X3Installation and OperationGuide

E0004, Version 02May 2018

© ORBCOMM Inc.

Page 2: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

LEGAL NOTICE

This documentation is owned by ORBCOMM and protected by applicable copyright laws and international treatyprovisions. Other copyrighted names used are the property of their respective owners. Therefore, you must treat thisdocumentation like any other copyrighted material. This publication, or any part thereof, may not be reproduced ortransmitted in any form or by any means, electronic or mechanical, including photocopying, recording, storage in aninformation retrieval system, or otherwise, without prior written permission by ORBCOMM, Inc. 395 W Passaic Street,Suite 325, Rochelle Park, NJ 07662 USA Phone 703-433-6325. The information in this document is for informationpurposes only and contains technical information and descriptions of the ORBCOMM product(s) and is subject tochange without notice. No warranty or representation, express or implied, is made with respect to its contents.

E0004, Version 02 © ORBCOMM Proprietary

2

Page 3: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

CONTACT INFORMATION

Visit ORBCOMM Onlinewww.ORBCOMM.com

Contact Customer SupportTelephone: +49 (0) 228-926380

www.euroscansupport.com

Headquarters395 W Passaic Street, Suite 325

Rochelle Park, NJ 07662 USA

Tel: +1-703-433-6300

Fax: 1-703-433-6400

Email: [email protected]

E0004, Version 02 © ORBCOMM Proprietary

3

Page 4: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

TABLE OF CONTENTS

Legal Notice 2

Contact Information 3

TABLE OF CONTENTS 4

List of Figures 7

List of Tables 7

About this Installation Guide 8

Disclaimer 8

Purpose 8

Document Conventions 9

Terminology 9

Reference 10

Intended Use Statement 10

Regulations 10

Safety Guidelines 10

WEEE Statement 11

Revision History 11

1 Installation 12

1.1 Identify the Components 12

1.1.1 Euroscan RX3 12

1.1.2 Euroscan TX3 13

1.2 Review the Requirements 14

1.3 Review the Connector Blocks 15

1.3.1 Connector Block 1 (power supply and outputs) 16

1.3.2 Connector Block 2 (serial port) 17

1.3.3 Connector Block 3 (digital inputs) 17

1.3.4 Connector Block 4 (temperature inputs) 18

1.4 Mount the Recorder 18

1.4.1 Power supply 18

1.4.2 Temperature sensors 18

1.4.3 Digital Inputs 20

1.4.4 Fridge Connection 21

1.4.5 Door Lock Connection 21

1.4.6 GPS 21

1.4.7 Recorder 22

1.4.8 Install the Euroscan RX3 22

1.4.9 Install the EuroscanTX3 23

E0004, Version 02 © ORBCOMM Proprietary

4

Page 5: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

1.4.10 Install the Antenna 24

2 Configure the Recorder using DeviceManager 28

2.1 Basic Configuration Menus 28

2.2 Main Settings 28

2.3 Compartments 30

2.4 Alarms 31

2.5 Analog Sensors 32

2.5.1 Set up an Alarm for an Analog Sensor 34

2.6 Virtual Temperatures 34

2.7 Digital Sensors 36

2.8 Display 38

2.9 Printer 40

2.10 Fridge 42

2.11 GPS 43

2.12 Communication 45

2.13 Fuel 47

2.14 Battery 49

2.14.1 Set up Alarming on a Low Battery Voltage 50

2.14.2 Set up Low Power Mode on Low Battery Voltage Detection 51

2.15 Door Locks 51

3 Installation Qualification 53

3.1 Recorder 53

3.2 Communication 53

3.3 Sensors 53

3.4 Peripherals 53

4 Operate the Recorder 54

4.1 Control Panel 54

4.1.1 LCD Display 54

4.1.2 Keyboard 55

4.1.3 Printer 56

4.1.4 Low Power Mode 56

4.2 User Menu Euroscan TX3/RX3 56

4.2.1 (Menu - 1) Print menu 57

4.2.2 (Menu - 2) Alarm settings 59

4.2.3 (Menu - 3) User settings menu 60

4.2.4 (Menu - 4) Status menu 62

5 Maintenance 63

5.1 Inspection 63

E0004, Version 02 © ORBCOMM Proprietary

5

Page 6: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

5.2 Error Codes 63

5.3 RMA 63

5.4 Replace a Paper Roll 64

5.5 Euroscan TX3 / RX3 Recorder Calibration 65

5.6 Euroscan TX3 / RX3 Recorder Temperature Verification 66

5.7 Technical Specifications 67

5.8 Remove the Recorder 69

5.9 Factory Settings 69

E0004, Version 02 © ORBCOMM Proprietary

6

Page 7: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

LIST OF FIGURES

Figure 1: RX3 Recorder 8

Figure 2: TX3 Recorder 9

Figure 3: Example Installation on a Truck 19

Figure 4: Example Installation on a Trailer 20

Figure 5: Main Settings Menu 29

Figure 6: Compartments Menu 30

Figure 7: Alarm - General Settings Tab 31

Figure 8: Alarm Tab 32

Figure 9: Analog Sensor Tab 33

Figure 10: Virtual Temperature - Sensor Tab 35

Figure 11: Digital Sensor Tab 36

Figure 12: Digital Sensor 8 Tab 38

Figure 13: Display Menu 39

Figure 14: Printer Menu 41

Figure 15: Fridge Alarms Tab 42

Figure 16: GPS Menu 44

Figure 17: Communication - Protocols Tab 45

Figure 18: Communication - iGPRS Tab 46

Figure 19: Communication - SMS Tab 46

Figure 20: Communication - Bluetooth Tab 47

Figure 21: Fuel Menu 48

Figure 22: Battery Menu 49

Figure 23: Door Locks Menu 52

LIST OF TABLES

Table 1: Euroscan RX3 Package Contents 12

Table 2: RX3 Articles 13

Table 3: Euroscan TX3 Package Contents 14

Table 4: TX3 Articles 14

E0004, Version 02 © ORBCOMM Proprietary

7

Page 8: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

ABOUT THIS INSTALLATION GUIDEThank you for purchasing this ORBCOMM Euroscan branded TX3 / RX3 recorder (hereafter referred to as theEuroscan TX3 / RX3 recorder). Read these instructions carefully and keep them in a safe place. Always follow allsafety instructions. All statements, technical information and recommendations related to ORBCOMM products arebased on information believed to be reliable, but the accuracy or completeness is not guaranteed.

Both products (RX3 and TX3) are produced by ORBCOMM in the European Union. ORBCOMM has a policy ofcontinuous development and improvements. Therefore, products, guides and technical information are subject tochange without prior notice.

Disclaimer

Important

This guide contains information about Euroscan TX3 / RX3 recorders. No representations or warrantiesare made as to the accuracy or completeness of the information contained herein. No representation orwarranties are made as to the completeness and compliance of any installations, which are performedusing this guide.

For information regarding Liability, Warranty, Guarantee and/or Service, please refer to the EquipmentSales Terms and Conditions ORBCOMM Europe B.V. (available on request).

PurposeThis guide contains detailed installation information for and operation of the Euroscan TX3 / RX3 recorders. Followthe instructions and recommendations of this guide for a proper installation. Improper installations will void theproduct warranty. The intended audiences for this guide include field support personnel, product evaluators andcertified third-party personnel. It is particularly intended for personnel who are responsible for system installation andactivation. In addition, and is appropriate, this guide may be used for customer training purposes.

Figure 1: RX3 Recorder

E0004, Version 02 © ORBCOMM Proprietary

8

Page 9: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 2: TX3 Recorder

Document ConventionsThe common conventions used in this guide are below.

Symbol Description

[ ] Used when referring to exact recorder menu items or options.

< > Used to indicate buttons, such as <green> button.

Danger/Caution/Warning

Indicates an explicit message possibly resulting in injuries, unexpected behavior, or damaged hardware.

User alert

Indicates a message that requires special attention.

Note:

Will be used to indicate a message with information related to the current section.

Terminology

Term Definition

Recorder: The X3 recorder. It is the device intended to be used to make measurements, alone or in conjunctionwith supplementary device(s).

Temperature sensor: Element of a measuring instrument or measuring chain that is directly affected by the temperature.

Refrigerator A refrigerator connected to the recorder. Also referred to as reefer or fridge.

Keyboard The keyboard is the panel on the front of the recorder with the colored buttons.

Protection guard Cage to protect temperature sensors.

E0004, Version 02 © ORBCOMM Proprietary

9

Page 10: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Term Definition

Mapping Reading sensor from external source and processing as own sensor information.

OC Open circuit.

SC Short circuit.

ReferenceThe content of the following documents may be useful in conjunction with this guide. These documents areavailable upon request.

[1] [E0003] [PRO.244] DeviceManager User Guide

[2] [EN-WHT-0004] Bringing a unit online

[3] [E0002] [PRO.234] ColdChainView User Guide

Intended Use StatementThe recorder is designed to safely operate under the following conditions:

l Operating voltage: 10-32 VDC (negative earth), protected against alternator load shedding.l Temperature in operation: -30 °C / +70 °C (-22 °F / 158 °F)l Temperature maximum: -40 °C / +85 °C (-40 °F / 185 °F);l Humidity: 97% relative humidity at 25 °C (77 °F).l No special ventilation requirements. Euroscan recorders are designed for use in an automotive environment.l For protection a 10A floating fuse must be fitted in the positive (+VE) power line as close as possible to the

power connection (provided in installation kit).

Use of this product in adverse conditions will void the product warranty.

RegulationsOnly ORBCOMM trained and qualified personnel should be allowed to install, replace or service the recorder. TheORBCOMM certified installer needs to perform the installation of the recorder complying with at least the following:

l This installation and operation guide and other relevant documentation provided by the manufacturer.l EMC Directive 2004/108/ECl Harmonized standards under Directive 1999/5/ECl WEEE Directive 2012/19/EUl Traffic regulations of the country of installation and countries in which the recorder will be used.l Regulations and instructions described in the installation and operation manual of any supplementary device

(s).

Safety Guidelinesl Be aware of hazards involved with electrical circuitry and be familiar with standard practices for preventing

accidents.l Do not modify the recorder in any way.

E0004, Version 02 © ORBCOMM Proprietary

10

Page 11: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

l Do not work on the system or connect or disconnect cables during periods of lightning activity.l Do not expose the Euroscan RX3 recorder to rain or moisturel Do not expose the Euroscan TX3 recorder (the inside) to rain or moisture during installationl Do not use the recorder if it has been physically damaged or shows to be abused.l Do not install near heat sources such as exhaust pipes.l Do not work on the installation when the recorder is connected to a power supply, except when connecting the

antenna(s) (see ESD warning for the Euroscan RX3 installation instruction).l Only use accessories specified by the manufacturer.l A lithium battery is used in the recorder. Do not try to charge, discharge or replace this battery.

WEEE StatementDisposal of this product should be handled according to all national laws and regulations.

The mark shown to the right is in compliance with Waste Electrical and Electronic EquipmentDirective 2002/96/EC (WEEE). The mark indicates the requirement NOT to dispose the equipment asunsorted municipal waste, but use the return and collection systems according to local law.

Revision History

Document Version Publication Date Reason for Change

1.0 15 Jul 2015 Newly established

1.1 3 Sep 2015 Updated statement about lithium battery in section 4.7 “Technical specifications”.

1.2 23 Oct 2015 Removed low-voltage directive

Update drawing regarding fuse

Updated description of digital input connections

1.3 19 Oct 2017 Updated references from EuroTool to DeviceManager

Added (New) Chapter for configuring the device over DeviceManager

Updated document to reflect changes introduced until Firmware version 3.35.0

02 May 2018 Initial release in ORBCOMM format for firmware version 3.35.0.

E0004, Version 02 © ORBCOMM Proprietary

11

Page 12: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

1 INSTALLATIONThe two recorder versions, Euroscan TX3 and Euroscan RX3, look different. The Euroscan RX3 is suitable for cabininstallation and the Euroscan TX3 for outside mounting on a trailer. Both versions are available with or without aprinter. On the rear of the recorder, the connectors are designed for up to six temperature sensors, four digital inputs,a power supply, CAN bus (optional), digital output and two RS-232 COM ports. If no free radio slot is available, the useof the optional Euroscan universal mounting kit is strongly recommended.

1.1 Identify the ComponentsIn general, Euroscan TX3 / RX3 temperature recorders are supplied with all required components for a standardinstallation. A standard installation includes the mounting of the recorder, and mounting and connecting of twotemperature sensors. Optionally, you can connect four additional sensors and up to four digital (status) inputs.

1.1.1 Euroscan RX3The Euroscan RX3 has been developed for mounting in a vehicle cabin. The chassis of the recorder meets thedimensions of a single DIN radio slot (according to ISO 7736) and can be easily mounted in an available slot.

Euroscan RX3 temperature recorders are boxed in environmentally friendly cardboard packaging and are shippedwith the following:

Table 1: Euroscan RX3 Package Contents

Quantity Description

1 Recorder

1 Temperature sensor (15mtr)

1 Temperature sensor (22mtr)

1 Safety bracket temperature sensor (protection guard)

1 Power cable (black/red/yellow)

1 ISO 7736 installation kit

1 Waterproof 10A fuse bracket including 10A fuse

E0004, Version 02 © ORBCOMM Proprietary

12

Page 13: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Quantity Description

2 Removal keys

1 Phoenix 8 connector

1 Phoenix 6 connector

1 Screw M3 x 20

1 Nut M3

1 O-ring M4

2 Temperature sensor clamps

1 X3 Quick Start Guide

1 X3 Safety instructions

1 X3 Certificate of conformity

Table 2: RX3 Articles

Article Number Description

420.001.0206 RX3 Recorder without communication module

420.025.0206 RX3 Recorder with 3G/GPS communication module (without antenna)

1.1.2 Euroscan TX3The Euroscan TX3 has been developed especially for mounting outside on a box body or trailer. The recorder iscontained in a waterproof polymer plastic box (IP65). Like the Euroscan RX3, the connectors are on the back of theunit. Cabling is installed through watertight cable glands, which are mounted in the recorder box.

Euroscan TX3 temperature recorders are boxed in environmentally friendly cardboard packaging and are shipped withthe following:

E0004, Version 02 © ORBCOMM Proprietary

13

Page 14: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Table 3: Euroscan TX3 Package Contents

Quantity Description

1 Recorder

1 Temperature sensor (6mtr)

1 Temperature sensor (22mtr)

1 Safety bracket temperature sensor (protection guard)

1 Power cable (black/red/yellow)

1 ISO 7736 installation kit

1 Waterproof 10A fuse bracket including 10A fuse

4 Blind nut

4 Screw M5 x 30

1 Phoenix 8 connector

1 Phoenix 6 connector

1 Screw M3 x 20

1 Nut M3

1 O-ring M4

2 Temperature sensor clamps

1 X3 Quick Start Guide

1 X3 Safety instructions

1 X3 Certificate of conformity

Table 4: TX3 Articles

Article Number Description

410.001.0206 TX3 Recorder without communication module

410.025.0206 TX3 Recorder with 3G/GPS communication module (without antenna)

1.2 Review the RequirementsEnsure you have the following functional and installation requirements before you begin:

l Power supply 12-24 VDC (negative earth)

l Preferable radio slot and/or IP20 proof location available for Euroscan RX3

l Free IP65 proof mounting location on trailer for Euroscan TX3

l (For Recorder with Modem) An activated SIM card, enabled for (data) roaming and SMS functionality.

l (International traceable) calibration equipmentl Appropriate working tools for applying the installationl Supplementary mounting materials (like kit (accepted by the food and pharma industry), cable trunking, and

E0004, Version 02 © ORBCOMM Proprietary

14

Page 15: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

fixing materials for cable mounting)l Latest version of DeviceManager software package with sufficient permissions for any installation.

1.3 Review the Connector BlocksBoth versions have identical PCBs, so the connections for temperature sensors, digital inputs and power supply arethe same for both versions. On the back of the recorder you will find four connector blocks (see figure), eachdescribed below.

Connector 1

Pin 1: Power Supply (+)

Pin 2: Power Supply (-)

Pin 3: Display Backlight

Pin 4: Alarm Out

Pin 5: Can Hi

Pin 6: Can Lo

Connector 2

Pin 1: GND

Pin 2: COM 2 - Rx

Pin 3: COM 2 - Tx

Pin 4: COM 1 - Rx

Pin 5: COM 1 - Tx

Connector 3

Pin 1: Digital Sensor D1 (+)

Pin 2: Digital Sensor D1 (-)

Pin 3: Digital Sensor D2 (+)

Pin 4: Digital Sensor D2 (-)

Pin 5: Digital Sensor D3 (+)

Pin 6 Digital Sensor D3 (-)

Pin 7 Digital Sensor D4 (+)

Pin 8 Digital Sensor D4 (-)

E0004, Version 02 © ORBCOMM Proprietary

15

Page 16: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Connector 4

Pin 1: GND Analog Temperature Sensor

(T1, T2, T3) (-)

Pin 2: T1 Analog Temperature Sensor (+)

Pin 3: T2 Analog Temperature Sensor (+)

Pin 4: T3 Analog Temperature Sensor (+)

Pin 5: Digital Sensor D3 (+)GND AnalogTemperature Sensor

(T4, T5, T6) (-)

Pin 6 T4 Analog Temperature Sensor (+)

Pin 7 T5 Analog Temperature Sensor (+)

Pin 8 T6 Analog Temperature Sensor (+)

1.3.1 Connector Block 1 (power supply and outputs)Power supply

Connect the power supply on pin 1 (+) and pin 2 (-). The recorder is suitable for a voltage between 10-32 VDC(negative earth).

Power consumption when printing is 25 W.

Display background light (preferable for the Euroscan RX3)

Usually the display background light switches on after pressing any key and switches off automatically after a fewseconds if no further key is pressed. If a permanent background light is required while driving, connect pin 3 to avehicle ignition +signal.

Never connect display background light directly to vehicle battery.

Alarm outputs

Pin 4 is a digital alarm output. The output switches to ground in case of an alarm situation and is limited to 1Aoutput current. Below are two examples of how the digital alarm can be connected.

Option 1 - Direct Connection

E0004, Version 02 © ORBCOMM Proprietary

16

Page 17: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Option 2 - Toggle Connection

Option 2 is recommended in case an alarm is chosen that has peak currents higher than 1A.

1.3.2 Connector Block 2 (serial port)The temperature recorder has two serial communication (COM) ports. These are used for a permanent connectionwith external devices. For proper connection use a suitable connector (connector block 5-way, P/N 005.000.0005).

Pins 2 and 3 are used for COM 2

Pins 4 and 5 are used for COM 1

Pin 1 is a shared pin for the ground of both COM ports.

Both inputs are activated by default and are pre-programmed as follows:

COM1 = UCP Protocol

COM2 = UCP Protocol.

The protocol should be changed to match the communication protocol used by the external device.

1.3.3 Connector Block 3 (digital inputs)Euroscan TX3 / RX3 recorders offer the possibility to connect four digital inputs. Pins 1-8 are accordingly marked asD1-D4. For the status inputs, consider the polarity.

Pins 2, 4, 6, and 8 are internally connected to the power supply.

Pins 1, 3, 5, and 7 are signal inputs.

All four inputs are de-activated by default, the next functions are pre-programmed:

D1 = Back Door

D2 = Side Door

D3 = Defrost

D4 = Refrigeration.

E0004, Version 02 © ORBCOMM Proprietary

17

Page 18: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

At every opening or closing of the input circuit a status change will be recorded into memory, but only if the input hasbeen activated and configured correctly in the parameter settings.

1.3.4 Connector Block 4 (temperature inputs)Euroscan TX3 / RX3 recorders offer the possibility to connect six temperature sensors. Pins 1-8 are accordinglymarked with T1-T6. Pins 2, 3, 4, 6, 7 and 8 are signal inputs and pins 1 and 5 are internally connected to ground. Thepolarity of the sensor cable is not relevant.

In the factory settings inputs 1 and 2 are activated and pre-programmed as follows: T1 = Return Air, T2 = Front.Inputs 2 to 6 are de-activated by default, and are pre-programmed as follows:

T3 = Rear

T4 = Probe

T5 = Probe

T6 = Probe.

A used input must always be activated and configured in the parameter menu.

Never use tinned wire ends in the phoenix connectors of the recorders. You can apply a ferrule on thestranded wire or fold back the stranded wires over the isolation and fully insert in the phoenix connector(so isolation included).

1.4 Mount the Recorder

Wiring should be free of obstacles, kinks or dents. The use of wiring loom is recommended to preventdamage to the cable (that is. due to vibration).

1.4.1 Power supplyThe power supply must be connected directly to the vehicle or refrigerator battery. The included 10 A (T) floating fusemust be fitted in the +power line as close as possible to the power connection. The Euroscan TX3 / RX3 recorders aresuitable for a voltage between 10 - 32 Volt DC.

1.4.2 Temperature sensorsEuroscan TX3 / RX3 recorders can only be used with Euroscan temperature sensors as supplied with the Euroscanpackage.

E0004, Version 02 © ORBCOMM Proprietary

18

Page 19: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Type Temperature Range Accuracy Length Part Number

Temp. Standard

-50 °C to +70 °C

0.1 °C 6m 009.000.5106

15m 009.000.5115

22m 009.000.5122

Temp. standard with connector 0.1 °C 3m 009.000.5103

Temp. standard .2 °C 6m 009.000.5006

15m 009.000.5015

22m 009.000.5022

Glycerin probe 0.2 °C 12m 009.001.0003

Before installation, determine how many measurement points are required to retrieve the desired information. Onceyou know the number and position of the sensors, you can come to a conclusion about the air temperature in anentire compartment.

Observe the following before planning the installation of the temperature sensors:

l Do not mount the temperature sensor in a location without air circulation.l Protect the sensor position against bumping of load, doors, etc.l Leave a minimum distance of 0.5 m between the channel of the interior light and the sensors.l ORBCOMM recommends at least one sensor per compartment and one sensor in the return air flow. The best

position of a compartment sensor is in the middle, under the ceiling, at about 1/3 of the compartment lengthmeasured from the back.

l Mount the compartment sensor with the Euroscan protection guard, which will allow sufficient air circulationaround the sensor.

l For future calibration requirements, it is advisable to allow enough spare cable to enable the sensor to belowered to the floor.

Figure 3: Example Installation on a Truck

E0004, Version 02 © ORBCOMM Proprietary

19

Page 20: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 4: Example Installation on a Trailer

1.4.3 Digital InputsThe digital inputs allow monitoring and registration of digital signals. Typical functions are defrost, refrigeration(on/off), back and side doors (open/close), battery back-up and compartment on/off. By configuring the parameters,the interpretation of the corresponding status can be distinguished.

There are three ways of connecting door switches or other digital signals:

l Standard switch contact on digital input (low)

l Switched to battery (+) (high)

l Switched to ground (-) (low)

E0004, Version 02 © ORBCOMM Proprietary

20

Page 21: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Digital input distinct between high levels and low levels around 5 volts. A voltage level lower than4 volts is low level, a level higher than 6 volts is high level. The digital active can be matched tolow or high level in menu 6 of the recorder.

1.4.4 Fridge ConnectionThe Euroscan X3 recorders can be connected to several types of fridges from different suppliers. Remember that thefridge needs to be prepared to communicate with a 3rd party (telematics) device, before it can communicate with theEuroscan temperature recorder.

Additionally, the correct communication protocol should be configured in the X3 temperature recorder for successfulcommunication. For more information about configuring the communication protocol, refer to section 2.12

The Euroscan X3 recorder is compatible with refrigeration units from the following suppliers:

l Carrierl Thermo Kingl Mitsubishil Konvekta

For more detailed information and requirements about connecting a fridge unit to the X3 temperaturerecorder, please contact your distributor or ORBCOMM Euroscan support.

1.4.5 Door Lock ConnectionThe Euroscan X3 recorders can be connected to Door Lock Controllers from several suppliers. Connecting a door lockcontroller may offer the possibility to remotely (un)lock and (dis)arm a door lock.

Remember that the Door lock controller should be prepared to communicate with a 3rd party (telematics) device,before it can communicate with the Euroscan temperature recorder.

Additionally, the correct communication protocol should be configured in the X3 temperature recorder for successfulcommunication. For more information about configuring the communication protocol, refer to section 2.12.

For more detailed information and requirements about connecting a door lock controller to the X3temperature recorder, please contact your distributor or ORBCOMM Euroscan support.

Additional settings may be required in the X3 recorder’s configuration, depending on the connected doorlock controller.

1.4.6 GPSRemember the following when mounting a recorder with internal antenna or an external antenna:

l Always mount horizontally with the reception surface facing up.l Do not choose a location covered by metal, metal containing components or paint. Also pay attention to

windows in which metal film is processed.l Mount in clear sight.l Wiring should be free of obstacles, kinks or dents. This could influence the performance of the reception

E0004, Version 02 © ORBCOMM Proprietary

21

Page 22: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

antenna cable.l Mount in an interference free location.

Testing of the GPS signal cannot be compared to reception on smart phones. These use the assisted GPStechnology in which location detection is used via cell towers and Wi-Fi.

1.4.7 RecorderThe installation set of the Euroscan TX3 / RX3 recorder contains almost all components required for a standardinstallation with two temperature sensors. In addition, some general materials like a kit (accepted by the food andpharma industry), cable trunking and fixing materials for cable mounting are required. Use the existing cabletrunkings for both outside and inside walls. If no existing cable trunkings are available, mount new ones.

Do not use self-adhesive cable trunkings as adhesion will not last due to heavy temperature fluctuationsand peaks.

All drilled holes need to be sealed with a suitable sealant.

1.4.8 Install the Euroscan RX3The Euroscan RX3 recorder is designed to be mounted within the cabin of a vehicle in a single DIN radio slot(according to ISO 7736).

Optional Mounting Kit

If no radio slot is available the recorder should be mounted with the optional mounting kit (P/N: 001.000.1202 RXmounting frame nonmetal). This will replace a radio slot and can be fixed either on or under the dashboard and onthe back wall. Ensure that the position chosen allows the driver to see the display and use the operator keyboard.Remember that access to the printer is required to replace the paper roll.

E0004, Version 02 © ORBCOMM Proprietary

22

Page 23: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

When installing an Euroscan RX3 unit with a communication module, prevent Electrical StaticDischarges (ESD) damage by connecting the power before connecting the GPS + GPRS antennas.

1. Select a suitable position for the Euroscan RX3 recorder, for example a free car radio slot in the dashboard, orabove the driver. If there is no free slot, ORBCOMM recommends the optional mounting kit (P/N:001.000.1202 RXmounting frame nonmetal). The mounting kit can be fitted on top, or underneath thedashboard.

2. Push the mounting frame into the slot and bend the metal flaps to secure its position.3. Install the sensors from the body to the driver’s cabin. Ensure you fit the cables along the chassis with the

harness, so that they won’t break when tilting the cabin.4. Take the connector blocks off the back of the instrument and fix the cables according to the wiring diagram

(see section 1.3).5. Connect the power supply via the 10 A fuse provided, directly to the main vehicle battery, the recorder will start

recording automatically.6. Attach, where applicable, the GPS + GPRS antenna.

Ensure adequate power is supplied permanently to the recorder at all times.

7. Test the functionality and do a printout before pushing the instrument into the slot.

1.4.9 Install the EuroscanTX3The Euroscan TX3 recorder has been designed for outside mounting directly on the body. Usually it is fixed under therefrigeration unit on the front side of the body where it is easily accessible.

Cables should be installed via watertight cable glands. This avoids humidity penetration into the box. Foreach cable a separate gland should be used unless you use a gland especially designed for more cables.

1. Mark four holes at the front of the body in an easily accessible location (usually underneath the refrigeratorunit to the right or left-hand side). Then drill holes with a 10 mm drill.

2. Insert the four rubber mounting nuts. Mount the recorder using the four screws and washers provided (notemetal washer to be located on the outside of the mounting lug fixed to the box). Ensure screws are screwed in

E0004, Version 02 © ORBCOMM Proprietary

23

Page 24: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

tight. Use any available entrance for the temperature sensors. If no entrance is available, drill a hole largeenough at suitable location through bulkhead to pass the temperature sensors through. Make sure that thecable glands of the box show downwards.

3. Position sensor no. 1 to the return air (RET.AIR) usually next to the refrigerator sensor, but only if good airflowis around it, otherwise locate sensor onto grill.

4. Position sensor no. 2 at high level usually to the roof, either in the center or to the side, 2 - 3 meters in from therear doors.

5. Ensure all cables are installed neatly into plastic channels or similar. Ensure that there is at least 1 - 2 meters ofspare cable in channels, this will facilitate calibration.

6. Connect power cable through the 10 A fuse provided, directly to the main vehicle or refrigerator battery,recorder will start recording automatically.

Ensure adequate power is supplied permanently to the recorder at all times.

7. Ensure all holes drilled through the body are sealed with a suitable sealant.

1.4.10 Install the AntennaAntenna Installation Position

1. Mount the TX bracket or magnetic antenna in a position that the black top of the antenna has a clear line-of-sight to the satellites. Make sure that the 3G/GPRS antenna has a clear line-of-sight.

2. Stick the RX antenna on the inside of the windscreen and make sure that it has a clear view to the sky above.

E0004, Version 02 © ORBCOMM Proprietary

24

Page 25: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

l Do NOT let the antenna hang on the connection cablel Do NOT mount the antenna and wiring close to a heat source (like heating channels or

exhaust pipes)l Do NOT cut or extend or make any changes to the cablesl Do NOT curl up cablesl Do NOT bend the cables in sharp angles as this might break the core of the wirel Do NOT place the antenna too close to toll systemsl Make sure that the antenna has a clear view to the sky (towards the satellites)l Place cables into a cable gutterl Install the antenna according to the installation standards (and not directly in the drivers

view).

Connect the Antenna

ESD Caution:

Before connecting the antennas, make sure that the recorder is already connected to power.

Only for TX

Make sure the antenna leads into the two holes of the cable gland, as shown in the figure, and then attach the cablegland to the trailer box with the included M20 nut.

Connect the antenna cables to the connections on the back (RX model) or left side (TX model) of the recorder, asseen in the figure.

RX (back)                                                         TX (left side)

TX model:

1. Put the recorder into the trailer box and fasten the recorder inside the box with the four black screws andwashers.

2. Tighten the cable gland, leaving enough wire (10 cm) inside the trailer box to allow for easy access.

RX model:

E0004, Version 02 © ORBCOMM Proprietary

25

Page 26: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

1. Put the recorder into the radio slot until it locks into place.

3M Module Safety Instructions

Only ORBCOMM trained and certified personnel are allowed to make changes to the recorder. Replacingthe modem without receiving training from ORBCOMM will void the warranty of the device.

Make sure that any work on the recorder is done at an ESD save workstation.

Failing to do so will damage the equipment beyond repair and void the warranty.

Disconnected the recorder from power while working.

A replacement modem (part number: 006.000.9003, 3G Module + GPS) for Euroscan products can be ordered fromORBCOMM.

The installation or replacement of a modem in the recorder should always be performed by personnel trained byORBCOMM and should follow the procedure of the training.

3G modules are only suitable in Euroscan X3 recorders that perform on Platform 7(https://www.coldchainview.com).

SIM and GPRS settings

To establish online communication for the recorder, follow the instructions below:

Make sure the following information is available and checked.

l Have an activated SIM-card that supports GPRS data.l Verify that the SIM-card works before installation.l Have the specific APN settings for the SIM card and if applicable, the correct

pin code.

First make the changes to the configuration settings to accommodate the SIM card you want to install.

To access the menu on the recorder, hold down the [MENU] button (green) for 4 seconds until a prompt for the PINCODE appears on the display. Press [1111] to access the General Settings menu.

1. Change the GPRS settings in Menu 11 “Communication Settings”2. For GPRS communication, go to COM4 and select “UCP protocol”. You find this in Menu 11.4.0.

E0004, Version 02 © ORBCOMM Proprietary

26

Page 27: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

3. Enter the menu 11.4.1 “GPRS settings”a. If applicable provide the pin-code of the SIM card.

4. Go to Menu 11.4.1.3 to the “APN server”a. Choose one of the APN pre-sets that are available in the recorder by pressing [<] [>].

OR

Set it to “Manual input” if you want to provide your own APN settings for this SIM card.

b. Enter the specific values of your SIM card

“APN server”/ “APN user” / “APN Password”

c. Leave the DNS settings blank.5. Reboot to recorder to apply the configuration settings.6. Power off the recorder to install the SIM card.

7. Install the SIM card in the SIM card holder on the back of the recorder.

a. Press the yellow push button down into the recorder to release the SIM card holder.b. Place a SIM card in to the holder and place the holder with the SIM card back into the recorder.

8. Power on the recorder.

If you run into problems while bringing the recorder online, you can trouble shoot with the “Bringing a unit online”document [2] that you can request from your distributor.

E0004, Version 02 © ORBCOMM Proprietary

27

Page 28: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

2 CONFIGURE THE RECORDER USING DEVICEMANAGERConfigure the recorder using the DeviceManager software package. For information about connecting the X3 recorderto the DeviceManager software, please refer to the DeviceManager User Guide [1].

The following sections describe the parameters that can be set through the Configuration menu of DeviceManager,including their functions and examples.

2.1 Basic Configuration MenusDeviceManager Configuration menus include items in the list below. To complete a basic configuration, all menuitems shown in bold, should be checked before moving on to the Installation Qualification chapter.

l Main Settingsl Compartmentsl Alarmsl Analog Sensorsl Virtual Temperaturesl Digital Sensorsl Displayl Printerl Fridgel GPSl Communicationl Fuell Batteryl Door Locks

2.2 Main SettingsMain settings is the first view to open when clicking <Change Configuration>. From here you can edit generalinformation and settings about the recorder.

E0004, Version 02 © ORBCOMM Proprietary

28

Page 29: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 5: Main Settings Menu

Vehiclename: The identification of the recorder

Vehiclename can be changed for better identification.

By default, the Vehiclename is the serial number followed by the recorder type. For example,11501814X3 or 12501050X3.

Copy Trailer ID: Allows the Vehiclename to be automatically replaced with the name of a connected peripheral.

For example, the name can be replaced by the name of a connected Fridge unit.

Customer ID: Allows you to assign a recorder directly to a customer account on the ColdChainView server.

Ensure you have the correct Customer ID before modifying this field. This is an 8-digitnumber.

Language: The current language set for the recorder.

Sensor Measure interval: The interval between each temperature measurement.

Can be set to a value between 1 and 60 minutes.

Display/Terminal settings

Temperature format: The temperature format of the recorder

Can be set to °C (Celsius) or °F (Fahrenheit)

Distance format: The distance format of the recorder.

Can be set to KM (Kilometers) or MI (Miles).

Date/Time format: The Date/Time format of the recorder.

Can be set to DD/MM/YYYY or MM/DD/YYYY.

E0004, Version 02 © ORBCOMM Proprietary

29

Page 30: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Timezone: The current timezone offset.

This field will always show the default offset without daylight saving time.

Auto daylight saving timecorrection:

To enable or disable the automatic change of summer/winter time in a time-zone.

Pincode: Allows you to set the Pincode of the recorder.

The pincode is required to access the parameter menu directly from the recorder

Changing the pincode enhances the security of the device. For more information, please refer tothe DeviceManager User Guide [1].

2.3 CompartmentsCompartments can be used to group various sensors together. From the compartments menu, you can enable anddisable compartments, and assign alarm groups to a compartment.

Figure 6: Compartments Menu

E0004, Version 02 © ORBCOMM Proprietary

30

Page 31: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Compartment X On: Allows you to enable or disable the compartment.

If the compartment is disabled; No alarm monitoring will be active for the analog sensors inthe compartment, even if an Alarmgroup is assigned.

Compartment Name: Allows you to set the name of the compartment that will be used in ColdChainView, printed onthe ticket and displayed on the recorder display.

Alarmgroup: Allows you to choose the alarm group assigned to the compartment.

The alarm groups must be enabled and configured in the Alarms tab. See section 2.4 for moreinformation about alarm groups.

2.4 AlarmsUse Alarm groups to set alarm thresholds for analog sensors connected to a compartment. The Alarms menu isdivided into sub-tabs, the General Settings tab, which covers settings for every alarm group, and multiple Alarm Xtabs, which cover settings for individual alarm groups.

Figure 7: Alarm - General Settings Tab

Alarm Repetitions: Allows you to set the number of buzzer activations when an alarm remains active.

Once the alarm number repetition is reached:-The Buzzer stops.-The alarm remains activated.

Alarm repetition interval: Allows you to set the time interval between buzzer activations when an alarm remains active.

This option is unavailable when the Alarm Repetitions is set to 0

Alarm Output Function: Allows you to set the function of the Alarm Output (AO) on connector 1:

-The option Switches with alarm events activates an external device (sound or light) in case of analarm.

-The option Switched with external commands starts or stops a connected fridge unit.

FridgeSwitch Function: Not used at this time.

E0004, Version 02 © ORBCOMM Proprietary

31

Page 32: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 8: Alarm Tab

Alarm X On: Allows you to enable or disable an alarm group.

Even if the alarm group is enabled the alarm group must be assigned to a compartment tobe monitored.

See section 2.2 for more information about compartments.

Alarm name: Allows you to enter a name for the alarm group.

Alarm group function: Allows you to select a general function for the alarm group (read-only).

Upper threshold: Allows you to set the upper limit for temperatures before the activation of the alarm.

Lower threshold: Allows you to set the lower limit for temperatures before the activation of the alarm.

Initial delay: Allows you to set an initial delay before monitoring the sensors whether an alarm condition isfulfilled.

This is intended to ignore alarms, for example, when a recorder is started and the compartmenthas not yet reached the Set Point temperature.

Upper alarm delay: Allows you to set the time limit before the activation of an alarm when the upper threshold hasbeen exceeded.

Lower alarm delay: Allows you to set the time limit before the activation of an alarm when the lower threshold hasbeen exceeded.

2.5 Analog SensorsFrom the Analog Sensors menu you can configure the Analog Sensors connected to the recorder, or map thetemperature information from external sources to the recorder.

E0004, Version 02 © ORBCOMM Proprietary

32

Page 33: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

For each temperature record written in the memory of the recorder, the recorder checks 10 temperature records andstores them based on the settings of the sensor. For example:

l Sensor measure interval = 1 minute: temperature sample taken every 6 seconds.l Sensor measure interval = 5 minutes: temperature sample taken every 30 seconds.l Sensor measure interval = 10 minutes: temperature sample taken every minute.

Figure 9: Analog Sensor Tab

Temperature X On: Allows you to enable or disable a sensor.

Disabling a sensor disables the information on the Display and the Printout, stopsrecording/logging and alarm monitoring for the selected sensor.

Sensor function: Allows you to select a general function for the sensor (read-only)

Sensor name: Allows you to set the name of the sensor that will be used in ColdChainView, printed on theticket and displayed on the recorder display.

Sensor type: Allows you to set the sensor type that will function as data input.

The sensor type is printed on the ticket, except for when the sensor function is set to probe.

External sensor type: Allows you to set the input from which the data must be mapped.

Only available when selecting the Sensor Type External Sensor, Transcan Protocol, RemoteProtocol or Fridge.

Print on compartment X: Allows you to assign the compartment on which the temperature data of this sensor will beprinted.

E0004, Version 02 © ORBCOMM Proprietary

33

Page 34: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Alarm on compartment X: Allows you to assign the compartment on which the sensor will be monitored for alarms.

To prevent unexpected behavior, do not select more than one compartment for eachsensor.

Logging method: Allows you to choose the temperature recording type.

- Off: Does not log temperature records for this sensor.

- Average (Default): Logs the average of the 10 temperature values as a record.

- Minimum value: Logs the lowest value of the 10 temperature values as a record.

- Maximum value: Logs the highest value of the 10 temperature values as a record.

Alarm on: Allows you to set the temperature alarm condition type.

- Average (Default): Alarm condition based on the average of 10 temperature values.

- Actual: Alarm condition based on the last measured temperature value.

- Minimum: Alarm condition based on the lowest of 10 temperature values.

- Maximum: Alarm condition based on the highest of 10 temperature values.

2.5.1 Set up an Alarm for an Analog SensorTo set up an alarm for an Analog Sensor, verify the following settings are checked:

l On the Analog Sensors menu:l The Analog Sensor is enabled, (Temperature X On is checked).l The Analog Sensor is assigned to a single compartment for alarm monitoring, (Alarm on compartment

X is checked).l On the Compartments menu:

l The Compartment where the sensor is assigned is enabled, (Compartment X On is checked).l An Alarm Group is assigned to the Compartment (Alarmgroup is not set to No Alarmgroup).

l On the Alarms menu:l The Alarm Group where the compartment is linked is enabled, (Alarm X On is checked).l Initial Delay, Upper Alarm Delay and Lower Alarm Delay are set to a value greater than 0.l Upper Threshold and Lower Threshold are set to the maximum and minimum allowed temperatures

respectively.

If all above settings are correctly set up, an alarm will sound as soon as the temperature of the sensor is outside ofthe bounds (created by the alarm group thresholds) for a specified period (defined by either the upper or lower alarmdelay, depending on the exceeded threshold).

2.6 Virtual TemperaturesVirtual sensors allow you to map the temperature information of sensors connected via an external source to therecorder.

E0004, Version 02 © ORBCOMM Proprietary

34

Page 35: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

The data obtained from external sensors mapped to the virtual sensor cannot be monitored for alarm situations.

As with the analog sensors; for each temperature record written in the memory of the recorder, the recorderchecks 10 temperature samples and stores it based on the settings of the sensor.

Figure 10: Virtual Temperature - Sensor Tab

Temperature X On: Allows you to enable or disable a sensor.

Disabling a sensor disables the information on the display and the printout, and stopsrecording/logging for the selected sensor.

Sensor function: Allows you to select a general function for the sensor (read-only).

Sensor name: Allows you to set the name of the sensor that will be used in ColdChainView, printed on theticket and displayed on the recorder display.

Sensor type: Allows you to set the sensor type that will function as data input.

External sensor type: Allows you to set the input from which the data must be mapped.

Print on compartment X: Allows you to assign the compartment on which the temperature data of this sensor will beprinted.

Logging method: Allows you to choose the temperature recording type.

- Off: Does not log temperature records for this sensor.

- Average (Default): Logs the average of the 10 temperature values as a record.

- Minimum value: Logs the lowest value of the 10 temperature values as a record.

- Maximum value: Logs the highest value of the 10 temperature values as a record.

E0004, Version 02 © ORBCOMM Proprietary

35

Page 36: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

2.7 Digital SensorsThe Digital Sensors menu allows you to configure the digital sensors connected to the recorder, or map the digitalinformation from external sources to the recorder.

Figure 11: Digital Sensor Tab

E0004, Version 02 © ORBCOMM Proprietary

36

Page 37: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Digital X On: Allows you to enable or disable a sensor.

Disabling a sensor disables the information on the display and the printout, stops recording /logging and alarm monitoring for the selected sensor.

Sensor function: Allows you to select a general function for the sensor.

By changing the function, the icon on the display will change accordingly. Listed below are allavailable icons.

Sensor name: Allows you to set the name of the sensor that will be used in ColdChainView, printed on theticket and displayed on the recorder display.

Print on compartment X:(Sensor 1-4 Only)

Allows you to assign the compartment on which the data of this sensor will be printed.

The data from a digital sensor is printed only on journey tickets.

Input level: Allows you to set the input level of the digital. The state of the digital can be compared to:

* Polarity:

l High: Contact closed = input active & Contact open = input inactive. Alarm is switchedon Low level

l Low: Contact closed = input inactive & Contact open = input active. Alarm is switchedon High level

* Copy the state of a digital input from an external device.

l External Input, Transcan Protocol or Remote Protocol.

* Copy the state of a digital input form a connected fridge.

l State of Digitals 1-4 (availability depends on fridge), Pretrip status or Defrost status.

* Copy the state of an input from a connected Doorlock.

l Doorlock Door State or Doorlock Lock State.

External sensor: Allows you to set the input from which the data must be mapped.

Voltage when digital is high:(Sensor 8 only):

Specifies the voltage when the digital input is considered at a high level. See Figure 12).

E0004, Version 02 © ORBCOMM Proprietary

37

Page 38: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Alarm on sensor: Allows you to enable or disable the alarm monitoring on a sensor.

Alarm delay: Allows you to set a delay before the digital alarm activation.

Figure 12: Digital Sensor 8 Tab

2.8 DisplayThe Display menu allows to configure the recorder’s display.

E0004, Version 02 © ORBCOMM Proprietary

38

Page 39: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 13: Display Menu

Display Settings

Display contrast: Allows you to set the contrast of the display.

The contrast determines the darkness of the screen and should be configured to optimally seethe data from a normal viewing angle.

Display backlight: Allows you to set the backlight intensity.

A higher intensity will make the screen brighter when operating the recorder.

Setting the backlight to 0 will disable the backlight.

Sensor Screen Position

E0004, Version 02 © ORBCOMM Proprietary

39

Page 40: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Position 1-6: Allows you to set which temperature sensor should be displayed on the recorder’s main screen.

For example, setting position 3 to position 1 will show the information of Sensor 1 in the thirdposition of the first bar. Setting position 5 to position 2 will show the information of Sensor 2 inthe second position of the second bar.

The same sensor can be placed in multiple positions if desired.

Setting the Position to 0 will disable the displaying of temperature information in this position.

No information is shown when the configured sensor is turned off. Make sure theconfigured sensor is turned on. See section 2.5 or 2.6 for more information about AnalogTemperature Sensors and Virtual Temperature Sensors.

Fridge

Alarm level threshold Allows you to set whether fridge alarms should be displayed on the recorder’s display.

- Don’t Display (Default): Alarms are not displayed when fridge alarms occur.

- All Alarms: Displays the message “Fridge” when any fridge alarm occurs.

- Only shutdown alarms: Displays the message “Fridge” only when a fridge shutdown alarmoccurs.

2.9 PrinterThe Printer menu allows to configure the recorder’s printer.

E0004, Version 02 © ORBCOMM Proprietary

40

Page 41: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 14: Printer Menu

Header Text: Allows you to set the header text at the top of a ticket.

Upper Limit: Allows you to set the upper limit for graphs printed on tickets.

Lower Limit: Allows you to set the lower limit for graphs printed on tickets.

If the total temperature range between upper and lower limit can be divided by 9 you achieve anoptimal result for the printout.

Graphical Journey ReportLength:

Allows you to set the distance in millimeters between hours on a Graphical Journey ticket.

Setting this to a higher number will increase the space between hours on the printed ticket.

When printing a graphical ticket over a period longer than or equal to 2 days, a default of2mm/hour is used to save paper.

User Menu Available: Allows you to set the Day start time, Day end time and Print time period from the recorder menu.

Clearing this check box will only allow modification of these settings through DeviceManager.

E0004, Version 02 © ORBCOMM Proprietary

41

Page 42: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Delivery Ticket: Allows you set which temperature values are printed on a delivery ticket.

- Print actual values only (Default): Only prints Actual temperature values.

- Print actuals + average values: Prints Actual temperature value and an average valuecalculated over the Historical report length set.

- Print actuals + average min/max values: Prints Actual temperature value, an average valuecalculated over the Historical report length set and the minimum and maximum temperaturevalue within this period.

Journey report timespan toprint:

Allows you to preset the timespan of a journey ticket.

These settings are stored as Day start time and Day end time in the recorder.

Historical report length: Allows you to set how much information should be used for creating a historic ticket.

Clicking on the button behind the numeric value switches the control between Hours or Days.

This setting is saved as Print time period in the recorder.

Numeric Report & Event Report

- Allows you to choose the extra information to add on the numerical and event tickets.

If no box is checked, only the temperature values and (if configured to print) digital values areprinted on the numerical tickets.

2.10 FridgeThe Fridge menu allows to configure the alarm group thresholds based on the set points of a connected fridge.

To use this feature, a fridge unit must be connected to the recorder.

Figure 15: Fridge Alarms Tab

E0004, Version 02 © ORBCOMM Proprietary

42

Page 43: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Auto Alarms:

Auto Alarm: Allows you to enable or disable the linking of a compartment to an Alarm Group and setting thethresholds based on the deltas set below, based on the connected fridge’s status.

Switch alarm off withfridge:

Allows you to unlink the alarm groups from the compartments in case the fridge turns off.

Auto Alarm Delay: Allows you to set a delay between the fridge turning off and the unlinking of the alarm groupsfrom the compartments.

When using this feature, set the delay to at least 1 minute. Setting the value to 0 will havea different behavior depending on the connected fridge model and can lead to unexpectedbehavior.

Auto Alarm Group Deltas

Delta +: The upper tolerance from the compartment set point.

For example, if the set point is 8°C and the Delta + is 6°C, the upper threshold will become 14°C.

The Delta + can be set to a value between 3°C and 9°C.

Delta -: The lower tolerance from the compartment setpoint.

For example, if the setpoint is 8°C and the Delta - is 6°C, the upper threshold will become 2°C.

The Delta - can be set to a value between 3°C and 9 °C.

Group x: The delta setting for compartment x.

2.11 GPSThe GPS menu allows you to configure when to write position and mileage records.

These settings are only used in combination with an X3 with a modem installed.

E0004, Version 02 © ORBCOMM Proprietary

43

Page 44: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 16: GPS Menu

Position

Loginterval (Time): Allows you to set a time interval for logging the current position.

Setting this to 0 disables logging on time interval.

Loginterval (Distance): Allows you to set a distance interval for logging the current position.

Setting this to 0 disables logging on distance interval.

Store position onTemperature:

Allows you to set a distance interval for logging the current position.

Setting this to 0 disables logging on distance interval.

Start/Stop

Stop Detection delay: Allows you to specify the time period after which the recorder is deemed to have stoppedmoving.

Start/stop detectiondistance:

Allows you set the distance which the recorder may move before detecting whether the recorderis moving.

E0004, Version 02 © ORBCOMM Proprietary

44

Page 45: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Mileage

Distance record interval(Time):

Allows you to set a time interval for logging the current driven mileage.

Setting this to 0 disables logging on time interval.

Distance record interval(Distance):

Allows you to set a distance interval for logging the current driven mileage.

Setting this to 0 disables logging on distance interval.

Speed limit alarm: Allows you to set an alarm for exceeding a certain speed limit.

Setting this to 0 disables this functionality.

Store mileage on stopevent:

Allows you to enable/disable the writing of the current driven mileage after the recorder hasdetected that it stopped moving.

2.12 CommunicationThe Communication menu allows you to set the functions of the communication ports of the recorder, set the APNand UCP settings for connecting to the ColdChainView platform, set SMS information for direct alarm reporting viathe recorder’s modem and set the Bluetooth settings when using an external Bluetooth module.

Figure 17: Communication - Protocols Tab

COM 1 & COM2 Function: Allows you to set the protocol used for the external communication ports (on CON1) of therecorder.

COM 3 Function: Allows you to activate the accelerometer protocol on the internal communication port of therecorder.

This COM port is reserved for future applications.

COM 4 Function: Allows you to set the protocol used for the internal communication port of the recorder.Generally, the modem is connected to this port

Changing the setting for this COM port may cause your device to be unable to connect tothe modem and therefore cannot connect to the ColdChainView platform.

E0004, Version 02 © ORBCOMM Proprietary

45

Page 46: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

COM 5 Function: -

CAN 0 Function: -

Figure 18: Communication - iGPRS Tab

iGPRS Working Mode: Allows you to specify if the modem can use roaming.

SIM Pincode: Allows you to enter the pincode for unlocking the SIM card.

APN Server: Allows you to select predefined operator settings for connecting to a GSM network

Make sure you select the APN settings corresponding to the SIM card in the device, or thedevice may not be able to get a network connection.

In case your operator is not listed in the APN Server menu, manually enter the:

- APN Server Address

- APN Username

- APN Password

Obtained from the distributor of the SIM card, and verify the unit can connect to the network.

UCP Server: Allows you to select to which type of ColdChainView platform the device should connect to.

Changing the server will automatically fill in the correct UCP Server Address and Port.

Do not manually enter a UCP Server Address and Port unless explicitly instructed. Enteringincorrect settings can cause data to be send to an incorrect server.

Figure 19: Communication - SMS Tab

E0004, Version 02 © ORBCOMM Proprietary

46

Page 47: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Telephone #1 & #2: Allows you to set a phone number to which a text message will be send in case an alarmsituation occurs.

The phone number should contain the country code (without leading 00 or +) followed by yourpersonal phone number. For example, “31612345678”

The sending of SMS must be enabled for the inserted SIM card. This cannot be configuredin the recorder and should be discussed with the provider of the SIM card.

SMS Mode: Not used at this time.

Figure 20: Communication - Bluetooth Tab

Bluetooth Pincode: Not used at this time.

LAP0 - LAP7: Not used at this time.

External Bluetooth protocol: Not used at this time.

2.13 FuelThe Fuel menu allows you to setup various settings for recording the fuel usage of a connected fridge unit or anexternal fuel sensor.

E0004, Version 02 © ORBCOMM Proprietary

47

Page 48: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 21: Fuel Menu

Fuel Level

Log interval: Allows you to set the time interval for recording the fuel level.

Setting this to 0 disables this functionality.

Log step interval: Allows you to set the percentage for recording the fuel level.

Setting this to 0 disables this functionality.

Low fuel level warning at: Allows you to set a threshold of remaining fuel in the tank before an alarm is activated.

Use External Fuel Sensor: By enabling this option, the recorder will save data from an external fuel sensor as opposed tothe fuel sensor of a connected fridge.

Fuel 100% voltage: Allows you to set the voltage when the external sensor indicates the fuel tank is full.

Fuel 0% voltage: Allows you to set the voltage when the external sensor indicates the fuel tank is empty.

Fuel Theft Alarm

Alarm delay: Allows you to set the time limit before the activation of an alarm when the Alarm threshold hasbeen exceeded.

Setting this to 0 will cause the recorder to immediately activate the alarm when fuel thefthas been detected.

Alarm threshold: Allows you to set the fuel consumption threshold which is used to determine whether fuel isbeing stolen.

Send SMS on alarm: Allows you to enable or disable the sending of an SMS through the modem of the unit

To use this feature, a phone number must be added to the recorder in theCommunication>SMS menu.

The sending of SMS must be enabled for the inserted SIM card. This cannot be configuredin the recorder and should be discussed with the provider of the SIM card.

E0004, Version 02 © ORBCOMM Proprietary

48

Page 49: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

2.14 BatteryThe Battery menu allows you to enable the logging of battery related information and allows you to set thresholds fora low battery alarm and activating the low power mode.

Figure 22: Battery Menu

Logging

Enable Power ModeRecords:

Allows you to enable or disable the writing of battery voltage records.

Battery voltage recordinterval:

Allows you to set an interval for logging the current battery voltage.

Setting this to 0 disables this functionality.

Battery

Low battery threshold: Allows you to set the lower limit for the voltage before the recorder will register having too lowpower.

The recorder will only register an alarm situation when the Enable Battery Low AlarmRecords setting is enabled. No visual or audible alarm will sound when low power is detected.

Low battery delay: Allows you to set the time limit before the activation of an alarm when the threshold has beenexceeded.

Setting this to 0 will cause the recorder to immediately activate the alarm when low powerhas been detected.

The recorder will only register an alarm situation when the Enable Battery Low AlarmRecords setting is enabled. No visual or audible alarm will sound when low power is detected.

Enable Battery Low AlarmRecords:

Allows you to enable or disable the writing of alarm records into the memory of the recorder.

E0004, Version 02 © ORBCOMM Proprietary

49

Page 50: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Initiates Data Transfer: Allows you to enable or disable initiating a data transfer when a Battery Low Alarm record hasbeen written in the memory of the recorder.

Enabling this option will speed up detection of a low power situation on the CCV platform.

Send SMS on Low BatteryAlarm:

Allows you to enable or disable the option to send a text message to all registered phonenumbers when a Battery Low Alarm record has been written in the memory of the recorder.

The recorder can only send a text message when a phone number has been saved inmemory. For more information see section 2.12

Force fridge start on lowbattery:

Allows you to enable or disable the option to start a connected fridge when a low battery recordhas been written in the recorder memory.

Force fridge start on lowbattery:

Allows you to set how long the fridge should be powered on in case of a low battery situation.

Low power mode

Low battery powerthreshold:

Allows you to set the voltage threshold for going into low power mode.

Low battery power delay: Allows you set the time limit before the activation of the low power mode after the threshold hasbeen exceeded.

Setting this to 0 will cause the recorder to immediately go into low power mode when thethreshold has been exceeded.

Low power after inactivity: Allows you to set a time limit before the activation of the low power mode after the recorder hasbeen inactive.

Setting this to 0 disables this functionality.

Wakeup interval: Allows you to specify an interval after which the recorder will go out of low power mode andresume normal operation for a specified period.

The period can be specified in the Wakeup time parameter.

Setting this option to 0 disables this functionality.

Wakeup time: Allows you to specify the period in which the recorder will resume normal operation afterwaking up while in low power mode.

If the recorder’s power is still below the threshold specified, the recorder will go back intolow power mode after this period has expired.

Inactive time recordinterval:

Allows you to set an interval for logging an inactivity record.

Setting this to 0 disables this functionality.

2.14.1 Set up Alarming on a Low Battery Voltage

This option requires additional setup on the CCV platform.

To set up alarming for a low battery voltage, the following settings should be checked:

E0004, Version 02 © ORBCOMM Proprietary

50

Page 51: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

l On the Battery menu:l The logging of battery voltages is enabled, (Enable Power Mode Records is checked).l The battery voltage record interval is set to a value higher than 0.l The Low battery threshold (left side) is set to a value greater than the Low battery power threshold

(right side).l The logging of low battery alarms is enabled, (Enable Battery Low Alarm Records is checked).l (optional) The recorder is set to initiate a data transfer on an alarm situation to speed up the process of

alarming (Initiates Data Transfer is checked).l In ColdChainView (for more information, see the ColdChainView User Guide [3]):

l An exception is set up to notify users of a low battery voltage (Battery Low Voltage Alarms is checked;Send Options are set and Receivers are added).

l The exception is linked to the device (can be checked on the Manage Exceptions view).

If all above settings are correctly set up, an alarm message will be sent as soon as the voltage of the recorder is belowthe threshold (set by the low battery threshold) for a specified period (defined by the low battery delay). No visible oraudible alarm will sound on the recorder.

2.14.2 Set up Low Power Mode on Low Battery Voltage DetectionTo set up low power mode on a low battery voltage, the following settings should be checked:

l On the Battery menu:l The logging of battery voltages is enabled, (Enable Power Mode Records is checked).l The battery voltage record interval is set to a value greater than 0.l The Low battery power threshold is set to the desired voltage.

In case alarming on low battery is enabled, this value should be less than the Low battery threshold onthe left side.

l (optional) The delay for enabling low power mode is set (Low battery power delay is set to a valuegreater than 0)

l (optional) A wake-up period is set in which the recorder will temporarily resume normal operation(Wake-up interval and Wake-up time are set to a value greater than 0)

If all above settings are correctly set up, the recorder will go into low power mode as soon as the voltage of therecorder is below the threshold (set by the low battery power threshold) for a specified period (defined by the lowbattery power delay). Optionally, after a certain interval (set by the wake-up interval) the recorder will resume normaloperation temporarily (defined by the wake-up time) after which the device will go back into low power mode, unlessthe voltage is above the threshold (set by the low battery power threshold).

2.15 Door LocksThe Door Locks menu allows you to configure settings for door lock related communication.

These settings are only used in combination with door lock controllers (connected over either COM orCAN communication) that are approved by ORBCOMM Euroscan. Please contact your retailer for moreinformation.

E0004, Version 02 © ORBCOMM Proprietary

51

Page 52: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Figure 23: Door Locks Menu

Doorlock pincode: Allows you to set the pincode used for (un)locking and (dis)arming the doorlock.

Controller Address: Allows you to set the address of the door lock controller.

This setting is only used for specific door lock controller models.

TransSafety Arm/DisarmMode:

Allows you to set the locking and arming behavior when using a Trans-Safety Door LockController.

For specifications on the behavior of each mode, please contact ORBCOMM Euroscansupport.

E0004, Version 02 © ORBCOMM Proprietary

52

Page 53: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

3 INSTALLATION QUALIFICATIONBefore leaving the installation location check all applicable tests below. At the very least, check sections 3.1 and 1.2.

3.1 Recorder

Test Yes No

Is there a minimum of 25W available over the power supply?

This can be checked by printing any ticket.

Is the recorder running with the most recent firmware?

This can be found in recorder menu 3.11 and on the parameter printout.

3.2 Communication

Test Yes No

Does the recorder indicate it is connected to the server?

Long press the status menu button and cycle to COM4. The status should indicate “GPRS: OK, CONNECTED TOSERVER!”

Is the current GPS location of the device available?

Long press the status menu button and cycle to COM4. The status should indicate “GPS: OK, POSITIONS AVAILABLE”.

Is the recorder present in the customer account?

Requires internet access and sufficient privileges.

3.3 Sensors

Test Yes No

Are the connected temperature sensors working as expected?

Short press the status key and verify the temperature values of all the sensors.

Are the digital contacts working as expected?

Operate the digital contact and view the status on the display’s main screen (top right icons).

3.4 Peripherals

Test Yes No

Does the recorder indicate an active fridge connection?

Requires the fridge to be turned on and can be checked in the status menu.

Does the recorder indicate an active doorlock connection?

Requires a functional doorlock and can be checked in the status menu.

Does the recorder indicate an active EBS connection?

Requires a functional EBS controller and can be checked in the status menu.

E0004, Version 02 © ORBCOMM Proprietary

53

Page 54: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

4 OPERATE THE RECORDEREuroscan TX3 / RX3 recorders are developed and produced to conform to the applicable European and Nationalguidelines, for the delivery of chilled and frozen transport goods in transport vehicles (EN12830).

Euroscan TX3 / RX3 recorders can provide evidence of correct temperatures for every trip in the form of a deliveryticket, numerical or graphical print-out. All data is stored with a date / time stamp in a large flash memory. Data willnot be lost if power supply is disconnected. The real-time clock is powered by an internal back-up battery.

Although the Euroscan TX3 / RX3 recorders have been specifically designed and tested for use in a harsh vehicleenvironment, there are certain circumstances beyond ORBCOMM’s control, for example, lightning strikes, high voltagepeaks, theft, manipulation, where data loss could occur. Because the temperature data might be crucial to providingevidence in the case of transport damages, ORBCOMM strongly advises you to take the following precautions:

l Print or download data to a computer on aweekly basis as a backup.l For a long-term storage of the data, ORBCOMM recommends downloading the data via DeviceManager. In

addition to the Bluetooth connection, ORBCOMM offers the communication options for automated datatransfer by use of a GPRS modem. For further information please contact the ORBCOMM sales team or visitwww.euroscansupport.com.

l Check the correct functioning of the recorder frequently (minimum – together with the refrigerator service).l Check the recording system every 12 months to see if the temperature measurement error is within the

maximum permissible error. The annual test is obligatory, according to resp. EN 12830 or EN 13486.l Follow the installation and user instructions in this guide.

l Do not weld without disconnecting the power from the Euroscan TX3 / RX3 recorder or the vehicle.

l Do not take the power supply from a generator system without extra filter protection against high voltagepeaks. Preferably, always take power direct from the vehicle or refrigerator battery.

4.1 Control PanelThe control panel of the Euroscan TX3 / RX3 consists of three main components:

l LCD displayl Keyboardl Printer (optional)

4.1.1 LCD Display

The display has four lines of information, showing the following content in the operating mode.

Line 1: Alarm monitoring activated; temperatures; status of digital inputs.

Line 2: Rotating display of each active temperature with sensor name and temperature value.

Line 3: Day, date and time with indication of summer / winter time.

Line 4: Description of the button functions.

In every other mode, the content of the display is dependent on the user menu.

E0004, Version 02 © ORBCOMM Proprietary

54

Page 55: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

For more information on the user menus, refer to section 4.2.

4.1.2 KeyboardEuroscan RX3 / TX3 is completely menu controlled. Use the four colored buttons to operate the functions (likeprinting, activating alarms or changing parameters). The functions of the buttons are always displayed on the bottomline of the display.

When navigating through the menus, the buttons are as follows:

Button Display Function

Blue Previous item in the menu.

< Edit mode: previous item from the list.

Yellow Next item in the menu.

> Edit mode: next item from the list.

Green edit Menu select, move one menu level down or enter Edit mode.

accept Edit mode: accept input and go to next menu point.

Red <-Menu Move up one menu level.

<-Cncl Edit mode: cancel input and display the non-changed value.

Press and hold for 4 seconds to reject input and go back to the previous menu.

When entering free programmable text, such as names, the button functions are as follows:

Button Display Function

Blue Next character in the list.

Yellow Previous character in the list.

Green < One character to the left.

Red > One character to the right.

+Blue + Yellow <-Cncl Cancel input and display the non-changed value.

Press and hold for 4 seconds to reject the input and go back to theprevious menu.

+Green + Red accept Accept input and go to next menu point.

E0004, Version 02 © ORBCOMM Proprietary

55

Page 56: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

4.1.3 PrinterThe thermal printer is installed on the right side of the recorder. For more information about operating the printerthrough the user menu, refer to chapter 4.2.1 (including subchapters).

Tear paper only when printing has stopped to avoid damage to the printer mechanism.

A printout must be torn downwards over the edge of the bottom plastic part.

For more details about replacing the paper roll, refer to chapter 5.4.

4.1.4 Low Power ModeThe Euroscan TX3 / RX3 recorder can reduce power usage by putting itself into a low power mode. In this mode, allperipheral components and all communication are switched off. The recorder will only do measurement, powermanagement and store measured temperatures. Low power mode can be initiated by inactivity or when the batteryvoltage drops below a set limit for a specified time.

By default, there is no communication with the server or any connected device during low power mode.

During low power mode, the display of the recorder is turned off and the keyboard does not cause any actions to beperformed. The recorder automatically powers up after the power supply is once again over the set threshold.

It is possible to set a wake-up interval and time, which can be used to re-establish communication with the server.During this wake-up time, the recorder transfers all recorded data to the server. If the power supply is still below thethreshold after the wake-up time has passed, the recorder goes back into low power mode. For more informationabout setting low power mode, refer to section 2.14.

4.2 User Menu Euroscan TX3/RX3The recorder has four different user menus, which are accessible via the keyboard without a PIN code:

l Print menul Alarm menul User settings menul Status menu

E0004, Version 02 © ORBCOMM Proprietary

56

Page 57: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

4.2.1 (Menu - 1) Print menu

Press the <blue> button. The last selected print choice will be displayed. Printing will start after 4 seconds. Repeatedlypressing the <blue> button scrolls between the available print options:

l Delivery ticketl Journey ticket graphicall Journey ticket numericall Historical ticket

Hold the <blue> button for more than 4 seconds to reach the following sub-menus:

(M - 1.1) Select compartment to print

Press the <green> button to confirm that you want to change thesettings. Press and to select a compartment, and thenpress to confirm your selection.

E0004, Version 02 © ORBCOMM Proprietary

57

Page 58: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

(M - 1.2) Time zone offset for printing

Use this option to change the time zone of your printout.

(M - 1.3) Print report EVENTS

Press <green / > to start printing the event report.

(M - 1.4) Print report PARAMETER

Press <green / > to print the parameter report after enteringthe pin code.

The pincode for a parameter print is (1-2-1-2)

(M - 1.5) Historical ticket

Press <green / >to select a historical date for printing.Pressing <green / >again lets you select the period of yourhistorical report.

Press <green / >a third time to choose that type of report youwant to have printed. You can change the report type by pressingthe <blue> or <yellow> buttons. Printing starts after 4seconds.

(M - 1.6) Delivery ticket setting

Press to set the desired information printed on the deliveryticket. You can select from the following options:

• Actual only

• Actual + average

• Actual + average + min/max

Press <green / > to confirm your choice.

(M - 1.7) Print time period

This option defines the total print period.

E0004, Version 02 © ORBCOMM Proprietary

58

Page 59: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

(M - 1.8) Day start time

This option defines the time that is used as start time for theprintout (printouts are printed backwards until this time).

(M - 1.9) Day end time

This option defines the time from which the printout is printedbackwards (note that a printout is always printed backwards, that is,from the day end time until start time).

Examples:

- You want to make a printout for a certain date in the past for atime period that exceeds the day start time. Change day start timeto 0:00 h and enter the desired time period.

- You want to make a printout for 2 days. Change the time period to2 days, day start time to 0:00 h - day end time to 0:00 h.

(M – 1.10) Journey marker

Use the journey marker to set the start point of a journey ticket. Todefine a starting point for a dedicated journey, hold the <yellow>button for more than 4 seconds. The display will indicate the statusas shown in the picture on the right.

The printed ticket will never be longer than the print time period asdefined in (M - 1.7) Print time period.

For example: The journey marker is set on 13:00h and the printtime period is set to 2 hours. If a ticket is printed on 14:00h, thestart time will be 13:00h. If a ticket is printed at 15:30h, the starttime will be 13:30h.

4.2.2 (Menu - 2) Alarm settings

Up to four different alarm types can be assigned to four different compartments. The various alarms (andcompartments) are only available if the supervisor has pre-set and configured them in the parameter menu.

Press the <yellow> button to access the alarm menu where you have direct access to compartment 1 and 2.

E0004, Version 02 © ORBCOMM Proprietary

59

Page 60: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

(M - 2.1) Compartment 1

Press the <yellow> button twice to enter the options wherecompartment settings can be changed. Use the <blue / > and<yellow / > buttons to toggle between the compartments thatare available.

The value given in the brackets shows the current setting. Press<green / > to change the alarm group for the selectedcompartment. The alarm group can be selected by pressingand . Press to confirm the selection.

(M - 2.2) Compartment 2 The same as compartment 1

(M - 2.3) Compartment 3 The same as compartment 1

(M - 2.4) Compartment 4 The same as compartment 1

(M - 2.5) Digital input 1

The Euroscan TX3 / RX3 recorders have four digital inputs. Theseinputs can be used for invoking alarms from door switches andrefrigerators. The alarm condition is reached if an input remains inan alarm condition for a certain period of time. This preset (delaytime) can be set up to 60 minutes.

(M - 2.6) Digital input 2 The same as Digital input 1.

(M - 2.7) Digital input 3 The same as Digital input 1.

(M - 2.8) Digital input 4 The same as Digital input 1.

(M - 2.9) Alarm output test

Press <green / > to initiate the external alarm for 10 seconds.This is the A0-output on the back of the recorder. Use this output toconnect a light or buzzer for additional signaling.

4.2.3 (Menu - 3) User settings menuWithin the user settings menu, several adjustments can be made to offer maximum user convenience. Press the<green> button to activate the user setting menu.

Use the <blue / > and <yellow / > buttons to toggle between the available menu options. The actualsetting is displayed between the brackets (..). Enter the edit mode using the <green / > button.

(M - 3.1) Time zone offset

On the third row of the display, the time is shown for the selectedtime zone while editing this setting.

E0004, Version 02 © ORBCOMM Proprietary

60

Page 61: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

(M - 3.4) DST correction

Choose to have the recorder adjust the time according to daylightsaving time in the selected time zone.

(M - 3.5) Select language

Choose the language setting. Changing this changes the languageon both the display and on printed tickets.

(M - 3.6) Set display contrast

Choose the display contrast. If you set this value too low, you mightnot see anything on the display.

(M - 3.7) Set display backlight

Set the intensity of the backlight. This applies to the displaybacklight that switches on when you press any key. The backlightautomatically switches off after 30 seconds if no key has beenpressed.

(M - 3.8) Set buzzer volume

Set the volume of the buzzer. This only applies to the sound whenthe keys are pressed and not to the alarm sounds.

(M - 3.9) Set buzzer frequency

Change the frequency (pitch) of the buzzer. This only applies to thesound when the keys are pressed and not to the alarm sounds.

(M - 3.10) Set buzzer on-time

Change how long the buzzer should sound. This only applies to thesound when the keys are pressed and not to the alarm sounds.

E0004, Version 02 © ORBCOMM Proprietary

61

Page 62: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

(M - 3.11) Firmware version

See the current firmware version of the recorder.

4.2.4 (Menu - 4) Status menu

(M - 4.1) Information view

Press the <red> button while in the main view to change the displaymode between full menu information and only showing actualtemperatures. These values enlarged with readings to one decimalpoint.

To return to the main display press any other button.

(M - 4.2) Compartment view

Press the <red> button three times to change the display mode tothe compartment view. Each subsequent press cycles through theactivated compartments and shows the sensors connected to thecompartment.

If a fridge is connected, this view will also show the compartmentmode, set point and return/supply air temperature for thecompartment (only if available).

Press the <red> button after you reach the last compartment tochange the display back to displaying actual temperatures.

(M - 4.3) Communication protocol view

Long pressing the <red> button from the main view changes thedisplay mode to the communication protocol view. Press the<green> button to cycle through all available communication portsto verify the set protocol.

Press the <red> button while in the communication protocol view tocycle the information on the screen based on the protocol set to theport.

Prress the <yellow button> to return to the main display.

E0004, Version 02 © ORBCOMM Proprietary

62

Page 63: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

5 MAINTENANCE

5.1 InspectionPerform a visual inspection of the recorder. Especially look for cracks of housing, rust, oxidation, cured rubbers, cut orbroken cables.

5.2 Error CodesIf the display shows one of the following values:

OC (l) the input is activated but no sensor is connected

(ll) the sensor has an open circuit (sensor or wire failure)

SC (l) the sensor has a short circuit (sensor or cable failure)

---.- (l) the sensor is N/A (Not Available)

5.3 RMAIf material needs to be returned to Euroscan, follow RMA instructions below to secure proper handling and support.Obtain a Return Material Authorization form by contacting your customer care team.

Ensure you have the following information at hand:

l Product typel Product serial number

Contact details for starting an RMA procedure can be found on the support website, accessible through the followinglink: http://www.euroscansupport.com/rma/. During the RMA process you will be provided an RMA number.

Before returning goods make sure the RMA number is clearly visible on the outside of the package and included inany accompanying documentation. All RMA’s require:

l Ship-to addressl Bill-to addressl Contact namel Phone numberl E-mail addressl Method of return shipmentl Your P.O. Numberl Detailed description of the probleml Any special instructions

If the recorder cannot be repaired, you will receive a letter of explanation, and be given the option to have the recorderreturned to you at your expense or to have ORBCOMM scrap the recorder.

E0004, Version 02 © ORBCOMM Proprietary

63

Page 64: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

5.4 Replace a Paper RollA colored line appears on the last meter of paper indicating that the paper roll needs to be replaced soon. Areplacement paper roll can be ordered through ORBCOMM (part number 007.000.0401 - set of five replacement paperrolls).

ORBCOMM is not responsible for any damages to the printer unit when using paper rolls not obtained fromORBCOMM.

To change a paper roll:

1. Pull down the clear plastic flap. The printer compartment slides forward.

2. Remove the empty roll.

3. Put new paper roll into the printer, and make sure that the paper is fed in the correct way.

E0004, Version 02 © ORBCOMM Proprietary

64

Page 65: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

4. Install the printer with the flap open.

5. Close the flap only after the printer is fully inserted.

6. Test if the paper roll is properly replaced by printing a ticket.

Tear paper only when printing has stopped to avoid damage to the printer mechanism.

A printout must be torn downwards over the edge of the bottom plastic part.

5.5 Euroscan TX3 / RX3 Recorder CalibrationThe Euroscan TX3 / RX3 recorders have an option to adjust the offset of the A/D converter with a correction factor.Because this offset is subject to aging, it is recommended you repeat this procedure on a regular basis (that is, at theannual reference check).

E0004, Version 02 © ORBCOMM Proprietary

65

Page 66: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

The correction factor is a fixed parameter used in the formula, which converts the measured resistance into thecorresponding temperature. This procedure is NOT applicable for calibrating individual sensors. Note that the effecton the measured and displayed temperature is not linear.

Adjusting the correction factor applies to ALL temperature sensors.

Adjusting the correction factor may only be done by Euroscan Certified Installers.

Set the correction factor

1. Connect the temperature calibration block to CON4 of the recorder.2. Enter the parameter menu by pressing the <green> button for 4 seconds. The display will show: "ENTER

PINCODE".3. Enter the factory PIN code.4. Select menu [12 Factory settings] by using the <blue> and <yellow> buttons. Enter the menu by pressing the

<green button>5. Select menu [12.5 Correct. Factor] by using the <blue> and <yellow> buttons. Enter the menu by pressing the

<green button>.6. Wait for the recorder to compare the measured value of the resistor with the expected value of the calibration

block. On the first line, the recorder will display a recommended correction factor based on the measuredvalue. This factor can be set on line two.

7. Use the <blue> and <yellow> buttons to adjust the correction factor. The correction factor is limited from -9 to+9.

8. Press the <green> button to apply the correction factor.

EC-2200-00

5.6 Euroscan TX3 / RX3 Recorder Temperature VerificationThis procedure applies to all Euroscan temperature recorders. The verification procedure determines the accuracy ofthe installed Euroscan recorder, together with the attached sensors. The combined measuring system must betested, at least every 12 months to ensure that it functions within the given tolerances of (±1°C).

The verification procedure described here is a testing procedure and is based on the assumption that theconfiguration parameters of the recorder are set correctly. There are no further setting options on the recorder or thesensors. If the result of the verification is not within the given tolerance, replace the sensor and re-test. If the readingis still outside the (±1°C) tolerance, please contact your customer care team about returning the recorder.

Equipment

l A reference thermometer with a valid calibration certificate, conforming to National and European Standards,and must have an indicated tolerance of (±0.2°C) of the given temperature.

l Cable tie

E0004, Version 02 © ORBCOMM Proprietary

66

Page 67: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

l Verification certificatel A bowl containing crushed ice and demi water (only for freezing point test).

Procedure

The verification procedure should be performed within ±5°C of the operating temperature of the vehicle/trailer. Forchilled transport, the ideal verification temperature is 0°C.

Two different verification methods for temperatures exist: the first one is performed at 0°C (freezing point test) andthe second one at any other temperature.

In both cases, each individual sensor is tested. The results are documented on the verification certificate, togetherwith the serial number of each sensor. To successfully conduct this test, the recorder should be changed to singledisplay for the selected sensor.

To perform ameaningful test, the sensor of the reference thermometer must be connected with the vehicle sensor ina thermo-conductive way. This can be achieved by directly binding them together using a cable tie.

Freezing Point Test

When conducting the freezing point test (0°C), the sensors are individually placed into a mixture of crushed ice anddemi water.

The sensors are immersed at least 10 cm into the crushed ice and demi water mixture, which should be stirred every30 seconds to provide an equal temperature distribution.

When the temperatures have stabilized for at least 5 minutes, the values given by the recorder and the referencethermometer are filled onto the form, together with the serial numbers of the sensors.

Other temperatures

If a temperature verification other than 0°C is necessary, the test should be performed at a temperature of ±5°C of thefuture operation temperature. Therefore, in the case of vehicles transporting frozen products, the test should beundertaken at -20°C. The vehicle compartment should be cooled to the required temperature, and the cable to thereference thermometer, fed underneath the closed doors, with the instrument outside.

When the temperatures have stabilized for at least 5 minutes, the values given by the recorder and the referencethermometer are filled onto the form, together with the serial numbers of the sensors.

Evaluation

If one of the sensors does not pass the test, the sensor should be replaced and the test performed again. If the resultis still negative, the temperature recorder from Euroscan should be returned following the RMA procedure (section5.3).

5.7 Technical SpecificationsFor technical support please contact your customer care team:

Technical specification:

l Operating voltage: 10-32VDC (negative earth), protected against alternator load sheddingl Power consumption: Nominal value 0.6W, max. 25W (while printing)l Temperature in operation: -30°C / +70°C (-22°F / 158°F)l Temperature maximum: -40°C / +85°C (-40°F / 185°F);l Humidity: 97% relative humidity at 25°C (77°F).l Memory size: 8 MB

E0004, Version 02 © ORBCOMM Proprietary

67

Page 68: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

l Inputsl 6 x temperatures for Euroscan sensors: measuring range –50°C to +70°Cl 1 x digital for display background light, active >5 VDCl 4 x digital, closed circuit

l Outputsl 1 x open input, switched to ground and current limited to 1A

l Data portsl 2 x RS-232 connectors for external devicesl 1 x CAN bus connectorl 1 x Internal Bluetooth module

l Accelerometer

Appliance class:

This product is categorized in appliance class III.

Ventilation:

No special requirements. Euroscan recorders are designed for use in an automotive environment.

IP Rating

Euroscan TX3, trailer version for outside mounting, IP65

Euroscan RX3, cabin version for cabin mounting, IP20

Dimensions (W x H x D):

Euroscan TX3: (Including Trailer box) 225 x 185 x 111.77 mm (8.86 x 7.28 x 4.4 inch)

(Excluding Trailer box) 204 x 162 x 89 mm (8.03 x 6.38 x 3.5 inch)

Euroscan RX3: 186 x 58 x 150 mm (7.32 x 2.28 x 5.91 inch)

The dimensions of the RX3 recorder comply with the ISO 7736 regulations and fit a single DIN size.

Maintenance:

Use a cleaning moistened duster, without alcohol or other volatile cleaning products.

E0004, Version 02 © ORBCOMM Proprietary

68

Page 69: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Circuit protection:

For protection, a 10 A floating fuse must be fitted in the positive (+VE) power line as close as possible to the powerconnection (contained in installation kit).

Battery:

The recorder contains a lithium battery with a life expectancy of ten years. Upon disposal of the recorder, dispose ofthe battery according to all applicable national laws and regulations.

5.8 Remove the RecorderWhen the recorder needs to be removed from its casing (for example, when exchanging a recorder during an RMAprocedure) the following steps should be followed:

Do not apply any excessive force to remove a recorder

Euroscan RX3

1. Insert the keys provided into the keyways at each side of the front face of the recorder to release the locks.2. Gently slide the RX3 recorder forward.3. Disconnect the connectors at the back of the RX3 recorder.

Euroscan TX3

1. Loosen the four screws in the corners of the device casing.2. Gently tilt the TX3 recorder forward.3. Disconnect the connectors at the back of the TX3 recorder.4. Remove the TX3 recorder from the casing.

5.9 Factory SettingsTime and Language Settings

DST Correction Auto. Adjustment

Time zone offset UTC+1 hour(s)

Select language English

Temperature Inputs

T1 input On

T1 type Temp. Standard

Logging Avg.

Alarm Avg.

T2 input On

T2 type Temp. Standard

Logging Avg.

E0004, Version 02 © ORBCOMM Proprietary

69

Page 70: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Alarm Avg.

T3 input Off

T4 input Off

T5 input Off

T6 input Off

Digital Inputs

Compartment 1 On

Compartment name Compartment 1

Print T1 Yes

Alarm on T1 On

Print T2 Yes

Alarm on T2 On

Print T3 No

Alarm on T3 Off

Print T4 No

Alarm on T4 Off

Print T5 No

Alarm on T5 Off

Print T6 No

Alarm on T6 Off

Print D1 No

Print D2 No

Print D3 No

Print D4 No

Compartment 2 Off

Compartment 3 Off

Compartment 4 Off

Alarm Settings

Alarm group 1 Off

Alarm group 2 Off

Alarm group 3 Off

Alarm group 4 Off

Alarm repetitions 0 repetitions

Output function Alarm

Printer Settings

Graph upper limit + 15°C

Graph lower limit -30°C

E0004, Version 02 © ORBCOMM Proprietary

70

Page 71: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Graph mm. per hour 6 mm

User menu Yes

Delivery ticket setting Actual only

Print time period 10 hours

00:00

Day start time 00:00

Day end time 18:00

General Settings

Distance unit Km.

Temp. unit °C

Date format dd/mm/yyyy

Sample rate 0 min.

Vehicle ID1 [SERIALNUMBER]X3

Header text Abcdef

Customer ID <blank>

Correct. Factor 0

Menu Default settings

Pin code2 1111

Communication Settings

COM1 function UCP protocol

COM2 function UCP protocol

COM3 function No protocol

COM4 function UCP protocol

APN server m2m.business

APN username <blank>

APN password <blank>

DNS server 1 <blank>

DNS server 2 <blank>

TCP server www.coldchainview.com

TCP port 49701

Roaming Allowed

SMS Tel. 1 <blank>

SMS Tel. 2 <blank>

Log interval Off

Log distance Off

1The VehicleID is by default the Serial number of the unit with the type indicated afterwards. For Example: “11501814X3” (TX3)or “12502587X3” (RX3)2The Pin code is not printed on a parameter printout.

E0004, Version 02 © ORBCOMM Proprietary

71

Page 72: E0004 X3 Installation and Operation Guide - Euroscan Installa… · X3-INSTALLATIONANDOPERATIONGUIDE LEGALNOTICE ThisdocumentationisownedbyORBCOMMandprotectedbyapplicablecopyrightlawsandinternationaltreaty

X3 - INSTALLATION AND OPERATION GUIDE

Stop detection 5 minute(s)

Speed alarm Off

Odometer 000000.00 km

Com5, Infrared port UCP protocol

CAN0 function No protocol

E0004, Version 02 © ORBCOMM Proprietary

72