exports and annual surplus
CZ1 0.74 CZ2 1.05 CZ3 1.01 CZ4 1.11 CZ5 1.14 CZ6 1.04 CZ7 1.12 CZ8 1.11 CZ9 1.18
CZ10 1.05 CZ11 1.11 CZ12 1.14 CZ13 0.89 CZ14 1.30 CZ15 0.98 CZ16 1.07
Storage Overview
E3 analyzed the additional value of a battery storage system to an existing PV system of a 2700 sf, mixed fuel home
BTM TDV rate scenario
• BTM generation receives full TDV value (~$0.20/kWh); exported generation receives net surplus compensation value (~$0.03/kWh)
Battery assumptions
• 14 kWh
• 5 kW
• 90% round trip efficiency
• $500/kWh fully installed
32
02468
101214161820
CZ01 CZ02 CZ03 CZ04 CZ05 CZ06 CZ07 CZ08 CZ09 CZ10 CZ11 CZ12 CZ13 CZ14 CZ15 CZ16
Syst
em Si
ze (k
W)
2700 sqft, PV180, BTM TDV, Mid Cost PV
PV Sized to Electric kWh PV Sized to Maximize Net Benefits
PV Sized to Electric TDV PV Sized to Zero Net Benefits
Sizing Comparison BTM TDV With Storage, Mid Cost PV
Ratio of PV Sized to Zero Net Benefits
PV Sized to Electric kWh
33
Installing storage (without accounting for the storage costs) increases the benefits to the homeowner, allowing them to install more solar
The Santa option: Demonstrates how PV value increases if coupled with storage at no cost
Retail for self-use, NSC for exports and annual surplus
CZ1 2.05 CZ2 2.78 CZ3 2.70 CZ4 3.09 CZ5 3.09 CZ6 2.89 CZ7 2.97 CZ8 3.17 CZ9 3.77
CZ10 3.75 CZ11 3.76 CZ12 3.71 CZ13 3.66 CZ14 4.26 CZ15 3.47 CZ16 3.02
storage costs not included
Sizing Comparison Avoided Cost for Exported Energy With Storage, Mid Cost PV
CZ1 1.48 CZ2 2.21 CZ3 1.96 CZ4 2.71 CZ5 2.23 CZ6 1.73 CZ7 1.87 CZ8 2.29 CZ9 2.39 CZ10 2.47 CZ11 2.82 CZ12 2.63 CZ13 2.49 CZ14 2.73 CZ15 2.33 CZ16 1.90 34
Changing the rate structure to avoided cost for exported energy increases the next benefits of solar + storage and therefore increases the amount of solar that can be installed before net benefits are reduced to zero; annual surplus at NSC
Includes storage costs
NEW
Ratio of PV Sized to Zero Net Benefits
(with Storage Costs) PV Sized to Electric kWh
02468
101214161820
CZ01 CZ02 CZ03 CZ04 CZ05 CZ06 CZ07 CZ08 CZ09 CZ10 CZ11 CZ12 CZ13 CZ14 CZ15 CZ16
Syst
em Si
ze (k
W)
2700 sqft, PV180, Avoided Cost for Exported Energy, Mid Cost PV
PV Sized to Electric kWh PV Sized to Maximize Net Benefits
PV Sized to Electric TDV PV Sized to Zero Net Benefits
PV Sized to Zero Net Benefits (with Storage Cost) PV Sized to Electric + Gas TDV
35
4. Software Tools The CBECC-Res Compliance Software May Be Used For:
• Part 6 Compliance, and
• Part 11 (Calgreen, Reach Codes, etc)
The Software can be used to:
• Size PV for Part 6 compliance or lower target EDRs for Reach Codes
• Assess the impact of battery storage on lowering EDR
• Assess the impact of precooling and other DR strategies on lowering EDR
• Assess the impact HPWH DR on lowering EDR
36
4. Software Tools – Input Screens
This screen can be used to specify EDR targets required by reach codes
37
4. Software Tools – Input Screens
38
4. Software Tools – Input Screens
39
4. Software Tools – Results Screens
For Compliance with Part 6
40
4. Software Tools – Input Screens
For Compliance with Part 11
41
Questions?
42
BEES Impact on EUI
Impacts of Building Standards on Home Energy Use
43
2019 BEES Schedule 2019 STANDARDS UPDATE SCHEDULE
DATE MILESTONES
February 2016-July 2016 Measures Identified and approval August 2016 to June 2017 Stakeholder meeting/workshop & final staff workshop April, 2017 CASE Reports submitted to the CEC December 1, 2017 45-day Language Hearings March 1, 2018 Adoption of 2019 Standards at Business Meeting June1, 2018 to November 2018
Staff work on Software, Compliance Manuals, Electronic Documents Available to Industry
November 1, 2018 Approval of the Manuals January 1, 2019 Software, Compliance Manuals, Electronic Documents
Available to Industry January 1, 2020 Effective Date
Informational Resources
• Energy Efficiency Standards approved computer compliance programs, CBECC-Res and CBECC-Com can be downloaded for free at: http://www.energy.ca.gov/title24/2016standards/2016_computer_prog_list.html
• Information on the current 2016 Building Energy Efficiency Standards, including Compliance Manuals, worksheets and additional resources can be found at: http://www.energy.ca.gov/title24/2016standards/index.html
• To receive documents and notification of upcoming events, please sign up on the List Serve for the 2019 Building Energy Efficiency Standards (Docket #2016-BSTD-06) at: http://www.energy.ca.gov/title24/2019standards/prerulemaking/index.html
• Title 24 Support Hotline: [email protected]
http://www.energy.ca.gov/title24/2016standards/2016_computer_prog_list.htmlhttp://www.energy.ca.gov/title24/2016standards/index.htmlhttp://www.energy.ca.gov/title24/2019standards/prerulemaking/index.html
Document.pdfDocument.pdfSlide Number 12019 ZNE Strategy ZNE Strategy: the 2015 IPER VisionSlide Number 4Slide Number 5Slide Number 6Slide Number 7Slide Number 8Oversupply and ramping:A new challenge as more renewables are integrated into the gridSlide Number 10Slide Number 11Slide Number 12Slide Number 13Slide Number 14Slide Number 15Slide Number 16Slide Number 17Slide Number 18Slide Number 19Slide Number 20Slide Number 21Slide Number 22TDV ZNE requires a larger PV system than Site ZNEPV CostsThree solar compensation policiesCost-Effectiveness of Offsetting �Elec kWh in a Mixed Fuel Home�3 - Strategies for Reach Codes��NEM Rules and Oversizing PV – DRAFT�PV Sizing MethodsSizing Comparison �NEM 2.0, Mid Cost PVSizing Comparison�AC for Exports, Mid Cost PVSizing Comparison�BTM TDV, Mid Cost PVStorage OverviewSizing Comparison�BTM TDV With Storage, Mid Cost PVSizing Comparison�Avoided Cost for Exported Energy �With Storage, Mid Cost PVSlide Number 35Slide Number 36Slide Number 37Slide Number 38Slide Number 39Slide Number 40Slide Number 41Slide Number 42Slide Number 43Informational Resources