Earth leakage clamp applications Application note Earth leakage clamp applications Causes of leakage currents Since there is no such thing as perfect insulation, if any conductor is raised to a potential above that of earth some current is bound to flow to earth from that conductor. The amount of current that flows is dependant on Voltage on the conductor The capacitive reactance between the conductor and earth Resistance between conductor and earth Currents that flow to earth are called leakage currents and are usually very small values. However the amount of current that is required to cause distress or harm to a human being or animal is also small, these currents must be limited by circuit design to safe values. If this is not possible then an RCD (residual current device) is fitted for personal protection. An earth leakage clamp is generally a lightweight pocket size clamp meter designed to measure a.c. earth leakage currents. They enable earth leakage faults to be detected and located without having to isolate and disconnect circuit wiring. In addition, most of these clamps are capable of performing a.c. current tests like any normal clamp meter. The measurement of earth leakage can be conducted on single or three phase systems. . The following applications show positions of conductors in respect to the jaws of the clamp. Single Phase / Two Wire Circuits This diagram illustrates the method of leakage measurement utilising the live and neutral. The phase and neutral currents should ideally cancel each other out, showing zero leakage.. 3 Phase circuits 3 phase circuit leakage can be conducted using a similar test to the single phase application. For 3 wire circuits, clamp all 3 phases. For 4 wire circuits, include the neutral in the jaws. .

Earth leakage clamp applications

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Earth leakage clamp applications

Earth leakage clamp applications Application note

Earth leakage clamp applications Causes of leakage currents Since there is no such thing as perfect insulation, if any conductor is raised to a potential above that of earth some current is bound to flow to earth from that conductor. The amount of current that flows is dependant on

� Voltage on the conductor

� The capacitive reactance between the conductor and earth

� Resistance between conductor and earth Currents that flow to earth are called leakage currents and are usually very small values. However the amount of current that is required to cause distress or harm to a human

being or animal is also small, these currents must be limited by circuit design to safe values. If this is not possible then an RCD (residual current device) is fitted for personal protection. An earth leakage clamp is generally a lightweight pocket size clamp meter designed to measure a.c. earth leakage currents. They enable earth leakage faults to be detected and located without having to isolate and disconnect circuit wiring. In addition, most of these clamps are capable of performing a.c. current tests like any normal clamp meter. The measurement of earth leakage can be conducted on single or three phase systems. .

The following applications show positions of conductors in respect to the jaws of the clamp.

Single Phase / Two Wire Circuits

This diagram illustrates the method of leakage measurement utilising the live and neutral.

The phase and neutral currents should ideally cancel each other out, showing zero leakage..

3 Phase circuits

3 phase circuit leakage can be conducted using a similar test to the single phase application.

For 3 wire circuits, clamp all 3 phases. For 4 wire circuits, include the neutral in the jaws.

.

Page 2: Earth leakage clamp applications

Earth leakage clamp applications Application note

Earth Conductors

The diagram above illustrates earth leakage measurement by utilising the earth conductor only. The same principle can be used for 3 phase circuits.

It should be mentioned that this method will only measure the leakage current in the earth conductor, not the total leakage on the system.

A.C. Current

As previously mentioned some earth leakage clamps can be used as a standard current clamp meter by simply clamping the phase in the jaws.

UK

Archcliffe Road Dover

CT17 9EN England

T +44 (0) 1304 502101

F +44 (0) 1304 207342

[email protected]

UNITED STATES

4271 Bronze Way

Dallas TX 75237-1019 USA

T 800 723 2861 (USA only)

T +1 214 333 3201

F +1 214 331 7399

[email protected]

OTHER TECHNICAL SALES OFFICES

Valley Forge USA, College Station USA, Sydney

AUSTRALIA, Täby SWEDEN, Ontario CANADA,

Trappes FRANCE, Oberursel GERMANY, Aargau

SWITZERLAND, Kingdom of BAHRAIN, Mumbai

INDIA, Johannesburg SOUTH AFRICA, Chonburi

THAILAND

CERTIFICATION ISO

Registered to ISO 9001:2008 Cert. no. Q 09250

Registered to ISO 14001-2004 Cert. no. EMS 61597

DET300E_AN_en_V02 www.megger.com

Megger is a registered trademark