Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 2: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

Drives & Controls Services, Inc.OVER 30 FIELD REPRESENTATIVES WORLD

WIDE

24 HOUR SUPPORT

OVER 400 YEARS COLLECTIVE ELECTRICALMINING EXPIERENCE

EXPIERENCE IN ALMOST ALL MAKES ANDMODELS OF REGULATORS OLD AND NEW

Page 3: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

WWW.DRIVESANDCONTROLS.COM

Page 4: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

USA•Tyler, Texas•Bogata, Texas•Heath, Texas•Henderson, Texas•Jasper, Alabama•Bradenton, Florida•Casper, Wyoming•Gillette Wyoming•Dubois, Wyoming •Edmonton, Alberta, CAN

•Mackay, Queensland, QLD•Dysart, Queensland•New Castle, New South Wales•Cartagena, Columbia

Locations

Drives & Controls Services, Inc.

Page 5: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 6: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•HIGH VOLTAGE CIRCUITS•LOW VOLTAGE CIRCUITS•LIGHTING CIRCUITS

Page 7: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 8: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•Boom was pulled back and pinned afteran extended outage•Dragline power tripped at the substation•Suspected Sync Motor Stator failure•Primary 200 amp fuses were blown on the7200/480 transformers

Page 9: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

480 VOLT PHASE to PHASE to GROUND BLOWS 8KV FUSEON PRIMARY OF TRANSFORMER

Page 10: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 11: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 12: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 13: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 14: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 15: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 16: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 17: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•Old cable was replaced•Dragline power still tripped withground fault•Measured a ground fault on primaryof “C Phase” transformer

Page 18: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•Replaced grounded transformer with spare•Dragline power still tripped with ground fault•Measured a ground fault on primaryof “C Phase” on the “new transformer”

Page 19: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 20: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•Acquired bank of three transformers from anearby mine•Power was applied to dragline•200 amp primary fuse blew again•Found secondary wiring error

Page 21: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 22: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•On a schematic it looks simple

Page 23: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•Not so much in reality

Page 24: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

“B” to “C” PhaseShort Circuit

Page 25: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•All leads were disconnected and isolatedagain•Rang out each lead to the phase of thebreaker it was feeding and megged toground•We found that one of the “B” phase leadshad been connected to “C” phasetransformer

Page 26: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•2 weeks ago another of thesetransformers had a catastrophic failure•Causing a fire in the High Voltage room

Page 27: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•The “B” phase transformer explodedblowing the lid off and breaking a primarybushing

Page 28: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 29: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 30: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•A flash and then smoke was observed bythe operator on his camera system

Page 31: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•The electricians were called and killedpower at the substation•Operator and oiler put out the fire with afire extinguisher•All three transformers were replaced with anew “matched” set•The primary high voltage cable wasreplaced

Page 32: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 33: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 34: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•An AC ground alarm was detected in theoperator cab

Page 35: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•Boom lights are sometimes part of the480 volt circuit•All 480 volt circuits begin at the 3phase buss in the high voltage room•From there they are connected to thererespective breaker panels•The first step is to isolate the primarycircuit of the ground

Page 36: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 37: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 38: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•The dragline power was disconnectedlocked, tagged and grounded at thesubstation•The incoming fuses to the 7200 / 480transformer bank were removed

Page 39: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 40: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•The next task was to locate the cablewith the ground fault•The third cable disconnected had theground•It was then traced hand over handthrough the cable tray•It led to the boom lighting breaker panelmounted on the dragline front wall

Page 41: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 42: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•Boom lighting breaker panel fedthe boom lighting ballast box

Page 43: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•The lighting ballast primary fuseswere remove one at a time until theground went away•The ground was then isolated to onelighting circuit on the boom

Page 44: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 45: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

GROUND FAULT WASFOUND AT THE LAMPSOCKET

Page 46: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 47: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 48: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 49: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

•High temperature in the high voltageroom•3 transformers for the main buss and 3for the auxiliary buss•The two end transformers on the mainbuss were much hotter

Page 50: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 51: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor
Page 52: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

• 3 - 250 KVA transformers should have afull load of 903 amps or 301 amps perphase•This buss feeds the GF Exciters, MFExciters•All motor blowers, 4 house fans, 8exhaust fans, 6 bleeder fans and theboom lights

Page 53: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

• An estimated average load of 700 to800 amps•With the M-G sets off we measured “A”278 amps, “B” 238 amps and “C” 300amps

Page 54: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

• We performed a windings test on bothbanks of the transformers by injecting120 volts ac on the primary andmeasuring the output•We then swapped transformers to getthe best windings match per set oftransformers

Page 55: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor

• Now the current in the main buss wasnear zero with the M-G sets and all fansand blowers off•The mine has since replaced all of themain and auxiliary transformers withnew “matched” transformers

Page 56: Drives & Controls Services, Inc. · • 3 - 250 KVA transformers should have a full load of 903 amps or 301 amps per phase •This buss feeds the GF Exciters, MF Exciters •All motor