Page 1: EA900 - Emergency lighting, UPS, Lighting, Measurement

EA900II series220/230/240V

Supplying critical and clean power without interruption, the EA900II series offers high performance Uninterruptible Power Supplies (UPS) for servers, networking, and other high availability equipment.

EA900

Page 2: EA900 - Emergency lighting, UPS, Lighting, Measurement

EA900II series220/230/240V

Table of contents

5 Introduction

8 Outdoor series

10 Batteries

11 Reliability

12 Control

14 Technical data sheet EA900II

16 Technical data sheet EA900IIR

18 Technical data sheet EA900IIRT

20 Technical data sheet EA900 Outdoor

21 Notes

Page 3: EA900 - Emergency lighting, UPS, Lighting, Measurement

Introduction

The need to have a reliable power source 24x7 is more important than ever in today’s business environment. Supplying critical and clean power without interruption, the EA900II series offers high performance Uninterruptible Power Supplies for servers, networking, and other high availability equipment.

The systems in the EA900II series are equipped with advanced features such as true online double conversion topology and optional control through the network. This makes the EA900II the solution to handling both today’s demands and those of the future.

True Online Double Conversion

The EA900II applies true online double conversion technology, providing you with clean and high quality power. The zero transfer time ensures that power is supplied without interruption, thereby fully protecting mission-critical devices.

Output Power Factor

The EA900II series have the upgraded power factor of 0.9. This allows users to increase the usable power of your UPS without increasing the system’s footprint. The upgrade eliminates the costs for UPS expansions, valuable space and allows users to use the UPS to its full capacities.

Wide Input Voltage Range

The EA900II provides stable power to connected devices in unstable power conditions. It is capable of handling a wide input voltage range.

Pure Sine-wave

The pure sine-wave output of the EA900II series guarantees compatibility with all kinds of loads, providing perfect power protection for versatile applications such as networking, telecoms and other mission critical usage.

Optional Emergency Power Off (EPO) Function

The EA900II can be optional equipped with an Emergency Power Off function, providing users with a way of immediately shutting down all output power from the UPS in the case of emergencies such as fire, flood, and overheating equipment.

Time

150

100

50

0

-50

-100

-1500 100 200 300 400 500

Vol

ts

Input socket on the backside of the EA900II rackmount

5EA900II SERIES / www.eastpwr.com

“Gartner, Inc. estimates that two out of five enterprises that experience a disaster will go out of business within five years of the event”

4 EA900II SERIES / www.eastpwr.com

Page 4: EA900 - Emergency lighting, UPS, Lighting, Measurement

User-friendly LCD Display

The user friendly LCD display, situated at the front of the EA900II, provides you with instantaneous information about values such as input and output voltage, input and output frequency, load in percentage terms, and available battery capacity.

Self-diagnosis at UPS Start Up

The UPS will perform advanced self-diagnostics to ensure the functionality of the UPS system and batteries, and to anticipate events before they occur.

Cold Start

In the absence of any AC input, the cold start function allows users to start the UPS with the batteries, and without any damage to them or the circuits. This means that users can easily configure the UPS, even if no AC input is available.

Digital Control Technology (DCT)

The EA900II series is equipped with a 32 bit data bus microprocessor, which is capable of quickly and accurately detecting and controlling all changes to the UPS through the use of innovative software.

Advance PFC Technology

The power factor correction technology within the EA900II series uses a filter to significantly reduce harmonics. This means that the system’s efficiency loss is significantly lower, which translates into better performance and reliability and reduced operating costs. This advanced design can also be used in a redundant mode to share the system’s load

Lightning and Surge Protection

The EA900II series’ UPS systems come with lightning and surge protection as standard, thus protecting the equipment against voltage spikes. Surge protection works by channeling the extra voltage into the outlet’s groundning wire, preventing it from flowing through electronic devices, while also allowing normal voltage to be maintained.

Short Circuit and Overload Protection

A short circuit is an abnormal connection between two nodes of an electrical circuit, and can cause huge damage to the UPS and any equipment attached to it. The EA900II circuit protection device will protect against potential short circuit damage, overheating, fire, or even explosions. The UPS is also equipped with overload protection, meaning that the fuse will automatically be triggered when a load exceeds its value. Both protection devices ensure the safety and reliability of the UPS and any equipment that is attached to it.

Variable Fan Speed

The intelligent variable fan speed ensures that the speed of the fans is adjusted to the amount of load and heat dissipation of the UPS.

EMI RFI Noise Filter

Electromagnetic interference (EMI or radio frequency interface, RFI) is a disturbance which affects an electrical circuit. The EMI RFI Noise Filter will protect your UPS system against any interference which may interrupt the effective performance of the device.

6 7EA900II SERIES / www.eastpwr.com EA900II SERIES / www.eastpwr.com

The fans will provide the necessary cooling of UPS and its components

Overview of the EA900II series buttons and indication lights located on the front of the ups

Front side of the EA900II rackmount

Page 5: EA900 - Emergency lighting, UPS, Lighting, Measurement

The EA900 series are also available in an outdoor solution to fit all locations including the outdoor locations which are still in demand for solid, reliable power solutions.

The EA900 Outdoor is designed to fit all locations and environments and is unique in its own range. It also incorporate many specs with no loss of any of the mandatory specifications that are so important when it comes to supplying backup to your security solutions.

IP55

The cabinets are built and designed for applications where a sealed environment from water and dust is required. Furthermore the system is designed in such a way that it is frost and corrosion resistant providing maximum protection for the UPS and batteries.

Features and Benefits

IP55 Protection Wide Operating Temperature Range

-30 to +50 ˚C Frost and Corrosion Resistant Wide Input Voltage and Frequency Range to

perfectly adopt to poor grid conditions Lightning Protection

Static Transfer Switch

The EA900 Outdoor UPS is equipped with a manual bypass switch enabling field engineers to execute maintenance without interrupting the power supplied to the load and keeping MTTR to a minimum.

Communication Interfaces

The EA900 Outdoor UPS provides users the ability to send alarms by using dry contact during events such as mains failure, low battery voltage, common failure and so on.

Optional SNMP Card

The SNMP card allows users to connect the EA900 Outdoor directly to the ethernet network and the internet. This solution means that you can conveniently monitor and manage the UPS with a standard web browser, while simultaneously being able to shutdown multiple computers and operating systems over the network.

Color

Standard any RAL color is available. On request Camouflage or other special colors can be ordered as an option.

Outdoor Series

8 9EA900II SERIES / www.eastpwr.com EA900II SERIES / www.eastpwr.com

Page 6: EA900 - Emergency lighting, UPS, Lighting, Measurement

Batteries

Charge Voltage (V)

Charge Current (A)

90% 100% Capacity

Advanced Battery Management

The EA900II series is equipped with a sophisticated three step charger for efficiently charging the UPS while prolonging battery life.

Step 1 The charger provides a constant charge current until the battery has reached 80% of its capacity, meaning that the UPS is ready to operate again when a new power failure occurs.

Step 2 The charge voltage is held constant for about 60 minutes, allowing the charge current to gradually decline towards the end of this period. The battery will now have been charged to about 90% of its capacity.

Step 3 The charge voltage drops to a float-charge in order to compensate for self discharge, thereby prolonging the life of the batteries.

Optional Extended Runtime

The EA900II series can be upgraded with extra battery packs, allowing users to increase runtime from several minutes up to several hours.

Hot-swappable Battery Design

The EA900II 6 and 10 kVA battery packs are hot-swappable and user replaceable, meaning that downtime during maintenance or replacement is kept to a minimum.

10 EA900II SERIES / www.eastpwr.com

Sealed Lead Acid batteries used in the the EA900II series

Reliability

Optional Maintenance Bypass Cabinet Available for Models of 2K and Above

The maintenance bypass cabinet makes it possible to carry out extensive maintenance of the UPS and power equipment without interruption to the attached device, reducing costs and ensuring the best possible uptime for your system.

11EA900II SERIES / www.eastpwr.com

Manual Bypass Switch located on the bypass cabinet

Page 7: EA900 - Emergency lighting, UPS, Lighting, Measurement

RS232 + Dry Contact (optional)

The EA900II is equipped with a multifunctional RS232 port. This can be used for dry contact, supplying relay functionality for a low battery, AC fail, and other common failures of custom-wired applications. It can also be connected to a computer or server for the standard shutdown software.

Standard Shutdown Software

The EA900II comes with standard software which can automatically shutdown the server or computer when a power failure occurs. This software allows the UPS to instruct the operating systems to close down a PC when it is running unattended. Users can set the parameters with which to schedule when the computer or server should shutdown, making sure that no significant data is lost and important backups are created. Updates will be automatically sent by email, so that users are always aware of what is happening, even at remote locations.

Control

12 EA900II SERIES / www.eastpwr.com

UPS information provided to the control room for easy management

5 4 3 2 1

9 8 7 6

Communication slot

The multifunctional communication slot is conveniently located at the back of the UPS and can be used to accommodate a variety of accessory cards. The wide range of cards that are available means that the EA900II can be used for various applications and in numerous locations.

SNMP Card

The SNMP card allows users to connect the EA900II directly to the ethernet network and the internet. This solution means that you can conveniently monitor and manage the UPS with a standard web browser, while simultaneously being able to shutdown multiple computers and operating systems over the network.

Environmental Card

The environmental card provides the functionality with which to remotely monitor environmental and UPS conditions using a standard web browser, SNMPview, or third-party network management software. Users can observe the ambient temperature, humidity, or the presence of water in the remote location, along with the status of additional contact devices such as a smoke detector or an open-door/window sensor.

Relay I/O Card

The Relay I/O card can be inserted in the SNMP slot at the back of the UPS, providing dry contact relay outputs for custom-wired applications and delivering support for the built-in shutdown of AS/400 systems. This option provides contact closures for the remote monitoring of alarm conditions in the UPS, delivering signals for On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS.

GPRS Card

The GPRS card can be used with the EA900II and enables the user to have an in depth overview of the status of the UPS and the power at a particular location without any network or internet connection. The status can be viewed using the web interface, an SNMPview or third-party network management software. As long as there is GPRS coverage, you will be able to deploy this card.

USP’s Software license free Monitor 1000 UPS systems in a single view Diversity of Operating Systems supported Integrate with your Building Management

System or Network Management System Real-time email and SMS alarm notification Monitor suroundings in real-time via

environmental sensors

13EA900II SERIES / www.eastpwr.com

The Relay I/O card

Installation of an internal SNMP card into a rackmount EA900II ups

Page 8: EA900 - Emergency lighting, UPS, Lighting, Measurement

Technical data sheet EA900II

14 EA900II SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power N.V.

EAST Power N.V. technical data sheet EA900II [True Online Double Conversion 1 - 10kVA]

Model EA901II EA902II EA903II EA906II EA9010II

VA Ratings 1kVA 2kVA 3kVA 6kVA 10kVA

Real Power Rating 900 Watt 1.800 Watt 2.700 Watt 5.400 Watt 9.000 Watt

INPUT

Rated Voltage 220 VAC or 120 VAC 220 VAC

Rated Frequency 50Hz/60Hz [auto sensing]

Voltage Range

110 ~ 295 ± 5VAC [50% Load]; 140 ~ 295 ± 5VAC [100% Load]

110 ~ 295± 5VAC [50% Load]

50/60/70/80 ~ 150 ± 5VAC [60%/70%/80/100% Load] 140 ~ 295 ± 5VAC [100% Load]

Frequency Range 50Hz: 45 ~ 55Hz ± 0.5%; 60Hz: 55 ~ 65Hz ± 0.5%

Phase Single Phase + N + G

Power Factor > 0.98 > 0.99

Input Current [Linear Load/Full Load] 5.0A or 10.0A 9.0A or 20.0A 14.0A or 30.0A 27.0A 46.0A

THD < 6% < 5%

Bypass Voltage Range 186VAC ~ 252VAC or 90VAC ~ 140VAC 186VAC ~ 252VAC

OUTPUT

Rated Voltage 208/220/230/240 VAC or 100/110/115/120/127 VAC

Power Factor 0.9 [220 VAC] 0.8 [120 VAC]

Voltage Distortion ± 1%

DC Component Voltage < 200mv

Output Current Crest Factor 3 : 1

RATED FREQUENCY

AC Mode Same as Input Frequency

Battery Mode 50Hz/60Hz ± 0.2Hz

Phase Lock Speed < 1Hz/s

Wave Distortion < 3% [100% Linear Load]; < 5% [Non-Linear Load]

TRANSFER TIME

From Mains mode to Battery mode 0ms

From Battery mode to Mains mode 0ms

From Mains mode to Bypass mode < 4ms < 0ms

From Bypass mode to Mains mode < 4ms < 0ms

From Normal mode to ECO mode < 10ms < 10ms

System EfficiencyFull Load > 90% > 92%

ECO Mode > 94%

Inverter Overload Capability150% ~ 150% transfer to bypass mode within 30s

105% ~ 125%: 10mins; 125% ~ 150%: 30sec.

> 150% transfer to bypass within 300ms > 150%: 100ms

15EA900II SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power N.V.

EAST Power N.V. technical data sheet EA900II [True Online Double Conversion 1 - 10kVA]

Model EA901II EA902II EA903II EA906II EA9010II

VA Ratings 1kVA 2kVA 3kVA 6kVA 10kVA

Real Power Rating 900 Watt 1.800 Watt 2.700 Watt 5.400 Watt 9.000 Watt

BATTERY

Battery Type 12V Maintenance Free Sealed Lead-Acid

DC Voltage 24V 48V 72V 192V

Capacity 12V/9Ah 12V/9Ah 12V/9Ah 12V/9Ah

Quantity 2 4 6 16

CHARGER

Output Voltage 27.5 ± 0.4V 55.0 ± 0.6V 82.5 ± 0.9V 220.8 ± 1V

Charger Method 3 Stage Charging

Input Voltage Range 80 ~ 300VAc or 40 ~ 150 VAC 150 ~ 300 VAC

Charger CurrentStandard model: 1A;

Long Backup model: 6A [12A optional]Standard model: 1A;

Long Backup model: 8A

ProtectionOver Temperature; Fan testing

AC L and N polarity; Output Short Circuit

Control Silence Alarm; Cold Start; AC Restart; Auto Restart

Communication RS232, USB, SNMP [optional]

Display LCD & LED

SYSTEM

Operating Environment

Operating Temp.

0 ~ 40 ˚C

Storage Temp.

-25 ~ 55 ˚C

Humidity 20 ~ 90% [non-condensing]

Noise < 50dBA < 55dBA

Dimensions [mm] [H x W x D] 215 x 144 x 357 341 x 191 x 452455 x 262 x 514 [Long Backup model]

735 x 262 x 514 [Standard model]

Packing Dimensions [mm] [H x W x D]

Long Backup 315 x 230 x 445 462 x 320 x 564

540 x 360 x 650

Standard 795 x 360 x 650

Net. Weight / Gross Weight

Long Backup

6.0 / 7.0 12.0 / 13.3 12.5 / 13.8 26.0 / 28.0

Standard 10.1 / 11.1 20.0 / 21.3 24.0 / 25.3 67.0 / 75.0

Page 9: EA900 - Emergency lighting, UPS, Lighting, Measurement

Technical data sheet EA900IIR

16 EA900II SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power N.V.

EAST Power N.V. technical data sheet EA900IIR [True Online Double Conversion 1 - 10kVA]

Model EA901IIR EA902IIR EA903IIR EA906IIR EA9010IIR

VA Ratings 1kVA 2kVA 3kVA 6kVA 10kVA

Real Power Rating 900 Watt 1.800 Watt 2.700 Watt 5.400 Watt 9.000 Watt

INPUT

Rated Voltage 220 VAC

Rated Frequency 50Hz/60Hz [auto sensing]

Voltage Range110 ~ 295 ± 5VAC [50% Load]; 140 ~ 295 ± 5VAC

[100% Load]110 ~ 295 ± 5VAC [50% Load]

Frequency Range 50Hz: 45 ~ 55Hz ± 0.5%; 60Hz: 55 ~ 65Hz ± 0.5%

Phase Single Phase + N + G

Power Factor > 0.98 > 0.99

Input Current [Linear Load/Full Load] 5.0A 9.0A 14.0A 27.0A 46.0A

THD < 6% < 5%

Bypass Voltage Range 186VAC ~ 252VAC

OUTPUT

Rated Voltage 208/220/230/240 VAC

Power Factor 0.9

Voltage Distortion ± 1%

DC Component Voltage < 200mv

Output Current Crest Factor 3 : 1

RATED FREQUENCY

AC Mode Same as Input Frequency

Battery Mode 50Hz/60Hz ± 0.2Hz

Phase Lock Speed < 1Hz/s

Wave Distortion < 3% [100% Linear Load]; < 5% [Non-Linear Load]

TRANSFER TIME

From Mains mode to Battery mode 0ms

From Battery mode to Mains mode 0ms

From Mains mode to Bypass mode < 4ms < 0ms

From Bypass mode to Mains mode < 4ms < 0ms

From Normal mode to ECO mode < 10ms < 10ms

System EfficiencyFull Load > 90% > 92%

ECO Mode > 94% NO ECO

Inverter Overload Capability150% ~ 150% transfer to bypass mode within 30s

105% ~ 125%: 10mins; 125% ~ 150%: 30sec.

> 150% transfer to bypass within 300ms > 150%: 100ms

17EA900II SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power N.V.

EAST Power N.V. technical data sheet EA900IIR [True Online Double Conversion 1 - 10kVA]

Model EA901IIR EA902IIR EA903IIR EA906IIR EA9010IIR

VA Ratings 1kVA 2kVA 3kVA 6kVA 10kVA

Real Power Rating 900 Watt 1.800 Watt 2.700 Watt 5.400 Watt 9.000 Watt

EXTERNAL BATTERY PACK (for standard runtime)

Battery Type 12V Maintenance Free Sealed Lead-Acid

DC Voltage 24V 48V 72V 192V

Capacity 12V/9Ah 12V/9Ah 12V/9Ah 12V/9Ah

Quantity 2 4 6 16

CHARGER

Output Voltage 27.5 ± 0.4V 55.0 ± 0.6V 82.5 ± 0.9V 220.8 ± 1V

Charger Method 3 Stage Charging

Input Voltage Range 80 ~ 300VAc or 40 ~ 150 VAC 150 ~ 300 VAC

Charger CurrentStandard model: 1A;

Long Backup model: 6A [12A optional]

Standard model: 1A; Long Backup model: 1A/3A/5A/8A

[Jumper Settings]

ProtectionOver Temperature; Fan testing

AC L and N polarity; Output Short Circuit

Control Silence Alarm; Cold Start; AC Restart; Auto Restart

Communication RS232, USB, SNMP [optional]

Display LCD & LED

SYSTEM

Operating Environment

Operating Temp.

0 ~ 40 ˚C

Storage Temp.

-25 ~ 55 ˚C

Humidity 20 ~ 90% [non-condensing]

Noise < 50dBA < 55dBA

Dimensions [mm] [H x W x D]

Long Backup 88 x 483 x 442

88 x 483 x 492 132 x 483 x 560 [UPS]

Standard 88 x 483 x 600 131 x 483 x 560 [Battery Pack]

Packing Dimensions [mm] [H x W x D]

Long Backup 165 x 600 x 530

165 x 530 x 700 215 x 535 x 660 [UPS]

Standard 165 x 530 x 810 226 x 546 x 676 [Battery Pack]

Net. Weight / Gross Weight

Long Backup

9.5 / 10.5 12.5 / 13.5 13.5 / 14.5 19.0 / 21.2 20.0 / 22.2

Standard 13.8 / 14.8 21.0 / 22.0 30.5 / 31.5 59.0 / 63.6 60.6 / 64.6

Page 10: EA900 - Emergency lighting, UPS, Lighting, Measurement

EAST Power N.V.Technical data sheet EA900IIRT [Double Conversion 1-3kVA]

Model EA901IIRT EA902IIRT EA903IIRT

VA Ratings 1000VA 2000VA 3000VA

Real Power Rating 800 Watt 1600 Watt 2400 Watt

INPUT

Rated Input Voltage 220VAC or 120VAC

Rated Input Frequency 50Hz/60Hz [auto-sensing]

Input Voltage Range 110~295VAC [50% load]; 140~295VAC [100% load] or 50/60/70/80 ~ 150VAC ± 5VAC [60%/70%/80%/100% load]

Input Frequency Range 45 ~ 55Hz ± 0.5% 50Hz; 55 ~ 65Hz ± 0.5% 60Hz

Phase Single Phase + N + GND

Power Factor > 0.98

Input Current [Linear Full Load] 4.0A or 10A 8.1A or 20A 12.1A or 30A

THD < 6%

Bypass Voltage Range 186 ~ 252VAC or 90 ~ 140VAC

OUTPUT

Rated Voltage 208/220/230/240VAC or 100/110/115/120/127VAC [programmable]

Power Factor 0.8

Voltage Distortion ± 1%

DC Component Voltage <200mv

Output Current Crest Factor 3:1

RATED FREQUENCY

AC Mode same as input frequency

Battery Mode 50/60Hz ± 0.2Hz

Phase Lock Speed < 1Hz/s

Wave Distortion 100% linear load <3%; 100% non-linear load <5%

TRANSFER TIME

From Mains mode to Battery mode 0ms

From Battery mode to Mainse mode 0ms

From Mains mode to Bypass mode < 4ms

From Bypass mode to Mains mode < 4ms

From Normal mode to ECO mode < 10ms

System EfficiencyFull Load > 90%

ECO mode > 94%

Inverter Overload Capability 105 ~ 150% transfer to bypass mode after 30s; >150% transfer to bypass after 300ms

EAST Power N.V.Technical data sheet EA900IIRT [Double Conversion 1-3kVA]

Model EA901IIRT EA902IIRT EA903IIRT

VA Ratings 1000VA 2000VA 3000VA

Real Power Rating 800 Watt 1600 Watt 2400 Watt

BATTERY

Battery Type Maintenance Free Sealed Lead-Acid

DC Voltage 24VDC 48VDC 72VDC

Build-In Batteries 12V/9Ah 12V/9Ah 12V/9Ah

Battery Quantity 2 4 6

CHARGER

Output Voltage 27.5 ± 0.4VDC 55.0 ± 0.6VDC 82.5 ± 0.9VDC

Charger Method Three-Stage Charging

Input Voltage Range 80 ~ 300VAC or 40 ~ 150VAC

Charge Current Standard Model: 1A; Long Backup Model: 6A [optional 12A]

ProtectionOver-temperature protection; Fan testing protection

AC Switched polarity protection; output short circuit protection

Control Silence; cold start; AC restart; Auto restart

Communication RS232/USB Optional: SNMP/Dry Contact

Display LCD/LED

SYSTEM OPERATING ENVIRONMENT

Operating Environment

Operating Temperature 0 ~ 40 ˚C

Storage Temperature -25 ~ 55 ˚C

Relative Humidity 20 ~ 90% [non-condensing]

Altitude 0 ~ 1500m [power derating above 1500m]

Noise < 50db

UPS Dimensions [WxDxH] mm

UPS 483 x 440 x 88 [2U]

Battery Bank 483 x 440 x 88 [2U]

Packing Dimensions [WxDxH] mm

UPS 530 x 600 x 165

Battery Bank 530 x 600 x 165

Net/Gross Weight [Kg]

UPS 13.8/14.8 12.5/13.5 12.5/13.5

Battery Bank N/A 18.0/19.0 24.0/25.0

Technical data sheet EA900IIRT (1-3 kVA)

18 EA900II SERIES / www.eastpwr.com 19EA900II SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power N.V.

Product Specifications are subject to change without further notice, © EAST Power N.V.

Page 11: EA900 - Emergency lighting, UPS, Lighting, Measurement

EAST Power N.V. technical data sheet Outdoor UPS [True Online Double Conversion 1000VA - 3000VA]

Model EA1K-HW EA2K-HW EA3K-HW

VA Rating 1 kVA 2 kVA 3 kVA

Real Power Rating 800 Watt 1.600 Watt 2.400 Watt

INPUT

Phase Single Phase + N + G

Voltage Range 110 ~ 300 VAC

Frequency Range 45 ~ 55Hz or 55 ~ 65Hz

Frequency Tracking Speed 1Hz/s

Input Power Factor > 0.98 [Full Load]

DC INPUT

DC Power Supply Voltage 24 VDC 48 VDC 72 VDC

Float Voltage 27.5 ± 0.4 VDC 55.0 ± 0.6 VDC 82.5 ± 0.9 VDC

Battery Type Maintenance Free Sealed Lead-Acid

Battery Capacity Compatible [12V/65AH ~ 12V/120AH]

OUTPUT

Power Factor 0.8

Rated Voltage 220 VAC

Rated Frequency 50Hz/60Hz

Voltage Precision 220 VAC ± 2%

Frequency Precision 50Hz ± 0.2%

Waveform Pure Sine Wave

Wave Form Distortion < 3% [Linear Load]; < 5% [ Non-Linear Load]

Efficiency > 90%

Current Crest Factor 3 : 1

Overload Capacity > 110%: transfer to bypass after 1 min.; > 150%: transfer to bypass after 200ms

Transfer Time 0ms

GENERAL

Protection Degree IP55

Lightning Protection Class C

Operating Temperature -20 ~ 50˚C

Storage Temperature -25 ~ 60˚C

Relative Humidity 0 ~ 95% [non-condensing]

ProtectionI/P Over/Under Voltage, O/P Over/Under Voltage, Short Circuit, Inverter Overtemperature,

Battery Low Voltage, Surge Protection

Communication RS232/Dry Contact

Alarm Signals AC Supply out of tolerance, Battery Low Voltage,Overtemperature, Lightning Protection Failure

Input Isolation Transformer Yes

Bypass Static and Manual Bypass Switch

Cooling Forced Air [Load Dependend]

Noise < 45dBA

Dimensions [mm] [H x W x D]1 kVA [ incl. 2pcs battery] 2 kVA [ incl. 4pcs battery] 3 kVA [ incl. 6pcs battery]

1000 x 660 x 700 1400 x 660 x 900 1400 x 660 x 900

Technical data sheet EA900 Outdoor

Product Specifications are subject to change without further notice, © EAST Power N.V.

18 EA900II SERIES / www.eastpwr.com

Notes..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

19EA900II SERIES / www.eastpwr.com

Page 12: EA900 - Emergency lighting, UPS, Lighting, Measurement

EAST UPS Middle East Trading FZE

P.O. Box 10559Ras Al KhaimahUnited Arab Emirates

T +971 72 076 609F +971 72 041 010