DELTA2

Microprocessor Controller. System Programming Manual.

DELTA 2 RANGE. MICROPROCESSOR CONTROLLER

SYSTEM PROGRAMMING MANUAL

UNITS WITH PGD DISPLAY

Page 2: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

2

CONTENTS

PGD Display ___________________________________________________________ 3

Description of Menus ____________________________________________________ 4

Manufacturers Section ___________________________________________________ 5

User Section ___________________________________________________________ 12

Maintenance Section ___________________________________________________ 16

Inputs/Outputs Section _________________________________________________ 19

Clock Section __________________________________________________________ 21

Alarms _______________________________________________________________ 15

Document Reference: E 4.19-03-01-02

Page 3: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

3

PGD DISPLAY

Turning the unit On/Off : Pressing the “ ESC” & the “ Enter / Return” arrow buttons together turns on and off the unit at the display. Pressing the up arrow button followed by the “ Enter / Return” arrow button also turns unit on/off. Follow on screen instruction.

Alarm button: By pressing this button you can display the alarm that has occurred & reset it manually. When the red led indicator lights up, at least one alarm condition has occurred. If there are multiple alarms then using the arrow “ up ” & “ down ” buttons lets you scroll through them.

Up arrow button: Displays the program windows and allows the user to set the value of the control parameter

Down arrow button: Displays the program windows and allows the user to set the value of the control parameter. In default menu, pressing down arrow button displays unit operating mode.

Enter / Return arrow button: Confirms the set data. Escape button: By pressing this button, you go back one level from where you are.

Program button: By pressing this button, you get a range of sub-menu’s.

+

Page 4: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

4

PROGRAM BUTTON Pressing the “Prg” button brings up a screen with various sub-menu’s some which are password protected. Sub-menu’s are as follows:

DESCRIPTION OF THE MENUS Menu Level 1 Sub Menu Level Description

Maintenance Run Hours View of component operational hours

Alarm Log View alarm history log

Reset Run Hrs � Reset run hours and adjust run hours maintenance alarm thresholds

Calibration � Adjust calibration of sensors.

Manual Procedure � Manual operation of components. Unit must be Off.

Humidifier � Auto drain setup, change cylinder, disable hum.

Input/Output Values of inputs and outputs, humidifier status, EVD status, controller info

Clock Set date and time and enable time zones

Setpoints Adjust Humidity and Temperature setpoints

User Unit OnOff Control Unit On Off by remote, keyboard and auto restart options

Temperature Control Setpoint limits, control bands, cooling \ heating outputs limits

Humidity Control Setpoint limits, control bands, valve dehum limits, humidifier output limit

EC Fan Speed \ pressure \ airflow setpoints, fan operational limits.

Alarms Temperature and humidity alarms. Adjust serious and non serious alarms

B.M.S (Supervisor) Protocol, address and Baud Rate settings

Force AOUT Force minimum voltage on Y4 and Y2 analog outputs

Password Change service password

Manufacturer Unit Configuration Enable and disable of installed options. Normally set at factory

Humidifier Sensor config. Humidifier size, type, drain options, conductivity options

Parameters On / Off points for installed heating / cooling devices. Erase alarm history

pLAN (Handshake) Local area network (handshake) setup and operation parameters

EVD Driver Electronic expansion valve driver setup menu. See additional prog guide

Timing Adjustment of time delays for components & alarms. PID timing

Initialization Restore default values, change manufacturer passwords

Version Software and BIOS version. Required for querying software with factory

Board Switch Select controller for display to view. View network status

Notes

1. Maintenance sub-menus with � symbol are protected by the service password. 2. Menu user is protected by service password 3. Menu Manufacturer is protected by manufacturer password 4. Some submenus and options may not be available depending on installed and enabled options in

Manufacturer menu. There is also an Alarm list included at the end of this manual.

Page 5: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

5

MANUFACTURER SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons

until you get to MANUFACTURER. This section is password protected and the relevant password is required for access to some screens. To enter the password the “up” and “down” & “enter” arrow keys are used.

The manufacturer’s part of the program is subdivided into 6 distinct sections as outlined below. Each section will be examined separately. Sections are:

UNIT CONFIGURATION.

HUMIDIFIER.

PARAMETERS.

PLAN(HANDSHAKE).

EVD DRIVER. TIMING.

UNIT INITIALISATION. UNIT CONFIGURATION – SUBSECTION.

TABLE NO. 1 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Supervisor Y/N See Note If a Supervisor is connected to the unit Select Temp C/F C/F C Degrees Fahrenheit or Centigrade Regulation Type P / P+I P Can be set as P+I to add an Integration Time

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Heaters No. 0/1/2/B See Note If Unit has heaters & number of stages Compressors No. 0/1/2 See Note If Unit has compressors & number of compressors EN 0-10V Cool Y/N See Note If Unit Has Proportional Cooling \ Cooling Valve

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION EN Head Pressure Control Y/N See Note To enable head pressure control from pCO Regulation Type See Note See Note Can be pCO, VSD or read only. Number Outputs 1/2 See Note Depends on number of condensers

Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION Head Pressure Probes Type 0-10/4-20 See Note Type of probe connected. Can be 0-10V or 4-20mA Min Value 00.0bar 00.0bar Lower range of probe Max Value 00.0bar 30.0bar Upper range of probe

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION Refrigerant Type See Note See Note Type Refrigerant Used

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION En Return Air Probe Y/N Y For units with Return Air Probe Select Type Probe See Note NTC Sensor is always NTC. PT 1000 in special cases

Page 6: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

6

TABLE NO. 1 CONTINUED Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Enable Supply Air Probe Y/N See Note Only for units with this option. NTC or PT 1000 if used

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION Select Probe For Temp Regulation RA\SA RA Select for temperature control on return air or supply air

Screen Ref – 9 TEXT OPTION FACTORY SET DESCRIPTION B7 Configuration See Note See Note Air Pressure \Water Out Temperature \ Airflow Sensor

Screen Ref – 10 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Configuration Enable EC Fan Y/N See Note For units with EC Fan fitted Strategy 1/2/3/4/5 See Note See Note 1 below En De-Hum Speed Y/N See Note Enables a set fan speed for when unit is in De-Hum

Screen Ref – 11 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 3 Volt Step 00.0V See Note Sets the voltage change after each time delay Time Delay 000S See Note Time unit must be outside set pressure before voltage to

fan is stepped

Screen Ref – 12 TEXT OPTION FACTORY SET DESCRIPTION Air Pressure Sensor Type See Note 0-10V Normally 0-10V. Option for 4-20mA. Range Low 000pa 000pa Zero scale for pressure sensor High 0000pa See Note End scale for pressure sensor

Screen Ref – 13 TEXT OPTION FACTORY SET DESCRIPTION Air Flow Measurement K-value of inlet ring 000 See Note K-value of inlet ring. Used for airflow calculation Number of Fans 1/2/3/4 See Note Number of fans in unit. Used for airflow calculation

Screen Ref – 14 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 5 Control Band 00000 See Note Control band for controlling airflow in m3/hr Integral Time 000sec See Note Integral time for controlling airflow Derivative Time 00s See Note Derivative time for controlling airflow.

Screen Ref – 15 TEXT OPTION FACTORY SET DESCRIPTION En Dryer Y/N See Note For units that are to control an external dryer Dryer Type See Note See Note Depends on dryer type – On/Off or Proportional En Dryer Alarm Y/N See Note Enable alarm input for dryer

Screen Ref – 16 TEXT OPTION FACTORY SET DESCRIPTION Enable Water Inlet Probe See Note See Note For CW or units with Freecooling. Probe type is NTC

Notes

1. Strategy 1 - Gives a user selectable 0-10V value to have a fixed speed for the EC Fan. Strategy 2 - Fan speed varies tracking temperature setpoint with user selectable start and stop points. Strategy 3 - Fan speed varies tracking a pressure setpoint with user selectable start and stop points. If pressure read is outside the pressure setpoint plus differential for the set Time Delay the voltage to the fan is increased or decreased by the set Voltage Step. The controller will then check pressure for the set Time Delay and repeat process if necessary. Strategy 4 – Fan speed can be controlled from a BMS within user selectable limits. Strategy 5 – Fan speed varies to maintain a constant airflow.

Page 7: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

7

TABLE NO. 1 CONTINUED Screen Ref – 17 TEXT OPTION FACTORY SET DESCRIPTION En ext.air temp P. Y/N See Note For units with external air temperature sensor Select Type See Note See Note Only for units with this option. NTC or PT 1000 if used

Screen Ref – 18 TEXT OPTION FACTORY SET DESCRIPTION Enable Freecooling Y/N See Note For units with Freecooling. Freecooling With W/A See Note Depends on Freecooling Type. W=Water & A= Ext. Air

Screen Ref – 19 TEXT OPTION FACTORY SET DESCRIPTION Freecooling by AO Y/N See Note For units with Freecooling. Activates Analog Output

Screen Ref – 20 (pCO Small Board Only) ID7 Configuration See Note See Note Sets alarm input ID7 Condensate Pump or Flow Switch

Screen Ref – 21 (pCO Xs Board Only) ID3 Configuration See Note See Note Sets alarm input ID3 Heater Trip or Flow Switch

Screen Ref – 22 (pCO Xs Board Only) ID6 Configuration See Note See Note Sets alarm input ID6 Filter Clog or Condensate Pump

Screen Ref – 23 TEXT OPTION FACTORY SET DESCRIPTION Condensate Pump Alarm Input N/C N/O See Note Depends on Condensate Pump Type & Alarm Output

Screen Ref – 24 TEXT OPTION FACTORY SET DESCRIPTION Configuration of ID7 Flow Alarm See Note See Note See Note 1 Below

Screen Ref – 25 TEXT OPTION FACTORY SET DESCRIPTION Configuration of alarm output NO8 See Note See Note Can be Serious or Common alarm output

Screen Ref – 26 TEXT OPTION FACTORY SET DESCRIPTION Configuration of output NO13 See Note See Note Can be Slave Fan / On/Off Dryer / Damper output

Notes 1. Loss of Water Flow alarm can be configured for Glycol or Dual cooling depending on unit type. If set for

glycol then when controller detects a loss of water flow alarm all water valves are closed and the compressor is stopped to prevent a high pressure alarm. When set for dual cooling the valves are closed but the compressor is left running.

HUMIDIFIER – SUBSECTION. TABLE NO. 2

Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION En Hum Probe Y/N See Note For units with humidity sensor fitted Select Probe Type See Note 0-1 V Always 0-1V. 0-10V & 4-20mA Options in Special Cases

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Humidity Sensor Start 000.0% 010.0% Default settings for reading Humidity Sensor Stop 000.0% 090.0% Default settings for reading Humidity Sensor

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION En Humidifier Y/N See Note For units with humidifier fitted Select type humidifier installed See Note See Note Type of humidifier installed.

Page 8: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

8

TABLE NO. 2 CONTINUED

Screen Ref – 4 (KUE Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Humidifier Type See Note See Note Size and voltage of humidifier installed Custom Humidifier See Note See Note Special code of non-standard humidifier. Special case only

Screen Ref – 5 (KUE Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Drain if steam requests drops Y/N Y Humidifier drains water if steam request drops Enable Drain with voltage Y/N N Allow humidifier to drain with electrodes powered

Screen Ref – 6 (KUE Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Drain bottle after inactivity Y/N Y Drains bottle if humidifier inactive for x days Inactivity days 000 3 Number of days inactive to drain

Screen Ref – 7 (KUE Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Dilution drain time 50-200% 100% Percentage adjustment of drain time threshold Dilution drain frequency 50-200% 100% Percentage adjustment of drain frequency threshold

Screen Ref – 8 (KUE Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Override conductivity 0 to 2000 0 Manual conductivity reading (0 = not enabled)

Screen Ref – 9 (KUE Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Conductivity Alarm Pre-Alarm (warning) 0-2000 1000 Threshold value for conductivity warning alarm Alarm 0-2000 1250 Threshold value for high conductivity alarm. Shuts down

humidifier

Screen Ref – 10 (ST and LT Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Humidifier See Note See Note Humidifier Size. xx kg/hr depending on Unit Voltage See Note See Note Based on Unit Voltage Phases Number 3 3 Always 3 Phase Power Tam Model 100 100 Always a Tam 100 Transformer

Screen Ref – 11 (ST and LT Type Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Enable drain with voltage Y/N N Humidifier cannot drain when live Parameter C0 See Note See Note Set at factory, do not adjust Parameter C1 See Note See Note Set at factory, do not adjust

PARAMETERS – SUBSECTION. TABLE NO. 3

Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Compressors with Freecooling Y/N See Note For units with Freecooling. Can be with or without.

Screen Ref – 2 Rotation of Compressors Y/N Y Compressor Operation is Rotated for Equal Wear Compressors for Dehumidification. 0/1/2 1 Normally only 1 Compressor set for Dehumidification

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION Compressor 1 without Freecooling Set 000.0% 025.0% Defines Operation Point of Compressor 1 Hysterisis 000.0% 025.0% Defines Operation Point of Compressor 1

Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION Compressor 2 without Freecooling Set 000.0% 075.0% Defines Operation Point of Compressor 2 Hysterisis 000.0% 025.0% Defines Operation Point of Compressor 2

Page 9: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

9

Table No. 3 continued

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION Compressor 1 with Freecooling Set 000.0% 050.0% Defines Operation Point of Compressor 1 in Freecooling Hysterisis 000.0% 016.0% Defines Operation Point of Compressor 1 in Freecooling

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION Compressor 2 with Freecooling Set 000.0% 083.3% Defines Operation Point of Compressor 2 in Freecooling Hysterisis 000.0% 016.6% Defines Operation Point of Compressor 2 in Freecooling

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Step Heater 1 Set 000.0% 025.0% Defines Operation Point of Heater 1 Step Heater 1 Hysterisis 000.0% 025.0% Defines Operation Point of Heater 1

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION Step Heater 2 Set 000.0% 050.0% Defines Operation Point of Heater 2 Step Heater 2 Hysterisis 000.0% 025.0% Defines Operation Point of Heater 2

Screen Ref – 9 TEXT OPTION FACTORY SET DESCRIPTION Cool Valve 0-10V Start 0.00% 0.00% If Cooling Valve Installed Stop 100.00% 100.00% If Cooling Valve Installed Dehumidification with CW Valve Y/N See Note Set as Y if Cooling Valve Installed

Screen Ref – 10 TEXT OPTION FACTORY SET DESCRIPTION Prop. Heat 0-10V Start 0.00% 0.00% If Proportional 0-10V Heating Installed Stop 100.00% 100.00% If Proportional 0-10V Heating Installed

Screen Ref – 11 TEXT OPTION FACTORY SET DESCRIPTION ECX Valve 0-10V Start 0.00% 0.00% If Freecooling Valve Installed Stop 100.00% 100.00% If Freecooling Valve Installed Dehumidification with CW Valve Y/N See Note Set as Y if Freecooling Valve Installed

Screen Ref – 12 TEXT OPTION FACTORY SET DESCRIPTION Step Humidification Set 000.0% 050.0% Defines Operation Point of External Humidifier Step Humidification Hysterisis 000.0% 050.0% Defines Operation Point of External Humidifier

Screen Ref – 13 TEXT OPTION FACTORY SET DESCRIPTION Step Dehumidification Set 000.0% 070.0% Defines Operation Point of Dehumidification Step Dehumidification Hysterisis 000.0% 030.0% Defines Operation Point of Dehumidification

Screen Ref – 14 TEXT OPTION FACTORY SET DESCRIPTION Low Temp Limit Stop Dehum Set 000.0% 060.0% Low Temp Point where Dehum is enabled / disabled Hysterisis 000.0% 035.0% Low Temp Point where Dehum is enabled / disabled

Screen Ref – 15 TEXT OPTION FACTORY SET DESCRIPTION Dryer 0-10V Start 0.00% 0.00% If Proportional 0-10V Dryer Control is Installed Stop 100.00% 100.00% If Proportional 0-10V Dryer Control is Installed

Page 10: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

10

Table No. 3 continued Screen Ref – 16 TEXT OPTION FACTORY SET DESCRIPTION Head Pressure Control Condenser 1 Setpoint 00.0bar See Note Head pressure setpoint. Pressure at which fans start Differential 00.0bar See Note Head pressure control band

Screen Ref – 17 TEXT OPTION FACTORY SET DESCRIPTION Fan Speed Control Module 1 Y/N N Humidifier cannot drain when live Low Voltage 00.0V See Note Low output voltage to Fan Speed Control Module 1 High Voltage See Note See Note High output voltage to Fan Speed Control Module 1

Screen Ref – 18 TEXT OPTION FACTORY SET DESCRIPTION Head Pressure Control Condenser 2 Setpoint 00.0bar See Note Head pressure setpoint. Pressure at which fans start Differential 00.0bar See Note Head pressure control band

Screen Ref – 19 TEXT OPTION FACTORY SET DESCRIPTION Fan Speed Control Module 2 Y/N N Humidifier cannot drain when live Low Voltage 00.0V See Note Low output voltage to Fan Speed Control Module 2 High Voltage See Note See Note High output voltage to Fan Speed Control Module 2

Screen Ref – 19 TEXT OPTION FACTORY SET DESCRIPTION Erase Alarm History Y/N N Erases Alarm History

PLAN(HANDSHAKE) – SUBSECTION.

Table No. 4 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION No. of Units in Local Network 000 See Note For Local Network of up to 16 Units

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Local Network Mode See Note See Note Master Control / Rotate by Time or Alarms /

Rotate by Alarm Only

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION Units in Standby 000 See Note Assign No. of Units in Standby (Rotate by Time & Alarm) Reset Sequence Y/N See Note Resets the Rotation Sequence (Rotate by Time & Alarm)

Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION Hours/Minutes Hour/Min See Note Select Hours or Minutes (Rotate by Time & Alarm) Rotation Time 000 See Note Can be set up to 500 (Rotate by Time & Alarm)

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION Units in Standby 000 See Note Assigns No. of Units in Standby (Rotate by Alarm Only) Set standby unit 000 See Note Choice of unit to enter standby (Rotate by Alarm Only)

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION Force Unit in Standby Mode Y/N See Note Makes Standby Units Available Delay Time Low Temperature 000m 003m Time Delay to Start Standby Units Low Temperature Delay Time High Temperature 000m 003m Time Delay to Start Standby Units High Temperature

Page 11: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

11

Table No. 4 continued

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Low Temperature Offset 00.0 C 04.0 C Starts Standby Units 4 C below Setpoint Low Temperature Differential 00.0 C 03.0 C Stops Standby Units 3 C below Setpoint

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION High Temperature Offset 00.0 C 04.0 C Starts Standby Units 4 C above Setpoint High Temperature Differential 00.0 C 03.0 C Stops Standby Units 3 C above Setpoint

TIMING – SUBSECTION.

TABLE NO. 5 Screen Ref -1 TEXT OPTION FACTORY SET DESCRIPTION Time delay switching main fan on. 000 Sec 001 Sec Main fan start up delay time. Time delay switching main fan off. 000 Sec 020 Sec Main fan off delay time. Device 000 Sec 020 Sec Settle Timer - Delays all components on start except fan

Screen Ref -2 TEXT OPTION FACTORY SET DESCRIPTION Delay EC Fan Output 0000 Sec 000 Sec Delays activation of EC Fan output

Screen Ref -3 TEXT OPTION FACTORY SET DESCRIPTION PID Timing Integral Time 0000 Sec 0600 Sec Integration time for P+I \ PID control. Deritive Time 0000 Sec 0000 Sec Deritive time for PID control. Must be set for proper

operation. Delay Loss of Water Flow Alarm 0000 Sec 0010 Sec Loss of Water Flow Alarm Delay

Screen Ref -4 TEXT OPTION FACTORY SET DESCRIPTION Low pressure alarm delay time. 0000 Sec 0180 Sec Low pressure alarm override time Temp/Hum alarm delay time. 0000 Sec 0600 Sec Temperature & Humidity Alarm Time Delays

Screen Ref -4 TEXT OPTION FACTORY SET DESCRIPTION Delay Alarm loss of Air Flow 0000 Sec 0010 Sec Air Flow Alarm time Delay

Screen Ref -5 TEXT OPTION FACTORY SET DESCRIPTION Delay Serious Alarm 0000 Sec 0000 Sec Serious Alarm Time Delay Delay Non-Serious Alarm 0000 Sec 0000 Sec Non Serious Alarm Time Delay

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION Compressor Min Off Time 0000 Sec 0180 Sec Defines Minimum Compressor on Time Compressor Min On Time 0000 Sec 0060 Sec Defines Minimum Compressor off Time

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Winter Start LP Override Delay 0000 Sec 0180 Sec LP Switch time delay for Winter Start

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION Start Delay Same Compressor 0000 Sec 0360 Sec Defines Start Delay of the Same Compressor Compressor Inter Stage Delay 0000 Sec 0010 Sec Defines an Inter Stage Delay for Twin Compressors

Screen Ref – 9 TEXT OPTION FACTORY SET DESCRIPTION Heater Inter Stage Delay 0000 Sec 0003 Sec Heater Inter Stage Delay

Page 12: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

12

UNIT INITIALISATION – SUBSECTION

TABLE NO. 6 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Press Enter Key to insert default values

N/A N/A Pressing the enter key will insert default values

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION New Manufacturers Password 0000 N/A Allows Manufacturers Password to be changed

Notes 1. Great care must be exercised in this section as using this will reload the factory settings but the unit must then be re-configured to reflect the installed options. Default DX unit is a single circuit DX unit with 2 stage heating & Default CW unit is a CW unit with 0-10V valve with 2 stage heating .

USER SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until you

get to USER. This section is password protected and the relevant password is required for access to some screens. To enter the password the “up” and “down” & “ enter” arrow keys are used.

The users’s part of the program is subdivided into 8 distinct sections as outlined below. Each section will be examined separately. Sections are:

UNIT ON/OFF CONTROL

TEMPERATURE CONTROL

HUMIDITY CONTROL

EC FAN

ALARMS BMS(SUPERVISOR) FORCE AOUT

PASSWORD

UNIT ON/OFF CONTROL – SUBSECTION

TABLE NO. 7 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Enable On/Off Keyboard Y/N Y Enables/Disables On/Off at Display Enable On/Off by Remote Y/N Y Enable On/Off by remote digital input

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Auto restart after power failure Y/N Y Enables auto restart of unit after power failure Auto restart after fire alarm Y/N N Enables auto restart after fire alarm

Page 13: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

13

TEMPERATURE CONTROL – SUBSECTION

TABLE NO. 8 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Temperature setpoint limits Minimum. 00.0 C 16.0 C Minimum allowable temperature setpoint value entered. Maximum. 00.0 C 26.0 C Maximum allowable temperature setpoint value entered.

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Temperature - Cooling Band 00.0 C See Note 02.0 C DX Units & 01.7 C CW & Freecooling Units Temperature - Heating Band 00.0 C See Note 02.0 C DX Units & 01.7 C CW & Freecooling Units Temperature - Neutral Zone 00.0 C See Note 00.0 C DX Units & 00.3 C CW & Freecooling Units

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION Cooling Output Limit Min Output 0.00V 00.00V Minimum cooling output voltage (0-10V Cooling Only) Max Output 0.00V 10.00V Maximum cooling output voltage (0-10V Cooling Only)

Screen Ref –4 TEXT OPTION FACTORY SET DESCRIPTION Heating Output Limit Min Output 0.00V 00.00V Minimum heating output voltage (0-10V Heating Only) Max Output 0.00V 10.00V Maximum heating output voltage (0-10V Heating Only)

Screen Ref –5 TEXT OPTION FACTORY SET DESCRIPTION ECXV Output Limit Min Output 0.00V 00.00V Minimum freecooling output voltage Max Output 0.00V 10.00V Maximum freecooling output voltage

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION Diff Air/Water Start Freecooling 00.0 C 5.0 or 14.0 C See notes 2 – 4 at end of this table Diff Air/Water Stop Freecooling 00.0 C 4.5 or 13.5 C See notes 2 – 4 at end of this table

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Diff RA above Setpoint to Start Freecooling

00.0 C 0.5 C Sets the temperature above setpoint that the return air has to be before freecooling can take place

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION Supply Air Temp Limit Enable Y/N See Note If Supply Air Limit Temperature Sensor Fitted Setpoint 00.0 C 15.0 C If Supply Air Limit Temperature Sensor Fitted Offset 00.0 C 05.0 C If Supply Air Limit Temperature Sensor Fitted

Notes 1. Sets how the freecooling valve will operate during dehum. If both high and low limits are set equal then the valve will operate in direct on/off mode, to the set voltage, using the set & hysteresis programmed in Parameters section. If high and low limits are set to different values then the valve will operate proportionally over the humidity band. 2. If Freecooling unit is selected as Freecooling with Compressors (Parameters Screen 1) then Freecooling will be enabled when the water is 5.0 C below the Return Air Temperature and will stop again when water rises to 4.5 C below Return Air Temperature 3. If Freecooling unit is selected as Freecooling without Compressors (Parameters Screen 1) then Freecooling will be enabled when the water is 14.0 C below the Return Air Temperature and will stop again when water rises to 13.5 C below Return Air Temperature 4. Values noted in notes 1 & 2 are user adjustable.

Page 14: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

14

HUMIDITY CONTROL – SUBSECTION TABLE NO. 9

Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Humidity setpoint limits Minimum. 000.0 % 35.0% Minimum allowable humidity setpoint value entered. Maximum. 000.0 % 65.0% Maximum allowable humidity setpoint value entered.

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Humidity Control Band 00.0% 5.0% Control Humidity Band

Humidity Neutral Zone 00.0% 1.0% Control Humidity Neutral Zone

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION Humidifier Output Limit 00.0Kg/hr See Note Depends on size of unit. (ST & LT humidifiers only)

Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION Limit production set 000% See Note Depends on size of unit. (KUE humidifiers only)

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION Dryer Output Limits Min Output 0.00V 00.00V Minimum dryer output voltage (Proportional dryer only) Max Output 0.00V 10.00V Maximum dryer output voltage (Proportional dryer only)

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION Dehumidification Valve Limit CW Valve

Low Limit 0.00V 10.00V See Note 1 below High Limit 0.00V 10.00V See Note 1 below

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Dehumidification Valve Limit ECXV

Low Limit 0.00V 10.00V See Note 1 below

High Limit 0.00V 10.00V See Note 1 below

Notes: 1. Sets how the chill water valve will operate during dehum. If both high and low limits are set equal then the valve will operate in direct on/off mode to the set voltage using the set & hysteresis programmed in Parameters section. If high and low limits are set to different values then the valve will operate proportionally over the humidity band.

EC FAN – SUBSECTION

TABLE NO. 10 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 1 Fixed Fan Speed Voltage 00.0V See Note Sets the fixed speed of the EC Fan

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 2 Operation Range Voltage Min 00.0V See Note Sets minimum speed for EC Fan when tracking temp Max 00.0V See Note Sets maximum speed for EC Fan when tracking temp

Screen Ref –3 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 3 Air Pressure Setpoint 0000pa 50pa Sets the Air Pressure Setpoint Diff 000pa 5pa Sets the Differential for Air Pressure Control

Page 15: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

15

TABLE NO. 10 CONTINUED Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 3 Operation Range Voltage Min 00.0V See Note Sets minimum speed for EC Fan when tracking pressure Max 00.0V See Note Sets maximum speed for EC Fan when tracking pressure

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION EC Fan De-Hum Speed Voltage 00.0V See Note Sets the fixed EC Fan speed for when unit is in De-Hum

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 4 Operation Range Voltage Min 00.0V See Note Sets minimum speed for EC Fan when controlled from BMS Max 00.0V See Note Sets maximum speed for EC Fan when controlled from BMS

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION EC Fan Strategy 5 Operation Range Voltage Min 00.0V See Note Sets minimum speed for EC Fan when controlling airflow Max 00.0V See Note Sets maximum speed for EC Fan when controlling airflow

ALARMS – SUBSECTION

Table No. 11

Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Temperature Alarm - Low Offset 00.0 C 6.0 C Room low temperature alarm offset from setpoint. Temperature Alarm - High Offset 00.0 C 6.0 C Room high temperature alarm offset from setpoint.

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Humidity Alarm - Low Offset 000.0 % 020.0 % Room low humidity alarm offset from setpoint. Humidity Alarm - High Offset 000.0 % 020.0 % Room high humidity alarm offset from setpoint.

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION Temp Alarm Entering Water Low 00.0 C -5.0 C Entering Water Low Temp Alarm Threshold Temp Alarm Entering Water High 00.0 C 45.0 C Entering Water High Temp Alarm Threshold

Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION Temp Alarm Leaving Water Low 00.0 C -5.0 C Leaving Water Low Temp Alarm Threshold Temp Alarm Leaving Water High 00.0 C 45.0 C Leaving Water High Temp Alarm Threshold

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 1-18

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 19-36

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 37-54

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 55-73

Screen Ref – 9 TEXT OPTION FACTORY SET DESCRIPTION Select Alarm Type See Note See Note S=Serious & N=Non-serious. For Alarms : 73-77

Page 16: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

16

B.M.S (SUPERVISOR) – SUBSECTION

Table No. 12 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION BMS Serial Address 000 N/A If connected to a Supervisor (BMS), unit must be

addressed. Protocol Type See Note See Note Carel, Modbus, LON FTT10, BACnet MS/TP, Trend,

SNMP TCP/IP, BACnet TCP/IP

Screen Ref –2 TEXT OPTION FACTORY SET DESCRIPTION Supervisor Comms Speed See Note See Note From 1,200 – 19,200 bps

FORCE AOUT – SUBSECTION

Table No. 13 Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Force Analogue Output Y4 Y/N N To Force Analogue Output Y4 Output Voltage 00.0V 10.0V Can be set from 00.0V to 10.0V

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Force Analogue Output Y2 Y/N N To Force Analogue Output Y2 Prop Heat Output Voltage 00.0V 10.0V Can be set from 00.0V to 10.0V

MAINTENANCE SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until you

get to MAINTENANCE. This section is password protected and the relevant password is required for access to some screens. To enter the password the “up” and “down” & “ enter” arrow keys are used.

The maintenance part of the program is subdivided into 6 distinct sections as outlined below. Each section will be examined separately. Sections are:

RUN HOURS

ALARM LOG

RESET RUN HOURS

SENSOR CALIBRATION

MANUAL PROCEDURE

HUMIDIFIER

Page 17: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

17

RUN HOURS – SUBSECTION TABLE NO. 14

Screen Ref -1 TEXT OPTION FACTORY SET DESCRIPTION Run Hours Fan 0000 N/A Gives Fan Run Hours Run Hours Compressor 1 0000 N/A Gives Compressor 1 Run Hours Run Hours Compressor 2 0000 N/A Gives Compressor 2 Run Hours

Screen Ref -2 TEXT OPTION FACTORY SET DESCRIPTION Run Hours Heater 1 0000 N/A Gives Humidifier Run Hours Run Hours Heater 2 0000 N/A Gives Dehumidification Run Hours

Screen Ref -3 TEXT OPTION FACTORY SET DESCRIPTION Run Hours Humidifier 0000 N/A Gives Heater 1 Run Hours Run Hours Dehumidify 0000 N/A Gives Heater 2 Run Hours

Screen Ref -4 TEXT OPTION FACTORY SET DESCRIPTION Run Hours 0-10V Cooling 0000 N/A Gives 0-10V Cooling Run Hours Run Hours 0-10V Heating 0000 N/A Gives 0-10V Heating Run Hours Run Hours Freecooling 0000 N/A Gives Freecooling Run Hours

ALARM LOG – SUBSECTION

Table No. 15 Screen Ref -1 TEXT OPTION FACTORY SET DESCRIPTION Alarm History N/A N/A Press Alarm Button to view Alarm History

RESET RUN HOURS – SUBSECTION

Table No. 16 Screen Ref -1 TEXT OPTION FACTORY SET DESCRIPTION Fan Hours Alarm Threshold 000 x 000 200 x 1000 Fan Run Hours Alarm Threshold Reset 000000 N/A Reset of Run Hours Fan

Screen Ref -2 TEXT OPTION FACTORY SET DESCRIPTION Comp 1 Hours Alarm Threshold 00 x 000 100 x 1000 Compressor 1 Run Hours Alarm Threshold Reset 000000 N/A Reset of Run Hours Compressor 1

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION Comp 2 Hours Alarm Threshold 00 x 000 100 x 1000 Compressor 2 Run Hours Alarm Threshold Reset 000000 N/A Reset of Run Hours Compressor 1

Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION Heater 1 Hours Reset Y/N N Heater 1 Run Hours Reset Heater 2 Hours Reset Y/N N Heater 2 Run Hours Reset

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION Humidifier Hrs Reset Y/N N Humidifier Run Hours Reset Dehum. Hours Reset Y/N N Dehumidification Run Hours Reset

Screen Ref – 6 TEXT OPTION FACTORY SET DESCRIPTION 0-10V Cool Hours Reset Y/N N 0-10V Cooling Run Hours Reset 0-10V Heat Hours Reset Y/N N 0-10V Heating Run Hours Reset Freecooling Hours Reset Y/N N Freecooling Run Hours Reset

Page 18: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

18

SENSOR CALIBRATION – SUBSECTION

Table No. 17 Screen Ref –1 TEXT OPTION FACTORY SET DESCRIPTION Sensor Calibration Offset Temperature +/-9.9 C 00.0 C Allows Sensor Recalibration. +/- 9.9 C Available Humidity +/-9.9 % 0.0% Allows Sensor Recalibration. +/- 9.9 % Available

Screen Ref – 2 TEXT OPTION FACTORY SET DESCRIPTION Sensor Offset – Supply Air Temp +/-9.9 C 00.0 C Allows Sensor Recalibration. +/- 9.9 C Available Sensor Offset – Enter Water Temp +/-9.9 C 00.0 C Allows Sensor Recalibration. +/- 9.9 C Available

Screen Ref – 3 TEXT OPTION FACTORY SET DESCRIPTION Sensor Offset – External Air Temp +/-9.9 C 00.0 C Allows Sensor Recalibration. +/- 9.9 C Available Sensor Offset – Leaving Water +/-9.9 C 00.0 C Allows Sensor Recalibration. +/- 9.9 C Available

Screen Ref – 4 TEXT OPTION FACTORY SET DESCRIPTION Sensor Offset – Air Pressure +/-9.9 pa 00.0 pa Allows Sensor Recalibration. +/- 9.9 pa Available

Screen Ref – 5 TEXT OPTION FACTORY SET DESCRIPTION Sensor Offset – Airflow +/-1000 C 00.0 C Allows Sensor Recalibration. +/- 1000m3/hr Available

MANUAL PROCEDURE – SUBSECTION

The screens below are only available when the unit is “OFF”.

Table No. 18 Screen Ref –1 TEXT OPTION FACTORY SET DESCRIPTION Man Procedure – Fan (Master) Y/N N Allows Manual Running of Fan ( Master Fan) Man Procedure – Fan (Slave) Y/N N Allows Manual Running of Fan ( Slave Fan ) Screen Ref –2 TEXT OPTION FACTORY SET DESCRIPTION Man Procedure – Heater 1 Y/N N Allows Manual Running of Heater 1 Man Procedure – Heater 2 Y/N N Allows Manual Running of Heater 2 Screen Ref –3 TEXT OPTION FACTORY SET DESCRIPTION Man Procedure – Alarm NS Y/N N Allows proving of Non Serious Alarm Output Man Procedure – Alarm S Y/N N Allows proving of Serious Alarm Output Screen Ref –4 TEXT OPTION FACTORY SET DESCRIPTION Man Procedure – Compressor 1 Y/N N Allows Manual Running of Compressor 1 Man Procedure – Compressor 2 Y/N N Allows Manual Running of Compressor 2 Screen Ref –5 TEXT OPTION FACTORY SET DESCRIPTION Man Procedure – AOUT 1 0.00V 0.00V Allows Manual Setting of Analogue Output 1 Man Procedure – AOUT 2 0.00V 0.00V Allows Manual Setting of Analogue Output 2 Screen Ref - 6 TEXT OPTION FACTORY SET DESCRIPTION Man Procedure – AOUT 3 0.00V 0.00V Allows Manual Setting of Analogue Output 3 Man Procedure – AOUT 4 0.00V 0.00V Allows Manual Setting of Analogue Output 4

Page 19: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

19

HUMIDIFIER – SUBSECTION Table No. 19

Screen Ref – 1 TEXT OPTION FACTORY SET DESCRIPTION Humidifier Auto Drain Enable Y/N N To enable additional automatic humidifier drain Drain Interval 00Hr 05Hr From 00 to 99Hr Drain Length 000Sec 120Sec From 000 to 240Sec Screen Ref –2 (KUE Humidifier Only) TEXT OPTION FACTORY SET DESCRIPTION Cylinder Change Empty Cylinder Y/N N Manually drains the humidifier cylinder Flush new Cylinder Y/N N Performs 15min wash cycle on new cylinder Screen Ref –24 TEXT OPTION FACTORY SET DESCRIPTION Disable Humidifier Y/N N Allows Disabling of Humidifier Manual Drain Y/N N Allows Manual Humidifier Drain of 120 Seconds

INPUTS / OUTPUTS SECTION

The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until you

get to INPUTS / OUTPUTS. This section is not password protected.

TABLE NO. 20 Screen Ref -1 TEXT OPTION FACTORY SET DESCRIPTION Control Air Temperature N/A N/A Active Readout of I/O Control Air Humidity. N/A N/A Active Readout of I/O

Screen Ref -2 TEXT OPTION FACTORY SET DESCRIPTION Analog Input Return Air Temp N/A N/A Active Readout of I/O Analog Input Supply Air Temp N/A N/A Active Readout of I/O Analog Input Entering Inlet Temp N/A N/A Active Readout of I/O

Screen Ref -3 TEXT OPTION FACTORY SET DESCRIPTION Analog Input Leaving Water Temp N/A N/A Active Readout of I/O Analog Input External Air N/A N/A Active Readout of I/O Analog Input Air Pressure

Screen Ref -4 TEXT OPTION FACTORY SET DESCRIPTION Analog Input Airflow N/A N/A Active Readout of I/O

Screen Ref -5 TEXT OPTION FACTORY SET DESCRIPTION Analog Input Circuit 1 Head Pressure N/A N/A Active Readout of I/O Analog Input Circuit 2 Head Pressure N/A N/A Active Readout of I/O

Screen Ref -6 TEXT OPTION FACTORY SET DESCRIPTION Digital Inputs N/A N/A Active Readout of I/O

Screen Ref -7 TEXT OPTION FACTORY SET DESCRIPTION Analog Output – Cool 0-10V N/A N/A Active Readout of I/O Analog Output – Heat 0-10V N/A N/A Active Readout of I/O

Page 20: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

20

TABLE NO. 20 CONTINUED Screen Ref -8 TEXT OPTION FACTORY SET DESCRIPTION Analog Outputs – Condenser 1 N/A N/A Active Readout of I/O Analog Outputs – Condenser 2 N/A N/A Active Readout of I/O

Screen Ref -9 TEXT OPTION FACTORY SET DESCRIPTION Analog Outputs – Freecool Valve N/A N/A Active Readout of I/O Analog Outputs – Dryer 0-10V N/A N/A Active Readout of I/O Screen Ref -7 Text Option Factory Set Description Analog Outputs – EC Fan 0-10V N/A N/A Active Readout of I/O

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION Digital Outputs N/A N/A Active Readout of I/O

Screen Ref – 9 TEXT OPTION FACTORY SET DESCRIPTION Humidifier Contactor N/A N/A On or Off Humidifier Fill Valve N/A N/A On or Off Humidifier Drain Valve N/A N/A On or Off

Screen Ref – 10 TEXT OPTION FACTORY SET DESCRIPTION Humidifier Measured Current N/A N/A Active Readout of Current Humidifier Target Current N/A N/A Active Readout of Current Humidifier Nominal Current N/A N/A Active Readout of Current

Screen Ref – 11 TEXT OPTION FACTORY SET DESCRIPTION Humidifier Water Level N/A N/A Normal, High Humidifier Electrical Conductivity N/A N/A xxxx microsiemens Humidifier Production N/A N/A xx.x Kg/Hr

Screen Ref – 12 Humidifier Cylinder Worn N/A N/A Yes or No Humidifier Cylinder Mode N/A N/A Start, Run, Full, Foam, Low Current & High Current Humidifier Cylinder Status N/A N/A Evaporating, Draining, Filling

Screen Ref – 13 Humidifier Status N/A N/A Status of humidifier Humidifier Activity N/A N/A Current humidifier function

Screen Ref – 14 Humidifier cylinder condition N/A N/A Cylinder OK, Cylinder being worn, Cylinder depleted

Screen Ref – 15 Perm memory write cycles N/A N/A Number of writes to permanent menory Application cycle time N/A N/A Active readout of program cycle time in ms

Page 21: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

21

CLOCK SECTION The screens below appears when the “Prg” button is pressed & using the arrow up & arrow down buttons until you

get to CLOCK. This section is password protected and the relevant password is required for access to some screens. To enter the password the “up” and “down” & “ enter” arrow keys are used.

TABLE NO.21 Screen Ref -1 TEXT OPTION FACTORY SET DESCRIPTION Regulation Clock - Hour See Note See Note Sets Clock Hours & Minutes Regulation Clock - Date See Note See Note Sets Clock Date in format MM/DD/YY Regulation Clock - Day See Note See Note Mo, Tu, We, Th, Fr, Sa, Su

Screen Ref -2 TEXT OPTION FACTORY SET DESCRIPTION Clock Password 0000 0000 Password Required

Screen Ref -3 TEXT OPTION FACTORY SET DESCRIPTION Auto Temp Set Point Variation Y/N N Enables Automatic Temperature Set Point Variation

Screen Ref -4 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 1 – Start Hour 00.00 00.00 Time Zone No. 1 Temperature Set Point Start Hour Temperature Set Point 00.0 C 00.0 C Time Zone No. 1 Temperature Set Point

Screen Ref -5 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 2 – Start Hour 00.00 00.00 Time Zone No. 2 Temperature Set Point Start Hour Temperature Set Point 00.0 C 00.0 C Time Zone No. 2 Temperature Set Point

Screen Ref -6 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 3 – Start Hour 00.00 00.00 Time Zone No. 3 Temperature Set Point Start Hour Temperature Set Point 00.0 C 00.0 C Time Zone No. 3 Temperature Set Point

Screen Ref – 7 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 4 – Start Hour 00.00 00.00 Time Zone No. 4 Temperature Set Point Start Hour Temperature Set Point 00.0 C 00.0 C Time Zone No. 4 Temperature Set Point

Screen Ref – 8 TEXT OPTION FACTORY SET DESCRIPTION Auto Humidity Set Point Variation Y/N N Enables Automatic Humidity Set Point Variation

Screen Ref – 9 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 1 – Start Hour 00.00 00.00 Time Zone No. 1 Humidity Set Point Start Hour Humidity Set Point 00.0 % 00.0 % Time Zone No. 1 Humidity Set Point

Screen Ref – 10 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 2 – Start Hour 00.00 00.00 Time Zone No. 2 Humidity Set Point Start Hour Humidity Set Point 00.0 % 00.0 % Time Zone No. 2 Humidity Set Point

Screen Ref – 11 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 3 – Start Hour 00.00 00.00 Time Zone No. 3 Humidity Set Point Start Hour Humidity Set Point 00.0 % 00.0 % Time Zone No. 3 Humidity Set Point

Screen Ref – 12 TEXT OPTION FACTORY SET DESCRIPTION Time Zone N. 4 – Start Hour 00.00 00.00 Time Zone No. 4 Humidity Set Point Start Hour Humidity Set Point 00.0 % 00.0 % Time Zone No. 4 Humidity Set Point

Page 22: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

22

ALARMS SECTION Notes : 1. Please note that the ALARMS generated will depend on the unit type & configuration. 2. All alarms can be set as Serious or Non-Serious in the user section of the controller. All serious alarms will shut down the unit 3. A05 & A09 are deemed Serious alarms by default. A05 can be changed by the user. 4. A06 is deemed non serious by default to keep a slave module of a duplex unit running in the event of a master air flow alarm. This is only when A05 is set as a non serious alarm. 5. A35 & A08 will always disable the Humidifier whether set as Serious or Non-Serious. 6. A36, if set in unit configuration as glycol will stop compressors and close all water valves. If set as dual cooling will close water valves and leave compressors running. 7. A39 indicates a fault detected in the controllers permanent memory during start up. Should this alarm occur please refer to factory for further support. 7. There may also be some additional alarms which are order specific.

ALARM LIST AL 01 Compressor 1 HP / Thermal Overload AL 02 Compressor 2 HP / Thermal Overload AL 03 Compressor 1 LP AL 04 Compressor 2 LP AL 05 Air Flow Alarm (Serious Alarm) AL 06 Air Flow Alarm – Slave AL 07 Alarm Electric Reheat High Temp Trip AL 08 Condensate Pump / High Water Level AL 09 Smoke/Fire (Serious Alarm) AL 10 Alarm Air Filter AL 11 High Temperature Alarm AL 12 Low Temperature Alarm AL 13 High Humidity Alarm AL 14 Low Humidity Alarm AL 15 High Entering Water Temperature AL 16 Low Entering Water Temperature AL 17 Compressor 1 Run Hours AL 18 Compressor 2 Run Hours AL 19 Fan Run Hours AL 20 Return Air Temperature Probe Fault Or Offline AL 21 Entering Water Temperature Probe Fault Or Offline AL 22 External Air Temperature Probe Fault Or Offline AL 23 Supply Air Temperature Probe Fault Or Offline AL 24 Return Air Humidity Probe Fault Or Offline AL 25 Leaving Water Temperature Probe Fault Or Offline AL 26 High Leaving Water Temperature AL 27 Low Leaving Water Temperature AL 28 High Current Into Humidifier AL 29 Lack Of Water Into Humidifier AL 30 Lack Of Current Into Humidifier AL 31 Alarm Clock AL 32 Spare / Custom AL 33 Spare / Custom AL 34 Spare / Custom AL 35 Water Under Floor AL 36 Loss of Water Flow Alarm AL 37 Air Pressure Probe Fault or Offline AL 38 Dryer Alarm AL 39 Permanent Memory Read/Write Error (Contact Factory)

Page 23: E4.19-03-01-02 Controls Programing Guide PGD Controls/Controls...Manual Procedure Manual operation of components. Unit must be Off. Humidifier Auto drain setup, change cylinder, disable

DELTA2 Microprocessor Controller. System Programming Manual.

23

Notes: