TECHNICAL DOCUMENTATION

DTR HC3P

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

Table of contents1. INTRODUCTION1.1 PRECAUTIONS1.2 TRANSPORT1.3 PACKAGE CONTENT1.4 USE AND PRINCIPLE OF OPERATION2. DEVICE CONSTRUCTION, DIMENSIONS, TECHNICAL DATA2.1 CONSTRUCTION2.2 DIMENSIONS2.3 TECHNICAL DATA3. ASSEMBLY4. INSTALLATION INSTRUCTIONS5. PRECAUTIONS & WARNINGS6. CONNECTION SCHEMES7. TERMS OF WARRANTY7.1 WARRANTY CARD7.2 WARRANTY FORM7.3 SERVICE CARD

ENG TECHNICAL DOCUMENTATION

1. INTRODUCTION

Thank you very much for purchasig Reventon Group device. We would like to congratulate you on excellent choice.

1.1 PRECAUTIONS

The buyer and the user of the device should read carefully the following instructions and proceed to the content recommendations. Proceeding due to the following instruction guarantees the correct usage and safety. In case of any doubts please contact the producer. The producer reserves the rights to make changes to the technical documentation without previous notice. The producer is not responsible for the damages which occur due to improper installation, not keeping the device in repair or using the device out of line. The installation should be carried out by the professional installers, who possess the qualifications to install these types of devices. The installers are responsible for making the installation as instructed in the technical data. Regulations and safety rules must be followed. During the installation, use, service and periodical inspections all regulations and safety rules must be followed. In case of unserviceable please plug out the device and contact with the authorized person or the producer.

1.2 TRANSPORT

During the acceptance of goods, it is needed to check the device to exclude any damages. During the transport, it is needed to use the proper equipment, it is necessary to carry the device by two people. In case of any damages please fill in the damage report in presence of the supplier.

1.3 PACKAGE CONTENT

- Air water heater- Operation and maintenance manual and warranty card

Casing: made of expanded polypropylene EPP, resistant, light and reliable. The material can carry considerable loads without deforming. It does not degrade under the influence of a lubricant, oil, crude oil and most of chemicals. It has an excellent sound insulation property, that is why it is used as casings, material is environmentally friendly and "green", i.e. 100% recyclable. Aesthetic design gives new nature to the device.

1.4 USE AND PRONCIPLE OF OPERATION

Devices Reventon Group HC3P series are used to heat spaces such as: production halls, warehouses, commercial room, service spaces, garages, workshops, greenhouses, tents, shops, malls, shopping malls and churches. Air water heaters must be connected to central heating system. Application of modern technologies in Reventon Group devices guarantees high effectiveness and comfort of the consumption. Original colors of the devices match to every interior. The device is made very precisely and will work smoothly for many years.

* The product has got the two years of warranty.

2. DEVICE CONSTRUCTION, DIMENSIONS, TECHNICAL DATA

2.1 CONSTRUCTION

- Casing- Air stators- Heating coil- Axial blowing fan- Rotating mounting bracket

Air stators: made of polypropylene PP. It is possible to adjust manually the air stators to achieve the needed direction of the air flow.

Heating coil: made of aluminum and copper. The temperature of the heating factor is 120°C; maximum pressure 1,6 MPa; headers diameter ¾”. Depending on the water heater model we offer 1, 2 and 3 rows .

Axial blowing fan: protective grid made of steel wire galvanized, metal blades.The motor has got the safety degree IP 54. Current rate 0,47A- 0,6A. 3-phase devices. Models HC3P 20, HC3P 30, HC3P 35, HC3P 45 have fans with diameter 400mm. Models HC3P 50 and HC3P 70 have fans with diameter 450 mm.

Rotating mounting bracket: made of steel, element for mounting the device on the wall or ceiling. Solid and durable construction, possible to assemble device in parallel on the angle 60°. Possible rotation horizontally.

2.2

HC3P 20, HC3P 30, HC3P 35, HC3P 45

598 mm (a) 636 mm (b)

głębokość: 320mm (c)

698 mm (a)szerokość: 739 mm (b) głębokość: 340 mm (c)

heating coils

DIMENSIONS

height: width:

HC3P 50, HC3P 70

height:

b

c

a

2.3 TECHNICAL DATA

* Temperature rise according to parameters: water 90/70°C and inlet air temperature 0°C.

** The measurement at 5 m from the unit

Unit of measure

kW

kW

m³/h

m

dm³

°C

°C

A

V/Hz

-

kg

dB

22,4 33,9 46,7 68,526,4 43,3

8–22,4 12,9-33,9 20,1-46,7 30-68,59,05-26,4 18,4-43,3

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,8 28,6 29,6 46,525,2 46,7

120120 120120120120

0,47 0,60,47 0,47 0,47 0,6

400/50 400/50400/50400/50400/50400/50

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

CODE

TECHNICAL DATA

Nominal heating capacity water 90/70°C and inlet air temperature 0°C

Heating power range

Maximum airflow

Maximum range of air stream

Number of rows pcs.

Capacity of water

Air temperature rise *

Maximum temperature of heating agent

Rated current

Power supply voltage

rev/minMotor speed

Motor power

Motor IP

Connection diameter

Weight

Noise **

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

3600 3400 4600 45003300 3100

23 22 26 2521 20

1400 1360 13601400 1400 1400

190 190190190 240 240

54 54 54 54 57 57

1,6 1,6 1,6 1,61,6 1,6MPaMaximum operating pressure

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

0 5 10 15 20

22,4 20,9 19,1 17,4 15,6

17,6 21,5 25,3 29,2 33

1 0,92 0,84 0,77 0,69

6 5 5 4 3

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

90/70

0 5 10 15 20

19,1 17,4 15,6 13,9 12,2

14,8 18,7 22,5 26,3 30,1

0,84 0,76 0,69 0,61 0,54

5 4 3 3 2

80/60

0 5 10 15 20

15,6 13,8 12,1 10,5 8,85

12 15,9 19,7 23,5 27,3

0,68 0,61 0,53 0,46 0,39

3 3 2 2 1

70/50

0 5 10 15 20

8,41 6,79 5,24 3,73 2,29

6,5 10,3 14,2 18 21,9

0,37 0,29 0,23 0,16 0,1

1 1 0 0 0

50/30

0 5 10 15 20

26,4 25 22,9 20,8 18,7

23 26,5 30 33,5 36,9

1,2 1,1 1,01 0,92 0,82

7 8 6 5 4

90/70

0 5 10 15 20

22,9 20,8 18,7 16,6 14,6

19,3 22,8 26,3 29,8 33,2

1,01 0,91 0,82 0,73 0,64

6 5 4 5 4

0 5 10 15 20

18,6 16,5 14,5 12,5 10,5

15,7 19,2 22,7 26,1 29,5

0,81 0,72 0,63 0,55 0,46

5 5 4 3 5

0 5 10 15 20

9,98 8,05 6,17 4,36 2,65

8,4 11,9 15,4 18,9 22,4

0,43 0,35 0,27 0,19 0,11

4 3 2 5 2

0 5 10 15 20

33,9 31,7 29 26,4 23,8

28,2 31,4 34,6 37,8 40,9

1,52 1,4 1,28 1,16 1,05

5 4 4 3 4

90/70

0 5 10 15 20

29,1 26,5 23,8 21,2 18,7

23,8 27 30,2 33,3 36,4

1,28 1,16 1,05 0,93 0,82

4 3 4 3 2

0 5 10 15 20

23,8 21,2 18,6 16,1 13,7

19,5 22,6 25,8 28,9 32

1,04 0,93 0,82 0,71 0,6

4 3 2 3 2

0 5 10 15 20

13,1 10,6 8,28 5,97 3,74

10,7 13,9 17,0 20,2 23,3

0,57 0,46 0,36 0,26 0,16

2 4 2 1 4

0 5 10 15 20

43,3 44,5 40,9 37,3 33,9

43,2 45,6 48 50,3 52,6

2,12 1,96 1,8 1,64 1,49

27 24 20 17 16

90/70

0 5 10 15 20

41,4 37,8 34,3 30,8 27,4

37,2 39,5 41,9 44,2 46,4

1,82 1,66 1,51 1,35 1,2

21 18 17 14 11

0 5 10 15 20

34,7 31,1 27,6 24,3 20,9

31,1 33,4 35,7 38,0 40,2

1,52 1,36 1,21 1,06 0,92

17 14 12 10 8

0 5 10 15 20

20,9 17,5 14,2 10,9 7,61

18,8 21,0 23,2 25,3 27,3

0,91 0,76 0,62 0,47 0,33

8 8 5 3 3

0 5 10 15 20

46,7 44,3 40,7 37,1 33,7

29 32,3 35,5 38,7 41,9

2,11 1,95 1,79 1,64 1,49

11 10 8 7 8

90/70

0 5 10 15 20

41,1 37,5 34,0 30,6 27,2

24,9 28,1 31,3 34,5 37,7

1,81 1,65 1,5 1,34 1,2

9 7 8 6 5

50/30

80/60

70/50

50/30 70/50 80/60

50/30

70/50 80/60

80/60

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

HC3P 20 3600 m3/h HC3P 20 3600 m3/h HC3P 20 3600 m3/h

HC3P 20 3600 m3/h HC3P 30 3300 m3/h HC3P 30 3300 m3/h

HC3P 30 3300 m3/h HC3P 30 3300 m3/h -3400 m3/h HC3P 35

- m3/h HC3P 35 3400 - m3/h HC3P 35 3400 - m3/h HC3P 35 3400

HC3P 45 3100 m3/h HC3P 45 3100 m3/h HC3P 45 m3/h 3100

HC3P 45 3100 m3/h HC3P 50 -4600 m3/h HC3P 50 -4600 m3/h

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

3. Air water heaters Reventon Group HC3P series can be assembled on the wall or ceiling via rotating mounting brackets. The drawings below show the ways of assembly. In the bigger accommodation, it is recommended to assemble more than one device. Follow the parameters which are provided on the drawings.

ASSEMBLY

Reventon Group devices can be assembled on the wall or ceiling via rotating mounting bracket. It is possible to assemble the device in parallel on the angle 60°. Please follow the parameters as shown below.

4. INSTALLATION INSTRUCTIONSThe installation should be made by the qualified staff, who possess the needed rights to install electrical devices, as instructed in the following documentation. The duct size for air water heaters Reventon Group HC3P should be chosen by the designer.

5. PRECAUTIONS & WARNINGS All works concerning electrical installation should be made by the qualified staff, who possess the qualifications due to the domestic and local norms. These recommendations include service and disassembly as well. Not following to the recommendations may cause electrocution, device damages or its incorrect work.

- Before service or exchange of the device it is obligatory to cut off the current supply.

- Do not cover the inlet and outlet of the device.

- Do not use the device in room with high moisture or close to the water basin.

- Do not install, service the device with wet hands or barefoot.

- Do not use the device in room with flammable fumes, gas and high concentration of dust.

- The device should be kept out of reach of children and animals.

- During the assembly use the filter on the hydraulic supply.

- Please use the following valves:

ź vent valve in the highest place on the hydraulic installation,ź cut off valve on the supply and return of the device.

- The device should be secured against pressure increase in the water installation.

- Before plugging the electric supply check the leak tightness.

- The device does not consist of the anti-frost protection. The temperature in the room should not go below 0°C. In such case please empty the device out of water.

- It is recommended to check the electric installation before the first start.

- It is recommended to use the external current deferential protection.

- After the turn off, the elements of device may be warm.

- After operating time of the device, please utilize it concerning the local norms and regulations.

Assembly on the ceiling Assembly on the wall.

Example arrangement for few devices in the room.

5-10m

10m

7-25m

20-50m

3-7m

7-12m

0.15m0.15m

min. 0.2m

Mounting via rotating mounting bracket

60

0 5 10 15 20

34,3 30,8 27,4 24,0 20,7

20,8 24,0 27,2 30,3 33,4

1,5 1,35 1,2 1,05 0,9

8 7 5 6 4

0 5 10 15 20

20,6 17,2 13,9 10,7 7,41

12,5 15,6 18,7 21,8 24,8

0,89 0,75 0,6 0,46 0,32

4 5 3 5 2

0 5 10 15 20

68,5 67,2 61,7 56,3 51,1

46,5 47,3 49,5 51,7 53,9

3,2 2,96 2,72 2,48 2,25

11 10 8 8 7

90/70

0 5 10 15 20

62,6 57,1 51,8 46,6 41,4

38,7 41 43,2 45,4 47,5

2,75 2,51 2,27 2,05 1,82

9 9 7 6 5

0 5 10 15 20

52,4 47,0 41,8 36,7 31,7

32,4 34,6 36,8 38,9 41,0

2,29 2,06 1,83 1,6 1,39

8 6 5 4 5

0 5 10 15 20

31,7 26,6 21,5 16,6 11,6

19,6 21,7 23,8 25,8 27,7

1,38 1,15 0,94 0,72 0,5

5 3 3 4 2

70/50 50/30

80/60 70/50 50/30

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

Parameters

Inlet and outlet water temperature[°C]

TInlet air temperature[°C]

Heating capacity [kW]

Outlet air temperature[°C]

Water flow [m³/h]

Pressure drop in the heat exchanger [kPa]

HC3P 50 -4600 m3/h HC3P 50 -4600 m3/h -4500 m3/h HC3P 70

-4400 m3/h HC3P 70 -4500 m3/h HC3P 70 -4500 m3/h HC3P 70

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

White

Black

Orange

Brown

Red

Brown

Grey

WhiteGrey

Orange

Red

Black

Brown

Blue

Opening the air stators must be made by two hands in parallel. Not keeping to the following recommendation may cause the damages of

the air stators.

While plugging the device to the water installation do remember to hold its stub pipes by pipes spanner, not keeping to the

recommendation may cause the damages of the heating coil.

6. CONNECTION SCHEMES

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

7. TERMS OF WARRANTY

I Reventon Group Sp. z o.o. [Ltd.] 3B Montazowa Street , 43-300 Bielsko-Biała,Poland, is the producer of the Reventon Group brand. The warranty concerns the following devices and it is valid for 2 (two) years:

- air water heater Reventon Group HC20 3P 22 kW 400V - air water heater Reventon Group HC30 3P 26kW 400V -air water heater Reventon Group HC35 3P 34kW 400V -air water heater Reventon Group HC45 3P 43kW 400V - air water heater Reventon Group HC50 3P 47kW 400V -air water heater Reventon Group HC70 3P 69kW 400V

II Warranty is valid in the European Union.

III The terms of warranty are valid from purchasing the device (the date issuing a document confirming the purchase of the device) but not further than 30 (thirty) months from leaving the producer’s warehouse. IV The defects revealed during the warranty period will be removed free of charge in 14 working days. The service will be done by the installation company due to the terms included in warranty card. The elements will be supplied by the Reventon Group Sp. z o.o. during the warranty period.

V Warranty does not cover the parts of the device subject to normal maintenance and the cases as below:

a) Mechanical defects, damages from the impact of the improper transportation or damages through improper storage.

b) Defects through: - improper usage and service; - using the device in the improper conditions (too high humidity, too high or too low temperature, impact of the surrounding, sun etc.);

-modified equipment that has been modified or repaired without written agreement of the producer; - connecting additional equipment, which is not recommended by the producer or inconsistent with the technical documentation;

- improper power supply.

c) Elements which wear and tear such as discolor or using.

VI All changes in record in the warranty terms or any constructive modifications, independent service outside the Reventon Group Sp. z o.o. service or use, uncaring, makes the warranty not valid.

VII To obtain the service it is needed to send to the producer warranty card with the signature, document confirming the purchase, (copy of the invoice) and correctly filled the warranty form.

VIII Not following to any of warranty regulations makes the warranty not valid.

IX All correspondence, returns, complains should be send to the following address: Reventon Group Sp. z o.o. 3B Montazowa Street, 43-300 Bielsko-Biała, Poland or e-mail: [email protected]

The producer reserves the rights to make changes to the technical documentation without previous notice.

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

Warranty card

Reventon Group [Ltd.] 3B Montazowa Street, 43-300 Bielsko-Biała, Poland

:

:

: :

:

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517

Reventon Group Sp. z o.o. [Ltd.] , 3B Montażowa Street, 43-300 Bielsko-Biała, Poland, www.reventongroup.eu

Unit of measure

CODE

Nominal heating capacity water 90/70°C and inlet air temperature 0°C [kW]

kW

TECHNICAL DATA

Heating power range kW

Maximum airflow m³/h

Maximum range of air stream

m

Number of rows pcs.

Capacity of water dm³

Air temperature rise * °C

Maximum temperature of heating agent °C

Maximum operating pressure

MPa

Rated current A

Power supply voltage V~Hz

Motor speedrev/min

Motor IP -

Connection diameter „

Weight kg

Noise ** dB

22,4 33,9 46,7 68,526,4 43,3

8,41–22,4 13,1–33,9 20,6–46,7 31,7–68,59,98-26,4 20,9-43,3

3600 3400 4600 45003300 3100

3100 2900 3800 37002800 2600

2400 2200 2900 28002100 1900

1 2 2 31 2

0,65 1,35 1,95 2,850,8 1,7

17,6 28,2 29 46,523 43,2

120120 120120120120

1,6 1,6 1,6 1,61,6 1,6

0,84 1,080,65 0,860,54 0,70

0,840,650,54

0,840,650,54

0,840,650,54

1,080,860,70

230/50 230/50230/50230/50230/50230/50

Motor power

1400 1360 13601400 1400 1400

1050 1050 1050105010501050

750 750750750750750

190 190

150150 150 150 190

190190 240 240

190

160160120 120120120

3/4 3/4 3/4 3/43/4 3/4

11,5 12,5 17,5 19,512 14

54 54 54 5454 54

W

23 22 26 2521 20

54 575248

4442

544842

544842

544842

575244

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

3 stage

2 stage

1 stage

HC3P 20 HC3P 30 HC3P 35 HC3P 45 HC3P 50 HC3P 70

WHHC3P20-1514

WHHC3P30-1626

WHHC3P35-1515

WHHC3P45-1627

WHHC3P50-1516

WHHC3P70-1517