4
Domestic Hot Water Heaters and Boilers FTIIC-12R

Domestic Hot Water Heaters and Boilers - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Futera II/Fut… · Hot Water Supply and Hydronic Heating Boilers Futera

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Domestic Hot Water Heaters and Boilers - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Futera II/Fut… · Hot Water Supply and Hydronic Heating Boilers Futera

Domestic Hot Water Heaters and Boilers

FTIIC-12R

Page 2: Domestic Hot Water Heaters and Boilers - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Futera II/Fut… · Hot Water Supply and Hydronic Heating Boilers Futera

Features and Benefits

Low NOx, High Efficiency, Hot Water Supply and Hydronic Heating Boilers

Futera II Series hot water supply boilers provide dependable

performance with 85% near condensing efficiency, with industry-

leading NOx levels of less than 10 ppm.

Quality components include a rugged heat exchanger that prevents

rust and corrosion for the life of the heater. Finned tubes are industrial

grade copper with fins and tubewalls formed as one, providing

optimum heat transfer. Each tube is rolled into either all-bronze

headers – standard on all Futera II water heaters

or cast iron headers – standard on all Futera II

boilers. The tubes are individually field replaceable.

The heat exchanger is superior in design, durability and

serviceability – each is hydrostatically tested, approved

and stamped for 160 psi ASME operation.

Futera II Series boilers and water heaters are also available with corrosion-resistant, brushed stainless steel jacket. Ideal for outdoor or indoor installation in harsh environments such as coastal areas and processing applications requiring wash down.

Standard Features

• Flame Safeguard Control

• Up to 85% Efficient

• Bronze Headers – Water Heaters

• Cast Iron Headers – Boilers

• Finned Copper Tube Heat Exchanger – Four-Pass

• Gasketless Heat Exchanger Assembly

• Stainless Steel Combustion Chamber

• 2-Stage Digital Operator

• Special Alloy Burner

• Less Than 10 ppm NOx

• Compact, Low Maintenance Design

• Venting Flexibility

• CSA Design Certified & Listed (Formally) AGA/CGA

• Proven Pilot (UV Flame Detection)

• Factory Installed ASME Relief Valve

• Outlet Thermometer

• High Limit Control with Manual Reset

• Factory Mounted and Wired Flow Switch

• Low Air Pressure Switch

• Easy Access To All Components

• 5-Year Heat Exchanger Warranty on Water Heaters

• 10-Year Heat Exchanger Warranty on Boilers

• Heat Exchanger Drain

• National Board Certified

• Pump Delay Relay

• CSD-1 and FM Compliant Gas Train

Optional Equipment

• Cupro-Nickel Finned Tubes

• Outdoor Installation

• Thru-Wall Venting

• Direct Venting

• Stainless Steel Jacket

• Barometric Damper

• On-Off Firing

• Freeze Protection Package

Compact, low maintenance design and venting flexibility permit easy

installation and service, making the Futera II the perfect choice for

virtually any hot water supply application.

++

*Pool heater applications available in non U.S. markets.

2

Page 3: Domestic Hot Water Heaters and Boilers - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Futera II/Fut… · Hot Water Supply and Hydronic Heating Boilers Futera

Advanced Diagnostic SystemThe Futera II features an easy-to-read LCD display that provides

clear indication of inlet water temperature or setpoint in Fahrenheit

or Celsius. The display also provides information for setting

temperature control parameters. Advanced troubleshooting and

self-diagnostic control provides a step-by-step cycle of operation.

Each step is automatically tested and indicated, allowing for

simplified and less costly troubleshooting.

Proven Pilot Ignition SystemThe Futera II Series uses a proven pilot with interrupted spark

ignition and UV flame detection. The UV detector and igniter

assembly provide highly reliable ignition and easy service.

This important design feature provides long-life reliability. An

observation port allows easy inspection of the flame at the top of

the boiler.

The Turbo Pilot®: Reliability At Its BestFutera’s independent “Turbo-Pilot” system with UV detection is

far more durable and reliable than any competitive ignition system

available today.

At 8,000 btu’s the “Turbo-Pilot” provides

a sure-fire source for burner ignition.

Smart Service DesignA Honeywell RM Series Flame Safeguard, limit controls and terminal

strips are neatly arranged and easily accessible in the front-facing panel.

RBI Temperature ControllerSP Setpoint or Target

Temperature:

The Setpoint is the inlet water

temperature that the operating

control will try to match by staging

the boiler between ‘Off’, ‘Stage 1’ and ‘Stage 2.’

D1 Boiler Differential:The boiler differential is centered around the setpoint so that when the sensor reads 1/2 of D1 below the setpoint, Stage 1 will be energized. When the sensor reads a temperature 1/2 of D1 above the setpoint, stage will turn off.

D2 Interstage Differential:The Interstage Differential is the difference in temperature between Stage 1 being called on, and Stage 2 being called on.

Air Intake Fan

Brass WaterConnections

Vent

All BronzeHeaders(Water Heaters)

Drain Valve

Viewport

Gas Orifice

Pre-Mixing Gas/Air Box

Flame Safeguard Control

Special AlloyBurner

Stainless Steel Combustion Chamber

Finned Copper Tube Heat Exchanger

Heat Exchanger “V” Baffles

Stainless Steel Base

OPERATING CONTROL

ON

OFF

BOILERDIAGNOSTICS

HIGHLIMIT

LOWWATER

LOW AIRFLOW

FLAME FAILURE

CALL FORLOW FIRE

TRIALIGNITION

MAINBURNER

IGNITIONSTATUS

K1 K2CALL FORHIGH FIRE

RBI

32

Page 4: Domestic Hot Water Heaters and Boilers - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Futera II/Fut… · Hot Water Supply and Hydronic Heating Boilers Futera

"C"

"D"

"G"WATER INLET/OUTLET

"A"

"J" "B"

"I"(ASMEFLANGE)

AIR INTAKE

"H" GAS

"F"THRU WALL VENT

"E"STANDARDEXHAUST

3/4 in[19 mm]DRAIN

SIDE VIEW FRONT VIEW BACK VIEW

260 North Elm Street, Westfield, MA 01085Tel. (413) 564-5515 Fax (413) 568-96137555 Tranmere Drive, Mississauga, Ontario L5S 1L4Tel. (905) 670-5888 Fax (905) 670-5782www.rbiwaterheaters.com

Note: Certified South Coast Air Quality Management District (SCAQMD) Protocol Rule 1146.2; Ventura County APCD Rule 74.11.1* Ratings reflect boilers only. For boiler efficiency information please visit www.ahridirectory.org

In the interest of product improvement, RBI reserves the right to make changes without notice.

Futera II Series — Dimensions

SizeA B C D E F G H I J

In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. In. In. mm500 43-1/32 1,093 21-9/32 540 37-13/16 960 11-21/32 296 8 203 6 152 26-3/32 663 1 2 22-5/16 567750 49-17/32 1,258 21-9/32 540 44-9/32 1,125 14-21/32 377 10 254 8 203 32-9/16 827 1 2 22-5/16 5671000 56-1/32 1,423 21-9/32 540 50-27/32 1,291 18-5/32 461 10 254 9 229 39-1/16 992 1-1/4 2 22-5/16 5671250 50-11/16 1,287 25-3/16 640 44-13/32 1,128 16-27/32 428 12 305 10 254 31-13/16 808 1-1/4 2-1/2 27-9/32 6931500 55-3/16 1,402 25-3/16 640 48-25/32 1,239 18-29/32 480 12 305 10 254 36-5/16 922 1-1/4 2-1/2 27-9/32 6931750 59-11/16 1,516 25-3/16 640 53-29/32 1,369 20-29/32 531 14 356 12 305 40-13/16 1,037 1-1/2 2-1/2 27-9/32 6931950 64-3/16 1,631 25-3/16 640 58-17/32 1,487 23-21/32 601 14 356 12 305 45-5/16 1,151 1-1/2 2-1/2 27-9/32 693

Futera II Series Boilers — Temperature Rise/Pressure Drop

Size

20°F 11.1°C 25°F 13.9°C 30°F 16.7°C 35°F 19.4°CFlow Rate Pres Drop Flow Rate Pres Drop Flow Rate Pres Drop Flow Rate Pres Drop Flow Rate Pres Drop Flow Rate Pres Drop Flow Rate Pres Drop Flow Rate Pres Drop

GPM Ft ∆L/s kPa GPM Ft ∆L/s kPa GPM Ft ∆L/s kPa GPM Ft ∆L/s kPa500 42.5 .53 2.7 1.5 34.0 0.35 2.1 1.0 – – – – – – – –750 63.8 1.57 4.0 4.6 51.0 1.04 3.2 3.1 42.5 0.70 2.7 2.2 36.4 0.60 2.3 1.61000 85.0 3.44 5.4 10.1 68.0 2.27 4.3 6.7 56.7 1.60 3.6 4.8 48.6 1.20 3.1 3.61250 106.3 2.11 6.7 6.2 85.0 1.40 5.4 4.1 70.8 1.00 4.5 2.9 60.7 0.70 3.8 2.21500 127.5 3.57 8.1 10.5 102.0 2.36 6.4 7.0 85.0 1.70 5.4 5.0 72.9 1.30 4.6 3.71750 – – – – 119.0 3.67 7.5 10.8 99.2 2.60 6.3 7.7 85.0 2.00 5.4 5.81950 – – – – 132.6 5.14 8.4 15.1 110.5 3.70 7.0 10.8 94.7 2.80 6.0 8.1

Futera II Series Water Heaters — Hourly Recovery Capacity ∆T (GPH & LPH)**Size 40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C500 1,224 4,629 816 3,086 612 2,314 490 1,851 408 1,543 350 1,322750 1,877 7,096 1,252 4,731 939 3,548 751 2,838 626 2,365 536 2,0271000 2,500 9,450 1,667 6,300 1,250 4,725 1,000 3,780 833 3,150 714 2,7001250 3,121 11,798 2,081 7,866 1,561 5,899 1,248 4,719 1,040 3,933 892 3,3711500 3,741 14,141 2,494 9,427 1,870 7,070 1,496 5,656 1,247 4,714 1,069 4,0401750 4,359 16,478 2,906 10,985 2,180 8,239 1,744 6,591 1,453 5,493 1,245 4,7081950 4,976 18,809 3,317 12,539 2,488 9,405 1,990 7,524 1,659 6,270 1,422 5,374

Futera II Series — Ratings*

SizeInput Boiler Output AMP

DrawShipping Weight

MBH kW MBH kW lbs. kgs.500 500 147 425 125 5.9 535 243750 750 220 638 187 5.9 578 2621000 1,000 293 850 249 5.9 690 3131250 1,250 366 1,062 311 8.7 775 3521500 1,500 440 1,275 374 8.7 835 3791750 1,750 513 1,488 436 10.7 900 4081950 1,950 571 1,658 486 10.7 960 435

ModelsFB=BoilerFW=Water Heater