EARTH FAULT DETECTING

METHODS ON

COMPENSATED

NETWORKS

Page 2: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

SUMMARY

Events during normal network condition

Asymmetry on compensated networks

Usage of Petersen coil controller

Events during single earth-fault condition

Prevention of evolving permanent earth faults

Main types of permanent earth faults

Different methods for detecting earth faults

Residual definite time overcurrent protection

Directional residual delayed overcurrent protection

Transient earth fault protection

New method: admittance earth fault protection

09-Nov-17 2

Page 3: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 3

ASYMMETRY ON

COMPENSATED

NETWORKS

Page 4: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

SOURCES OF ASYMMETRY ON

COMPENSATED NETWORKS

09-Nov-17 4

Asymmetrical arrangement of phase conductors

Iron core structure of power transformers

Isolator’s leakage resistance

Asymmetrical elements connected to the network

Page 5: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

CONSEQUENCES OF

ASYMMETRY

09-Nov-17 5

Increased phase voltages

Increased risk of earth-faults

It can block the tuning of the Petersen coil (because of high U0)

Petersen coil is not tuned

Earth-fault current is increased

Earth-fault is continuous

Risk of dangerous step voltage is high

Protection trip is needed

Page 6: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

SYMMETRIZATION METHODS

09-Nov-17 6

Cyclic transposition of the phase conductors

Needs reconstruction of the network

Mounting on several locations

Long time without power supply

Continuous grounding resistor

Several disadvantages

Added symmetrizing capacitors (provided by Protecta)

Mounting at the substation only

Lower costs

Short time without power supply

Page 7: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 7

USAGE OF

PETERSEN COIL

CONTROLLER

Page 8: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

PRINCIPLE OF COMPENSATION

(PETERSEN COIL)

09-Nov-17 8

Page 9: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

PRINCIPLE OF COMPENSATION

(PETERSEN COIL)

09-Nov-17 9

Page 10: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

ADVANTAGES OF USING PETERSEN

COIL CONTROLLER

09-Nov-17 10

Why is it important to use an automatical controller for the Petersen coil?

To check the level of compensation whenever it is needed

The network always changes: feeders can be connected or disconnected to the busbar any time

Because the capacity of the zero sequence network can change any time, the Petersen coil

must follow the change of the capacity

It always keeps the Petersen coil in a well-tuned position

Page 11: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

RESULT OF THE MEASUREMENT: THE

RESONANT CURVE

09-Nov-17 11

Page 12: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 12

PREVENTION OF

EVOLVING

PERMANENT

EARTH FAULTS

Page 13: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

WHAT CAN INCREASE THE RISK OF

EVOLVING PERMANENT EARTH

FAULTS?

09-Nov-17 13

Use of grounding (shunt) resistor � it increases the fault current, so the fault

becomes stable

The Petersen coil is not well tuned � High under- or overcompensation

Short time for using the Petersen coil alone

Page 14: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

AN EFFECTIVE WAY OF PREVENTION

09-Nov-17 14

Well-tuned Petersen coil

Example 1:

Example 2:

Example 3:

Page 15: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

WHY ”EXACT” COMPENSATION CAN

CAUSE PROBLEMS?

09-Nov-17 15

The U0 is relatively high:

Increased phase voltages

Problems of Petersen tuning procedure

Page 16: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

WHAT CAN BE THE BEST SOLUTION?

(IDEA OF PROTECTA)

09-Nov-17 16

Use of shunt inductance, which is connected parallel to the Petersen coil � in

case of possible earth fault the ”exact” compensation can be approached:

ADAPTIVE COMPENSATION

Page 17: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 17

MAIN TYPES OF

PERMANENT

EARTH FAULTS

Page 18: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

STABLE EARTH FAULTS WITH LOW

FAULT RESISTANCE

09-Nov-17 18

The fault current flows continuously

If the grounding resistance is switched on, the increased fault current is high

enough for overcurrent protections to detect the earth fault

Page 19: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

STABLE EARTH FAULTS WITH HIGH

FAULT RESISTANCE

09-Nov-17 19

The fault current flows continuously

If the grounding resistance is switched on, the increased fault current is NOT

enough for overcurrent protections to detect the earth fault

The primary 3I0 is 18A!

Page 20: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

INTERMITTENT EARTH FAULTS

09-Nov-17 20

The fault current does not flow continuously

The exact fault time is around 5-10msec, then the fault is cleared for many

periods

The time between faults can be 100msec – 500msec

Page 21: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 21

RESIDUAL

DEFINITE TIME

OVERCURRENT

PROTECTION

Page 22: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

EARTH FAULT CURRENT-BOOSTER

METHOD

09-Nov-17 22

The symmetrical component network:

Page 23: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

EARTH FAULT CURRENT-BOOSTER

METHOD

09-Nov-17 23

The zero sequence voltage and currents during the earth fault:

Healthy feeder: Faulty feeder:

Page 24: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

RESIDUAL DEFINITE TIME

OVERCURRENT PROTECTION

09-Nov-17 24

The setting parameters are:

Starting current (Istart)

Definite time delay (Tdelay)

Page 25: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

RESIDUAL DEFINITE TIME

OVERCURRENT PROTECTION

09-Nov-17 25

Advantages

Very simple solution

The list of parameters is short

It does not require U0 voltage

Disadvantages

Maintenance of the resistance is expensive

It cannot detect earth faults with high fault resistance

If the resistance is switched on, then the chance of clearing the earth fault by the Petersen coil

is zero

Dangerous step and touching voltage: the IEC-50522 standard does not allow to keep the

increased fault current for a long time (the fault time can be maximum 100-200ms)

Page 26: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 26

DIRECTIONAL

RESIDUAL DELAYED

OVERCURRENT

PROTECTION

Page 27: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

WATTMETRIC METHOD

09-Nov-17 27

The symmetrical component network:

Page 28: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

WATTMETRIC METHOD

09-Nov-17 28

The zero sequence voltage and currents during the earth fault:

Healthy feeder: Faulty feeder:

Page 29: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

DIRECTIONAL RESIDUAL DELAYED

OVERCURRENT PROTECTION

09-Nov-17 29

The setting parameters are:

Starting current (Istart)

Characteristic angle (RCA)

Operating angle (ROA)

Operating characteristic

Page 30: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 30

Advantages

It does not require any added primary or secondary element

The earth fault current is not increased

Disadvantages

It cannot detect intermittent earth faults

If the resistance of the Petersen coil is low, then the wattmetric component of the fault current is

too low � it is hard to set the characteristic well

It requires U0 voltage (and of course I0 current)

DIRECTIONAL RESIDUAL DELAYED

OVERCURRENT PROTECTION

Page 31: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 31

TRANSIENT EARTH

FAULT PROTECTION

Page 32: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

TRANSIENT METHOD

09-Nov-17 32

The symmetrical component network at the transient:

Page 33: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

TRANSIENT METHOD

09-Nov-17 33

The zero sequence voltage and currents at the faulty moment:

Healthy feeder: Faulty feeder:

Page 34: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

TRANSIENT EARTH FAULT

PROTECTION

09-Nov-17 34

The setting parameters are:

Minimal residual voltage (U0,min) and current (I0,min)

Number of the counted peaks

Reset time after the last detected peak (Treset)

Page 35: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 35

Advantages

It does not require any added primary or secondary element

The earth fault current is not increased

Very simple solution

The list of parameters is short

Disadvantages

It cannot detect the stable earth faults with high fault resistance

It requires U0 voltage (and of course I0 current)

TRANSIENT EARTH FAULT

PROTECTION

Page 36: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 36

NEW METHOD:

ADMITTANCE EARTH

FAULT PROTECTION

Page 37: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

ADMITTANCE CHANGE METHOD

09-Nov-17 37

The symmetrical component network:

Page 38: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 38

The zero sequence voltage and currents

Healthy feeder:

Faulty feeder:

ADMITTANCE CHANGE METHOD

Page 39: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 39

The measured zero sequence admittances (3I0/3U0):

∆Y switched OFF ∆Y switched ON Difference

Healthy feeder YC YC 0

Faulty feeder -(YC+YP) -(YC+YP+∆Y) ∆Y

ADMITTANCE CHANGE METHOD

Page 40: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 40

The application:

ADMITTANCE CHANGE METHOD

Page 41: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 41

The setting parameters are:

Minimal residual voltage (U0,min) and current (I0,min)

Voltage and current transformer ratios

Admittance value of the added coil

Line parameters (for calculating the fault location only)

ADMITTANCE EARTH FAULT

PROTECTION

Page 42: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

09-Nov-17 42

Advantages

It can detect stable faults with high fault resistance

The earth fault current is not increased

It can calculate the exact fault resistance

It can separate the earth faults (all the three types)

It can be used for adaptive compensation (mentioned earlier)

Disadvantages

It cannot detect the intermittent fault: it requires a different method. This different method is built

to the admittance protection

It requires U0 voltage (and of course I0 current)

ADMITTANCE EARTH FAULT

PROTECTION

Page 43: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17

THANK YOU FOR YOUR ATTENTION!