-SlOPE DIRECTION OF TAPERED INSUL. @ 1/4"/FT. MIN.
-TAPERED INSUL. CRICKET SLOPED @ 1/2" PER FT.
-CONTRACTOR TO VERIFY DIMENSION IN FIELD.
-INDICATES HIGH POINT OF INSULATION.
-EX. ROOF DRAIN TO BE REMOVED.
-ROOF DRAIN/ SUMP. SEE DETAIL A/A2
-EMERGENCY OVERFLOW SCUPPER. SEE DETAIL M/A2
-METAL COLLECTION BOX. SEE DETAIL N/A2
-METAL DOWNSPOUT. SEE CONST. NOTE #3
-CONC. SPLASH BLOCK. SEE CONST. NOTE #4
-EXISTING VENT STACK. SEE DETAIL B/A2
-EXISTING ROOF EXHAUST FAN. SEE DETAIL C/A2
-EXISTING MECH. UNIT. SEE DETAIL E/A2
-PITCH POCKET TO BE INSTALLED. SEE DETAIL D/A2
-WALKWAY PADS. SEE CONST. NOTE #6
-CONDUIT CURB. SEE DETAIL J/A2
-EX. SUPPORT TO BE REMOVED. SEE DEMO NOTE #4
-EX. MECH. TO BE REMOVED. SEE DEMO NOTE #4
- METAL GUARD RAIL. SEE DETAIL H/A2
SR.
EMR.
MGR.
GENERAL NOTES1. ALL FLAT ROOFS TO RECEIVE 1/4" PER FOOT TAPERED
RIGID INSULATION MINIMUM UNLESS OTHERWISE NOTED.2. FIELD VERIFY ALL DIMENSIONS OF EACH ROOF PRIOR TO
THE BID.3. ALL MATERIALS ARE NEW UNLESS OTHERWISE NOTED
"EXISTING".4. ALL WOOD BLOCKING, PLYWOOD & NAILERS TO BE
PRESSURE TREATED. (P.T.)5. ALL WOOD BLOCKING INDICATED IN DETAILS IS TO BE
ANCHORED TO THE EXISTING STRUCTURE.6. ALL MEMBRANE FLASHING INDICATED IS TO EXTEND A
MINIMUM OF 8". (VERTICAL OR HORIZONTAL).7. CONTRACTOR IS TO SURVEY THE EXISTING ROOF DECKS
W/A LEVEL (AFTER DEMOLITION) TO VERIFY THE SLOPESINDICATED ON PLAN ARE ACCURATE. NOTIFY ARCHITECTIMMEDIATELY OF ANY DISCREPANCIES PRIOR TOPERFORMING ANY ADDITIONAL ROOFING OPERATIONS.
8. CONTRACTOR IS TO INSPECT THE UNDERSIDE OF ALLROOF DECKS PRIOR TO ROOFING OPERATIONS TO INSURETHAT NO INTERIOR MATERIALS, EQUIPMENT, FINISHES OROBJECTS WILL BE PIERCED OR DAMAGED.
9. CONTRACTOR ASSUMES ALL RESPONSIBILITY DURINGPROJECT & WILL REPLACE ANY & ALL DAMAGEDEQUIPMENT W/NO ADDITIONAL COST TO OWNER.
10. SITE AREAS DISTURBED SHALL BE CLEANED &RE-LEVELED, W/LAWN AREAS MAGNETICALLY RAKED TOREMOVE ANY METAL DEBRIS & RE-SEEDED AS REQUIREDTO MATCH ADJACENT CONDITIONS.
11. CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR CLEANUP OF ROOFING MATERIALS & DEBRIS THAT PENETRATESTHE INTERIOR ENVELOPE OF THE BUILDING W/NOADDITIONAL COST TO THE OWNER.
12. SNAKE/CLEAN OUT ALL EXISTING VERTICAL &HORIZONTAL LEADERS OUT TO NEAREST MANHOLEOUTSIDE OF BUILDING.
13. ALL CRICKETS ARE TO BE SLOPED @ A MINIMUM OF 1/2"PER FOOT & COORDINATE CRICKETS AROUND EXIST. HVACUNITS AS REQUIRED TO AVOID PONDING.
14. SNAKE/CLEAN OUT ALL EXISTING VENT STACK BEFORETHE INSTALLATION OF METAL SLEEVE.
15. ALL DRAIN PIPING IS INSULATED ABOVE THE CEILINGS.THE EXACT ROUTE WILL BE DETERMINED IN THE FIELD,MAKE MINOR ADJUSTMENT IN THE ROUTE AT NOADDITIONAL COST TO OWNER.
16. NEW INSULATION TO BE A MINIMUM OF 4" AT ALL EXISTING& NEW ROOF DRAINS.
17. ALL ANTENNAS, CONDUITS & ANY OTHER OBJECTS TOREMAIN AFFECTED BY SCOPE OF WORK TO BE REMOVED& REINSTALLED.
18. CONTRACTOR SHALL COMPLY WITH NFPA 1, CHAPTER 16 &NFPA 241, STANDARD FOR SAFEGUARDINGCONSTRUCTION, ALTERATION & DEMOLITION OPERATIONS.
DEMOLITION NOTES x
1. REMOVE ENTIRE EXISTING ROOFING, INSULATION, BALLASTAND ANY OTHER ASSOCIATED COMPONENTS AFFECTEDBY SCOPE OF WORK.
2. REMOVE ALL EXISTING PERIMETER EDGE DRAINAGEAND/OR WOOD BLOCKING & ASSOCIATED COMPONENTSAFFECTED BY SCOPE OF WORK.
3. REMOVE EXISTING ROOF DRAIN AND ASSOCIATED SUMP.4. REMOVE ALL EXISTING ABANDONED MECHANICAL
EQUIPMENT- DUCT PENETRATIONS, SUPPORTS AND ANYOTHER ROOF EQUIPMENT NOT BEING USED. REMOVE ALLBLOCKING AND.OR OTHER ASSOCIATED COMPONENTSABOVE CORRESPONDING ROOMS/ CLASSROOMS VERIFYWITH OWNER. SEE CONSTRUCTION NOTE #5
5. REMOVE AND RETAIN FOR REINSTALLATION EXISTINGACT/GRID SUPPORTS AFFECTED BY SCOPE OF WORK.
CONSTRUCTION NOTES x
1. INSTALL NEW .60 MILL EPDM ROOFING SYSTEM AND ALLASSOCIATED MATERIALS (PER MANUFACTURER) (SEEPLAN & PROJECT MANUAL FOR ALL ROOFINGINSTALLATIONS AND CONDITIONS)
2. INSTALL NEW METAL DOWNSPOUTS @ ALL INDICATEDSCUPPER LOCATIONS. SEE DETAIL
3. INSTALL NEW CONCRETE SPLASH BLOCKS @ ALLINDICATED DOWNSPOUT LOCATIONS. SEE PROJECTMANUAL.
4. RELOCATE EXISTING ROOF DRAIN. PROVIDE PLUMBING TO CONNECT AT NEW LOCATION. SEE PROJECT MANUAL.
5. INFILL ALL EXISTING ABANDONED ROOF PENETRATIONS-WITH NEW GYPSUM DECKING TO MATCH EXIST. INSERTPANELS IN BETWEEN EXIST BULB TEES. SEE PROJECTMANUAL.
6. WALKWAY PADS TO BE INSTALLED. SEE PLAN FOR ESTIMATED LOCATIONS & PROJECT MANUAL.
ROOF AREAS
ROOF "J" -13,890 SFROOF "I" -830 SFROOF "S" -830 SF
-15,550 SF(THIS AREA IS APPROXIMATE- V.I.F.)
IECC CODE REQUIREMENT R- VALUE TOTALCONNECTICUT ZONE: 5ASBSC REQUIREMENT: R24 = U .042 OR LESS
FACTORY MUTAL ENGINEER & RESEARCH CORPORATION (FM):ROOF ASSEMBLY CLASSIFICATION OF NON-COMBUSITBLE,WIND UPLIFT REQUIREMENT OF I-60 FOR FIELD, I-90 FORPERIMETER AND I-120 FOR CORNERS, IN ACCORDANCEWITH FM PROPERTY LOSS PREVENTION DATA SHEETS 1-28
ROOFS: "J", "I", "S"
OUTSIDE AIR .17EPDM 0.33COVER BOARD 2.204" POLYISO INSUL. 26.4CONCRETE DECK 1.5INSIDE AIR .61
R TOTAL: 31.21
ENERGY CONSERVATION
CODE INFORMATION
AutoCAD SHX Text
DATE OF ORIGINAL CONSTRUCTION
AutoCAD SHX Text
4. BUILDING AREA (Chapter 5)
AutoCAD SHX Text
(Stories Above Grade)
AutoCAD SHX Text
Actual Height (story/feet)
AutoCAD SHX Text
Allowable Height (story/feet)
AutoCAD SHX Text
3. BUILDING HEIGHT (Chapter 5)
AutoCAD SHX Text
2. CONSTRUCTION TYPE (Chapter 6)
AutoCAD SHX Text
Minimum Type Required
AutoCAD SHX Text
Actual Type Provided (existing)
AutoCAD SHX Text
DATE OF ADDITION
AutoCAD SHX Text
(Incidental)
AutoCAD SHX Text
(Primary)
AutoCAD SHX Text
2
AutoCAD SHX Text
1/30'-0"
AutoCAD SHX Text
3/75'-0"
AutoCAD SHX Text
(new)
AutoCAD SHX Text
2b
AutoCAD SHX Text
E-EDUCATIONAL
AutoCAD SHX Text
1954
AutoCAD SHX Text
CODE INFORMATION
AutoCAD SHX Text
5. AREA MODIFICATIONS TO TABLE 503
AutoCAD SHX Text
(for each separate building as defined by fire walls and/or exterior walls)
AutoCAD SHX Text
1. GROUP CLASSIFICATION (Chapter 3)
AutoCAD SHX Text
2b
AutoCAD SHX Text
--
AutoCAD SHX Text
8. FIRE-RESISTANCE RATED REQUIREMENTS FOR BUILDING ELEMENTS
GENERAL NOTES1. ALL FLAT ROOFS TO RECEIVE 1/4" PER FOOT TAPERED
RIGID INSULATION MINIMUM UNLESS OTHERWISE NOTED.2. FIELD VERIFY ALL DIMENSIONS OF EACH ROOF PRIOR TO
THE BID.3. ALL MATERIALS ARE NEW UNLESS OTHERWISE NOTED
"EXISTING".4. ALL WOOD BLOCKING, PLYWOOD & NAILERS TO BE
PRESSURE TREATED. (P.T.)5. ALL WOOD BLOCKING INDICATED IN DETAILS IS TO BE
ANCHORED TO THE EXISTING STRUCTURE.6. ALL MEMBRANE FLASHING INDICATED IS TO EXTEND A
MINIMUM OF 8". (VERTICAL OR HORIZONTAL).7. CONTRACTOR IS TO SURVEY THE EXISTING ROOF DECKS
W/A LEVEL (AFTER DEMOLITION) TO VERIFY THE SLOPESINDICATED ON PLAN ARE ACCURATE. NOTIFY ARCHITECTIMMEDIATELY OF ANY DISCREPANCIES PRIOR TOPERFORMING ANY ADDITIONAL ROOFING OPERATIONS.
8. CONTRACTOR IS TO INSPECT THE UNDERSIDE OF ALLROOF DECKS PRIOR TO ROOFING OPERATIONS TO INSURETHAT NO INTERIOR MATERIALS, EQUIPMENT, FINISHES OROBJECTS WILL BE PIERCED OR DAMAGED.
9. CONTRACTOR ASSUMES ALL RESPONSIBILITY DURINGPROJECT & WILL REPLACE ANY & ALL DAMAGEDEQUIPMENT W/NO ADDITIONAL COST TO OWNER.
10. SITE AREAS DISTURBED SHALL BE CLEANED &RE-LEVELED, W/LAWN AREAS MAGNETICALLY RAKED TOREMOVE ANY METAL DEBRIS & RE-SEEDED AS REQUIREDTO MATCH ADJACENT CONDITIONS.
11. CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR CLEANUP OF ROOFING MATERIALS & DEBRIS THAT PENETRATESTHE INTERIOR ENVELOPE OF THE BUILDING W/NOADDITIONAL COST TO THE OWNER.
12. SNAKE/CLEAN OUT ALL EXISTING VERTICAL &HORIZONTAL LEADERS OUT TO NEAREST MANHOLEOUTSIDE OF BUILDING.
13. ALL CRICKETS ARE TO BE SLOPED @ A MINIMUM OF 1/2"PER FOOT & COORDINATE CRICKETS AROUND EXIST. HVACUNITS AS REQUIRED TO AVOID PONDING.
14. SNAKE/CLEAN OUT ALL EXISTING VENT STACK BEFORETHE INSTALLATION OF METAL SLEEVE.
15. ALL DRAIN PIPING IS INSULATED ABOVE THE CEILINGS.THE EXACT ROUTE WILL BE DETERMINED IN THE FIELD,MAKE MINOR ADJUSTMENT IN THE ROUTE AT NOADDITIONAL COST TO OWNER.
16. NEW INSULATION TO BE A MINIMUM OF 4" AT ALL EXISTING& NEW ROOF DRAINS.
17. ALL ANTENNAS, CONDUITS & ANY OTHER OBJECTS TOREMAIN AFFECTED BY SCOPE OF WORK TO BE REMOVED& REINSTALLED.
18. CONTRACTOR SHALL COMPLY WITH NFPA 1, CHAPTER 16 &NFPA 241, STANDARD FOR SAFEGUARDINGCONSTRUCTION, ALTERATION & DEMOLITION OPERATIONS.
SL.
SYMBOL LEGEND
XXX
SLOPESL.
SL.
HIGHPOINT
R.F.
V.S.
P.P.
N.R.D.
E.R.D.H.P.
C.B.
V.I.F.
S.C.
M.U.
C.C.
D.S.
C.S.
-PLAN, SECTION, DETAIL, ELEV. # - SHEET #.
-EXISTING OUTLINE OF BUILDING.
-SlOPE DIRECTION OF TAPERED INSUL. @ 1/4"/FT. MIN.
-TAPERED INSUL. CRICKET SLOPED @ 1/2" PER FT.
-CONTRACTOR TO VERIFY DIMENSION IN FIELD.
-INDICATES HIGH POINT OF INSULATION.
-EX. ROOF DRAIN TO BE REMOVED.
-ROOF DRAIN/ SUMP. SEE DETAIL A/A2
-EMERGENCY OVERFLOW SCUPPER. SEE DETAIL M/A2
-METAL COLLECTION BOX. SEE DETAIL N/A2
-METAL DOWNSPOUT. SEE CONST. NOTE #3
-CONC. SPLASH BLOCK. SEE CONST. NOTE #4
-EXISTING VENT STACK. SEE DETAIL B/A2
-EXISTING ROOF EXHAUST FAN. SEE DETAIL C/A2
-EXISTING MECH. UNIT. SEE DETAIL E/A2
-PITCH POCKET TO BE INSTALLED. SEE DETAIL D/A2
-WALKWAY PADS. SEE CONST. NOTE #6
-CONDUIT CURB. SEE DETAIL J/A2
-EX. SUPPORT TO BE REMOVED. SEE DEMO NOTE #4
-EX. MECH. TO BE REMOVED. SEE DEMO NOTE #4
- METAL GUARD RAIL. SEE DETAIL H/A2
SR.
EMR.
MGR.
CONSTRUCTION NOTES x
1. INSTALL NEW .60 MILL EPDM ROOFING SYSTEM AND ALLASSOCIATED MATERIALS (PER MANUFACTURER) (SEEPLAN & PROJECT MANUAL FOR ALL ROOFINGINSTALLATIONS AND CONDITIONS)
2. INSTALL NEW METAL DOWNSPOUTS @ ALL INDICATEDSCUPPER LOCATIONS. SEE DETAIL
3. INSTALL NEW CONCRETE SPLASH BLOCKS @ ALLINDICATED DOWNSPOUT LOCATIONS. SEE PROJECTMANUAL.
4. RELOCATE EXISTING ROOF DRAIN. PROVIDE PLUMBING TO CONNECT AT NEW LOCATION. SEE PROJECT MANUAL.
5. INFILL ALL EXISTING ABANDONED ROOF PENETRATIONS-WITH NEW GYPSUM DECKING TO MATCH EXIST. INSERTPANELS IN BETWEEN EXIST BULB TEES. SEE PROJECTMANUAL.
6. WALKWAY PADS TO BE INSTALLED. SEE PLAN FOR ESTIMATED LOCATIONS & PROJECT MANUAL.
DEMOLITION NOTES x
1. REMOVE ENTIRE EXISTING ROOFING, INSULATION, BALLASTAND ANY OTHER ASSOCIATED COMPONENTS AFFECTEDBY SCOPE OF WORK.
2. REMOVE ALL EXISTING PERIMETER EDGE DRAINAGEAND/OR WOOD BLOCKING & ASSOCIATED COMPONENTSAFFECTED BY SCOPE OF WORK.
3. REMOVE EXISTING ROOF DRAIN AND ASSOCIATED SUMP.4. REMOVE ALL EXISTING ABANDONED MECHANICAL
EQUIPMENT- DUCT PENETRATIONS, SUPPORTS AND ANYOTHER ROOF EQUIPMENT NOT BEING USED. REMOVE ALLBLOCKING AND.OR OTHER ASSOCIATED COMPONENTSABOVE CORRESPONDING ROOMS/ CLASSROOMS VERIFYWITH OWNER. SEE CONSTRUCTION NOTE #5
5. REMOVE AND RETAIN FOR REINSTALLATION EXISTINGACT/GRID SUPPORTS AFFECTED BY SCOPE OF WORK.
FACTORY MUTAL ENGINEER & RESEARCH CORPORATION (FM):ROOF ASSEMBLY CLASSIFICATION OF NON-COMBUSITBLE,WIND UPLIFT REQUIREMENT OF I-60 FOR FIELD, I-90 FORPERIMETER AND I-120 FOR CORNERS, IN ACCORDANCEWITH FM PROPERTY LOSS PREVENTION DATA SHEETS 1-28
ROOFS: "J", "I", "S"
OUTSIDE AIR .17EPDM 0.33COVER BOARD 2.204" POLYISO INSUL. 26.4CONCRETE DECK 1.5INSIDE AIR .61
2X6 P.T. WOOD blocking. (same thickness as insulation)
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
epdm ROOF MEMBRANE.
AutoCAD SHX Text
(2) 2X12 P.T. WOOD BLOCKING.
AutoCAD SHX Text
compressible tube.
AutoCAD SHX Text
epdm ROOF MEMBRANE.
AutoCAD SHX Text
cont. 4" base layer of
AutoCAD SHX Text
rigid insulation.
AutoCAD SHX Text
expansion joint detail
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
g
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
exist. brick veneer.
AutoCAD SHX Text
exist. concrete block.
AutoCAD SHX Text
exist. metal deck.
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm membrane.
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
(1) 2"x6" p.t. wood blocking.
AutoCAD SHX Text
a3
AutoCAD SHX Text
compressible tube.
AutoCAD SHX Text
batt insulation.
AutoCAD SHX Text
cont. 4" base layer of
AutoCAD SHX Text
rigid insulation.
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
cover board.
AutoCAD SHX Text
termination bar w/backer rod
AutoCAD SHX Text
& continuous bead of sealant.
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
EXIST. mech. unit curb/dunnage
AutoCAD SHX Text
EXIST. mech. unit.
AutoCAD SHX Text
bar detail
AutoCAD SHX Text
e
AutoCAD SHX Text
a2
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
rtu. termination
AutoCAD SHX Text
refer to manufacturers
AutoCAD SHX Text
recommendations for nailing
AutoCAD SHX Text
pattern.
AutoCAD SHX Text
VENT STACK DETAIL
AutoCAD SHX Text
a2
AutoCAD SHX Text
b
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
ROOF DRAIN DETAIL
AutoCAD SHX Text
SCALE: 1 1/2" = 1'-0"
AutoCAD SHX Text
a
AutoCAD SHX Text
a2
AutoCAD SHX Text
drain sump.
AutoCAD SHX Text
OF NEW ROOF DRAIN.
AutoCAD SHX Text
AFTER INSTALLATION
AutoCAD SHX Text
UNDERDECK CLAMP.
AutoCAD SHX Text
LEADER. CONNECT
AutoCAD SHX Text
EXISTING OR
AutoCAD SHX Text
NEW VERTICAL
AutoCAD SHX Text
NEW no hub cast
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
LOCKING DOME.
AutoCAD SHX Text
CLAMP RING.
AutoCAD SHX Text
epdm membrane.
AutoCAD SHX Text
COVER BOARD.
AutoCAD SHX Text
EXIST. DECK.
AutoCAD SHX Text
PITCH POCKET DETAIL
AutoCAD SHX Text
d
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
SHEET METAL PITCH BOX.
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
4"
AutoCAD SHX Text
COVER BOARD.
AutoCAD SHX Text
TAPERED Insulation.
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm roof membrane.
AutoCAD SHX Text
2X6 P.T. WOOD blocking. (same thickness as insulation)
AutoCAD SHX Text
pourable filler.
AutoCAD SHX Text
filler.
AutoCAD SHX Text
EXISTING roof penetration.
AutoCAD SHX Text
exist. concrete deck.
AutoCAD SHX Text
a2
AutoCAD SHX Text
iron ROOF DRAIN.
AutoCAD SHX Text
EXIST. MECH. HOOD METAL flashing.
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
TAPERED Insulation.
AutoCAD SHX Text
exist. concrete deck.
AutoCAD SHX Text
epdm roofing membrane.
AutoCAD SHX Text
epdm roofing flashing.
AutoCAD SHX Text
2X6 P.T. WOOD blocking. (same thickness as insulation)
AutoCAD SHX Text
note: remove exist mech. unit curb. install new pre-manufactured curb w/min r=25
AutoCAD SHX Text
cont. 4" base layer of
AutoCAD SHX Text
rigid insulation.
AutoCAD SHX Text
c
AutoCAD SHX Text
a2
AutoCAD SHX Text
roof exhaust fan detail
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
note: EXIST. MECHANICAL UNIT tO BE REMOVED & Reinstalled AS REQUIRED FOR NEW CURB & ROOFING OPERATIONS. EXTEND ALL ELECTRICAL WIRING & DUCTWORK AS REQUIRED.
AutoCAD SHX Text
cont. 4" base layer
AutoCAD SHX Text
of rigid insulation.
AutoCAD SHX Text
cont. 4" base layer of
AutoCAD SHX Text
rigid insulation.
AutoCAD SHX Text
rtu support/
AutoCAD SHX Text
j
AutoCAD SHX Text
conduit curb detail
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm roof membrane.
AutoCAD SHX Text
TAPERED Insulation.
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
a2
AutoCAD SHX Text
cont. 4" base layer of
AutoCAD SHX Text
rigid insulation.
AutoCAD SHX Text
exist. conduit pipe.
AutoCAD SHX Text
rubber conduit curb.
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm roof membrane.
AutoCAD SHX Text
exist. roof. tie in new roof membrane into exist.
AutoCAD SHX Text
"typical" guardrail DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
EQ.
AutoCAD SHX Text
3'-6" MIN.
AutoCAD SHX Text
1[" o steel pipe
AutoCAD SHX Text
typical
AutoCAD SHX Text
6'-0" min.
AutoCAD SHX Text
for single section
AutoCAD SHX Text
6'-0" max.
AutoCAD SHX Text
1[" METAL pipe collar -
AutoCAD SHX Text
of railing
AutoCAD SHX Text
6'-0" max.
AutoCAD SHX Text
multiple sections
AutoCAD SHX Text
ATTACH TO metal flashing & edge
AutoCAD SHX Text
blocking - typical.
AutoCAD SHX Text
embed collar in mastic - typical.
AutoCAD SHX Text
sealant on all sides - typical.
AutoCAD SHX Text
EXPANSION BOLT to wood
AutoCAD SHX Text
pipe COLLAR -
AutoCAD SHX Text
see above.
AutoCAD SHX Text
1[" o steel pipe
AutoCAD SHX Text
typical
AutoCAD SHX Text
top of roof
AutoCAD SHX Text
edge flashing.
AutoCAD SHX Text
top of roof PARAPET WALL edge flashing.
AutoCAD SHX Text
blocking min. (4) per unit equally
AutoCAD SHX Text
spaced per manufacturers standards.
AutoCAD SHX Text
1[" o steel pipe - typical.
AutoCAD SHX Text
h
AutoCAD SHX Text
EQ.
AutoCAD SHX Text
EQ.
AutoCAD SHX Text
a2
AutoCAD SHX Text
roof to roof detail
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
cover board.
AutoCAD SHX Text
EPDM membrane.
AutoCAD SHX Text
EPDM flashing.
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
(5) 2"x6" p.t. block.
AutoCAD SHX Text
cover board.
AutoCAD SHX Text
EPDM membrane.
AutoCAD SHX Text
EPDM flashing.
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
k
AutoCAD SHX Text
a4
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
compressible tube. expansion joint.
AutoCAD SHX Text
1'-0"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1'-0"
AutoCAD SHX Text
8"
AutoCAD SHX Text
11"
AutoCAD SHX Text
metal Collection box
AutoCAD SHX Text
SCUPPER detail
AutoCAD SHX Text
n
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm membrane.
AutoCAD SHX Text
(2) 2"x6" P.T. WOOD BLOCKING.
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
exist. concrete block.
AutoCAD SHX Text
METAL SCUPPER. (METAL
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
\" P.T. PLYWOOD.
AutoCAD SHX Text
METAL COLLECTION BOX.
AutoCAD SHX Text
METAL DOWNSPOUT.
AutoCAD SHX Text
FLASHING ALL SIDES)
AutoCAD SHX Text
(3) 2"x6" p.t. wood blocking.
AutoCAD SHX Text
a2
AutoCAD SHX Text
metal gravel stop w/
AutoCAD SHX Text
cont. metal clip.
AutoCAD SHX Text
factory manufactured
AutoCAD SHX Text
see front profile below.
AutoCAD SHX Text
SCUPPER detail
AutoCAD SHX Text
m
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
a2
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm roof membrane.
AutoCAD SHX Text
w/cont. clip.
AutoCAD SHX Text
2"x6" 16" o.c. pt. studs.
AutoCAD SHX Text
4" rigid insulation.
AutoCAD SHX Text
exist. concrete fascia.
AutoCAD SHX Text
exist. brick veneer.
AutoCAD SHX Text
exist. concrete block.
AutoCAD SHX Text
manufactured metal edge
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
a2
AutoCAD SHX Text
l
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
edge detail
AutoCAD SHX Text
metal flashing w/cont. clip
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
metal flashing w/cont. clip
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
batt insulation.
AutoCAD SHX Text
[" pt. plywood.
AutoCAD SHX Text
2"x6" p.t. bottom plate.
AutoCAD SHX Text
2"x6" p.t. bottom plate.
AutoCAD SHX Text
4" rigid insulation.
AutoCAD SHX Text
exist. concrete fascia.
AutoCAD SHX Text
exist. brick veneer.
AutoCAD SHX Text
exist. concrete block.
AutoCAD SHX Text
metal flashing w/cont. clip
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
2"x6" pt. blocking.
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm roof membrane.
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
METAL SCUPPER. (METAL
AutoCAD SHX Text
FLASHING ALL SIDES)
AutoCAD SHX Text
PARAPET WALL BEYOND.
AutoCAD SHX Text
scupper OPENING NOT
AutoCAD SHX Text
TO EXCEED 8" WIDTH.
AutoCAD SHX Text
SAW CUT FOR METAL REGLET FLASHING, (1]" DEEP INTO EXIST. MASONRY) INSTALL METAL REGLET FLASHING W/CONT. METAL CLIP. insert ]" backer rod w/CONT. BEAD OF SEALANT & lead wedge 12" O.C.
AutoCAD SHX Text
epdm flashing.
AutoCAD SHX Text
epdm roof membrane.
AutoCAD SHX Text
w/cont. clip.
AutoCAD SHX Text
(4) 2"x6" p.t. wood blocking.
AutoCAD SHX Text
4" rigid insulation.
AutoCAD SHX Text
exist. deck.
AutoCAD SHX Text
exist. brick veneer.
AutoCAD SHX Text
exist. concrete block.
AutoCAD SHX Text
manufactured metal edge
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
A2
AutoCAD SHX Text
P
AutoCAD SHX Text
SCALE: 1[" = 1'-0"
AutoCAD SHX Text
edge detail
AutoCAD SHX Text
EXIST CONCRETE FASCIA.
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
NOTE: PARAPET WALL TO MATCH HEIGHT OF NEW INSULATION HEIGHT.
AutoCAD SHX Text
NOTE: PARAPET WALL TO MATCH HEIGHT OF NEW INSULATION HEIGHT.
AutoCAD SHX Text
METAL PIPE FLASHING.
AutoCAD SHX Text
METAL HOOD.
AutoCAD SHX Text
METAL CLAMP RING.
AutoCAD SHX Text
SEALANT.
AutoCAD SHX Text
SEALANT.
AutoCAD SHX Text
METAL CLAMP RING.
AutoCAD SHX Text
VENT STACK extension.
AutoCAD SHX Text
cover BOARD.
AutoCAD SHX Text
tapered insulation.
AutoCAD SHX Text
2 X 6 P.T. WOOD BLOCKING - SAME THICKNESS AS INSUL.