DRAFT PERMIT   

FOR  

SIEMENS INDUSTRY, INC.   

MND981098478   

FOR A  

HAZARDOUS WASTE STORAGE AND TREATMENT FACILITY  

LOCATED AT  

2430 ROSE PLACE  

ROSEVILLE, MINNESOTA   

REISSUED:   (month, day, year)           

MINNESOTA POLLUTION CONTROL AGENCY 520 LAFAYETTE ROAD NORTH 

ST. PAUL, MINNESOTA  55155‐4194 

Page 2: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

TABLE OF CONTENTS  

  Page 

PART I.  DESCRIPTION OF FACILITY ................................................................................................ 1 A.  REGULATED/PERMITTED UNITS .......................................................................................... 1 

PART II.  AUTHORIZED HAZARDOUS WASTE MANAGEMENT ...................................................... 3 A.  SPECIFIC HAZARDOUS WASTES AUTHORIZED TO BE MANAGED ....................................... 3 B.  STORAGE OF HAZARDOUS WASTE IN CONTAINERS ........................................................... 3 C.  TREATMENT AND STORAGE OF HAZARDOUS WASTE IN TANKS ........................................ 4 D.  TREATMENT OF HAZARDOUS WASTE IN MISCELLANEOUS UNITS ..................................... 6 E.  COMMENCEMENT OF NEW STORAGE AND TREATMENT ACTIVITIES ................................ 6 

PART III.  OPERATING CONDITIONS ............................................................................................... 9 A.  OPERATION AND MAINTENANCE ........................................................................................ 9 B.  NOTICE TO GENERATORS ................................................................................................... 13 C.  RECEIPT OF UNAUTHORIZED WASTES ............................................................................... 13 D.  GENERAL WASTE ANALYSIS ............................................................................................... 13 E.  PERSONNEL TRAINING ....................................................................................................... 14 F.  HANDLING MANIFESTS ...................................................................................................... 14 G.  MANIFEST DISCREPANCIES ................................................................................................ 14 H.  MONITORING ..................................................................................................................... 14 I.  STORAGE OF IGNITABLE, REACTIVE, AND INCOMPATIBLE WASTES ................................ 15 J.  INSPECTIONS ...................................................................................................................... 16 K.  SECURITY ............................................................................................................................ 16 L.  LIGHTING ............................................................................................................................ 17 M.  FINANCIAL ASSURANCE FOR CLOSURE .............................................................................. 17 N.  LIABILITY COVERAGE .......................................................................................................... 17 O.  DECONTAMINATION OF UNITS USED TO MANAGE LISTED HAZARDOUS WASTE ........... 17 P.  RECEIPT OF ORGANIC WASTES .......................................................................................... 19 Q.  WASTE PROCESSING .......................................................................................................... 19 

PART IV.  EMERGENCY PROCEDURES .......................................................................................... 20 A.  IMPLEMENTATION OF CONTINGENCY PLAN ..................................................................... 20 B.  AMENDMENT OF CONTINGENCY PLAN ............................................................................. 20 C.  PREPAREDNESS AND PREVENTION ................................................................................... 20 D.  EMERGENCY COORDINATOR ............................................................................................. 21 E.  RESPONSE TO SPILLS/LEAKS/RELEASES FROM REGULATED UNITS .................................. 21 F.  RESPONSE TO OTHER SPILLS/LEAKS/RELEASES FROM NON‐REGULATED UNITS ............ 23 G.  NOTIFICATION TO MPCA REGARDING SPILLS/LEAKS/RELEASES OF HAZARDOUS  

WASTE ................................................................................................................................. 24 H.  ADDITIONAL EMERGENCY COORDINATOR DUTIES AND NOTIFICATION TO OTHER 

AGENCIES ............................................................................................................................ 26 

Page 3: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

TABLE OF CONTENTS  

  Page  I.  CONTAINMENT MEASURES ............................................................................................... 27 J.  POST EMERGENCY CLEANUP ............................................................................................. 28 K.  STARTUP OF OPERATIONS ................................................................................................. 28 L.  POST EMERGENCY REPORTING ......................................................................................... 28 M. OPERATING RECORD .......................................................................................................... 28 

PART V.  RECORD KEEPING REQUIREMENTS ............................................................................... 29 A.  PLANS TO BE MAINTAINED AT THE FACILITY .................................................................... 29 B.  OPERATING RECORD .......................................................................................................... 29 C.  PERSONNEL RECORDS ........................................................................................................ 30 D.  INSPECTION RECORDS ........................................................................................................ 30 E.  MONITORING AND TESTING RECORDS ............................................................................. 31 F.  RETENTION AND DISPOSITION OF RECORDS .................................................................... 31 

PART VI.  REPORTING REQUIREMENTS ....................................................................................... 32 A.  REPORTING NONCOMPLIANCE .......................................................................................... 32 B.  REPORTING PLANNED CHANGES ....................................................................................... 32 C.  ANNUAL REPORTING REQUIREMENTS .............................................................................. 32 D.  CERTIFICATION AND SIGNATORY REQUIREMENTS ........................................................... 33 E.  SUBMITTAL OF WRITTEN REPORTS ................................................................................... 33 

PART VII.  CLOSURE ...................................................................................................................... 34 A.  NOTIFICATION OF CLOSURE ............................................................................................... 34 B.  CLOSURE PLAN ................................................................................................................... 34 C.  TIME ALLOWED FOR CLOSURE ........................................................................................... 34 D.  CERTIFICATION OF CLOSURE .............................................................................................. 34 

PART VIII.  CORRECTIVE ACTION FOR SOLID WASTE MANAGEMENT UNITS ............................. 35 

PART IX.  GENERAL CONDITIONS ................................................................................................. 36 A.  NO RELEASE FROM LIABILITY ............................................................................................. 36 B.  THIRD PARTY LIABILITY ...................................................................................................... 36 C.  FUTURE RULES .................................................................................................................... 36 D.  PROPERTY RIGHTS .............................................................................................................. 36 E.  OBLIGATION TO ENFORCE ................................................................................................. 36 F.  LIABILITY/RESPONSIBILITY ................................................................................................. 36 G.  DEFENSE UNDER OTHER STATUTES AND RULES ............................................................... 36 H.  MINIMUM STANDARDS ..................................................................................................... 37 I.  DUTY TO COMPLY ............................................................................................................... 37 J.  WASTE MINIMIZATION ...................................................................................................... 37

Page 4: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

 

TABLE OF CONTENTS  

  Page  K.  FALSE STATEMENTS ........................................................................................................... 37 L.  DUTY TO PROVIDE INFORMATION .................................................................................... 37 M.  INSPECTION AND ENTRY .................................................................................................... 37 N.  DUTY TO MITIGATE ............................................................................................................ 38 O.  BANKRUPTCY ...................................................................................................................... 38 P.  MODIFICATION, REVOCATION, AND REISSUANCE OF THIS PERMIT ................................ 38 Q.  OPERATION DURING REISSUANCE PERIOD ....................................................................... 38 R.  CONTINUATION OF EXPIRED PERMIT ................................................................................ 39 S.  TRANSFER OF PERMITS ...................................................................................................... 39 T.  SEVERABILITY ..................................................................................................................... 39 U.  EMERGENCY PERMITS ........................................................................................................ 39 V.  AUTHORIZED SIGNATURES ................................................................................................ 39 

PART X.  REVIEW OF SUBMITTALS AND EXTENSION OF SCHEDULES ......................................... 40 A.  REVIEW OF SUBMITTALS .................................................................................................... 40 B.  EXTENSION OF SCHEDULES ................................................................................................ 41 

PART XI.  LAND DISPOSAL REQUIREMENTS ................................................................................ 42 A.  GENERAL CONDITIONS ....................................................................................................... 42 

 APPENDICES   APPENDIX I – FACILITY MAP 

APPENDIX II – WASTE CODES APPENDIX III – EXPANSION DRAWING  

Page 5: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

 STATE OF MINNESOTA 

 POLLUTION CONTROL AGENCY 

 HAZARDOUS WASTE STORAGE AND TREATMENT FACILITY PERMIT 

 FOR  

SIEMENS INDUSTRY, INC.  

EPA ID NO. MND981098478   

In accordance with the provisions of Minn. Stat. chs. 115 and 116, Minn. R. 7001.0010 to 7001.0730, and Minn. R. 7045.0020 to 7045.1390, a Hazardous Waste Storage and Treatment Facility Permit (Permit) is hereby reissued to Siemens Industry, Inc. for a facility located at 2430 Rose Place, Roseville, Minnesota (Facility).   This Permit comprises the Resource Conservation and Recovery Act (RCRA) Permit which has been prepared based upon the information provided by Siemens Industry, Inc.’s most recent Permit Application (Part A and Part B) including revisions received through August 2012.  The Permit Application is referenced throughout this Permit and as such, is an integral and enforceable part of this Permit.  Siemens Industry, Inc. is the owner and operator of the Facility and is referred to as the Permittee hereinafter.  Specific operating, emergency, record keeping, reporting, and general conditions apply to the Facility which contains all permitted regulated units.  The Facility location is at latitude 93o, 12’; longitude 45o, 1’; Section 8, Township 29 North,  Range 23 West.  Hazardous waste is generated on site and off site; hence the Facility is considered an off‐site Facility.  This Permit authorizes and requires the Permittee to conduct the following hazardous waste management activities:     1.  Treat hazardous waste in tanks.   2.  Store hazardous waste in tanks.   3.  Store hazardous waste in containers.   4.  Treat hazardous waste in miscellaneous units.  The Permittee must at all times conduct its hazardous waste management activities in accordance with the terms and conditions of this Permit and any other requirements imposed by law or Minnesota Rules. 

Page 6: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

This Permit shall become effective on the date of reissuance by the supervisor of the Minnesota Pollution Control Agency's (MPCA) Land Permits Unit, Land and Air Compliance Section of the Industrial Division.  The original Permit was issued to U.S. Filter Recovery Services, Inc. on December 31, 1986.  This site later changed its name to U.S. Filter/Ionpure, Inc. and then became Siemens Water Technologies Corp in June 2006 and Siemens Industry, Inc. in March 2011.  This Permit is effective until five years from date of reissuance or until terminated, revoked, or modified by the MPCA, whichever comes first.  To obtain a future reissued Permit, the Permittee shall request that the MPCA review and reissue the Permit.  In accordance with Minn. R. 7001.0040, subp. 3, an application for reissuance of this Permit must be submitted to the MPCA no later than 180 calendar days prior to the expiration date of this Permit.    DATE OF REISSUANCE:         

Ainars Z. Silis Supervisor, Land Permits Unit Land & Air Compliance Section Industrial Division

Page 7: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

1 of 43 EPA ID MND981098478 

Revised 2/13 

 

PART I.  DESCRIPTION OF FACILITY 

 

A.  REGULATED/PERMITTED UNITS 

 Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota.  The Facility is west of Interstate 35W a few blocks north of the north end of State Highway 280 in the municipality of Roseville, Ramsey County, Minnesota (see Appendix I for the location of the Facility).  The Facility is located on Lots 1 and 2, Block 1, Rose Place Industrial Addition, PID082923210008‐5, according to the plat recorded with Ramsey County.  The Facility comprises approximately eight (8) acres of which about 4.5 acres are currently developed.  The Facility boundaries are shown in Appendix I of this Permit.  The Facility is a commercial hazardous waste facility that receives hazardous wastes from both foreign and domestic sources.  Hazardous waste management capabilities at the Facility include the receiving and processing of aqueous liquids, solids and sludges containing heavy metals and cyanides.  Many liquids and sludges are stored and transshipped for treatment and/or disposal.    The Facility receives canisters of spent anion, cation and chelating resins along with a variety of adsorptive medias used to treat wastewaters generated from various industries, including metal finishing and printed circuit fabricating industries.  The resins and media are used to remove various metals (e.g., copper, zinc, chrome, nickel and other mixed metals) and cyanide from the waste streams associated with these industries.  The canisters are transported back to the Facility where the spent resins are regenerated, and then returned to the industries for reuse.  The bulk of the wastes received at the Facility undergo various wastewater treatment procedures, which include:  chromium reduction, cyanide oxidation, electro‐chemical metal recovery, metal precipitation, acid and base neutralization, sludge dewatering/drying, resin regeneration, advanced recovery.  After metal removal, wastewater from these processes is treated further to satisfy discharge limitations through the pretreatment system, prior to discharge to the Metropolitan Council Environmental Services sewer system.  Precipitated metal hydroxides are processed for resale or recovery, if possible.  Other residues are shipped to a permitted facility for ultimate disposal.  The Waste Analysis Plan, Section 3 in the Permit Application, provides a detailed description of each treatment/recovery process at the Facility.  

Page 8: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

2 of 43 EPA ID MND981098478 

Revised 2/13 

Both containerized and bulk wastes may be received at the Facility for transshipment to other permitted hazardous waste treatment and disposal facilities.  Materials included in this category are certain inorganic liquid and solid wastes that the Facility either cannot or does not choose to treat on site for operational or economic reasons or to maximize metal recovery.  Materials in this category are stored on site in order to accumulate suitable quantities for transshipment.  Bulk wastes include sludges, acids, alkalines and cyanides.  The Facility is permitted to manage listed and characteristic hazardous wastes successively in the same hazardous waste management units provided the Permittee follows an established protocol for decontaminating those units.  An established decontamination protocol is used to clean these units to acceptable levels after the units have been used for the management of listed hazardous wastes.  The units can then be used to manage nonlisted hazardous wastes (i.e., characteristic hazardous wastes) and nonhazardous wastes.  The decontamination protocol is described in Part III.O. of this Permit (Section 14.9 of the Permit Application).  The Permittee is authorized (in Part II.B, C, and D) to operate 64 tanks, 14 container storage areas, three (3) sludge dryers, four (4) filter presses, and one (1) sludge treatment cart.  The filter presses, the sludge dryers, and the sludge treatment cart are “miscellaneous units” within the definition in Minn. R. 7045.0020 and are regulated in accordance with Minn. R. 7045.0539.  As described in Part II.B, C, and D, the Permittee is authorized through this Permit for the following capacities:  

Container Storage        93, 630 gallons (1702‐55 gal drums) Tank Storage and Treatment      291,697 gallons Filter Presses          190 cubic feet Sludge Dryers          9 cubic feet/hour Treatment Cart         110 gallons Sludge Roll‐Offs (2 @ 40 cubic yards)  80 cubic yards One‐Yard Totes        18 cubic yards 34 Cubic Foot containers       53 cubic yards 

 

Page 9: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

3 of 43 EPA ID MND981098478 

Revised 2/13 

PART II.  AUTHORIZED HAZARDOUS WASTE MANAGEMENT  

A.  SPECIFIC HAZARDOUS WASTES AUTHORIZED TO BE MANAGED 

 

  1.  The Permittee is hereby authorized to store and treat the hazardous wastes listed in Appendix II of this Permit.  

  2.  The Permittee is also authorized to manage any other hazardous waste not specifically identified in the "Hazardous Waste Description" but falling within the "hazardous waste codes" listed in Appendix II provided that the Permittee submits to the MPCA a written report identifying the hazardous waste and code WITHIN 15 DAYS of generation.  Subsequent reporting for that new hazardous waste stream accepted from the same generator is not required.    

  The Permittee is also authorized to manage any hazardous residue, contaminated soil, water, or debris generated from a spill cleanup response action.  Notification and Reporting requirements in Part IV. of this Permit must be followed.  

  3.  The Permittee shall not accept, store, repackage, or treat any hazardous waste entering the Facility for treatment or bulking that contains an average volatile organic concentration at the point of origination of 500 parts per million by weight (ppmw).  The average volatile organic 

concentration shall be determined using procedures specified in 40 CFR § 264.1083(a).  

B.  STORAGE OF HAZARDOUS WASTE IN CONTAINERS 

 

The Permittee is authorized to store the following types and quantities of hazardous wastes in containers as specified in the following table (“P” locations indicate primary container storage areas and “S” locations indicate secondary container storage areas):  

  

LOCATION 

MAXIMUM STORAGE CAPACITY 

gals, (# drums) 

 WASTE TYPE 

SECONDARY CONTAINMENT CAPACITY 

(gallons) 

P‐1 P‐2 P‐3 P‐4 P‐5 P‐6  

S‐1 S‐2 S‐3 S‐4 S‐5 S‐6 S‐7 S‐8 

4,400  (80) 6,600 (120) 9,295 (169) 24,860 (452) 

80 yd3 17,160 (312) 

 1,760 (32) 1,560 (28) 

12,760 (232) 1,155 (21) 18 yd3 

10,560 (192) 3,520 (64) 53 yd3 

Compatible Alkali Alkali Acid 

Solid Roll‐Off Acid  

Compatible Compatible 

Acid Cyanide Only 

Solid  Acid Acid Solid 

823 910 1,141 10,000 dry 

10,000  

680 10,000 10,000 1,600 dry 

10,000 10,000 dry 

Page 10: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

4 of 43 EPA ID MND981098478 

Revised 2/13 

In addition to drums, drum equivalents may also be stored.  For the purposes of calculating the volume of containers when totes (portable tanks) or ion exchange resin tanks are being stored in the container storage area, the following equivalency table may be used:  

Container Type  Gallons  Drums 

Tote  330  6 

42 ft3 ion exchange tank  315  5.7 

30 ft3 ion exchange tank  225  4.1 

20 ft3 ion exchange tank  150  2.7 

15 ft3 ion exchange tank  110  2.0 

12 ft3 ion exchange tank  90  1.6 

10 ft3 ion exchange tank  75  1.4 

3.5 ft3 ion exchange tank  26  0.5 

1.2 ft3 ion exchange tank  9  0.2 

0.45 ft3 ion exchange tank  3.8  0.06 

Lab Pack  20  ‐‐‐ 

C.  TREATMENT AND STORAGE OF HAZARDOUS WASTE IN TANKS  

The Permittee is authorized to store and treat the following types and quantities of hazardous wastes in tanks as specified in the following table:  Tank No. 

 Tank Name 

Tank Capacity (gallons) 

RCRA Function 

       11‐1T  Waste Hydrochloric Holding  10,000  S02 11‐2T  Waste Hydrochloric Holding  10,000  S02 12‐1T  Waste Misc. Acid Holding  5,000  S02 13‐1T  Waste Misc. Acid Holding  5,000  S02 14‐1T  Waste Chromium Holding  10,000  S02 15‐1T  Waste Cyanide Holding  3,000  S02 16‐1T  Waste Cyanide Holding  3,000  S02 17‐1T  Waste Alkaline Holding  10,000  S02 18‐1T  Waste Alkaline Holding  5,000  S02 19‐1T  Waste Misc. Compatible  Holding  5,000  S02 24‐1T  Waste Electroless Nickel Holding  5,000  S02 25‐1T    Waste Alkaline Compatible Holding  5,000  S02 26‐1T  Waste Alkaline Compatible Holding  5,000  S02 29‐1T  Waste Misc. Acid Holding    3,000  S02 31‐1T    Neutralization Reactor 1  5,000  T01 32‐1T  Neutralization Reactor 2  5,000  T01 33‐1T  Misc. Reactor 1  1,800  T01 34‐1T  Misc. Reactor 2  3,000  T01 35‐1T  Misc. Reactor 3  3,000  T01 36‐1T  Misc. Reactor 4  500  T01 37‐1T  pH Adjust Reactor  500  T01 

Page 11: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

5 of 43 EPA ID MND981098478 

Revised 2/13 

 Tank No. 

 Tank Name 

Tank Capacity (gallons) 

RCRA Function 

       42‐1T  Continuous Chromium Treatment 

Reactor  1,000  T01 

53‐1T  General Sludge Thickener 1  10,000  T01 53‐2T  General Sludge Thickener 2  10,000  T01 54‐1T  General Sludge Thickener 3  2,000  T01 55‐1T  General Sludge Thickener 4  2,000  T01 56‐1T  General Sludge Thickener 5  2,000  T01 59‐1T  Lime Sludge Thickener 1  10,000  T01 59‐2T  Lime Sludge Thickener 2  10,000  T01 61‐1T  Waste Alkaline Holding  10,000  S02 63‐1T  Waste Chromium Holding  10,000  S02 65‐1T  Electroless Nickel Recovery EMR Cell 1  800  T01 68‐1T  Waste Misc. Acid Holding  3,000  S02 70‐1T  Electroless Nickel Recovery EMR Cell 2  800  T01 72‐1T  Waste Misc. Acid Holding  3,000  S02 83‐1T  Cyanide Scrubber Sump  400  T01 84‐1T  Ammonia Scrubber Sump  200  T01 85‐1T  General Fume Scrubber Sump  800  T01 86‐1T  Cinch Scrubber Sump  250           T01 90‐1T  Batch Polish Reactor 3  5,000  T01 90‐2T  Batch Polish Reactor 4  5,000  T01 90‐3T  Batch Polish Reactor 5  5,200  T01 90‐4T  Batch Polish Reactor 6  8,000           T01 91‐3T  Dissolution Tank  980  T01 96‐1T  Waste Alkaline Compatible Holding  5,000           S02 96‐2T  Waste Alkaline Compatible Holding  5,000  S02 99‐1T  EMR Cell Feed Tank  5,000  S02 T‐0203   Caustic Regenerant Reclaim 1  565  S02 T‐0205  Caustic Regenerant Reclaim 2  565  S02 T‐0503  Sodium Chloride Regenerant Reclaim   3,000  S02 T‐0504  Hydrochloric Acid Regenerant Reclaim  470  S02 T‐0601   Spent Resin Hopper  880  S02 T‐0602   Spent Resin Hopper  880  S02 T‐0603   Spent Resin Hopper  880  S02 T‐0604  Spent Resin Hopper  1,365  S02 T‐0605   Spent Resin Hopper  880  S02 T‐0606  Spent Resin Hopper  880  S02 T‐0607  Spent Resin Hopper  1500  S02 T‐0608  Spent Resin Hopper  1500  S02 

 

Page 12: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

6 of 43 EPA ID MND981098478 

Revised 2/13 

  Tank No. 

 Tank Name 

Tank Capacity (gallons) 

RCRA Function 

       T‐1300   Regeneration Vessel  600  T01 T‐1400   Regeneration Vessel  680  T01 T‐1500   Waste Cyanide Resin Holding  190  T01 T‐1600   Waste Cyanide Holding  1,860  T01 T‐1700   Regeneration Vessel  610  T01 T‐1800   Regeneration Vessel  851  T01 

D.  TREATMENT OF HAZARDOUS WASTE IN MISCELLANEOUS UNITS 

 The Permittee is authorized to treat the following hazardous wastes in miscellaneous units as specified in the following table:  Unit No.  Unit Name  Unit Capacity  RCRA Function        M‐1  Sludge Treatment Cart  110 gallons  T04 M‐10    Filter Press  10 cu ft  T04 M‐120    Filter Press   20 cu ft  T04 M‐360    Sludge Dryer A   3 cu ft/hr  T04 M‐361    Sludge Dryer B   3 cu ft/hr  T04 M‐362    Sludge Dryer C   3 cu ft/hr  T04 M‐801    Filter Press   80 cu ft  T04 M‐802    Filter Press   80 cu ft  T04 

 The wastes managed in each unit are listed in the Waste Codes provided in Appendix II.  

E.  COMMENCEMENT OF NEW STORAGE AND TREATMENT ACTIVITIES 

 

In accordance with Minn. R. 7001.0720, subp. 2. item C., the Permittee shall not commence treatment or storage of hazardous waste in any of the new tanks, storage areas, or miscellaneous units (collectively “units” or “hazardous waste management units”) listed below until both of the following have occurred:  

  1.  The Permittee has submitted to the MPCA certification as follows:  

a.  The Permittee shall hire an independent qualified installation inspector, as defined in Minn.R. 7045.0020, subp. 45b, for installation of tank systems and an independent qualified registered professional engineer for installation of storage areas and miscellaneous units to supervise construction of the new units. 

Page 13: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

7 of 43 EPA ID MND981098478 

Revised 2/13 

b.  Upon completion of construction of the new units, the Permittee shall obtain from the independent qualified registered professional engineer and the installation inspector, certification that the units were installed in accordance with the plans and specifications and the terms and conditions of this Permit. 

 c.  The Permittee shall keep a copy of this certification at the Facility.  d.  The Permittee shall submit the certification to the MPCA WITHIN 30 DAYS after 

completion of installation of the new hazardous waste management unit.  The Permittee shall also submit to the MPCA for review and approval with the certification revised inspection checklists, financial assurance, contingency plan, and other Permit documents affected by the installation.  The MPCA approved revisions shall become an integral and enforceable part of this permit.  

 e.  Tank assessments must be submitted for all new tanks as required under Minn. 

R. 7045.0528, subp. 3.  New tanks are defined as tanks listed below in Part II.E.    2.  The MPCA has inspected the new units and provided the Permittee with a letter stating that the new units appear to have been constructed in accordance with the plans and specifications and this Permit.  Upon receipt of the letter the Permittee may proceed to place wastes in the new tanks or storage area.  Authorized Additional Capacity  In addition to the hazardous waste authorized to be stored or treated in Part II.B, C, and D, this Permit authorizes the Permittee to add the following additional capacity in the future to store and treat hazardous waste authorized by this permit.   

Container Storage  68,640 gallons Tank Storage and Treatment  62,130 gallons Filter Presses  60 cubic feet 

 The Permittee is also authorized to build an approximately 16,000 square foot addition on the south end of the existing hazardous waste storage and treatment building at the Facility (shown in Appendix III) for the storage and treatment of hazardous wastes authorized by this permit.  The construction of the addition must be in accordance with the approved drawings submitted by U.S. Filter Recovery Services, Inc. in the RCRA Part B application for reissuance first submitted on September 2, 1998, revised on December 8, 1998, revised again on December 30, 1998, and the final revision was received on January 12, 1999.  This expansion was approved when the permit was reissued on March 28, 1999.  Any changes to the approved plans must receive the written approval of the MPCA prior to construction.  

Page 14: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

8 of 43 EPA ID MND981098478 

Revised 2/13 

Proposed New Units:  

 Tank No. 

 Tank Name 

Tank Capacity (gallons) 

     13‐2T  Waste Miscellaneous Acid Holding Tank  5,000 13‐3T  Waste Miscellaneous Acid Holding Tank  5,000 13‐4T  Waste Miscellaneous Acid Holding Tank  5,000 30‐1T  Dock Reactor  6,000 30‐2T  Dock Reactor  6,000 30‐3T  Dock Reactor  6,000 90‐5T  Polishing Reactor  5,000 90‐6T  Polishing Reactor  5,000 90‐7T  Polishing Reactor  5,000 90‐8T  Polishing Reactor  5,000 90‐9T  Polishing Reactor  5,000 T‐2020  Regeneration Vessel  450 T‐2021  Regeneration Vessel  340 T‐2022  Regeneration Vessel  340 T‐2023  Regeneration Vessel  450 T‐2031  Regeneration Vessel  75 T‐2032  Regeneration Vessel  75 T‐2400  Regeneration Vessel  400 T‐2500  Regeneration Vessel  2000 

 New Filter Presses:  

Press No.  Press Name    M‐20  20 Cubic Foot Filter Press M‐40  40 Cubic Foot Filter Press 

 New Container Storage Area:  

 No. 

 Storage Container Area 

Capacity (gallons) 

     CSA F‐1  Acid Compatible Storage  68,640 

 

Page 15: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

9 of 43 EPA ID MND981098478 

Revised 2/13 

PART III.  OPERATING CONDITIONS 

 

A. OPERATION AND MAINTENANCE 

   1.  General    a.  The Permittee shall at all times properly operate and maintain the Facility, including all hazardous waste management units and all appurtenances related to the treatment and storage of hazardous wastes.  Proper operation and maintenance includes effective performance, adequate funding, adequate operator staffing and training, and adequate laboratory and process controls.  The Permittee shall install and maintain appropriate back‐up and auxiliary facilities as needed to remain in compliance with the terms and conditions of this Permit.    b.  The Permittee shall prevent the discharge of hazardous waste from the Facility to the surface waters or ground waters of the State.  The Permittee shall prevent hazardous waste from entering drains, sewer inlets, storm sewers, sanitary sewers, doorways, vents, tunnels, pipes, windows, and other areas with permeable floors.    c.  The Permittee shall operate and maintain the Facility to minimize the possibility of fire, explosion, or other event that might allow hazardous wastes to escape into the air, land, or water.    2.  Containers    a.  Condition of Containers.  The Permittee must ensure that the type and condition of containers used to store hazardous waste will be selected and maintained in accordance with Minn. R. 7045.0526 and the operations manual set forth in Section 13 of the Permit Application.  Specifically,    1)  The containers must be of sturdy leak‐proof construction, adequate wall thickness, adequate weld, hinge, and seam strength.  Further, they must be of sufficient strength to withstand side and bottom shock, when filled, without impairment of the ability of the container to fully contain the hazardous waste.    2)  The containers must have lids, caps, hinges, or other closure devices of sufficient strength and construction so that when closed they will withstand dropping, overturning, or other shock without impairment of the container's ability to fully contain the hazardous waste.  

Page 16: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

10 of 43 EPA ID MND981098478 

Revised 2/13 

  3)  The containers must be made of or lined with materials which will not react with, and are otherwise compatible with, the hazardous waste to be stored and other substances that the container may foreseeably contact, so that the ability of the container to contain the waste is not impaired.      4)  If a container holding hazardous waste does not meet the above requirements, or if it begins to leak, the Permittee shall transfer the hazardous waste in the defective container to a container that does meet the above requirements, or manage the waste in some other way that complies with the requirements of Minn. R 7045.0526.    b.  Management of Containers.    1)  A container holding hazardous waste must be labeled with an accumulation start date, the words "Hazardous Waste," and a content description.  Containers must be kept closed during storage, except when it is necessary to add or remove waste.    2)  A container holding hazardous waste must not be opened, handled, or stored in a manner which may rupture the container or cause it to leak.    c.  Container Secondary Containment.  The Permittee shall maintain the container storage area secondary containment system to ensure that the system is capable of collecting and holding spills, leaks, and precipitation.  The maintenance of the secondary containment system must ensure that:    1)  The compatible base underlying the containers is free of cracks or gaps and is sufficiently impervious so as to contain leaks and spills until the collected material is detected and removed.    2)  The compatible base is sloped to drain and remove liquid resulting from leaks and spills.    3)  The secondary containment system has sufficient capacity to contain at least ten percent of the volume of all containers.    4)  The interface between the dike or sidewall and the underlying base of the container storage area secondary containment system is sealed to contain leaks, spills, and accumulated liquids.    3.  Tanks.  The Permittee shall operate the tank system (tank(s), ancillary equipment, and secondary containment system) in accordance with Minn. R. 7045.0528 and this part of this Permit.  Written tank system assessments required by Minn. R. 7045.0528, subps. 2 and 3 must be maintained at the Facility.     

Page 17: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

11 of 43 EPA ID MND981098478 

Revised 2/13 

a.  Tank Secondary Containment and Detection of Releases.  The Permittee’s tank secondary containment system consists of an external liner.  This secondary containment system must be operated to prevent the migration of hazardous waste or constituents or accumulated liquid to the soil, ground water, or surface water, as well as to detect and collect releases and accumulated liquid until the collected material is removed.  Specifically, the secondary containment system must be:    1)  Constructed of or lined with materials that are maintained to be compatible with the hazardous waste placed in the tanks and must have sufficient strength and thickness to prevent failure owing to pressure gradients, including static head and external hydrological forces, physical contact with the waste to which it is exposed, climatic conditions, and the stress of daily operation, including stresses from nearby vehicular traffic.    2)  Placed on a foundation or base capable of providing support to the secondary containment system, resistant to pressure gradients above and below the system, and capable of preventing failure due to settlement, compression, or uplift.    3)  Provided with a leak detection system that is designed and operated to detect the failure of either the primary or secondary containment structure or the release of any hazardous waste or accumulated liquid in the secondary containment system WITHIN 24 HOURS.    4)  Sloped or otherwise designed or operated to drain and remove liquids resulting from leaks, spills, and precipitation.    b.  General Tank Operating Requirements.    1)  In addition to the requirements of Part III.A.3.a., the Permittee shall maintain the external liner secondary containment system in accordance with Minn. R. 7045.0528, subp. 4, item E.    2)  The Permittee shall maintain secondary containment for tank ancillary equipment in accordance with Minn. R. 7045.0528, subp. 4, item H.    3)  Valves, pipes, fittings, and other closure devices and appurtenances must be of sufficient strength to withstand shock and internal pressure without impairment of the ability of the tank to fully contain the waste.  Gasketed closures must be fitted with gaskets comprised of materials that are sufficient to prevent leakage and that will not be deteriorated by the contents.    4)  The Permittee shall use check valves for spill prevention controls.  Further, high level alarms shall be used as overfill prevention devices.  These controls and devices shall be properly operated and maintained to prevent failure of the tank system.  

Page 18: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

12 of 43 EPA ID MND981098478 

Revised 2/13 

4.  Miscellaneous Units.  The Permittee shall operate the miscellaneous units, ancillary equipment, and secondary containment system in accordance with the requirements below.    a.  Miscellaneous Unit Secondary Containment and Detection of Releases.  The Permittee's miscellaneous unit secondary containment system consists of an external liner.  This secondary containment system must be operated to prevent the migration of hazardous waste or constituents or accumulated liquid to the soil, ground water, or surface water, as well as to detect and collect releases and accumulated liquid until the collected material is removed.  Specifically, the secondary containment system must be:    1)  Constructed of or lined with materials that are maintained to be compatible with the hazardous waste placed in the units and have sufficient strength and thickness to prevent failure owing to pressure gradients, including static head and external hydrological forces, physical contact with the waste to which it is exposed, climatic conditions, and the stress of daily operation, including stresses from nearby vehicular traffic.    2)  Placed on a foundation or base capable of providing support to the secondary containment system, resistant to pressure gradients above and below the system, and capable of preventing failure due to settlement, compression, or uplift.    3)  Provided with a leak detection system that is designed and operated to detect the failure of either the primary or secondary containment structure or the release of any hazardous waste or accumulated liquid in the secondary containment system within  24 hours, or at the earliest practicable time if the owner or operator can demonstrate to the commissioner that existing detection technologies or site conditions will not allow detection of a release within 24 hours.  If the owner or operator demonstrates that a leak will not be detected within 24 hours, the Commissioner will make a determination as to the acceptability of the leak detection system and the suitability of the period of time required to detect a leak based on information submitted by the owner or operator.    4)  Located on a surface that is sloped or otherwise constructed to drain and remove liquids resulting from leaks, spills, and precipitation.    b.  General Miscellaneous Unit Operating Requirements.  The Permittee shall ensure that the miscellaneous units and ancillary equipment are operated in accordance with the following requirements.    1)  Valves, pipes, fittings, and other closure devices and appurtenances must be of sufficient strength to withstand shock and internal pressure without impairment of the ability of the tank to fully contain the waste.  Gasketed closures must be fitted with gaskets comprised of materials that are sufficient to prevent leakage and that will not be deteriorated by the contents.   

Page 19: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

13 of 43 EPA ID MND981098478 

Revised 2/13 

  2)  The Permittee shall operate the miscellaneous units in compliance with both MPCA Air Quality Rules and Occupational Safety and Health Administration Standards.    3)  Miscellaneous units shall be operated and maintained as recommended in the manufacturer’s specifications.    4)  Adequate care shall be taken so as to prevent the tracking of sludge by foot or vehicle. 

B. NOTICE TO GENERATORS 

 In accordance with Minn. R. 7045.0452, subp. 3. item C., the Permittee shall notify and document in writing each generator from whom it receives wastes that the Permittee has received this Permit from the MPCA. 

C. RECEIPT OF UNAUTHORIZED WASTES 

 In the event the Permittee receives a shipment of hazardous wastes that the Permittee is not authorized to receive and store at the Facility, the Permittee shall IMMEDIATELY notify the MPCA and wait for further instructions before accepting the waste.  This is required by Minn. R. 7045.0452, subp. 3, item B. 

D. GENERAL WASTE ANALYSIS 

   1.  In accordance with the Waste Analysis Plan set forth in Section 3 of the Permit Application, and the requirements of Minn. R. 7045.0458, the Permittee shall obtain a detailed chemical and physical analysis of a representative sample of each waste that the Permittee intends to manage at the Facility.  The Permittee shall keep this analysis at the Facility and shall provide a copy to the MPCA upon request.    2.  The waste analysis must be repeated, to ensure that it is accurate and up‐to‐date, at anytime that:    a.  The Permittee has reason to believe that the process or operation generating the waste has changed.    b.  The Permittee has reason to believe a hazardous waste that has been received does not match the waste specified on the accompanying manifest.    c.  The waste analysis plan set forth in Section 3 of the Permit Application requires a particular shipment of hazardous waste to be analyzed. 

Page 20: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

14 of 43 EPA ID MND981098478 

Revised 2/13 

E. PERSONNEL TRAINING 

 The Permittee shall not allow any employee to work unsupervised at the Facility in a job related to hazardous waste management until that employee has received all training required by Minn. R. 7045.0454 and the Personnel Training Plan set forth in Section 8 of the Permit Application. 

F. HANDLING MANIFESTS 

 The Permittee shall comply with the manifest requirements in Minn. R. 7045.0474. 

G. MANIFEST DISCREPANCIES 

   1.  If the Permittee discovers a significant discrepancy in a manifest, the Permittee shall attempt to reconcile the discrepancy.  If the Permittee is unable to reconcile the discrepancy with the generator and transporter WITHIN FIFTEEN (15) DAYS, the Permittee shall IMMEDIATELY submit to the MPCA a letter describing the discrepancy, attempts made to reconcile it, and a copy of the manifest or shipping paper.  The type of discrepancy must be noted on the manifest.    2.  If the Permittee discovers a minor discrepancy in a manifest, the Permittee shall attempt to reconcile the discrepancy with the generator and transporter.  If the discrepancy cannot be reconciled, the Permittee shall note the type of discrepancy and its resolution on the manifest.      3.  The definitions of "significant discrepancy" and "minor discrepancy" can be found in Minn. R. 7045.0476, subp. 2. 

H.  MONITORING 

 In the event the Permittee shall be required by the MPCA to conduct monitoring, the following requirements shall be complied with:    1.  Samples and measurements taken for the purpose of monitoring shall be representative of the monitored activity.    2.  The method used to obtain a representative sample of the waste to be analyzed must be the appropriate method set forth in Title 40 of the Code of Federal Regulations, Part 261, Appendix I.  Laboratory methods must be those specified in the latest edition of the U.S. Environmental Protection Agency (EPA) publication Test Methods for Evaluating Solid Waste: Physical/Chemical Methods SW‐846, or an equivalent method approved by the MPCA. 

Page 21: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

15 of 43 EPA ID MND981098478 

Revised 2/13 

I.  STORAGE OF IGNITABLE, REACTIVE, AND INCOMPATIBLE WASTES 

   1.  General Requirements    a.  Required notices.  The Permittee shall take precautions to prevent accidental ignition or reaction of ignitable or reactive waste.  This waste must be separated and protected from sources of ignition or reaction, including, but not limited to open flames, smoking, cutting and welding, hot surfaces, frictional heat, static sparks, electrical sparks, mechanical sparks, spontaneous ignition, and radiant heat.  When ignitable or reactive waste is being handled, the Permittee shall confine smoking and open flame to specially designated locations.  "No Smoking" signs must be conspicuously placed wherever there is a hazard from ignitable or reactive waste.    b.  Required precautions.  As specifically required by Minn. R. 7045.0456, subp. 2, the Permittee of a Facility that treats, stores, or disposes of ignitable or reactive waste or that mixes incompatible wastes or incompatible wastes and other materials, shall take precautions to prevent reactions which:    1)  Generate extreme heat, pressure, fire, explosions, or violent reactions unless the Permittee is Permitted to handle these types of reactions.     2)  Produce uncontrolled toxic mists, fumes, dusts, or gases in sufficient quantities to threaten human health or the environment.    3)  Produce uncontrolled flammable fumes or gases in sufficient quantities to pose a risk of fire or explosions.    4)  Damage the structural integrity of the device or Facility.    5)  Through other means threaten human health or the environment.    2.  Special Requirements for Ignitable and Reactive Wastes    a.  Storage in containers.  Containers holding ignitable or reactive wastes and materials must be located at least 15 meters (50 feet) from the Facility's property line as delineated on the map Appendix I, hereof.    b.  Storage in tanks.  Ignitable and reactive wastes placed in tanks must be stored in such a way that they are protected from any materials or conditions which may cause the waste to ignite or react.  Protective distances must be followed as specified in the Uniform Fire Code.  

Page 22: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

16 of 43 EPA ID MND981098478 

Revised 2/13 

3.  Special Requirements for Incompatible Wastes    a.  Storage in containers.     1)  Incompatible wastes or wastes which are incompatible with other material must not be placed in the same container, unless compliance with Minn. R. 7045.0456, subp. 2, is achieved.    2)  Hazardous waste must not be placed in an unwashed container that previously held an incompatible waste or material.  As required by Minn. R. 7045.0458, subp. 2, the waste analysis plan must include analyses to comply with these special requirements.  Minn. R. 7045.0456, subp. 3, requires waste analyses, trial tests, and documentation to ensure compliance with Minn. R. 7045.0456, subp. 2.  All results obtained from testing must be maintained in the Facility operating record.    3)  A storage container holding a hazardous waste that is incompatible with any waste or other materials stored nearby in other containers, waste piles, open tanks, or surface impoundments, must be separated from other such waste or material by means of a dike, berm, wall, or other protective device.    b.  Storage in Tanks.  Incompatible wastes and/or incompatible wastes and materials must not be placed in the same tank, unless compliance with Part III.I.1.b. above is maintained. 

J.  INSPECTIONS 

 The Permittee shall conduct inspections at the Facility and for all hazardous waste management units as required under the inspection plan set forth in Section 5 of the Permit Application, Minn. R. 7045.0452, subp. 5, shall be followed. 

K. SECURITY 

 In accordance with Minn. R. 7045.0452, subp. 4, the Permittee shall maintain a 24‐hour surveillance system which continuously monitors and controls entry onto the active portion of the Facility, or an artificial or natural barrier which completely surrounds the active portion of the Facility and a means to control entry at all times through gates or other entrances to the active portion of the Facility.  The fence shall be locked at times when the Facility is unattended and access to the Facility shall be provided only to persons who are authorized by the Permittee to enter the Facility.  The Permittee shall post a sign legible from a distance of  25 feet with the legend, "Danger ‐ Unauthorized Personnel Keep Out," at each entrance to the Facility as defined in Minn. R. 7045.0020, subp. 3. 

Page 23: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

17 of 43 EPA ID MND981098478 

Revised 2/13 

L. LIGHTING 

 The Permittee shall provide adequate lighting for the Facility to ensure safety and proper operation. 

M. FINANCIAL ASSURANCE FOR CLOSURE 

   1.  Closure.  The Permittee shall provide an Irrevocable Standby Letter of Credit in the amount of the cost estimated to close the Facility, in accordance with the financial assurance requirements of Minn. R. 7045.0504.  The Permittee shall continue to maintain such Irrevocable Standby Letter of Credit unless the MPCA approves of the use of another mechanism as specified in Minn. R. 7045.0504. 

N. LIABILITY COVERAGE 

 The Permittee shall have and maintain liability coverage for sudden and accidental occurrences in the amount of at least One Million Dollars ($1,000,000) per occurrence, with an annual aggregate coverage in the amount of at least Two Million Dollars ($2,000,000), exclusive of legal defense costs in accordance with the requirements of Minn. R. 7045.0518.  The Permittee shall comply with this requirement through the use of an insurance policy in accordance with Minn. R. 7045.0518. 

O. DECONTAMINATION OF UNITS USED TO MANAGE LISTED HAZARDOUS WASTE 

 1.  The Permittee is authorized and required by this Permit to decontaminate any 

permitted units after using the units to manage listed hazardous wastes (Minn. R. 7045.0135) if the Permittee intends to manage either: 

   a.  Characteristic hazardous wastes (Minn. R. 7045.0131), or    b.  Nonhazardous wastes (henceforth referred as "nonlisted wastes") without 

carrying the F‐listed waste code.  

The following "Decontamination Protocol" and documentation requirements are a summary of the process described in Section 14.9 of the Application and must be completed each time a unit or group of units is to be used to manage nonlisted wastes after being used to manage listed hazardous wastes.  The summary of the Decontamination Protocol set out below is for convenience of reference herein only; it does not limit the obligation of the Permittee to fully carry out Decontamination Protocol as more fully described in the Permit Application.  The wastes for which each of these units are authorized are listed in Appendix II of this Permit.  

Page 24: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

18 of 43 EPA ID MND981098478 

Revised 2/13 

The requirements, outlined below, apply to any of the permitted units operated by the Permittee.  The decontamination requirements also apply to the ancillary equipment (pipes and pumps) that have been used to manage the listed wastes and that will be used to manage nonlisted wastes.     2.  Decontamination Protocol.     a.  The shift supervisor or technical manager will determine which units will be decontaminated.  These units will be listed on the Decontaminated Equipment Process Form (Exhibit 14.5 of the Permit Application).    b.  The operator will transfer the contents of each unit to the next authorized downstream unit.  Tap water will then be used to rinse the unit.  This rinseate will also be transferred to the next downstream unit.    c.  Each unit will be decontaminated with appropriate cleaners (high pressure water, chemicals, acid wash, etc.).  The rinseates from these processes will be managed as listed hazardous wastes.    d.  After the operator has determined that each unit has been rinsed thoroughly, a rinseate sample will be collected from each unit to verify decontamination.  This sample shall be analyzed for applicable RCRA metals (Minn. R. 7045.0131, excluding mercury) and cyanide, using Total Metal Analysis (not Toxic Characteristic Leaching Procedure).  The determination of the constituents for which the Permittee will sample for will be based on the technical manager's or shift supervisor's knowledge of the waste.  Any constituent for which there is a possibility of the concentration exceeding characteristic levels must be sampled and analyzed.  All analyses shall be conducted in accordance with the EPA methods indicated in Section 3.0 of the Permit Application.    e.  The technical manager or shift supervisor will review the analytical results and use this data to determine whether the levels are below the hazardous waste characteristic levels (Minn. R. 7045.0131).  Since no hazardous waste characteristic level for cyanide exists, cyanide decontamination levels will be based on maximum concentration discharge levels indicated in the Siemens Industry Inc. permit with Metropolitan Council Environmental Services for sewered wastes.  The discharge level for total cyanide under this Permit is 4.1 milligrams per liter.  This level will be used by the Permittee to determine whether the units have been decontaminated.  If the levels for RCRA metals and cyanide are below the levels indicated above, the decontaminated units can be used to manage nonlisted wastes.  If any of the constituents exceed these decontamination levels, steps 3 through 5 of the Decontamination Protocol must be repeated before the unit can be used to manage nonlisted wastes.    f.  The technical manager or shift supervisor will verify the decontamination procedure and will record the following information in the operating record on a Decontaminated Equipment Process Form:   

Page 25: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

19 of 43 EPA ID MND981098478 

Revised 2/13 

   1)  The unit name and number.    2)  The date and time of decontamination.     3)  All analytical results of the decontamination verification testing.    4)  A description of the decontamination methods used and comments regarding decontamination.    5)  The signature of the person authorized to verify that decontamination has been completed according to this procedure.    g.  Each Decontaminated Equipment Process Form shall be maintained in the Operating Record as indicated in Part V.B.12. of this Permit.  

P. RECEIPT OF ORGANIC WASTES 

 In the event that the Permittee receives a waste that the Permittee intends to treat for which the average volatile organic concentration of any of the organic waste codes exceeds 500 parts per million by weight (ppmw), the Permittee shall notify the MPCA and discuss the proposed treatment method.  The Permittee shall not commence treatment of such wastes until the Permittee has received written approval for treatment from the MPCA. 

Q. WASTE PROCESSING 

 All wastes received from off site shall be placed into the appropriate storage area within  24 hours.  All wastes being moved off site from a permitted storage area shall be removed from permitted storage not more than 24 hours prior to being shipped off site. 

Page 26: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

20 of 43 EPA ID MND981098478 

Revised 2/13 

PART IV.  EMERGENCY PROCEDURES 

 

A. IMPLEMENTATION OF CONTINGENCY PLAN 

 

In accordance with Minn. R. 7045.0466, subp. 3, the Permittee must ensure that the provisions of the contingency plan, set forth in Section 9 of the Permit Application, are carried out IMMEDIATELY whenever there is a release, fire, or explosion of hazardous waste or hazardous constituents which could threaten human health or the environment. 

B. AMENDMENT OF CONTINGENCY PLAN 

 

  1.  The Permittee shall amend the contingency plan whenever:  

  a.  This Permit is revised.  

  b.  Said plan fails in an emergency.  

  c.  The Facility changes in its design, construction, operation, maintenance, or other circumstance in a way that increases the potential for fires, explosions, or the release of hazardous waste or hazardous constituents, or changes the response necessary in an emergency.  

  d.  The designated emergency coordinator changes.  

  e.  The list of emergency equipment changes.  

  2.  The Permittee shall maintain a copy of its contingency plan at the Facility at all times.  

  3.  The Permittee shall submit a copy of its contingency plan to all local police departments, fire departments, hospitals, and all local and state emergency response teams that may be called upon to respond in an emergency situation at the Facility. 

C. PREPAREDNESS AND PREVENTION 

 

  1.  Required equipment.  At a minimum, the Permittee shall maintain emergency equipment required by the contingency plan.  

  2.  Testing and maintenance of equipment.  The Permittee shall test and maintain all Facility communications or alarm systems, fire protection equipment, and spill control equipment to ensure proper operation in time of emergency.  The maintenance and inspection of emergency equipment shall be conducted in accordance with the Inspection Plan set forth in Section 5 of the Permit Application. 

Page 27: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

21 of 43 EPA ID MND981098478 

Revised 2/13 

  3.  Access to communications or alarm system.  The Permittee shall ensure that whenever hazardous waste is being poured, mixed, spread, or otherwise handled, all personnel involved in the operation shall have immediate access to an internal alarm or emergency communication device, either directly or through visual and/or voice contact with another employee.    4.  Aisle space.  The Permittee shall maintain aisle space in all hazardous waste storage areas to allow the unobstructed movement in an emergency of personnel, fire protection equipment, spill control equipment, and decontamination equipment.  Aisle space of at least four (4) feet in width shall be maintained in all container storage areas. 

D. EMERGENCY COORDINATOR 

 In accordance with Minn. R. 7045.0468, subp. 1, the Permittee shall at all times have at least one (1) employee either on the Facility premises or on call with the responsibility for coordinating all emergency response measures.  The following persons qualify as the emergency coordinator and each assumes all responsibilities described in Part IV. of this Permit.  

Emergency Coordinators  

  Work  Home Primary     Peter Habig    651‐638‐1366    612‐354‐2693   Cell Phone      612‐840‐5319      Secondary     Leo Sharkey  651‐638‐1300    651‐490‐0435   Cell Phone    651‐402‐1389      Tertiary     Michael Wismer     651‐638‐1300    651‐653‐3533   Cell Phone    651‐343‐4801 

 The Permittee may change the names of employees who qualify as emergency coordinator by contacting the MPCA and identifying the new emergency coordinator(s). 

E.  RESPONSE TO SPILLS/LEAKS/RELEASES FROM REGULATED UNITS 

   1.  Tanks and Miscellaneous Units.  If there should be a leak of hazardous waste from the "tank system" (which is defined to include the tank, secondary containment system, and all ancillary equipment such as pumps, valves, monitoring equipment etc.), the Permittee shall comply with the following requirements:  

Page 28: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

22 of 43 EPA ID MND981098478 

Revised 2/13 

  a.  IMMEDIATELY stop the flow of hazardous waste into the tank system and inspect the tank system to determine the cause of the leak.    b.  WITHIN 24 HOURS after detection of the leak, or at the earliest practicable time, whichever is sooner, remove as much of the waste as is necessary to prevent further release of hazardous waste to the environment (i.e., escaping the secondary containment system) and repair the tank system.  

  c.  IMMEDIATELY conduct a visual inspection of all property affected by the release.  Based upon the inspection findings, the Permittee shall prevent further migration of the release to surrounding soils and surface waters.  All contaminated media, structures, and equipment shall be properly managed at the direction of the MPCA.  

  d.  The Permittee must notify the MPCA DUTY OFFICER IMMEDIATELY after a release of hazardous waste to the environment if it is determined, based on the criteria in Part IV.G, of this Permit, that such notification is required.  

  e.  The Permittee shall evaluate the release and submit a written report to the MPCA WITHIN 30 DAYS after detection of a release requiring implementation of the contingency plan.  This report must contain the following information and may be combined with the report required in Part IV.L of this Permit.  

  1)  The likely route of migration of the release.  

  2)  The characteristics of the surrounding soil, including soil composition, geology, hydrogeology, and climate.  

  3)  The results of any monitoring or sampling conducted in connection with the release, if available.  If sampling or monitoring is not available WITHIN 30 DAYS after detection of the release, the data must be submitted to the MPCA as soon as they become available.  

  4)  The proximity to downgradient drinking water, surface water, and populated areas.  

  5)  A description of response actions taken or planned.  

  f.  In addition to the requirements in items a. through e. above, the Permittee shall follow the procedures specified in Part IV, hereof (Emergency Procedures) if the leak should cause an emergency situation requiring implementation of the contingency plan.  

  The Permittee shall repair the tank secondary containment system in accordance with Minn. R. 7045.0528, subp. 8, items E and F.  

Page 29: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

23 of 43 EPA ID MND981098478 

Revised 2/13 

  g.  Upon evaluation of the 30 day written report submitted under Part IV.E.1.e, the Commissioner may require the Permittee to sample appropriate media (soil, surface water, ground water, air) as necessary to determine the extent of contamination.  Further, upon review of the sampling analysis, the Commissioner may require the Permittee to submit a remediation plan for approval and to remediate the contaminated media affected by the release.  Upon remediation, a final report summarizing remedial efforts taken shall be submitted to the Commissioner.    2.  Containers.  If there should be a leak of hazardous waste from a storage container, the Permittee shall comply with the following requirements:    a.  The Permittee shall IMMEDIATELY inspect the containers to determine which container or containers are leaking.  Having identified the leaking container or containers, the Permittee shall contain the spill as soon as possible.  Any leaking container and adjacent or affected area shall be inspected by the Permittee to determine the reason for the leak.  The contents of the container shall be overpacked into another container and be managed in accordance with Minn. R. 7045.0526, subp. 6, item C.    b.  Spilled or leaked waste or inadvertent run‐on must be removed from the secondary containment system in a timely manner.  If the collected material (including spill containment equipment and debris/residue) is a hazardous waste, the Permittee must managed the material in accordance with Minn. R. 7045.0526, subp. 6, item C.  If the collected material is discharged through a point source to waters, Minn. R. 7045.0526, subp. 6, item C, must be followed.    c.  The Permittee shall notify the MPCA DUTY OFFICER IMMEDIATELY after any leak or spill of hazardous waste to the environment if it is determined, based on the criteria in Part IV.G, of this Permit, that such notification is required.    d.  Part IV.L, of this Permit should be consulted to determine if a written report is required.    e.  The Commissioner may require the Permittee to sample appropriate media (soil, surface water, ground water, air) as necessary to determine the extent of contamination.  Further, upon review of the sampling analysis, the Commissioner may require the Permittee to remediate the contaminated media affected by the release.  Upon remediation, a final report summarizing remedial efforts taken shall be submitted for approval to the Commissioner. 

F. RESPONSE TO OTHER SPILLS/LEAKS/RELEASES FROM NON‐REGULATED UNITS 

 If there should be a leak or spill of hazardous waste to the environment (escaping the secondary containment system) from any source at the Facility other than the Permitted regulated units, the Permittee shall comply with the following requirements:  

Page 30: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

24 of 43 EPA ID MND981098478 

Revised 2/13 

  1.  The Permittee shall stop the leak or spill and clean up any released hazardous waste as soon as possible.    2.  The Permittee must IMMEDIATELY conduct a visual inspection of the area around the leak or spill and prevent further migration of the leaked or spilled hazardous waste to soils and surface waters.    3.  The Permittee shall notify the MPCA IMMEDIATELY after any leak or spill of hazardous waste to the environment if it is determined, based on the criteria in Part IV.G, of this Permit, that such notification is required.     4.  In addition to the requirements in items 1‐3 above, the Permittee shall follow the procedures specified in Part IV, hereof (Emergency Procedures) if the leak should require implementation of the contingency plan. 

G. NOTIFICATION TO MPCA REGARDING SPILLS/LEAKS/RELEASES OF HAZARDOUS WASTE 

   1.  Scope.  Minn. Stat. §§ 115.061 and 116.061 require notification to the MPCA regarding discharges to water and air, respectively, for materials other than hazardous waste.  Minn. R. 7045.0468, subp. 5, item B, and subp. 6 also provide requirements for reporting to the agency discharges of hazardous waste.  Compliance under items 3 and 5 below satisfies the agency notification requirements regarding releases of hazardous waste at permitted hazardous waste facilities for both the rules and statutes cited above      All notifications required by items 3 and 5 below must be made to the Minnesota Duty Officer at one of the appropriate numbers provided below.  Notification to the Minnesota Duty Officer satisfies the requirement for notifying the agency.      TWIN CITIES METRO AREA (AND OUTSIDE MINNESOTA):  651‐649‐5451      GREATER MINNESOTA:  1‐800‐422‐0798    2.  Statutory Language    MINN. STAT. § 115.061 DUTY TO NOTIFY AND AVOID WATER POLLUTION  

(a) Except as provided in paragraph (b), it is the duty of every person to notify the agency of the discharge, accidental or otherwise, of any substance or material under its control which, if not recovered, may cause pollution of waters of the state, and the responsible person shall recover as rapidly and thoroughly as possible such substance or material and take immediately such other action as may be reasonably possible to minimize or abate pollution of waters of the state caused thereby. 

 

Page 31: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

25 of 43 EPA ID MND981098478 

Revised 2/13 

(b) Notification is not required under paragraph (a) for a discharge of five gallons or less of petroleum, as defined in section 115C.02, subd 10.  This paragraph does not affect the other requirements of paragraph (a). 

   3.  Required Notification    a.  The following actions constitute compliance with the agency reporting requirements of Minn. Stat. § 115.061 and with Minn. R. 7045.0468, subp. 5, item B, and  subp. 6 regarding discharges of hazardous waste, other than releases to air, at permitted hazardous waste facilities.    The Minnesota Duty Officer must be notified immediately of any of the following discharges:    1)  A fire, explosion, or discharge that could threaten human health or the environment outside the Facility.    2)  A discharge to the secondary containment of a permitted unit that is NOT completely contained in the secondary containment and/or is NOT recovered in a timely manner.     4.  Statutory Language:    MINN. STAT. § 116.061.  AIR POLLUTION EMISSIONS ABATEMENT  

Subd. 1.  Emission notification required.  

(a) A person who controls the source of an emission must notify the agency immediately of excessive or abnormal unpermitted emissions that: 

 (1) may cause air pollution endangering human health.  (2) may cause air pollution damaging property; or  (3) cause obnoxious odors constituting a public nuisance. 

 (b) If a person who controls the source of an emission has knowledge of an event that has occurred and that will subsequently cause an emission described in paragraph (a), the person must notify the agency when the event occurs. 

 Subd. 2.  Abatement required.  A person who is required to notify the agency under subdivision 1 must take immediate and reasonable steps to minimize the emissions or abate the air pollution and obnoxious odors caused by the emissions. 

Page 32: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

26 of 43 EPA ID MND981098478 

Revised 2/13 

Subd. 3.  Exemption.  The following are exempt from the requirements of subdivisions 1 and 2: 

 1)  emissions resulting from the activities of public fire services or law enforcement services;  2)  emissions from motor vehicles, as defined in section 169.01,  subdivision 3;  3)  emissions from an agricultural operation deemed not a nuisance under  section 561.19, subdivision 2; or  4)  emissions from agency regulated sources that are routine or authorized by the agency. 

 Subd. 4.  Penalty exception.  A person who notifies the agency of emissions under subdivision 1 and who complies with subdivision 2 shall not be subject to criminal prosecution under section 115.071, subdivision 2.  Subd. 5.  Use of Notification.  Any notice submitted under subdivision 1 is not admissible in any proceeding as an admission of causation. 

   5.  Required Notification.  Compliance with the statutory notification requirements above in Part IV.G.4, and the requirement below in Part IV.G.5, constitutes compliance with the agency reporting requirements of Minn. R. 7045.0468, subp. 5, item B, and subp. 6 regarding discharges of hazardous waste to the air at permitted hazardous waste facilities.    Notification must be provided for a fire, explosion, or discharge that could threaten human health or the environment outside the facility. 

H. ADDITIONAL EMERGENCY COORDINATOR DUTIES AND NOTIFICATION TO OTHER AGENCIES 

 [For reporting requirements regarding discovery of "noncompliance" with a condition of this Permit which could endanger human health or the environment, please refer to Part VI, of this Permit.]  Whenever the contingency plan is implemented; the emergency coordinator shall IMMEDIATELY:    1.  Activate internal Facility alarms or communication systems.     2.  Identify the character, exact source, amount, and areal extent of any released material.  

Page 33: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

27 of 43 EPA ID MND981098478 

Revised 2/13 

  3.  Assess possible hazards to human health or the environment, considering both direct and indirect effects of the release, fire, explosion; effects from any toxic, irritating, or asphyxiating gases that are generated; and effects of any hazardous surface water run‐off from water or chemical agents used to control fire and explosions.    4.  Carry out the appropriate provisions of the contingency plan set forth in Section 9 of the Permit Application.    If the emergency coordinator determines that:    a.  The hazardous waste or hazardous constituent release, fire, or explosion could threaten human health or the environment, outside the Facility as defined in Part I, of this Permit, or    b.  Evacuation of local areas may be advisable, or  

c.  A released hazardous waste or hazardous constituent may cause pollution of the air, land resources, or waters of the state, the emergency coordinator shall IMMEDIATELY notify:    1)  Appropriate state and local authorities.     2)  The governmental official designated as the on‐scene coordinator for that geographical area, or the National Response Center at (800) 424‐8802.    The information in items a) through f) below shall be given to each of the above authorities at the time of the notification:    a)  Name and telephone number of reporter.    b)  Name and address of Facility.   c)  Date, time, and type of incident.    d)  Name and quantity of material involved.   e)  Extent of damages or injuries, if any.   f)  The possible hazards to human health and/or the environment. 

I. CONTAINMENT MEASURES 

 During an event that requires implementation of the contingency plan, the emergency coordinator shall ensure that releases, fires, and explosions do not occur, recur, or spread to other hazardous waste at the Facility.  If the Facility stops operations, the emergency coordinator shall monitor for leaks, pressure build‐up, gas generation, or ruptures in valves, pipes, or other equipment, wherever this is appropriate. 

Page 34: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

28 of 43 EPA ID MND981098478 

Revised 2/13 

J. POST EMERGENCY CLEANUP 

 IMMEDIATELY after an event that requires implementation of the contingency plan, the Permittee shall provide for treating, storing, or disposing of recovered waste, contaminated soil, ground water, and any other contaminated material resulting from the emergency incident at the Facility, in a manner required by applicable laws and rules. 

K. STARTUP OF OPERATIONS 

 The Permittee shall not recommence operations after an emergency until the EPA, MPCA, and local police and fire departments have been notified and the Facility is in compliance with Minn. R. 7045.0470, subp. 2. 

L. POST EMERGENCY REPORTING 

 WITHIN 15 DAYS after an event that requires implementation of the contingency plan as required by Minn. R. 7045.0466, subp. 3, the Permittee shall submit a written report to the Commissioner describing the incident, containing information as required by Minn. R. 7045.0470, subp. 3. 

M. OPERATING RECORD 

 The Permittee shall note in the operating record the time, date, and details of any incident that requires implementation of the contingency plan.   

Page 35: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

29 of 43 EPA ID MND981098478 

Revised 2/13 

PART V.  RECORD KEEPING REQUIREMENTS 

 

A. PLANS TO BE MAINTAINED AT THE FACILITY 

 The Permittee shall maintain at the Facility at all times a copy of the most recent MPCA‐approved version of the following plans:    1.  A waste analysis plan as set forth in Section 3 of the Permit Application, and that meets the requirements of Minn. R. 7045.0458.    2.  A personnel training plan as set forth in Section 8 of the Permit Application, and that meets the requirements of Minn. R. 7045.0454.    3.  A contingency plan as set forth in Section 9 of the Permit Application, and that meets the requirements of Minn. R. 7045.0466.    4.  A closure plan as set forth in Section 11 of the Permit Application, and that meets the requirements of Minn. R. 7045.0486.    5.  An inspection plan as set forth in Section 5 of the Permit Application, and that meets the requirements of Minn. R. 7045.0452, subp. 5. 

B.  OPERATING RECORD 

 The Permittee shall keep a written operating record at the Facility that contains the following information:      1.  The names of each hazardous waste generator and its EPA identification number.    2.  The arrival date of incoming hazardous waste, and the shipment date of outgoing hazardous waste, corresponding with the transporter's name and identification number.    3.  A description and statement of the quantity of each hazardous waste received, or shipped, and the method and date when waste was treated or stored.    4.  The location of each hazardous waste shipment or container within the Facility and the total quantity of hazardous waste at each location.  This information must be complete and up to date at all times.  This information must be cross‐referenced to the manifest accompanying the waste.    5.  The records and results of each waste analysis performed. 

Page 36: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

30 of 43 EPA ID MND981098478 

Revised 2/13 

  6.  The records and results of each inspection performed.    7.  The results of any monitoring performed at the Facility.    8.  Summary reports and details of all incidents which required implementation of the Contingency Plan.    9.  All annual reporting requirements specified in Part VI.C, of this Permit.    10.  All Land Disposal Restricted waste notifications required under Minn. R. 7045.1390.    11.  A copy of the notices provided by the Permittee to each of the generators from whom the Permittee is obtaining hazardous wastes for storage at the Facility as required by Part III.B, hereof.    12.  Copies of the Decontaminated Equipment Process Form (Exhibit 14.5 of the Application) for each decontamination procedure as required by Part III.O of this Permit. 

C. PERSONNEL RECORDS 

 The Permittee shall maintain at the Facility at all times a copy of the following personnel records:    1.  The job title for each position at the Facility related to hazardous waste management and the name of the employee filling each job.    2.  A written job description of each position at the Facility related to hazardous waste management.  This description may be consistent in its degree of detail with descriptions for other similar positions in the same company location or bargaining unit, but must include at least the requisite skill, education, or other qualifications and duties of employees assigned to each such position.    3.  A written description of the type and amount of both introductory and continuing training in accordance with the Personnel Training Plan set forth in Section 8 of the Permit Application, that will be given to each person filling a hazardous waste position referenced in item 1, above.    4.  Records that document the training provided to each employee filling a position referenced in item 1 above. 

D. INSPECTION RECORDS 

 The Permittee shall record all inspections in an inspection log.  These records must include the date and time of the inspection, the name of the inspector, a notation of the observations made, and the date and nature of any repairs or other remedial actions. 

Page 37: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

31 of 43 EPA ID MND981098478 

Revised 2/13 

E. MONITORING AND TESTING RECORDS 

 In accordance with Minn. R. 7001.0150, subp. 2, items B and C:    1.  The Permittee shall retain records of all monitoring information, including all calibration and maintenance records and all original strip chart recordings with other recordings for continuous monitoring instrumentation, copies of all reports and records required by this Permit, and records of all data used to complete the Permit Application for this Permit.    2.  Records of monitoring information shall specify:    a.  The date(s), exact place, and time(s) of sampling or measurements;    b.  The individual(s) who performed the sampling or measurements;    c.  The date(s) analyses were performed;    d.  The individual(s) who performed the analyses;    e.  The analytical techniques for methods used; and    f.  The results of such analyses. 

F. RETENTION AND DISPOSITION OF RECORDS 

 The Permittee shall maintain all records for at least three (3) years after generation of the record unless the record is required by Minn. R. 7045.0478, subp. 3 or Minn. R. 7001.0720, subp. 2, item B to be kept for a longer period of time.  Records required to be kept until closure of the Facility are listed in Minn. R. 7045.0478, subp. 3 or Minn. R. 7001.0720, subp. 2.  These retention periods are automatically extended during the course of and at least for the duration of an unresolved enforcement action regarding the Permittee and shall also be extended upon request of the Commissioner.  These records shall be made available to the Commissioner upon Request.  

Page 38: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

32 of 43 EPA ID MND981098478 

Revised 2/13 

PART VI.  REPORTING REQUIREMENTS 

 

A. REPORTING NONCOMPLIANCE 

 As used herein, the term "noncompliance" refers to any failure, intentional or unintentional, avoidable or unavoidable, to satisfy any requirement of this Permit.    1.  If the Permittee discovers that noncompliance with a condition of the Permit has occurred, which could endanger human health, public drinking water supplies, or the environment, the Permittee shall, WITHIN 24 HOURS after the discovery of the noncompliance, orally notify the Commissioner.  WITHIN FIVE (5) DAYS of the discovery of the noncompliance, the Permittee shall submit to the Commissioner a written description of the noncompliance; the cause of the noncompliance; the exact dates of the period of noncompliance; and, if the noncompliance has not been corrected, the anticipated time it is expected to continue and steps taken or planned to reduce, eliminate, and prevent recurrence of the noncompliance.    2.  For noncompliance occurrences not required to be reported under Part VI. A.1, above, the Permittee shall submit a written report to the Commissioner WITHIN 30 DAYS after the noncompliance is discovered. 

B. REPORTING PLANNED CHANGES 

 The Permittee shall give advance written notice to the Commissioner as soon as possible of any planned physical alteration of or addition to the Permitted Facility and of any activity that may result in noncompliance with its Permit or with any requirement of state or federal law.  This notice does not relieve the Permittee of:     1.  The requirement to obtain a modification of this Permit or,    2.  Any liability for noncompliance with this Permit or the law. 

C. ANNUAL REPORTING REQUIREMENTS 

   1.  Annual Report.  The Permittee shall submit an annual report to the MPCA no later than March 1st of each year, for the previous calendar year.  The annual report must include the information required by Minn. R. 7045.0482, subp. 2.  

2.  Financial Assurance for Closure with Applicable Cost Estimate Updates and Liability Coverage.  The Permittee shall by March 31st of each year submit to the MPCA updated closure financial assurance (with cost updates) and liability coverage, to reflect current financial conditions.  

Page 39: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

33 of 43 EPA ID MND981098478 

Revised 2/13 

  3.  Waste Minimization.  The Permittee shall certify each year at the time of submission of its annual report that a program is in place to reduce the volume and toxicity of waste to the maximum degree economically practicable, and that the method used to manage waste minimizes present and future threats to human health and the environment to the extent practicable as required by Minn. R. 7045.0478, subp. K.    4.  Fees.  The Permittee shall pay the required annual facility fee as specified in Minn. R. 7046.0020. 

D. CERTIFICATION AND SIGNATORY REQUIREMENTS 

 All reports or other information required to be submitted to the Commissioner in accordance with the terms and conditions of this Permit shall carry the certification required by Minn. R. 7001.0070 and 7001.0540. 

E. SUBMITTAL OF WRITTEN REPORTS 

 All written reports required to be submitted by the Permittee shall be sent to:  

Minnesota Pollution Control Agency Supervisor, Land Permits Unit Industrial Division Minnesota Pollution Control Agency 520 Lafayette Road North St. Paul, Minnesota  55155‐4194 

Page 40: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

34 of 43 EPA ID MND981098478 

Revised 2/13 

PART VII.  CLOSURE 

 

A. NOTIFICATION OF CLOSURE 

 The Permittee shall notify the Commissioner at least 45 days prior to the expected date of commencement of full or partial closure of the Facility.  The written notice shall include:    1.  The anticipated last day of operation.    2.  The existing inventory count and inventory reduction schedule.    3.  A discussion of how conditions of this Permit and state and federal law will be met. 

B. CLOSURE PLAN 

 If the Permittee shall decide to close all or a portion of the RCRA Facility, the Permittee shall close in accordance with the MPCA‐approved closure plan in effect at the time.  The present MPCA‐approved closure plan is set forth in Section 11 of the Permit Application.  The MPCA may require additional closure work plans to be developed if necessary to reflect Facility specific closure or partial closure activities to be conducted. 

C. TIME ALLOWED FOR CLOSURE  After receiving the final volume of hazardous waste at the Facility, the Permittee shall remove all hazardous wastes in accordance with the closure plan schedule in effect at the time, which shall not exceed 180 days unless approved by the Commissioner.  The present closure schedule is detailed in the closure plan set forth in Section 11 of the Permit Application. 

D. CERTIFICATION OF CLOSURE  WITHIN 60 DAYS after closure is completed, the Permittee shall submit to the Commissioner a certification signed by the Permittee and by an independent registered professional engineer that the Facility has been closed in accordance with the MPCA‐approved closure plan and any additional closure work plans if developed.  The certification shall contain language as stated in Minn. R. 7001.0070 and 7001.0540.  

Page 41: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

35 of 43 EPA ID MND981098478 

Revised 2/13 

PART VIII.  CORRECTIVE ACTION FOR SOLID WASTE MANAGEMENT UNITS 

 The Permittee maintains that currently, there are no known releases of hazardous waste or constituents requiring corrective action from any solid or hazardous waste management units (as defined in Minn. R. 7045.0020, subp. 36, item a.) at the Facility.  If any information becomes available concerning releases from solid or hazardous waste management units, the Commissioner will commence an action to modify this Permit to require the Permittee to undertake appropriate corrective action in accordance with Minn. R. 7045.0485.  

Page 42: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

36 of 43 EPA ID MND981098478 

Revised 2/13 

PART IX.  GENERAL CONDITIONS  

A. NO RELEASE FROM LIABILITY  

Issuance of this Permit by the MPCA does not release the Permittee from any liability, penalty, or duty imposed by Minnesota or federal statutes, rules or local ordinances, except the obligation to obtain this Permit. 

B. THIRD PARTY LIABILITY  

Issuance of this Permit by the MPCA does not release the Permittee from or affect any liability which either of the Permittee may incur as a result of the operation of the Permitted Facility. 

C. FUTURE RULES  

This Permit does not prevent the future adoption by the MPCA of pollution control rules, standards, or orders more stringent than those now in existence and does not prevent or affect the enforcement of these rules, standards, or any orders against the Permittee. 

D. PROPERTY RIGHTS  

This Permit does not convey a property right or an exclusive privilege. 

E. OBLIGATION TO ENFORCE  

This Permit does not obligate the MPCA or the Commissioner to enforce laws, rules, or plans. 

F. LIABILITY/RESPONSIBILITY  

This Permit authorizes the Permittee to perform the activities described in this Permit under the conditions of this Permit.  In issuing this Permit, the State and Commissioner assume no responsibility for injury to persons or damage to property or the environment caused by the activities of the Permittee including those activities authorized, directed, or undertaken under this Permit.  To the extent the State and Commissioner may be liable for the activities of State employees, that liability is explicitly limited to that provided in the Tort Claims Act, Minn.  Stat. § 3.736. 

G. DEFENSE UNDER OTHER STATUTES AND RULES  

Compliance with the terms of this Permit does not constitute a defense to any action brought under Section 7003 of the Resource Conservation and Recovery Act, Section 106(a) of the Comprehensive Environmental Response, Compensation, and Liability Act of 1980 (42 U.S.C. 9601 et seq., commonly known as CERCLA), the Minnesota Environmental Response and Liability Act of 1983 (Minn. Stat. ch. 115B), Minn. Stat. chs. 116, 400, 473, or any other Minnesota or Federal statutes, rules or regulations, or local ordinances.  

Page 43: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

37 of 43 EPA ID MND981098478 

Revised 2/13 

H. MINIMUM STANDARDS 

 This Permit establishes minimum standards for the operation of the Permitted Facility.  Nothing in this Permit precludes the Permittee from taking additional steps to protect the public health or welfare or the environment so long as these additional steps are not inconsistent with the terms and conditions of this Permit.  The Permittee is solely responsible for ensuring that the Permitted Facility adequately safeguards public health and welfare and the environment. 

I. DUTY TO COMPLY 

 The Permittee shall perform the actions and conduct the activity authorized by this Permit in accordance with the plans and specifications approved by the MPCA and in compliance with  the conditions of this Permit and applicable local, state, and federal hazardous waste laws, rules, ordinances, and regulations. 

J. WASTE MINIMIZATION 

 In accordance with Part VI.C.3, the Permittee shall certify at least annually that they have a program in place to reduce the volume and toxicity of the waste to the maximum degree economically practicable, and that the method used to manage the waste minimizes present  and future threats to human health and the environment to the extent practicable. 

K. FALSE STATEMENTS 

 The Permittee shall not knowingly make a false or misleading statement, representation, or certification in a record, report, plan or other document submitted to the MPCA or to the Commissioner.  The Permittee shall IMMEDIATELY upon discovery report to the Commissioner an error or omission in any such record, report, plan, or other document. 

L. DUTY TO PROVIDE INFORMATION 

 The Permittee shall, when requested by the Commissioner, submit within a reasonable time the information and reports that are relevant to the control of pollution, regarding the construction or operation of the Facility covered by this Permit, or regarding the conduct and the activity covered by this Permit, in accordance with Minn. Stat. §§ 115.04 and 116.07, subd. 9. 

M. INSPECTION AND ENTRY 

 When authorized by Minn. Stat. §§ 115.04, 115B.17, subd. 4, or 116.091, and upon presentation of proper credentials, the MPCA, or an authorized employee or agent of the MPCA, shall be allowed by the Permittee to examine and copy books, papers, records, or memoranda pertaining to the construction, modification, or operation of the Facility covered by this Permit or pertaining to the activity covered by this Permit. 

Page 44: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

38 of 43 EPA ID MND981098478 

Revised 2/13 

N. DUTY TO MITIGATE 

 If the Permittee discovers, through any means, including notification by the MPCA, that noncompliance with a condition of the Permit has occurred, the Permittee shall promptly take  all reasonable steps to minimize the adverse impacts on human health, public drinking water supplies, or the environment resulting from the noncompliance. 

O. BANKRUPTCY 

   1.  Notification of Bankruptcy.  The Permittee shall notify the Commissioner by certified mail of the commencement of a voluntary or involuntary proceeding under United States Code, Title 11, Bankruptcy, naming the Permittee as debtor, WITHIN TEN (10) DAYS after commencement of the proceeding.    2.  Incapacity of Financial Assurance and Liability Coverage.  The Permittee currently meets the requirements regarding Financial Assurance for Closure through the use of an Irrevocable Standby Letter of Credit and for Liability Coverage through an insurance policy. The Permittee shall be deemed to be without such required financial assurance or liability coverage in the event of bankruptcy proceedings involving any financial institution or insurer providing such financial assurance or liability coverage.  In such event, the Permittee shall have 60 days, upon notifying the MPCA of the bankruptcy proceeding, to obtain other means of financial assurance and liability coverage.  Failure to do so shall constitute a violation of this Permit.  (Minn. R. 7045.0522, subp. 2) 

P. MODIFICATION, REVOCATION, AND REISSUANCE OF THIS PERMIT 

 This Permit may be modified, revoked and reissued, or revoked without reissuance for cause, as specified in Minn. R. 7001.0170 to 7001.0190 and Minn. R. 7001.0730.  The filing of a request for a Permit Modification, Revocation and Reissuance, or Revocation without Reissuance, or the notification of planned changes or anticipated noncompliance on the part of the Permittee does not stay or affect the applicability or enforceability of a Permit condition.  Requests for modification of plans or specifications integral to this Permit must be approved by the Commissioner prior to implementing the requested change. 

Q.  OPERATION DURING REISSUANCE PERIOD 

 If the Permittee wishes to continue an activity allowed by this Permit after the expiration date of this Permit, the Permittee shall submit a complete application for reissuance of the Permit at least 180 calendar days before this Permit expires, unless written permission for a later date has been granted by the Commissioner. 

Page 45: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

39 of 43 EPA ID MND981098478 

Revised 2/13 

R.  CONTINUATION OF EXPIRED PERMIT 

 This Permit will remain in effect beyond the Permit's expiration date if the Permittee has submitted a timely and complete Application for reissuance of the Permit provided that the Commissioner determines, based on available information, that all of the following are true:    1.  The Permittee is in compliance with the terms and conditions of the expired Permit;       2.  The Permittee continues at all times to work diligently and in good faith to meet the requirements and satisfy the concerns of the Commissioner with respect to the Permit Application; and    3.  The Commissioner, through no fault of the Permittee, has not taken final action on the Application before the expiration date of this Permit. 

S. TRANSFER OF PERMITS 

 This Permit is not transferable to any person without the express written approval of the MPCA, and then only after compliance with the requirements of Minn. R. 7001.0190 and 7045.0452, subp. 3. item D.  A party to whom this Permit has been transferred shall comply with the terms and conditions of this Permit. 

T. SEVERABILITY 

 The provisions of this Permit are severable, and if any provision of this Permit, or the Application of any provision of this Permit to any circumstance is held invalid, the Application of such provision to other circumstances and the remainder of this Permit shall not be affected thereby. 

U.  EMERGENCY PERMITS 

 The Permittee need not comply with the conditions of this Permit to the extent and for the duration this noncompliance is authorized in an emergency Permit in accordance with Minn. R. 7001.0690. 

V.  AUTHORIZED SIGNATURES 

 The Permittee may allow an authorized representative to sign reports submitted in accordance with the requirements of this Permit in accordance with the conditions of Minn. R. 7001,0720, subp. 2, item F.  

Page 46: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

40 of 43 EPA ID MND981098478 

Revised 2/13 

PART X.  REVIEW OF SUBMITTALS AND EXTENSION OF SCHEDULES 

 

A. REVIEW OF SUBMITTALS 

 The review of each submittal, document, report, or schedule (collectively referred to hereafter as "submittal") which is required to be submitted to the Commissioner for review and approval shall be as follows:    1.  The Commissioner shall review each submittal made by the Permittee as required by this Permit.  In the event the submittal is approved, it shall become an integral and enforceable part of this Permit.  If the submittal is disapproved in whole or part, the Commissioner shall notify the Permittee in writing and shall explain the amendments or revisions that are necessary to bring the submittal into compliance with this Permit.    2.  Within 30 calendar days of receipt of any notice of disapproval or modification, or on the first working day thereafter (if said 30th day fell on a Sunday or Holiday) the Permittee shall:    a.  Submit revisions to correct inadequacies that led to disapproval, or,     b.  State in writing the reasons why the submittal, as originally submitted, should be approved.      The Permittee may have longer than 30 days to respond if the longer time period is specified in the Commissioner's review letter referenced in paragraph 1.    3.  If, within 30 calendar days from the date of the Permittee submission under  paragraph 2, above, the parties have not reconciled all issues with respect to the submittal, the Commissioner shall inform the Permittee of the second disapproval of the submittal and whether in the Commissioner's view, the Permittee may be in violation of the Permit.  In such event, the matter may be referred for enforcement action.    4.  The Commissioner and the Permittee shall provide the opportunity to consult with each other during the review of submittals or modifications. 

Page 47: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

41 of 43 EPA ID MND981098478 

Revised 2/13 

B. EXTENSION OF SCHEDULES 

 All time extensions must be requested by the Permittee in writing.  The requests shall specify the reasons why the extension is needed.  Extensions shall only be granted for such a period of time as the Commissioner determines is reasonable under the circumstances.  A requested extension shall not be effective until approved by the Commissioner.  The burden shall be on the Permittee to demonstrate to the satisfaction of the Commissioner that the request for the extension has been submitted in a timely fashion and that good cause exists for granting the extension and that the extension shall have no adverse effect upon human health or the environment.  Extension of compliance schedule dates provided in this Permit may be granted if requests are submitted in a timely fashion and good cause exists for granting the extension, and if the extension would have no adverse effect upon human health or the environment. 

Page 48: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

42 of 43 EPA ID MND981098478 

Revised 2/13 

PART XI.  LAND DISPOSAL REQUIREMENTS 

 

A. GENERAL CONDITIONS 

   1.  The Permittee shall comply with all applicable land disposal restrictions in Minn. R. 7045.1390, which incorporates by reference 40 CFR pt. 268, with the exceptions to incorporation listed in Minn. R. 7045.1390 and 7045.0090. All of the requirements in this Part XI are subject to the exceptions to incorporation listed in Minn. R. 7045.1390 and Minn. R. 7045.0090.    2.  A mixture of any restricted waste with any nonrestricted waste is a restricted waste under 40 CFR § 268.1.    3.  The Permittee shall not in any way dilute a restricted waste or the residual from treatment of a restricted waste as a substitute for adequate treatment to achieve compliance with the treatment standards in 40 CFR pt. 268, subp. D, to circumvent the effective date of a prohibition in 40 CFR pt. 268, subp. C, to otherwise avoid compliance with a prohibition in  40 CFR pt. 268, subp. C, or to circumvent a land disposal prohibition imposed by Section 3004 of RCRA.     4.  The Permittee shall prepare and maintain a current list of the hazardous waste codes for all wastes handled at the Facility that are identified or listed in 40 CFR § 268.20‐.39 . The list shall include all wastes and waste codes handled at the Facility, and any associated treatment standards, and shall be updated through the inclusion of new treatment standards, as promulgated or amended. This list shall be provided to the MPCA representative, or its designees, upon request.  B. TESTING AND RELATED REQUIREMENTS    1.  The Permittee shall test, in accordance with 40 CFR § 268.7, any waste generated at the Facility, or use knowledge of the waste, to determine if the waste is restricted from land disposal.    2.  For restricted wastes with treatment standards expressed as concentrations in the waste extract, as specified in 40 CFR § 268.40, the Permittee shall test the treatment residues, or an extract of such residues developed using the test methods described in 40 CFR § 268.40(b) (Method 1311, Toxicity Characteristic Leaching Procedure or TCLP) to assure that the treatment residues or extract meet the applicable treatment standards of 40 CFR § 268.40. Such testing shall be performed pursuant to the requirements of Minn. R. 7045.0458.  

Page 49: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

43 of 43 EPA ID MND981098478 

Revised 2/13 

  3.  A restricted waste for which a treatment technology is specified in 40 CFR § 268.42 may be land disposed after it is adequately treated using that specified technology or an equivalent treatment method approved by the EPA under the procedures set forth in 40 CFR § 268.42.     4.  For restricted wastes with treatment standards expressed as concentrations in the waste, as specified in 40 CFR § 268.40, the Permittee shall test the treatment residues (not an extract of such residues) to assure that the treatment residues meet the applicable treatment standards of 40 CFR § 268.40. Such testing shall be performed as required by 40 CFR § 268.40.   C. STORAGE PROHIBITIONS    1.  The Permittee shall comply with all the applicable prohibitions on storage of restricted wastes specified in 40 CFR § 268.50.    2.  The Permittee may store restricted wastes in tanks and containers solely for the purpose of the accumulation of such quantities of hazardous wastes as necessary to facilitate proper recovery, treatment, or disposal provided that:     a.  Each container is clearly marked to identify its contents and the date each period of accumulation begins.    b.  Each tank is clearly marked with a description of its contents, the quantity of each hazardous waste received, and the date each period of accumulation begins, or such information for each tank is recorded and maintained in the operating record at the Facility.    3.  The Permittee may store restricted wastes for up to one (1) year unless the MPCA can demonstrate that such storage was not solely for the purpose of accumulating such quantities of hazardous waste as are necessary to facilitate proper recovery, treatment or disposal.    4.  The Permittee may store restricted wastes beyond one (1) year provided that the Permittee proves that such storage was solely for the purpose of accumulating such quantities of hazardous waste as are necessary to facilitate proper recovery, treatment or disposal.     5.  The Permittee shall not store any liquid hazardous waste containing polychlorinated biphenyls (PCBs) at concentrations greater than or equal to 50 ppm unless the waste is stored in a storage facility that is a commercial storer of PCB waste as defined in 40 CFR § 761.3. This waste must be removed from storage and treated or disposed within one (1) year of the date when such wastes are first put into storage. Part XI.C.4 above, which allows storage for over one (1) year with specified demonstration, does not apply to PCB wastes.   

 

Page 50: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

APPENDICES

Page 51: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

APPENDIX I - FACILITY MAP

Page 52: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

I E

FACILITY MAP

INDUSTRY, INC.2430 Rose Place, Roseville, MN 55113 N

Page 53: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

I

II

APPENDIX 11- WASTE CODES

Page 54: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. ReRA Part B Application 082012

SIEMENS INDUSTRY, INC.ANTICIPATED WASTE RECEIPTS

(See footnotes on page 6 of 15for codes denoted by the asterisk, *, and other notej)

ANTICIPATED WASTE RECEIPTS BY RCRA WASTE TYPE ANDPROCESS CODE •

/

WASTE TYPE

HYDROCHLORIC ACID' 0002, F006, *examples include:

Hydrochloric Acid Based ActivatorHydrochloric Acid CleanerHydrochloric Acid PickleHydrochloric Acid Solder Brightener

SULFURIC ACID 0002, F006, FOl9, *examples include:

PROCESSCODE

SOlS02

TOl

SOlS02

TOlSulfuric Acid Anodizing BathsSulfuric Acid Based AcceleratorSulfuric Acid CleanerSulfuric Acid "Holding" Solution (P.C. Shops)

OTHER ACIDS 0001,0002, F006, FOl9,MNOI,*examples include:

Acetic AcidFluoboric based Accelerator AcidHydrofluoric AcidNitric Acid (Non-Chromate)Phosphoric AcidBrightener Solution

CYANIDE 0002,0003, F007, F008F009, FOlO, FOll, FOl2,*

examples include:

Cyanide Based DescalersCyanide Based Strippers

SOlS02

TOI

SOlS02

TOl

Section I Page I ofl5 EPA ID # MND98 1098478

Page 55: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. ReRA Part B Application 082012

Cyanide Contaminated Alkaline CleanersCyanide Dead RinsesCyanide Plating Solutions

CHROMIUM 0001,0002, F006, FOl9, F035,* SOlexamples include: S02

TOlChromatesChrome Based EtcherChrome Dead RinsesChrome Plating SolutionCCA Wood Treatment Wastes

COPPER ETCHANTSexamples include:

000 I, 0002, F006, * SOIS02

TOIDifferent types of copper etch ants shall bemaintained separate unless permission isrequested and approval is given by SII.The types of copper etchants acceptable atSII include:

AmmoniacalAmmonium BifluorideAmmonium PersulfateCupric ChloridePeroxy-SulfuricPotassium PermanganatePotassium PersulfateSodium Persulfate

CHELA TED 0002, F006, MNO I, *examples include:

Immersion Tin PlatingElectroless Copper PlatingElectroless Nickel PlatingElectroless Tin Plating

SOlS02

TOI

CLEAN ALKALINEexamples include:

Alkaline DeveloperAlkaline Resist Strip

Section I

0002, F006, *

Page 2 of IS

SOlS02

TOI

EPA ID # MND98I098478

Page 56: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. ReRA Part B Application 082012

ALKALINE 0002, F006, F019, *examples include:

Alkaline ElectrocleanerAlkaline Soak CleanerAlkaline Descalers (Non-Cyanide)

SOlS02

TOI

SPENT ION EXCHANGE RESIN 0002,0003, SOlF006, F019,.* S02

TOl

SLUDGE 0003, F006, F007, F008, F009,FOI0,FOll,FOI2,FOI9, *

examples include:

Aqueous Metal HydroxideSolid Metal HydroxideCopper Sulfate CrystalsQuenching Bath Sludge from Oil BathsSalt Bath Pot Cleaning SolutionsQuenching Wastewater Treatment Sludge

ORGANICS 0001, FOOl, F002, *examples include:

Trichloroethylene1, 1, I-TrichloroethaneMethylene ChlorideTetrachloroethyleneCarbon TetrachlorideChlorobenzeneOrthodichlorobenzeneChlorinated Fluorocarbons

FLAMMABLESDOOl, F003, F004., F005, *, **

COOLANTS/OILS 0001, K048, K049, K050,K051, K052, *, ***

MISCELLANEOUSexamples incliJde:

MN Regulated MNOI, MN02Spent Activated Carbon

SOlS02

TOIT04

SOlS02

TOl

SOl

SOl

SOlS02

TOIT04

Section I Page 3 of IS EPA ID # MND981098478

Page 57: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. RCRA Part B Application 082012

and Filters - F006, F007, F008,F009, FOIO, FOIl,F012, FOI9, *

Spent Pickle Liquor - K062Emission Control Dust or Sludge - K061Low level mercury waste - D009; *****Landfill leachate - F039

HAZARDOUS WASTES FROM COMMERCIAL CHEMICAL PRODUCTS

Section I

.POl3P021P022P029P030P033P063P074P075P098P099PIOIPI04PI06Pl2lU002U012U246U03lU159U052U2l1U037U044U032U052U052U056U057U070U071uonU075U078U079

barium cyanidecalcium cyanidecarbon disulfidecopper cyanidescyanide****chlorine cyanidehydrogen cyanidenickel cyanidenickel (II) cyanidepotassium cyanidepotassium silver cyanideethyl cyanidesilver cyanide.sodium cyanidezinc cyanideacetoneanilinebromine cyanideI-butanol2-butanone2-butanolcarbon tetrachloridechlorobenzenechloroformchromic acid, calcium saltcresolscresylic acidcyclohexanecyclohexanoneo-dichlorobenzenem-dichlorobenzenep-dichloroethylenedichlorodifluoromethane1, l-dichloroethylene1, 2-dichloroethylene

Page 4 of 15

SOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOl.SOISOlSOlSOlSOlSOlSOlSOlSOl

SOlSOlSOlSOl

EPA ID # MND981 098478

Page 58: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. RCRA Part 8 Application 082012

Section I

U088UOOIU067U076U077U208U209U227U043U042U078U079U210UI12U038UI17UI22.U133U134U134UI40U080U075U211UI21UI54UI45U226U080UI59UI61UI65UI69UI88UI96U202U208U209U210U213U220U226U227U228U228

diethyl phthalateethanolethane, I, 2-dibromo-ethane, I, I-dichloro-ethane, I, 2-dichloro-ethane, I, I, I, 2-tetrachloro-ethane, I, I, I, 2-tetrachloroethane, I, I, 2-trichloro-ethene, chloroethene, 2-chloroethoxy-ethene, I, I-dichloro-'ethene, trans-I, 2-dichloro-ethene, I, I, 2, 2-tetrachloro- .ethyl acetateethyl 4, 4'-dichlorobenzylateethyl etherformaldehydehydrazinehydrofluoric acidhydrogen fluorideisobutyl alcoholmethane, dichloro-methane, dichlorodifluoro-methane~ tetrachloro-methane, trichlorofluoro-methanol alcoholmethyl chloridemethyl chloroformmethylene chloride,methyl ethyl.ketonemethyl isobutyl ketonenaphthalenenitrobenzenephenolpyridinesaccharin and saltsI, I, I, 2-tetrachloroethaneI, I, 2, 2-tetrachloroethanetetrachloroethylenetetrahydrofurantolueneI, I, I-trichloroethaneI, I, 2-:trichloroethanetrichloroethenetrichloroethylene

Page 5 of 15

SOlSOlSOlSOlSOlSOlSOlSOl

SOlSOlSOlSOlSOlSOlSOlSOl

.SOlSOl

SOlSOlSOlSOlSOlSOlSOlSOlSOl

SOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOlSOl

EPA ID # MND98 1098478

Page 59: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. RCRA Part B Application 082012

U 121 trichloromonofluoromethaneU239 xylene

FOOTNOTES:

SOlSOl

*

**

***

*********

These wastes may also be hazardous by toxic characteristics (per the ToxicityCharacteristic Leaching Procedure, TCLP). EPA Waste Codes D004-D043apply.

Flammables are to include xylenes, ethyl acetate, ethyl benzene, ethyl ether (andother ethers), methyl isobutyl ketone, n-butyl alcohol, cyclohexanone, methanol(and other alcohols), cresols, cresylic acid, nitrobenzene, toluene, methyl ethylketone, ethanol, cyclohexane, 2-butanol, 2-butanone, benzene, oils, naphthalene,carbon disulfide, isobutanol, pyridine, acetone, various hydrocarbon distillates(such as keros~ne, mineral spirits, paint thinners, etc.) paint or ink wastes andmixtures ofthese solvents. Other solvents with flash points below 1400 F. thatare carcinogens or have unusual storage or safety requirements would not beaccepted at Siemens Water Technologies Corp.

Oils are defined by the proposed EPA definition for used oils. "Used oil" ispetroleum derived or synthetic oil, including but not limited to, oil used as a:

i) lubricant (engine~ turbine or gear);ii) hydraulic. fluid (including transmission fluid);iii) metalworking fluid (including cutting, grinding, machining, rolling,

stamping,quenching and coating oils); oriv) insulating fluid and coolant and which is contaminated through use or

subsequent management.

Soluble cyanide salts not elsewhere specified.Mercury wastes, D009 .:Only mercury compounds will be accepted at thefacility, no elemental mercury .

I

Section I Page 6 of 15 EPA ID # MND981098478

Page 60: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. RCRA Part B Application 082012

ANTICIPATED WASTE RECEIPTS BY RG:RAWASTE CODE

LISTED WASTES as found in Minnesota Rules 7045.0135

FOOl.- tetrachloroethylene- trichloroethylene~methylene chloride- I, I, I-trichloroethane- carbon tetrachloride- chlorinated fluorocarbon- mixtures of 10% or more of these solvents or their sludges

- tetrachloroethylene- methylene chloride- trichloroethylene- I, I, I-trichloroethane- chlorobenzene- t I, I, 2-trichloro-l, 2, 2-trifluoroethane- orthodichlorobenzene- trichlorofluoromethane- mixtures bf 10% or more of these solvents or their sludges

- xylene- ethyl ether- acetone- methyl isobutyl ketone- ethyl acetate-n-butyl alcohol~ethyl benzene- cyclohexanone- methanol- mixtures of 10% or more of these solvents or their sJudges

- cresols- cresylic acid- nitrobenzene- mixtures of 10% or more ofthese solvents or their sludges

- toluene- methyl ethyl ketone

Section 1 Page 7 of 15 EPA ID # MND981 098478

Page 61: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. ReRA Part B Application 082012

I'

I

- carbon disulfide- isobutanol- pyridine- mixtures of 10% or more ofthese solvents or their sludges

F006 Examples include treatment sludges from the following wastewaters.

- hydrochloric acid based activator- hydrochloric acid cleaner- hydrochloric acid solder brightener- sulfuric acid anodizing baths- sulfuric acid. based accelerator'- sulfuricaCid cleaner- sulfuric acid "holding" solution (P.e Shops)- acetic acid- fluoboricbased accelerator acid- hydrofluoric acid- nitric acid (non-chromate)- phosphoric acid- chromates- chromium based etcher, - chromium dead rinses- chromium.plating solution- copper etchants including: .

- ammoniacal- ammonium bifluoride- ammonium persulfate- cupric chloride- peroxy-sulfuric- potassium permanganate- potassium persulfate- sodium persulfate

- electro less copper plating- electro less nickel plating- alkaline developer- alkaline resist strip- alkaline electro cleaner- alkaline soak cleaner- alkaline descalers (non-cyanide)- liquid metal hydroxides- solid metal hydroxides- copper sulfate crystals- spent activated carbon and filters

Section I Page 8 ofl5 EPA lD # MND981098478

Page 62: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

(Siemens Industry, Inc. RCRA Part B Application 082012

F007 Spent cyanide plating bath solutions from electroplating operations, including:

- cyanide based descalers- cyanide based strippers- cyanide contaminated alkaline cleaners- cyanide dead rinses- cyanide plating solutions

F008 Plating sludges from cyanide bath tank bottoms, from electroplating operations,including: .

- cyanide based descalers- cyanide based strippers- cyanide contaminated alkaline cleaners- cyanide dead rinses- cyanide plating solutions

F009 Spent cyanide strippers and cleaner solutions, from electroplating operations,including:

- cyanide based descalers- cyanide based strippers- cyanide contaminated alkaline cleaners- cyanide dead rinses- cyanide plating solutions

FO10 - quenching bath sludge from oil baths where cyanides are used in the process

FOII - spen.t cyanide solutions from salt bath pot cleaning, operations from metal heattreating

FO12 - quenching wastewater treatment sludge from metal heat treating operationswhere cyanides are used in the process

FO19 Examples include treatment sludges from the following wastewaters.

- sulfuric acid anodizing baths- hydrofluoric acid- chromates- alkaline electro cleaner- alkaline soak cleaner- spent activated carbon and filters.

I

Section I Page 9 ofl5 EPA ID # MND981098478

Page 63: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. RCRA Part B Application 082012

F035 - wastewaters, process residuals, preservative drippage, and sp,ent formulationsfrom wood preserving process that use inorganic preservatives containingarseni~ or chromium.

F039 - leachate from the disposal of more than one restricted waste classified ashazardous ./

K048 - dissolved air flotation (DAF) float from the petroleum refming industry

K049 - slop oil emulsion solids from the petroleum refining industry

K050 - heat exchanger bundle cleaning sludge from the petroleum refming industry

KOSI - American Petroleum Institute separator sludge from the petroleum refiningindustry as specified in The Manual on Disposal of Refinery Wastes, Volume I,issued by the American Petroleum Institute, (Washington, D.C., 1969),available at the State of Minnesota Law Library

K052 - tank bottoms (leaded) from the petroleum refinery industry

K061 - emission control dust or sludge from the primary production of steel in electricfurnaces

K062 - spent pickle liquor from steel finishing operations

PO13 barium cyanideP021 calcium cyanideP022 carbon disulfideP029 copper cyanidesP030 cyanide (soluble cyanide salts), not elsewhere specifiedP033 chlorine cyanideP063 hydrogen cyanideP074 nickel cyanideP075 nickel (II) cyanideP098 potassium cyanideP099 potassium silver cyanidePI 0 1 ethyl cyanidePI04 silver cyanidePI06 sodium cyanideP 121 zinc cyanide I

U002 acetoneU012 anilineU246 bromine cyanideU031 I-butanolU 159 2-butanone

Section I Page 10 of 15 EPA ID # MND98 1098478

Page 64: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. ReRA Part B Application 082012

U053 2-butanolU211 carbon tetrachlorideU037 chlorobenzeneU044 chloroformU032 chromic acid, calcium saltU052 cresolsU052 cresylic acidU056 cyclohexaneU057 cyclohexanoneU070 o-dichlorobenzeneU07I m-dichlorobenzeneuon p-dichlorobenzeneU075 dichlorodifluoromethaneU078 I, I-dichloroethyle~eU078 I, 2-dichloroethyleneU088 diethyl phthalateUOOI ethanolU067 ethane, I, 2-dibromo-U076 ethane, I, I':dichloro-uon ethane, I, 2-dichloro-U208 ethane, I, I, I, 2-tetrachloro-U209 ethane, I, I, 2, 2-tetrachloro-U227 ethane, I, I, 2-trichloro-U043 ethene, chloro-U042 ethene,2-chloroethoxy-uon ethene, I, I-dichloro-U079 ethene, trans:' I, 2-dichloro-U210 ethene, I, I, 2, 2-tetrachloro-U I 12 ethyl acetateU038 ethyl 4, 4'-dichlorobenzilateU I I 7 ethyl etherU 122 formaldehydeU 133 hydrazineU 134 Hydrofluoric acidU 134 hydrogen fluorideUI40 isobutyl alcoholU080 methane, dichloro-U075 methane, dichlorodifluoro-U211 methane, tetrachloro-U 121 methane, trichlorofluoro-U044 methane, trichloro-U 121 methane, trichlorofluoro-U 154 methanol alcoholUI45 methyl chlorideU226 methyl chloroform

Section I Page II of 15 EPA ID # MND981098478

Page 65: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. RCRA Part 8 Application 082012

U053 2-butanolU211 carbon tetrachlorideU037 chlorobenzeneU044 chloroformU032 chromic acid, calcium saltU052 cresolsU052 cresylic acidU056 cyclohexaneU057 cyclohexanoneU070 o-dichlorobenzeneU07l m-dichlorobenzeneuon p-dichlorobenzeneU075 d ichlorod ifluoromethaneU078 1, I-dichloroethyleneU078 1, 2-dichloroethylene

I. U088 diethyl phthalateUOOl ethanol /

U067 ethane, l, 2-dibromo-U076 ethane, 1, l-dichloro-uon ethane, l, 2-dichloro-U208 ethane, l, l, l, 2-tetrachloro-U209 ethane, l, l, 2, 2-tetrachloro-U227 ethane, I, I, 2-trichloro-U043 ethene, chloro-U042 ethene, 2-chloroethoxy-U078 ~thene, I, l-dichloro-U079 ethene, trans-l, 2-dichloro-U210 ethene, l, I, 2, 2-tetrachloro-UI12 ethyl acetateU038 ethyl 4, 4'-dichlorobenzilateUll7 ethyl etherUl22 formaldehydeU133 hydrazineU134 Hydrofluoric acidUl34 hydrogen fluorideUl40 isobutyl alcohol

I

U080 methane, dichloro-U075 methane, dichlorodifluoro-U2ll methane, tetrachloro-Ul2l methane, trichlorofluoro-U044 methane, trichloro-Ul2l methane, trichlorofluoro- .Ul54 methanol alcoholUl45 methyl chlorideU226 methyl chloroform

.•.

Section I Page 11 of 15 EPA ID # MND98 1098478

Page 66: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. RCRA Part B Application 082012

U080 methylene chlorideU159 methyl ethyl ketoneU161 methyl isobutyl ketoneU 165 naphthaleneU169 nitrobenzeneUI88 phenolU 196 pyridineU202 saccharin and saltsU208 I, 1, 1, 2-tetrachloroethaneU209 1, 1, 2, 2-tetrachloroethaneU2IO tetrahydrofuranU220 tolueneU226 1, 1, I-trichloroethaneU227 1, I, 2-trichloroethaneU228 trichloroetheneU228 trichloroethyleneU 121 trichloromonofluoromethaneU239 xylene

Section I , Page 12 ofl5 EPA ID # MND98 1098478

Page 67: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, In.c. RCRA Part BApplication 082012

CHARACTERISTIC WASTES as found in Minnesota Rules 7045.0131

000 I - ignitable wastes, examples include:- ethanol and other alcohols- xylenes- ethyl acetate- ethyl benzene- ethyl ether (and other ethers)- methyl isobutyl ketone- n-butyl alcohol- cyclohexanone- methanol (and other alcohols)- cresols- cresylic acid- cyclohexane- 2-butanol- 2-butanone- benzene- nitrobenzene- toluene- methyl ethyl ketone- carbon disulfide- isobutanol- pyridine- acetone- various hydrocarbon distillates (such as kerosene, mineral spirits, paintthinners, etc.)

- paint wastes- waste inks- oils- naphthalene- aniline

000 I - oxidizers, examples include:- hydrogen peroxide- sodium hypochlorite- calcium hypochlorite- potassium permanganate- nitric acid- sodium and potassium dichromate- sodium and potassium chromate- sodium and potassium chlorate- sodium and potassium perchlorate- sodium and potassium persulfate

Section I Page 13 of 15 EPA ID # MND98 1098478

Page 68: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. ReRA Part B Application 082012

0002 corrosiv~s, examples include:- hydrochloric acids- sulfuric acids- acetic acid'- fluoboric based accelerator acid- hydrofluoric acid- nitric acid- phosphoric acid- hydrofluoric acid- hydrogen. fluoride- sodium and"other hydroxides, caustic soda and mixtures- ammonia- phenol- chromic acid

0003 Reactive Wastes examples include:- cyanide solutions and mixtures• chromic acid

Toxic Characteristic Wastes (by TCLP), examples include:

0004 0005 0006 0007 0008 0009 00]0001 ] 00]2 0013 0014 00]5 00]6 00]80019 0020 0021 0022 0023 0024 00250026 0027 0028 0029 0030 0031 00320033 0034 0035 0036 0037 0038 00390040 004] 0042 0043

- chromates- metal sludges, solutions and mixtures- spent activated carbon & Filters- spent ion exchange resins'. spill residues and contaminated soil- paint & ink wastes- waste oils and coolants

F030 (Proposed Code) Coolants and Oils• coolant/oils*

MNO] Unlisted Toxicity Characteristic Waste (Minnesota)examples are thiourea and formaldehyde used in process solutions

MN02 Unrelated Laboratory Waste Mixtures, Not Otherwise Regulated (Minnesota)See Minnesota Rules 7045.0137

Section I Page 14 of 15 EPA 10 # MND98 1098478

Page 69: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

Siemens Industry, Inc. ReRA Part B Application 082012

(

*

. ,

Oils are defined by the proposed EPA defmition for used oils. "Used oil" ispetroleum derived or synthetic oil, including but not limited to, oil used as a:

i) lubricant (engine, turbine or gear);ii) hydraulic fluid (including transmission fluid);iii) metalworking fluid (including cutting, grinding, machining, rolling,. stamping, quenching and coating oils); or

iv) insulating fluid and coolant and which is contaminated through use or subsequentmanagement.

Section 1 Page 15 of 15 EPA ID # MND98 1098478

Page 70: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

APPENDIX 111- ExpANSION DRAWING

Page 71: DRAFT PERMIT FOR MND981098478 A REISSUED · A. REGULATED/PERMITTED UNITS Siemens Industry Inc. (Facility) is located at 2430 Rose Place, Roseville, Minnesota. The Facility is west

rLOOR TRENCH SYSTEM

--.>-<•......•

,e