0User manual
0MV vacuum circuit breaker
0Evolis Merlin Gerin 024 kVEarthing truck
02005
1 Schneider Electric 07897591EN REV.A0
0Earthing truck (cmalt) operation
FunctionThe earthing truck has the function of connecting the busbars in one half-switchboard to earth. Naturally, the earthing operation must be carried out when de-energised so as not to create a short-circuit.
InterlockingIn order to de-energise a half-busbar in complete safety, it is necessary to use a key centre. This centre enables the operator to ensure that all of the circuit breakers are racked out in the half-switchboard to be connected to earth.The operation is carried out in the following manner (in order to earth busbar A, cf. figure 1):b rack out all of the circuit breakers on the half-switchboard, including that of the bus-sectioning cubicle (circuit breakers in cubicles 1 - 2 - 3),b lock these circuit breakers in the “racked out” position and remove the keys which are released (keys D1, D2 and C),b place these three keys in the corresponding key centre and remove the key that is released (STA). This then locks the circuit breaker keys in place,b unlock the earthing truck using the released key, which only enables the truck to be racked in the half-switchboard which has just been de-energised.
cmal
t.tif
DE
3105
0b
Figure 1: single line diagram example
DE
3105
0d
D1
1 2 3 4 5
D2 C
C D2 D1 STASTA STB
D5 D6
C D6 D5 STB
Busbar A
AD type feeder cubicle
Earthing truck cmalt Key centre
AD type incomer cubicle
AD type feeder cubicle
AD type incomer cubicle
CL-GL type bus-sectioning cubicle
Busbar B
2Schneider Electric 07897591EN REV.A0
0Earthing truck (cmalt) operation
Mechanism to disable racking of the earthing base in the energised half-switchboardCubicles in a switchboard equipped with an earthing base include a mechanism to avoid incorrect operation. This fool-proof system is different according to whether the cubicle is part of the half-busbar A or B in the switchboard (cf. figure 1). The earthing truck cannot be racked into a cubicle unless the key latch opposite the fool-proof system is lowered using the right key.The fool-proof system is mounted with one screw on the higher hole in cubicles belonging to the half-switchboard on the left hand side (cf. figure 2, safety no. 1), and with one screw on the lower hole in cubicles belonging to the half-switchboard on the right hand side (cf. figure 2, safety no. 2). Two screws are mounted on the bus-sectioning cubicle to make it impossible to rack in the earthing truck (cf. figure 2, safety no. 3).
Figure 2: locking mechanism, front view
DE
310
50e
Safety device no. 1: Insertion impossible in the right hand half-switchboard
fig.2
cma
lt_e
n.ep
s
Safety device no. 2: Insertion impossible in the left hand half-switchboard
Safety device no. 3: Bus-sectioning cubicle, impossible to insert the earthing truck
x3
STB
STA
CradleEarthing base
STA
STB
Earthing base
STA
STB
Earthing base
Cradle
Cradle
3 Schneider Electric 07897591EN REV.A0
0Earthing truck (cmalt) operation
OperationOnce the truck is unlocked, the sequence of operations is as follows:b insert the earthing truck in one of the cubicles of the de-energised half-switchboard,b rack-in the device with the door open,b manually charge the spring using the handle,b close the contacts of the earthing truck (press on the closing button).
When the earthing base is closed, a padlockable runner enables access to the opening button to be disabled, and thus enables the earthing truck to be locked in the closed position.Moreover, an interlock disables the possibility of racking the earthing truck out when it is closed (as for a circuit breaker). The earthing of busbars can therefore be made secure using padlocks (three padlocks at most).
When the earthing truck is open, this same runner also enables padlocked disabling of access to the closing button. In this position, racking out is possible.
These features should enable an earthing truck to be correctly installed and used on conventional switchboards having only one bus-sectioning cubicle but with an unlimited number of feeder and incomer cubicles.In the case of large switchboards with several bus-sectioning cubicles (i.e. switchboards in which it is not possible to talk in terms of half-switchboards) a specific study is required to adapt the interlocks to the configuration in question.
Electrical characteristicsAn earthing truck exists for each cubicle width.
syno
ptiq
ue.ti
f
ferm
é.ti
f
ouve
rt.ti
f
Closed Open
cmalt phase distance 230mm
cmalt phase distance 250mm
Un kV 24 24insulation voltage U impulse 125 125
power frequency 50 50making capacity kA 25 31.5
k 65 82
0789
7531
EN
© -
Sch
neid
er E
lect
ric -
All
right
s re
serv
ed.
07897591EN - REV. A0 04/2005
The Schneider group service centres are at your service for:engineering and technical assistancecommissioningtrainingpreventive and corrective maintenanceadaptationspare parts.Contact your sales representative who will put you in touch with your nearestSchneider group service centre or call us on 33 (0)4 76 57 60 60(Grenoble, France).
Schneider Electric Industries SASAddress:Department MVF - 38050 Grenoble cedex 9Tel : +33 (0)4 76 57 60 60Fax : +33 (0)1 47 51 80 20