    DEPARTMENT OF ELECTRICAL &ELECTRONICS ENGINEERING

    COURSE: POWER SYETMS-II

    BRANCH: Electrical and Electronics Engineering

    CLASS: III/I Sem.

    YEAR: 2013-2014

    LECTURE NOTES

    SHRI VISHNU ENGINEERING COLLEGE FOR WOMEN

    VISHNUPUR, BHIMAVARAM-534202

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    2/46

    DEPARTMENT OF EEE - SVECW Page 1

    CONTENTS Page No.

    UNIT1: Transmission Line Parameters 02

    UNITII: Performance of short and Medium Length 15

    Transmission lines

    UNITII: Performance of long transmission line 27

    UNIT IV: Power system transients 32

    UNITV: Various factor governing the performance of line 35

    UNITV1: Overhead line Insulators 42

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    3/46

    DEPARTMENT OF EEE - SVECW Page 2

    UNIT-I

    Transmission Line Parameters

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    4/46

    DEPARTMENT OF EEE - SVECW Page 3

    2. TRANSMISSION LINES

    The electric parameters of transmission lines (i.e. resistance, inductance, and capacitance) can be

    determined from the specifications for the conductors, and from the geometric arrangements ofthe conductors.

    2.1 Transmission Line Resistance

    Resistance to d.c. current is given by

    AR

    dc

    where is the resistivity at 20o

    Cis the length of the conductor

    A is the cross sectional area of the conductor

    Because of skin effect, the d.c. resistance is different from ac resistance. The ac resistance is

    referred to as effective resistance, and is found from power loss in the conductor

    Rpower loss

    I 2

    The variation of resistance with temperature is linear over the normal temperature range

    resistance

    ( )

    R2

    R1

    T T1 T2 temperature (oC)

    Figure 9 Graph of Resistance vs Temperature

    ( )

    ( )

    ( )

    ( )

    R

    T T

    R

    T T

    1

    1

    2

    2

    0 0

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    5/46

    DEPARTMENT OF EEE - SVECW Page 4

    RT T

    T TR2

    2

    1

    1

    2.2 Transmission Line Inductive Reactance

    Inductance of transmission lines is calculated per phase. It consists of self inductance of the

    phase conductor and mutual inductance between the conductors. It is given by:

    LGMD

    GMR2 10 7 ln [H/m]

    where GMR is the geometric mean radius (available from manufacturers tables)GMD is the geometric mean distance (must be calculated for each lineconfiguration)

    Geometric Mean Radius: There are magnetic flux lines not only outside of the conductor, but

    also inside. GMR is a hypothetical radius that replaces the actual conductor with a hollow

    conductor of radius equal to GMR such that the self inductance of the inductor remains the same.

    If each phase consists of several conductors, the GMR is given by

    1 2

    3

    n

    GMR d d d d d d d d d dn n n n nnn ( .... ).( . .... )......( . ..... )11 12 13 1 21 22 2 1 2

    2

    where d11=GMR1d22=GMR2

    .

    .

    .

    dnn=GMRn

    Note: for a solid conductor, GMR = r.e-1/4 , where r is the radius of the conductor.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    6/46

    DEPARTMENT OF EEE - SVECW Page 5

    Geometric Mean Distance replaces the actual arrangement of conductors by a hypothetical

    mean distance such that the mutual inductance of the arrangement remains the same

    b c a b

    a

    m c n

    GMD D D D D D D D D Daa ab an ba bb bn ma mb mnmn ( ... ).( ... ).....( ..... )' ' ' ' ' ' ' ' '

    '

    where Daa is the distance between conductors a and a etc.

    Inductance Between Two Single Phase Conductors

    r1 r2

    D

    LD

    r1

    7

    1

    2 10 ln' L

    D

    r2

    7

    2

    2 10 ln'

    where r1 is GMR of conductor 1r2 is GMR of conductor 2D is the GMD between the conductors

    The total inductance of the line is then

    L L LD

    r

    D

    r

    D

    r r

    D

    r r

    LD

    r r

    D

    r r

    T

    T

    1 2

    7

    1 2

    72

    1 2

    72

    1 2

    72

    1 2

    1 2

    7

    1 2

    2 10 2 10 2 10 21

    2

    4 10 4 10

    ln'

    ln'

    ln' '

    ln' '

    ln' '

    ln' '

    /

    If r1 = r2 , then

    L Dr

    T 4 10 71

    ln'

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    7/46

    DEPARTMENT OF EEE - SVECW Page 6

    Example: Find GMD, GMR for each circuit, inductance for each circuit, and total inductance

    per meter for two circuits that run parallel to each other. One circuit consists of three 0.25 cm

    radius conductors. The second circuit consists of two 0.5 cm radius conductor

    9 m

    a a

    6 m 6 m

    b b

    6 m circuit B

    c

    circuit A

    Solution:

    m = 3, n = 2, m n = 6

    GMD D D D B D Daa ab ba bb ca cb' ' ' ' ' '6

    where

    D D m

    D D D m

    D m

    aa bb

    ab ba cb

    ca

    ' '

    ' ' '

    '

    9

    6 9 117

    12 9 15

    2 2

    2 2

    GMD = 10.743 m

    Geometric Mean Radius for Circuit A:

    m481.0126e1025.0DDDDDDDDDGMR 9 243

    41

    23cccbcabcbbbaacabaaA

    2

    Geometric Mean Radius for Circuit B:

    m153.06e105.0DDDDGMR 42

    2

    41

    22'a'b'b'b'b'a'a'aB

    2

    Inductance of circuit A

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    8/46

    DEPARTMENT OF EEE - SVECW Page 7

    LGMD

    GMRH mA

    A

    2 10 2 1010743

    04816 2 12 10

    7 7 7ln ln

    .

    .. /

    Inductance of circuit B

    LGMD

    GMRH mB

    B

    2 10 2 1010 743

    01538503 107 7 7ln ln

    .

    .. /

    The total inductance is then

    L L L H mT A B 14 715 107. /

    The Use of Tables

    Since the cables for power transmission lines are usually supplied by U.S. manufacturers, the

    tables of cable characteristics are in American Standard System of units and the inductive

    reactance is given in /mile.

    X fL f GMD

    GMRm

    X fGMD

    GMRm

    X fGMD

    GMRmile

    X fGMD

    GMRmile

    X fGMR

    f GMD mile

    L

    L

    L

    L

    L

    2 2 2 10

    4 10

    4 10 1609

    2 022 10

    2 022 101

    2 022 10

    7

    7

    7

    3

    3 3

    ln /

    ln /

    ln /

    . ln /

    . ln . ln /

    Xa Xd

    If both, GMR and GMD are in feet, then Xa represents the inductive reactance at 1 ft spacing,

    and Xd is called the inductive reactance spacing factor.

    Example: Find the inductive reactance per mile of a single phase line operating at 60 Hz. The

    conductor used is Partridge, with 20 ft spacings between the conductor centers.

    D = 20 ft

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    9/46

    DEPARTMENT OF EEE - SVECW Page 8

    Solution: From the Tables, for Partridge conductor, GMR = 0.0217 ft and inductive reactance at

    1 ft spacing Xa= 0.465 /mile. The spacing factor for 20 ft spacing is Xd = 0.3635 /mile. The

    inductance of the line is then

    X X X mileL a d 0465 03635 08285. . . /

    Inductance of Balanced Three Phase Line

    Average inductance per phase is given by:

    LD

    GMR

    eq2 10

    7ln

    where Deq is the geometric mean of the three spacings of the three phase line.

    D D D Deq ab ac bc3

    Example: A three phase line operated at 60 Hz is arranged as shown. The conductors are ACSR

    Drake. Find the inductive reactance per mile.

    20ft 20 ft

    38 ft

    Solution:

    For ACSR Drake conductor, GMR = 0.0373 ft

    D ft

    L H m

    X mile

    OR

    from the tables X mile

    eq

    L

    a

    20 20 38 24 8

    2 1024 8

    0 037313 10

    2 60 1609 13 10 0 788

    0399

    3

    7 7

    7

    .

    ln.

    ./

    . /

    . /

    The spacing factor is calculated for spacing equal the geometric mean distance between the

    conductors, that is, X miled 2 022 10 60 24 8 0 3893. ln . . /

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    10/46

    DEPARTMENT OF EEE - SVECW Page 9

    Then the line inductance is X X X mile per phaseline a d 0788. /

    Example: Each conductor of the bundled conductor line shown in the figure is 1272 MCM

    Pheasant. Find:

    a) the inductive reactance in /km and /mile per phase for d = 45 cmb) the p.u. series reactance if the length of the line is 160 km and the base is 100 MVA, 345 kV.

    8 m 8 m

    Solution:

    a) The distances in ft are

    d ft

    D ft

    0 45

    0 30481476

    8

    0 30482625

    .

    ..

    ..

    For Pheasant conductors, GMR = 0.0466 ft.

    GMRb for a bundle of conductors is

    GMR GMR d ftb 00466 1 476 0 2623. . .

    The geometric mean of the phase conductor spacing is

    D fteq 26 25 26 25 52 49 33 073 . . . .

    The inductance of the line is then

    LD

    GMRH meq

    b

    2 10 2 10 330702623

    9 674 107 7 7ln ln ..

    . /

    The inductive reactance is

    X fL m km mileL 2 2 60 9 674 10 3 647 10 0 3647 0 58687 4. . / . / . /

    b) Base impedance ZV

    Sb

    b

    b

    2 2345

    1001190

    Total impedance of the 160 km line is

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    11/46

    DEPARTMENT OF EEE - SVECW Page 10

    X

    XX

    Zp u

    L

    Lp uL

    b

    160 0 3 647 58 3 5

    5835

    11900049

    . .

    .. . .. .

    2.3 Transmission Line Capacitive Reactance

    Conductors of transmission lines act like plates of a capacitor. The conductors are charged, and

    there is a potential difference between the conductors and between the conductors and the

    ground. Therefore there is capacitance between the conductors and between the conductors and

    the ground. The basic equation for calculation of the capacitance is the definition of the

    capacitance as the ratio of the charge and the potential difference between the charged plates:

    CQ

    VF

    where Q is the total charge on the conductors (plates)V is the potential difference between the conductors or a conductor and ground (i.e.

    plates)

    For transmission lines, we usually want the capacitance per unit length

    Cq

    VF m/

    where q is the charge per unit length in C/m

    V is the potential difference between the conductors or a conductor and ground (i.e.

    plates)

    Capacitance of a Single Phase Line

    r1 r2

    D

    For a two conductor line, the capacitance between the conductors is given by

    CD

    r r

    F m02

    1 2

    ln

    /

    where o is the permittivity of free space and is equal to 8.85 10-12 F/m

    D is the distance between the conductors, center to centerr1 and r2 are the radii of the two conductors

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    12/46

    DEPARTMENT OF EEE - SVECW Page 11

    Formally, this equation corresponds to the equation for inductance of a two conductor line. The

    equation was derived for a solid round conductor and assuming a uniform distribution of charge

    along the conductors. The electric field, and therefore the capacitance of stranded conductors is

    not the same as for solid conductors, but if the radii of the conductors are much smaller than the

    distance between the conductors, the error is very small and an outside radii of the strandedconductors can be used in the equation.

    For most single phase lines, r1 = r2 . In this case, half way between the conductors there is a point

    where E = 0. This is the neutral point n

    a n b

    Can Cbn

    The capacitance from conductora to point n is Can and is the same as the capacitance fromconductorb to n, Cbn. Can and Cbn are connected in series, therefore C C Can bn ab2 .

    1

    It follows that

    CD

    r

    an

    o2

    ln

    [F/m]

    Since XfC

    c

    1

    2

    X

    fD

    r

    f

    D

    rmc

    o

    1

    22

    2 8 62 109

    ln

    .ln

    The capacitive reactance in mile is

    Xf

    D

    r f

    D

    rmilec

    2 862 10 1

    1609

    1779 109 6

    .ln

    .ln

    Similarly as for inductive reactance, this expression can be split into two terms that are called

    capacitive reactance at 1 ft spacing (Xa) and the capacitive reactance spacing factor (Xd).

    1 C

    C C

    C C

    C Cab

    an bn

    an bn

    an bn

    1

    1 1If C Can bn , then C

    C

    C

    Cab

    an

    an

    an

    2

    2 2

    Therefore, C Can ab2

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    13/46

    DEPARTMENT OF EEE - SVECW Page 12

    Xf r f

    D milec1779 10 1 1779 106 6.

    ln.

    ln

    Xa Xd

    Xa is given in the tables for the standard conductors, Xd is given in the tables for the capacitivereactance spacing factor.

    Example: Find the capacitive reactance in M miles for a single phase line operating at 60 Hz.

    The conductor used for the line is Partridge, and the spacing is 20 ft.

    The outside radius of the Partridge conductor is r in ft06422

    0 0268. .

    The capacitive reactance is

    Xf

    D

    r fM mileC

    1779 10 1779 10 20

    0 026801961

    6 6.ln

    .ln

    .. .

    OR

    From tables X M milea' . .01074

    X M miled'

    . .00889 for 20 spacing

    X X X M mileC a d' ' . .01963

    This is the capacitive reactance between the conductor and the neutral. Line-to-line capacitive

    reactance is

    XX

    M mileCL L C

    20 0981. .

    Capacitance of Balanced Three Phase Line between a phase conductor and neutral is given by

    CD

    D

    F mno

    eq

    b

    2

    ln

    /

    where D D D Deq ab bc ca3 and Dab, Dbc, and Dca are the distances between the centers of the

    phase conductors, and Db is the geometric mean radius for the bundled conductors. (in the

    expression for Db the outside radius of the conductor is used, rather than the GMR from the

    tables.)

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    14/46

    DEPARTMENT OF EEE - SVECW Page 13

    The capacitive reactance to neutral than becomes

    Xf

    D

    Dmilecn

    eq

    b

    1779 106

    .ln .

    Example:a) A three phase 60 Hz line is arranged as shown. The conductors are ACSR Drake. Find the

    capacitive reactance for 1 mile of the line.

    b) If the length of the line is 175 miles and the normal operating voltage is 220 kV, find the

    capacitive reactance to neutral for the entire length of the line, the charging current for the line,

    and the charging reactive power.

    20ft 20 ft

    38 ft

    Solution:

    The outside radius for Drake conductors is r in ft1108

    20 0462

    ..

    The geometric mean distance for this line is

    D fteq 20 20 38 24 83 .

    From tables, X M milea' . .00912

    Xf

    D M mile

    X X X M mile

    d eq

    cn a d

    '

    ' '

    .ln

    .ln . . .

    . .

    1779 10 1779 10

    6024 8 0 0 952

    01864

    6 6

    This is the capacitive reactance to neutral.

    For the length of 175 miles,

    XX

    Ctotalcn

    1751065

    Charging current is

    I

    V

    X

    k

    ACLN

    Ctotal

    220

    3

    1065 119

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    15/46

    DEPARTMENT OF EEE - SVECW Page 14

    Reactive power to charge the line is

    Q V I k MVAr C LL C3 3 220 119 45 45.

    2.5 Transmission Line Losses and Thermal Limits

    The power losses of a transmission line are proportional to the value of resistance of the line. The

    value of the resistance is determined by the type and length of the conductor. The current in the

    line is given by the power being delivered by the transmission line.

    P E IR R equiv R cos IP

    Eequiv

    R

    R Rcos

    From that,

    P I RP

    ERloss equiv

    R

    R R

    2

    2

    cos

    Power utilities usually strive to maintain the receiving end voltage constant. The power delivered

    by the transmission line is determined by the load connected to the line and cannot be changed

    without changing the load. The only term in the above equation that can be regulated is the

    power factor. If the power factor can be adjusted to be equal to 1, the power losses will be

    minimum.

    Efficiency of the transmission line is given by

    %

    P

    P

    R

    S

    100%

    Thermal Limits on equipment and conductors depend on the material of the insulation of

    conductors. The I2R losses are converted into heat. The heat increases the temperature of the

    conductors and the insulation surrounding it. Some equipment can be cooled by introducing

    circulation of cooling media, other must depend on natural cooling. If the temperature exceeds

    the rated value, the insulation will deteriorate faster and at higher temperatures more immediate

    damage will occur.

    The power losses increase with the load. It follows that the rated load is given by the temperature

    limits. The consequence of exceeding the rated load for short periods of time or by small

    amounts is a raised temperature that does not destroy the equipment but shortens its service life.

    Many utilities routinely allow short time overloads on their equipment - for example transformers

    are often overloaded by up to 15% during peak periods that may last only 15 or 30 minutes.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    16/46

    DEPARTMENT OF EEE - SVECW Page 15

    UNIT-II

    Performance of Short and MediumLength Transmission Lines

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    17/46

    DEPARTMENT OF EEE - SVECW Page 16

    SHORT TRANSMISSION LINES

    The transmission lines are categorized as three types

    1) Short transmission linethe line length is up to 80 km

    2) Medium transmission linethe line length is between 80km to 160 km

    3) Long transmission linethe line length is more than 160 km

    Whatever may be the category of transmission line, the main aim is to transmit power from one

    end to another. Like other electrical system, the transmission network also will have some power

    loss and voltage drop during transmitting power from sending end to receiving end. Hence,

    performance of transmission line can be determined by its efficiency and voltage regulation.

    power sent from sending endline losses = power delivered at receiving end

    Voltage regulation of transmission line is measure of change of receiving end voltage from no-load to full load condition.

    Every transmission line will have three basic electrical parameters. The conductors of the linewill have resistance, inductance, and capacitance. As the transmission line is a set of conductors

    being run from one place to another supported by transmission towers, the parameters are

    distributed uniformly along the line.

    The electrical power is transmitted over a transmission line with a speed of light that is 3X10 8m sec. Frequency of the power is 50Hz. The wave length of the voltage and current of the power

    can be determined by the equation given below,

    f. = v where f is power frequency, &labda is wave length and v is the speed of light.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    18/46

    DEPARTMENT OF EEE - SVECW Page 17

    Hence the wave length of the transmitting power is quite long compared to the generally used

    line length of transmission line.

    For this reason, the transmission line, with length less than 160 km, the parameters are assumed

    to be lumped and not distributed. Such lines are known as electrically short transmission line.

    This electrically short transmission lines are again categorized as short transmission line (lengthup to 80 km) and medium transmission line(length between 80 and 160 km). The capacitive

    parameter of short transmission line is ignored whereas in case of medium length line the

    capacitance is assumed to be lumped at the middle of the line or half of the capacitance may be

    considered to be lumped at each ends of the transmission line. Lines with length more than 160

    km, the parameters are considered to be distributed over the line. This is called long transmission

    line.

    ABCD PARAMETERS

    A major section of power system engineering deals in the transmission of electrical power from

    one particular place (eg. Generating station) to another like substations or distribution units withmaximum efficiency. So its of substantial importance for power system engineers to be thorough

    with its mathematical modeling. Thus the entire transmission system can be simplified to a two

    port networkfor the sake of easier calculations.

    The circuit of a 2 port network is shown in the diagram below. As the name suggests, a 2 port

    network consists of an input port PQ and an output port RS. Each port has 2 terminals to connect

    itself to the external circuit. Thus it is essentially a 2 port or a 4 terminal circuit, having

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    19/46

    DEPARTMENT OF EEE - SVECW Page 18

    Supply end voltage = VS

    and Supply end current = IS

    Given to the input port P Q.

    And there is the Receiving end Voltage = VR

    and Receiving end current = IR

    Given to the output port R S.

    As shown in the diagram below.

    Now the ABCD parameters or the transmission line parameters provide the link between the

    supply and receiving end voltages and currents, considering the circuit elements to be linear innature.

    Thus the relation between the sending and receiving end specifications are given using ABCD

    parameters by the equations below.

    VS = A VR+ B IR-(1)

    IS = C VR+ D IR-(2)

    Now in order to determine the ABCD parameters of transmission line let us impose the requiredcircuit conditions in different cases.

    ABCD parameters, when receiving end is open circuited

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    20/46

    DEPARTMENT OF EEE - SVECW Page 19

    The receiving end is open circuited meaning receiving end current IR= 0.

    Applying this condition to equation (1) we get.

    Thus its implies that on applying open circuit condition to ABCD parameters, we get parameter

    A as the ratio of sending end voltage to the open circuit receiving end voltage. Since dimension

    wise A is a ratio of voltage to voltage, A is a dimension less parameter.

    Applying the same open circuit condition i.e IR= 0 to equation (2)

    Thus its implies that on applying open circuit condition to ABCD parameters of transmission

    line, we get parameter C as the ratio of sending end current to the open circuit receiving end

    voltage. Since dimension wise C is a ratio of current to voltage, its unit is mho.

    Thus C is the open circuit conductance and is given by

    C = IS VRmho.

    ABCD parameters when receiving end is short circuited

    Receiving end is short circuited meaning receiving end voltage VR= 0

    Applying this condition to equation (1) we get

    Thus its implies that on applying short circuit condition to ABCD parameters, we get parameter

    B as the ratio of sending end voltage to the short circuit receiving end current. Since dimensionwise B is a ratio of voltage to current, its unit is . Thus B is the short circuit resistance and is

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    21/46

    DEPARTMENT OF EEE - SVECW Page 20

    given by

    B = VS IR.

    Applying the same short circuit condition i.e VR= 0 to equation (2) we get

    Thus its implies that on applying short circuit condition to ABCD parameters, we get parameter

    D as the ratio of sending end current to the short circuit receiving end current. Since dimension

    wise D is a ratio of current to current, its a dimension less parameter. the ABCD parameters oftransmission line can be tabulated as:-

    Parameter Specification UnitA = VS / VRVoltage ratio Unit less

    B = VS / IR Short circuit resistance C = IS / VR Open circuit conductance mho

    D = IS / IR Current ratio Unit less

    SHORT TRANSMISSION LINEThe transmission lines which have length less than 80 km are generally referred as short

    transmission lines.

    For short length, the shunt capacitance of this type of line is neglected and other parameters like

    resistance and inductance of these short lines are lumped, hence the equivalent circuit isrepresented as given below,

    Lets draw the vector diagram for this equivalent circuit, taking receiving end current Irasreference. The sending end and receiving end voltages make angle with that reference receiving

    end current, of sand r, respectively.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    22/46

    DEPARTMENT OF EEE - SVECW Page 21

    As the shunt capacitance of the line is neglected, hence sending end current and receiving end

    current is same, i.e.

    Is = Ir.

    Now if we observe the vector diagram carefully, we will get,

    Vs is approximately equal to

    Vr+ Ir.R.cosr+ Ir.X.sinr

    That means,

    Vs Vr+ Ir.R.cosr+ Ir.X.sinras the it is assumed that sr

    As there is no capacitance, during no load condition the current through the line is considered aszero, hence at no load condition, receiving end voltage is the same as sending end voltage

    As per dentition of voltage regulation,

    Here, vrand vx are the per unit resistance and reactance of the short transmission line.

    Any electrical network generally has two input terminals and two output terminals. If we

    consider any complex electrical network in a black box, it will have two input terminals and

    output terminals. This network is called twoport network. Two port model of a networksimplifies the network solving technique. Mathematically a two port network can be solved by 2

    by 2 matrixes.

    A transmission as it is also an electrical network; line can be represented as two port network.

    Hence two port network of transmission line can be represented as 2 by 2 matrixes. Here the

    concept of ABCD parameters comes. Voltage and currents of the network can represented as ,

    Vs= AVr+ BIr(1)

    Is= CVr+ DIr(2)

    Where A, B, C and D are different constant of the network.

    If we put Ir= 0 at equation (1), we get

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    23/46

    DEPARTMENT OF EEE - SVECW Page 22

    Hence, A is the voltage impressed at the sending end per volt at the receiving end when receivingend is open. It is dimension less.

    If we put Vr= 0 at equation (1), we get

    That indicates it is impedance of the transmission line when the receiving terminals are short

    circuited. This parameter is referred as transfer impedance.

    C is the current in amperes into the sending end per volt on open circuited receiving end. It has

    the dimension of admittance.

    D is the current in amperes into the sending end per amp on short circuited receiving end. It is

    dimensionless.

    Now from equivalent circuit, it is found that,

    Vs = Vr+ IrZ and Is = Ir

    Comparing these equations with equation 1 and 2 we get,

    A = 1, B = Z, C = 0 and D = 1. As we know that the constant A, B, C and D are related for

    passive network as

    AD BC = 1.

    Here, A = 1, B = Z, C = 0 and D = 1

    1.1 Z.0 = 1

    So the values calculated are correct for short transmission line.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    24/46

    DEPARTMENT OF EEE - SVECW Page 23

    From above equation (1),

    Vs = AVr+ BIr

    When Ir= 0 that means receiving end terminals is open circuited and then from the equation 1,

    we get receiving end voltage at no load

    and as per definition of voltage regulation,

    Efficiency of Short Transmission Line

    The efficiency of short line as simple as efficiency equation of any other electrical equipment,

    that means

    MEDIUM TRANSMISSION LINE

    The transmission line having its effective length more than 80 km but less than 250 km, is

    generally referred to as a medium transmission line. Due to the line length being considerably

    high, admittance Y of the network does play a role in calculating the effective circuit parameters,

    unlike in the case of short transmission lines. For this reason the modelling of a medium length

    transmission line is done using lumped shunt admittance along with the lumped impedance inseries to the circuit.

    These lumped parameters of a medium length transmission line can be represented using two

    different models, namely.

    1) Nominal representation.

    2) Nominal T representation.

    Lets now go into the detailed discussion of these above mentioned models.

    Nominal representation of a medium transmission line

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    25/46

    DEPARTMENT OF EEE - SVECW Page 24

    In case of a nominal representation, the lumped series impedance is placed at the middle of the

    circuit where as the shunt admittances are at the ends. As we can see from the diagram of the network below, the total lumped shunt admittance is divided into 2 equal halves, and each half

    with value Y 2 is placed at both the sending and the receiving end while the entire circuitimpedance is between the two. The shape of the circuit so formed resembles that of a symbol ,

    and for this reason it is known as the nominal representation of a medium transmission line. Itis mainly used for determining the general circuit parameters and performing load flow analysis.

    As we can see here, VS and VR is the supply and receiving end voltages respectively, and

    Is is the current flowing through the supply end.

    IR is the current flowing through the receiving end of the circuit.

    I1 and I3 are the values of currents flowing through the admittances. And

    I2 is the current through the impedance Z.

    Now applying KCL, at node P, we get.

    IS = I1 + I2(1)

    Similarly applying KCL, to node Q.I2 = I3 + IR(2)

    Now substituting equation (2) to equation (1)

    IS = I1 + I3 + IR

    Now by applying KVL to the circuit,

    VS = VR+ Z I2

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    26/46

    DEPARTMENT OF EEE - SVECW Page 25

    Comparing equation (4) and (5) with the standard ABCD parameter equations

    VS = A VR+ B IR

    IS = C VR+ D IR

    We derive the parameters of a medium transmission line as:

    Nominal T representation of a medium transmission lineIn the nominal T model of a medium transmission line the lumped shunt admittance is placed in

    the middle, while the net series impedance is divided into two equal halves and and placed on

    either side of the shunt admittance. The circuit so formed resembles the symbol of a capital T,

    and hence is known as the nominal T network of a medium length transmission line and is shown

    in the diagram below.

    Here also Vs and Vr is the supply and receiving end voltages respectively, and

    Is is the current flowing through the supply end. Ir is the current flowing through the receiving

    end of the circuit. Let M be a node at the midpoint of the circuit, and the drop at M, be given by

    Vm. Applying KVL to the above network we get

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    27/46

    DEPARTMENT OF EEE - SVECW Page 26

    Now the sending end current is

    Is = Y VM + IR(9)

    Substituting the value of VM to equation (9) we get,

    Again comparing Comparing equation (8) and (10) with the standard ABCD parameter equations

    VS = A VR+ B IR

    IS = C VR+ D IR

    The parameters of the T network of a medium transmission line are

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    28/46

    DEPARTMENT OF EEE - SVECW Page 27

    UNIT-III

    Performance of Long TransmissionLines

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    29/46

    DEPARTMENT OF EEE - SVECW Page 28

    LONG TRANSMISSION LINE

    A power transmission line with its effective length of around 250 Kms or above is referred to as

    a long transmission line. Calculations related to circuit parameters (ABCD parameters) of such

    a power transmission is not that simple, as was the case for a short or medium transmission line.

    The reason being that, the effective circuit length in this case is much higher than what it was forthe former models(long and medium line) and, thus ruling out the approximations considered

    there like.

    a) Ignoring the shunt admittance of the network, like in a small transmission line model.

    b) Considering the circuit impedance and admittance to be lumped and concentrated at a point as

    was the case for the medium line model.

    Rather, for all practical reasons we should consider the circuit impedance and admittance to be

    distributed over the entire circuit length as shown in the figure below.

    The calculations of circuit parameters for this reason is going to be slightly more rigorous as we

    will see here. For accurate modeling to determine circuit parameters let us consider the circuit of

    the long transmission line as shown in the diagram below.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    30/46

    DEPARTMENT OF EEE - SVECW Page 29

    Here a line of length l > 250km is supplied with a sending end voltage and current of VS and IS

    respectively, where as the VRand IRare the values of voltage and current obtained from the

    receiving end. Lets us now consider an element of infinitely small length x at a distance x fromthe receiving end as shown in the figure where.

    V = value of voltage just before entering the element x.

    I = value of current just before entering the element x.

    V+V = voltage leaving the element x.

    I+I = current leaving the element x.

    V = voltage drop across element x.

    zx = series impedence of element x

    yx = shunt admittance of element x

    Where Z = z l and Y = y l are the values of total impedance and admittance of the long

    transmission line.

    the voltage drop across the infinitely small element x is given by

    V = I z x

    Or I z = V x

    Or I z = dV dx (1)

    Now to determine the current I, we apply KCL to node A.

    I = (V+V)yx = V yx + V yx

    Since the term V yx is the product of 2 infinitely small values, we can ignore it for the sake ofeasier calculation.

    we can write dI dx = V y (2)

    Now derevating both sides of eq (1) w.r.t x,

    d2V d x2= z dI dx

    Now substituting dI dx = V y from equation (2)

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    31/46

    DEPARTMENT OF EEE - SVECW Page 30

    d2V d x2 = zyV

    or d2V d x2 zyV = 0 (3)

    The solution of the above second order differential equation is given by.

    V = A1 exyz + A2 e

    xyz(4)

    Derivating equation (4) w.r.to x.

    dV/dx = (yz) A1 exyz (yz)A2 e

    xyz(5)

    Now comparing equation (1) with equation (5)

    Now to go further let us define the characteristic impedance Zcand propagation constant of along transmission line as

    Zc= (z/y)

    = (yz)

    Then the voltage and current equation can be expressed in terms of characteristic impedance and

    propagation constant as

    V = A1 ex

    + A2 ex

    (7)

    I = A1/ Zc ex

    + A2 / Zc ex

    (8)

    Now at x=0, V= VRand I= Ir. Substituting these conditions to equation (7) and (8) respectively.

    VR= A1 + A2(9)

    IR= A1/ Zc + A2 / Zc(10)

    Solving equation (9) and (10),

    We get values of A1 and A2 as,

    A1 = (VR+ ZCIR) 2

    And A1 = (VR ZCIR) 2

    Now applying another extreme condition at x=l, we have V = VS and I = IS.

    Now to determine VS and IS we substitute x by l and put the values of A1 and A2 in equation (7)

    and (8) we get

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    32/46

    DEPARTMENT OF EEE - SVECW Page 31

    VS = (VR+ ZC IR)el

    2 + (VR ZC IR)el

    /2(11)

    IS = (V

    RZC + IR)el/2 (VR / ZC IR)e

    l/2(12)

    By trigonometric and exponential operators we know

    sinh l = (el el) 2

    And cosh l = (el + el) 2

    equation(11) and (12) can be re-written as

    VS = VRcosh l + ZC IRsinh l

    IS = (VRsinh l)/ZC + IRcosh l

    Thus comparing with the general circuit parameters equation, we get the ABCD parameters of a

    long transmission line as,

    C = sinh l ZC A = cosh l D = cosh l B = ZCsinh l

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    33/46

    DEPARTMENT OF EEE - SVECW Page 32

    UNIT IV

    Power Sys tem Trans ients

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    34/46

    DEPARTMENT OF EEE - SVECW Page 33

    Bewley Lattice Diagram

    This is a convenient diagram devised by Bewley, which shows at a glance the position and

    direction of motion of every incident, reflected, and transmitted wave on the system at every

    instant of time. The diagram overcomes the difficulty of otherwise keeping track of the

    multiplicity of successive reflections at the various junctions.

    Consider a transmission line having a resistance r, an inductance l, a conductance g and acapacitance c, all per unit length.

    If is the propagation constant of the transmission line, and

    E is the magnitude of the voltage surge at the sending end,

    then the magnitude and phase of the wave as it reaches any section distance x from the sending

    end is Ex given by.

    Ex = E

    where

    e-.[

    e-j [

    . e- x = E . e - (+ j ) x = E e - x e - j x

    represents the attenuation in the length of line x

    represents the phase angle change in the length of line x

    Therefore,

    . attenuation constant of the line in neper/km

    phase angle constant of the line in rad/km.

    It is also common for an attenuation factorkto be defined corresponding to the length of a particular

    line. i.e. k = e-.O

    for a line of length l.

    The propagation constant of a line RI D OLQH RI VHULHV LPSHGDQFH z and shunt

    admittance y per unit length is given by

    = z.y = (r + j l) (g + j c)

    Similarly the surge impedance of the line (or characteristic impedance) Zo

    Z0

    = z= (r + j l)y (g + j c)

    When a voltage surge of magnitude unity reaches a junction between two sections with surge

    impedances Z1 and Z2, then a part . is transmitted and a part is reflected back. In traversing the

    second line, if the attenuation factor is k, then on reaching the termination at the end of the second

    line its amplitude would be reduced to N . . The lattice diagram may now be constructed as follows.

    Set the ends of the lines at intervals equal to the time of transit of each line. If a suitable time scale is

    chosen, then the diagonals on the diagram show the passage of the waves.High Voltage Transient Analysis

    In the Bewley lattice diagram, the following properties exist. (1) All waves travel downhill, because time always increases.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    35/46

    DEPARTMENT OF EEE - SVECW Page 34

    34

    (2) The position of any wave at any time can be deduced directly from the diagram.

    (3) The total potential at any point, at any instant of time is the superposition of all the

    waves which have arrived at that point up until that instant of time, displaced in

    position from each other by intervals equal to the difference in their time of arrival.

    (4) The history of the wave is easily traced. It is possible to find where it came from

    and just what other waves went into its composition.

    (5) Attenuation is included, so that the wave arriving at the far end of a line

    corresponds to the value entering multiplied by the attenuation factor of the line.

    4.3.1 Analysis of an open-circuit line fed from ideal source

    Let 2 is the time taken for a wave to travel from one end of the line to the other end of the

    line (i.e. single transit time) and kthe corresponding attenuation factor.

    Consider a step voltage wave of amplitude unity starting from the generator end at time t =0. Along the line the wave is attenuated and a wave of amplitude kreaches the open end attime 2. At the open end, this wave is reflected without a loss of magnitude or a change ofsign. The wave is again attenuated and at time 2 reaches the generator end with amplitude

    k2. In order to keep the generator voltage unchanged, the surge is reflected with a change

    of sign (-k2), and after a time 32 reaches the open end being attenuated to -k

    3. It is then

    reflected without a change of sign and reaches the generator end with amplitude -k4

    and

    reflected with amplitude +k4. The whole process is now repeated for the wave of amplitude

    k4.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    36/46

    DEPARTMENT OF EEE - SVECW Page 35

    35

    UNIT-V

    Various Factors Governing thePerformance of Transmission line

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    37/46

    DEPARTMENT OF EEE - SVECW Page 36

    36

    SKIN EFFECT

    The phenomena arising due to unequal distribution of current over the entire cross section of

    the conductor being used for long distance power transmission is referred as the skin effect

    in transmission lines. Such a phenomena does not have much role to play in case of a very

    short line, but with increase in the effective length of the conductors, skin effect increasesconsiderably. So the modifications in line calculation needs to be done accordingly.

    The distribution of current over the entire cross section of the conductor is quite uniform in

    case of a dc system. But what we are using in the present era of power system engineering is

    predominantly an alternating current system, where the current tends to flow with higher

    density through the surface of the conductors (i.e skin of the conductor), leaving the core

    deprived of necessary number of electrons. In fact there even arises a condition when

    absolutely no current flows through the core, and concentrating the entire amount on the

    surface region, thus resulting in an increase in the effective resistance of the conductor. This

    particular trend of an ac transmission system to take the surface path for the flow of current

    depriving the core is referred to as the skin effect in transmission lines

    Why skin effect occurs in transmission lines ?

    Having understood the phenomena of skin effect let us now see why this arises in case of an

    a.c. system. To have a clear understanding of that look into the cross sectional view of theconductor during the flow of alternating current given in the diagram below.

    Let us initially consider the solid conductor to be split up into a number of annular filaments

    spaced infinitely small distance apart, such that each filament carries an infinitely small

    fraction of the total current.

    Like if the total current = I

    Lets consider the conductor to be split up into n filament carrying current i such that I = n i .

    Now during the flow of an alternating current, the current carrying filaments lying on the core

    has a flux linkage with the entire conductor cross section including the filaments of the

    surface as well as those in the core. Whereas the flux set up by the outer filaments is

    restricted only to the surfaceitself and is unable to link with the inner filaments.Thus the flux

    linkage of the conductor increases as we move closer towards the core and at the same rate

    increases the inductance as it has a direct proportionality relationship with flux linkage. Thisresults in a larger inductive reactance being induced into the core as compared to the outer

    sections of the conductor. The high value of reactance in the inner section results in the

    current being distributed in an un uniform manner and forcing the bulk of the current to flow

    through the outer surface or skin giving rise to the phenomena called skin effect in

    transmission lines.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    38/46

    DEPARTMENT OF EEE - SVECW Page 37

    37

    Factors affecting skin effect in transmission lines.

    The skin effect in an ac system depends on a number of factors like:-

    1) Shape of conductor.

    2) Type of material.

    3) Diameter of the conductors.

    4) Operational frequency.

    FERRANTI EFFECT

    In general practice we know, that for all electrical systems current flows from the region of

    higher potential to the region of lower potential, to compensate for the potential difference

    that exists in the system. In all practical cases the sending end voltage is higher than the

    receiving end, so current flows from the source or the supply end to the load. But Sir S.Z.

    Ferranti, in the year 1890, came up with an astonishing theory about medium or long distance

    transmission lines suggesting that in case of light loading or no load operation of transmission

    system, the receiving end voltage often increases beyond the sending end voltage, leading to

    a phenomena known as Ferranti effect in power system.

    Why Ferranti effect occurs in a transmission line?

    A long transmission line can be considered to composed a considerably high amount of

    capacitance and inductance distributed across the entire length of the line. Ferranti Effect

    occurs when current drawn by the distributed capacitance of the line itself is greater than the

    current associated with the load at the receiving end of the line( during light or no load). This

    capacitor charging current leads to voltage drop across the line inductance of the transmission

    system which is in phase with the sending end voltages. This voltage drop keeps on

    increasing additively as we move towards the load end of the line and subsequently the

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    39/46

    DEPARTMENT OF EEE - SVECW Page 38

    38

    receiving end voltage tends to get larger than applied voltage leading to the phenomena called

    Ferranti effect in power system. It is illustrated with the help of a phasor diagram below.

    Thus both the capacitance and inductance effect of transmission line are equally responsible

    for this particular phenomena to occur, and hence Ferranti effect is negligible in case of a

    short transmission lines as the inductance of such a line is practically considered to benearing zero. In general for a 300 Km line operating at a frequency of 50 Hz, the no load

    receiving end voltage has been found to be 5% higher than the sending end voltage.

    Now for analysis of Ferranti effect let us consider the phasor diagrame shown above.

    Here Vris considered to be the reference phasor, represented by OA.

    Thus Vr= Vr(1 + j0)

    Capacitance current, Ic= jCVr

    Now sending end voltage Vs = Vr+ resistive drop + reactive drop.

    = Vr+ IcR + jIcX

    = Vr+ Ic (R + jX)

    = Vr+jcVr(R + j L) [since X = L]

    Now Vs = Vr-2cLVr+ j cRVr

    This is represented by the phasor OC.

    Now in case of a long transmission line, it has been practically observed that the line

    resistance is negligibly small compared to the line reactance, hence we can assume the length

    of the phasor Ic R = 0, we can consider the rise in the voltage is only due to OAOC =reactive drop in the line.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    40/46

    DEPARTMENT OF EEE - SVECW Page 39

    39

    Now if we consider c0 and L0 are the values of capacitance and inductance per km of the

    transmission line, where l is the length of the line.

    Thus capacitive reactance Xc= 1/( l c0)

    Since, in case of a long transmission line the capacitance is distributed throughout its length,the average current flowing is,

    Ic =1/2 Vr/Xc =

    1/2 Vr l c0

    Now the inductive reactance of the line = L0 l

    Thus the rise in voltage due to line inductance is given by,

    IcX =1/2Vr l c0X L0 l

    Voltage rise = 1/2 Vr2 l 2 c0L0

    From the above equation it is absolutely evident, that the rise in voltage at the receiving end

    is directly proportional to the square of the line length, and hence in case of a long

    transmission line it keeps increasing with length and even goes beyond the applied sending

    end voltage at times, leading to the phenomena called Ferranti effect in power system.

    CORONA

    Electric-power transmission practically deals in the bulk transfer of electrical energy, from

    generating stations situated many kilometers away from the main consumption centers or the

    cities. For this reason the long distance transmission cables are of utmost necessity for

    effective power transfer, which in-evidently results in huge losses across the system.

    Minimizing those has been a major challenge for power engineers of late and to do that one

    should have a clear understanding of the type and nature of losses. One of them being the

    corona effect in power system, which has a predominant role in reducing the efficiency of

    EHV(extra high voltage lines) which we are going to concentrate on, in this article.

    What is corona effect in power system and why it occurs?

    For corona effect to occur effectively, two factors here are of prime importance as mentioned

    below:-

    1) Alternating potential difference must be supplied across the line.

    2) The spacing of the conductors, must be large enough compared to the line diameter.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    41/46

    DEPARTMENT OF EEE - SVECW Page 40

    40

    Corona Effect in Transmission Line

    When an alternating current is made to flow across two conductors of the transmission line

    whose spacing is large compared to their diameters, then air surrounding the conductors

    (composed of ions) is subjected to di-electric stress. At low values of supply end voltage,

    nothing really occurs as the stress is too less to ionize the air outside. But when the potentialdifference is made to increase beyond some threshold value of around 30 kV known as the

    critical disruptive voltage, then the field strength increases and then the air surrounding it

    experiences stress high enough to be dissociated into ions making the atmosphere conducting.

    This results in electric discharge around the conductors due to the flow of these ions, givingrise to a faint luminescent glow, along with the hissing sound accompanied by the liberation

    of ozone, which is readily identified due to its characteristic odor. This phenomena of

    electrical discharge occurring in transmission line for high values of voltage is known as the

    corona effect in power system. If the voltage across the lines is still increased the glow

    becomes more and more intense along with hissing noise, inducing very high power loss into

    the system which must be accounted for.

    Factors affecting corona effect in power system.

    As mentioned earlier, the line voltage of the conductor is the main determining factor for

    corona in transmission lines, at low values of voltage (lesser than critical disruptive voltage)

    the stress on the air is too less to dissociate them, and hence no electrical discharge occurs.

    Since with increasing voltage corona effect in a transmission line occurs due to the ionization

    of atmospheric air surrounding the cables, it is mainly affected by the conditions of the cable

    as well as the physical state of the atmosphere. Let us look into these criterion now with

    greater details :-

    Atmospheric conditions for corona in transmission lines.

    It has been physically proven that the voltage gradient for di-electric breakdown of air isdirectly proportional to the density of air. Hence in a stormy day, due to continuous air flow

    the number of ions present surrounding the conductor is far more than normal, and hence its

    more likely to have electrical discharge in transmission lines on such a day, compared to a

    day with fairly clear weather. The system has to designed taking those extreme situations into

    consideration.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    42/46

    DEPARTMENT OF EEE - SVECW Page 41

    41

    Condition of cables for corona in transmission line

    This particular phenomena depends highly on the conductors and its physical condition. It has

    an inverse proportionality relationship with the diameter of the conductors. i.e. with the

    increase in diameter, the effect of corona in power system reduces considerably.

    Also the presence of dirt or roughness of the conductor reduces the critical breakdown

    voltage, making the conductors more prone to corona losses. Hence in most cities and

    industrial areas having high pollution, this factor is of reasonable importance to counter the ill

    effects it has on the system.

    Spacing between conductors.

    As already mentioned, for corona to occur effectively the spacing between the lines should be

    much higher compared to its diameter, but if the length is increased beyond a certain limit,

    the di-electric stress on the air reduces and consequently the effect of corona reduces as well.

    If the spacing is made too large then corona for that region of the transmission line might not

    occur at all.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    43/46

    DEPARTMENT OF EEE - SVECW Page 42

    42

    UNIT-VI

    OVERHEAD LINE INSULATORS

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    44/46

    DEPARTMENT OF EEE - SVECW Page 43

    43

    There are mainly three types of insulator used as overhead insulator likewise

    1. Pin Insulator

    2. Suspension Insulator

    3. Strain Insulator

    In addition to that there are other two types of electrical insulator available mainly for lowvoltage application, e.i. Stay Insulator and Shackle Insulator.

    Pin Insulator

    Pin Insulator is earliest developed overhead insulator, but still popularly used in power

    network up to 33KV system. Pin type insulator can be one part, two parts or three parts type,

    depending upon application voltage. In 11KV system we generally use one part type insulator

    where whole pin insulator is one piece of properly shaped porcelain or glass. As the leakage

    path of insulator is through its surface, it is desirable to increase the vertical length of the

    insulator surface area for lengthening leakage path. In order to obtain lengthy leakage path,

    one, tow or more rain sheds or petticoats are provided on the insulator body. In addition tothat rain shed or petticoats on an insulator serve another purpose. These rain sheds or

    petticoats are so designed, that during raining the outer surface of the rain shed becomes wet

    but the inner surface remains dry and non-conductive. So there will be discontinuations of

    conducting path through the wet pin insulator surface.

    In higher voltage like 33KV and 66KV manufacturing of one part porcelain pin insulator

    becomes difficult. Because in higher voltage, the thickness of the insulator become more and

    a quite thick single piece porcelain insulator can not manufactured practically. In this case we

    use multiple part pin insulator, where a number of properly designed porcelain shells are

    fixed together by Portland cement to form one complete insulator unit. For 33KV tow parts

    and for 66KV three parts pin insulator are generally used.

    Designing consideration of Electrical Insulator

    The live conductor attached to the top of the pin insulator is at a potential and bottom of theinsulator fixed to supporting structure of earth potential. The insulator has to withstand the

    potential stresses between conductor and earth. The shortest distance between conductor and

    earth, surrounding the insulator body, along which electrical discharge may take place

    through air, is known as flash over distance.

    1. When insulator is wet, its outer surface becomes almost conducting. Hence the flash overdistance of insulator is decreased. The design of an electrical insulator should be such that the

    decrease of flash over distance is minimum when the insulator is wet. That is why the upper

    most petticoat of a pin insulator has umbrella type designed so that it can protect, the rest

    lower part of the insulator from rain. The upper surface of top most petticoat is inclined as

    less as possible to maintain maximum flash over voltage during raining.

    2. To keep the inner side of the insulator dry, the rain sheds are made in order that these rain

    sheds should not disturb the voltage distribution they are so designed that their subsurface at

    right angle to the electromagnetic lines of force.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    45/46

    DEPARTMENT OF EEE - SVECW Page 44

    44

    Suspension Insulator

    In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator because size,

    weight of the insulator become more. Handling and replacing bigger size single unit insulator

    are quite difficult task. For overcoming these difficulties, suspension insulator was

    developed.

    In suspension insulator numbers of insulators are connected in series to form a string and

    the line conductor is carried by the bottom most insulator. Each insulator of a suspension

    string is called disc insulator because of their disc like shape.

    Advantages of Suspension Insulator

    1. Each suspension disc is designed for normal voltage rating 11KV(Higher voltage rating

    15KV), so by using different numbers of discs, a suspension string can be made suitable for

    any voltage level.

    2. If any one of the disc insulators in a suspension string is damaged, it can be replaced much

    easily.

    3. Mechanical stresses on the suspension insulator is less since the line hanged on a flexible

    suspension string.

    4. As the current carrying conductors are suspended from supporting structure by suspension

    string, the height of the conductor position is always less than the total height of the

    supporting structure. Therefore, the conductors may be safe from lightening.

  • 7/27/2019 Docs-EEEPSLNotes2013.pdf

    46/46

    45

    Disadvantages of Suspension Insulator

    1. Suspension insulator string costlier than pin and post type insulator.

    2. Suspension string requires more height of supporting structure than that for pin or postinsulator to maintain same ground clearance of current conductor.

    3. The amplitude of free swing of conductors is larger in suspension insulator system, hence,

    more spacing between conductors should be provided.

    Strain insulator

    When suspension string is used to sustain extraordinary tensile load of conductor it is referred

    as string insulator. When there is a dead end or there is a sharp corner in transmission line,

    the line has to sustain a great tensile load of conductor or strain. A strain insulator must

    have considerable mechanical strength as well as the necessary electrical insulating

    properties.

    Shackle Insulator or Spool Insulator

    The shackle insulator orspool insulator is usually used in low voltage distribution network.

    It can be used both in horizontal and vertical position. The use of such insulator has

    decreased recently after increasing the using of underground cable for distribution purpose.

    The tapered hole of the spool insulator distributes the load more evenly and minimizes the

    ibilit f b k h h il l d d Th d t i th f h kl