Earthing and Bonding for Common Bonded AC Electrified RailwaysPeter BrownElectrification & Plant Design Group

28 January 2014

Page 2: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 2

Page 3: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 3

Lineside conductor

Induction

cable capacitance

to earth

VL

VT

Page 4: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 4

Effects of Coupling

Errors in digital/data

circuits

Occupational safety hazard

Secondary safety concerns

Delays

System Unavailable

Equipment damage

Equipment malfunction

Hazardous touch

potential

Noise on voice

circuits

VT

Traction current

Magnetic field

VL

Page 5: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 5

Touch Voltage Limits – EN 50122-1

0

100

200

300

400

500

600

700

800

900

0.01 0.1 1 10 100 1000Time /s

Touc

h Vo

ltage

/V

EN 50122-1 AC Body Voltage RMS EN 50122-1 AC Eff Touch Voltage RMS

Actual voltage across the body

Effective touch voltage with shoes on

60 V continuous

645 V, 200 ms

Page 6: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 6

Mutual Screening Conductor

VL

• Earthed every 1 km using earth electrodes

• MSC reduces induction to cables by ~50 %

• Must be close to S&T cable

• Earth electrodes are a pain

• 19/3.25 (158 mm2) Al

4 Ω

Page 7: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 7

Return Screening Conductor

VL

• RSC – performance similar to MSC ~ 50-60 % reduction

• Installation & maintenance costs lower (no earth electrodes)

• Less risk of spiking cables• More tolerant of bond loss• Conductor must be rated for normal

and fault currents• Typical size: 19/4.22 (266 mm2) Al• Generic safety case pending• If MSC is already installed it can be

left – no need to maintain• AT+RSC ≡BT+MSC

Page 8: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 8

RSC Connections to the Rail

Axle counters / No track circuits

Single-rail track circuits

RSC

AEWTraction

RailSignal Rail

Traction Rail

Signal Rail

Double-rail track circuits

Impedance bonds

Spider plates

Page 9: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 9

Signalling Power Earthing Issues

• Locs – 10 Ω earth farmdifficult to maintain low resistancecompliance with BS 7671 disconnection times

• Circuit protective conductor (CPC)• Class II • LOCs in OCLZ

move outside OCLZbond to traction return

• Common bonding using RSC as CPCdisconnection timestraction return under dewirementreduction in differential voltages

Page 10: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 10

Bond sizes based on fault

• Bonds liable to carry traction fault:

– 6 kA 200 ms fault: 16 mm2 Cu, 25 mm2 Al– 12 kA 200 ms fault: 35 mm2 Cu, 50 mm2 Al

• Al is preferred – ½ capital cost, 1/7 scrap value

• Voltage drop across the bond must not exceed EN 50122-1 limits.

– Only a problem for long conductors

Page 11: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 11

Earth conductor max lengths based on size

Size (mm2) Max Length Cu

(m) Max Length Al

(m) 35 105 - 50 155 95 70 215 130 95 295 180 120 370 225

158 (19/3.25) 490 300 266 (19/4.22) 825 505

Based on 645 V max voltage drop for 12 kA 200 ms fault. Double length for 6 kA, 200 ms fault.

Page 12: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 12

LOCs, Signalling Power & Earthing

VL

Page 13: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 13

Common Bonding on the Railway

PSP

19/3.25 Al158 mm2

RSC

AEW

AEW

RSC400 m

FSP

Loc

Loc

Loc

FSP

Loc

Loc

Loc

FSP

Loc

Loc

Loc

50 mm2 Al or 35 mm2 Cu

RSC 19/4.22 AlFTE

Enhanced Insulation 2-

core

>10 m from FSP

650 V

Page 14: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 14

Classic Railway 6 kA

Two Track 25 kV Classic Lines with Return Conductors 6 kA Fault Level

Location Open RouteReturn Conductor

Ground Potentials (V)

Signalling Location Case

Trough

Earth Electrode

Extraneous Earth

Potential Difference at location case

Potential Difference signalling

equipment to traction voltage

SignallingEquipment

Room

Ue Earth Potential

Rise

Human Touch

Potential to Mast

Potential Difference signalling equipment to remote earth

Earth Potential Rise in Rails and in

Vehicle Body

© Roger White

Page 15: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 15

12 kA Railway: Common BondedTwo Track 25 kV Railway with AEWs & BEWs

12 kA Fault LevelLocation Signalling Equipment Remote BEW

AEW – Aerial Earth WireBEW – Buried Earth Wire

Ground Potentials (V)

Human Touch

Potential to Mast

Signalling Location Case

Trough

Trough Ground Potential

SignallingEquipment

Room

Earth Potential Rise in Rails plus Vehicle

Body

AEW

Potential Difference Signalling

equipment to remote Earth

BEW

AEW

Ue Earth Potential

Rise

© Roger White

Page 16: Earthing and Bonding for Common Bonded AC Electrified Railways IRSE [Compatibility... · for Common Bonded AC Electrified Railways ... System Unavailable Equipment damage ... Rail

18 February, 2014 Earthing and Bonding of Electrified Railways 16

PAN/E&P-E/EE/ESD/0102

• ‘Earthing and Bonding for AC Electrification Schemes applying Common Bonding’

–System approach to E&B to achieve • compliance to EN 50122-1• minimise interference to systems

–Substantial industry consultation–Publication: Feb/March 2014

(subject to approval of derogations)