2016 CALIFORNIA GREEN BUILDING STANDARDS CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 11
TITLE 19 CALIFORNIA CODE OF REGULATIONS
PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
2016 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 1
2016 CALIFORNIA BUILDING CODE (CBC)
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 2
(2015 INTERNATIONAL BUILDING CODE (IBC) W/2016 CALIFORNIA AMENDMENTS)
2016 CALIFORNIA ELECTRICAL CODE (CEC)
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 3
(2014 NATIONAL ELECTRICAL CODE (NEC) W/2016 CALIFORNIA AMENDMENTS)
2016 CALIFORNIA MECHANICAL CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 4
(2015 UNIFORM MECHANICAL CODE (UMC) W/2016 CALIFORNIA AMENDMENTS
2016 CALIFORNIA PLUMBING CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 5
(2015 UNIFORM PLUMBING CODE (UPC) W/2016 CALIFORNIA AMENDMENTS)
2016 CALIFORNIA ENERGY EFFICIENCY STANDARDS CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 6
2016 CALIFORNIA FIRE CODE (CFC)
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 9
(2015 INTERNATIONAL FIRE CODE (IFC) W/2016 CALIFORNIA AMENDMENTS)
2016 CALIFORNIA EXISTING BUILDING CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART10
(2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC))
2016 CALIFORNIA REFERENCED STANDARDS CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 12
AMERICANS WITH DISABILITIES ACT (ADA)
TITLE II - ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADAG)
1990 STATE FIRE MARSHAL REGULATIONS AND AMENDMENTS TO-DATE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, CALIFORNIA STATE
ACCESSIBILITY STANDARDS
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 19
1. ALL MATERIAL AND WORKMANSHIP SHALL CONFORM TO THE CURRENT EDITION
OF THE CALIFORNIA BUILDING CODE, CALIFORNIA MECHANICAL CODE,
CALIFORNIA PLUMBING CODE, CALIFORNIA FIRE CODE, CALIFORNIA
ELECTRICAL CODE, CALIFORNIA GREEN BUILDING CODE AND ALL APPLICABLE
LOCAL CODES, ORDINANCES AND STATE AMENDMENTS.
2. THE CONTRACTOR SHALL CHECK ALL THE DRAWINGS IMMEDIATELY UPON
THEIR RECEIPT AND SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS
BEFORE STARTING WORK. IMEG ENGINEERS PROJECT MANAGER SHALL BE
NOTIFIED OF ANY DISCREPANCIES.
3. NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED UNLESS SPECIFICALLY
SHOWN, NOTED OR APPROVED BY IMEG ENGINEERS. NOTCH DETAIL, IF SHOWN,
ARE FOR GENERAL GUIDANCE ONLY, IMEG ENGINEERS SHALL BE CONTACTED
IN WRITING TO APPROVE THE LOCATIONS OF PROPOSED NOTCHES.
4. CONNECTIONS AND IMPLIED CONSTRUCTION ASSEMBLIES THAT ARE NOT
SPECIFICALLY DESCRIBED OR DETAILED SHALL BE CONSTRUCTED USING
STANDARD CONSTRUCTION PRACTICES IN COMPLIANCE WITH THE GOVERNING
CODES AND ORDINANCES.
5. WHEN DETAILS LABELED "TYPICAL" OR "SIMILAR" ARE GIVEN ON THE
DRAWINGS, THE CONTRACTOR SHALL APPLY THE INTENT OF THE DETAIL TO
THAT SPECIFIC CONDITION.
6. WRITTEN INFORMATION AND DIMENSIONS SHALL TAKE PRECEDENCE OVER
GRAPHIC INFORMATION. DO NOT SCALE DRAWINGS.
7. DRAWINGS AND SPECIFICATIONS FOR THIS WORK HAVE BEEN PREPARED IN
ACCORDANCE WITH GENERALLY ACCEPTED STANDARDS OF PRACTICE TO
MEET THE MINIMUM REQUIREMENTS OF THE CURRENT EDITION OF THE CBC.
ANY OMISSIONS OR DISCREPANCIES ON THE PLANS OR ANY DEVIATIONS FROM
THE PLANS WHICH ARE NECESSITATED BY FIELD CONDITIONS OR ANY
CONDITION DIFFERENT FROM THOSE INDICATED ON THE PLANS SHOULD BE
BROUGHT TO THE ATTENTION OF IMEG ENGINEERS PRIOR TO CONTINUING
WITH CONSTRUCTION. ALL WORK IS TO BE COORDINATED SO THAT
COOPERATION BETWEEN ALL TRADES WHERE REQUIRED IS ACCOMPLISHED.
8. CONTRACTOR AND SUBCONTRACTORS ARE RESPONSIBLE FOR THE ORDER
AND MEANS OF CONSTRUCTION AND ALL TEMPORARY BRACING AND ERECTION
DURING CONSTRUCTION.
9. APPROVALS BY THE PROJECT INSPECTOR(S) SHALL NOT CONSTITUTE
AUTHORITY TO DEVIATE FROM THE PLANS AND SPECIFICATIONS.
10. THE PROVISIONS OF CFC AND CBC CHAPTER 33 SHALL BE ENFORCED ON THIS
PROJECT.
11. ALL WORK SHALL CONFORM TO 2016 TITLE 24, CALIFORNIA CODE OF
REGULATIONS (CCR)
12. A PROJECT INSPECTOR EMPLOYED BY THE DISTRICT (OWNER) AND APPROVED
BY THE DIVISION OF THE STATE ARCHITECT SHALL PROVIDE CONTINUOUS
INSPECTION OF THE WORK. THE DUTIES OF THE INSPECTOR ARE DEFINED IN
SECTION 4-342, PART 1, TITLE 24, CCR. CLASS 3.
13. TITLE 24 PARTS 1-5 MUST BE KEPT ON SITE DURING THE CONSTRUCTION.
THE SCOPE OF WORK AS STATED BELOW DOES NOT CONSTITUTE A DETAILED
AND FULL EXPLANATION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
REMOVAL AND REPLACEMENT OF EXISTING EXHAUST FANS WITH NEW EXHAUST
FANS AT LOCKER ROOMS.
ALL OTHER STRUCTURES AND ELEMENTS SHOWN ARE EXISTING, FOR REFERENCE
ONLY.
10931 STAMY RD, WHITTIER, CA 90604
LOCKER ROOMS EXHAUST FAN UPGRADE
EAST WHITTIER CITY SCHOOL DISTRICT
CODE REFERENCES
VICINITY MAP
HILLVIEW MIDDLE SCHOOL
PROJECT TEAM
OWNER
OWNER
EAST WHITTIER CITY SCHOOL DISTRICT
14421 E. WHITTIER BLVD,
WHITTIER, CA 90605
(562) 907-5900
GENERAL NOTES
SCOPE OF WORK
IMEG901 VIA PIEMONTE, SUITE 400ONTARIO, CA 91764tel: (909) 477-9615
MECHANICAL
PROJECT MANAGER: ERIC DESPLINTER, PEMECHANICAL ENGINEER: CHRISTIAN GUYNES, PEELECTRICAL ENGINEER: JUSTIN IGNACIO, EIT
IMEG901 VIA PIEMONTE, SUITE 400ONTARIO, CA 91764tel: (909) 477-9615
ELECTRICAL
IMEG901 VIA PIEMONTE, SUITE 400ONTARIO, CA 91764tel: (909) 477-9615
STRUCTURAL
STRUCTURAL ENGINEER: TERRY TSANG
ER
ET
SIG
ER
RE
ENI
GN
E
LANOISSEORPD
F
I A
N
OF CA L I FOR
STA
TE
D PM
ER
IC
eS LI
ME
HAN I CAL
C
.
NTE
R
Exp. 12/31/19
38688
REFERENCE SCALE IN INCHES
0 1 2
© 2018 IMEG CORP.
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Job Number
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
"LOCKER ROOMS EF UPGRADE"
EAST WHITTIER CITY SCHOOL DISTRICT
2/1
/2018 7
:53:5
9 P
M
10931 STAMY ROAD, WHITTIER, CA 90604
HILLVIEWMIDDLE SCHOOL
T0.0
COVER SHEET
Approver
ED
CG
18001320.00
02/01/18
BID DOCUMENTS
HIL
LV
IEW
M
IDD
LE
SC
HO
OL
18001320.0
0
901 VIA PIEMONTESUITE 400ONTARIO, CA91764
PH: 909.477.6915FAX: 909.477.6916www.imegcorp.com
SHEET INDEX
DWG.NO. DESCRIPTION
T0.0 COVER SHEET
M001 GENERAL NOTES, LEGEND AND DRAWING INDEX
M101 MECHANICAL FIRST FLOOR DEMOLITION PLAN
M201 MECHANICAL FIRST FLOOR REMODEL PLAN
M301 DETAILS/CONTROLS
E001 GENERAL NOTES, SPECIFICATIONS, LEGEND AND DRAWING LIST
E201 FIRST FLOOR POWER PLAN
SECTION 23 00 00 - BASIC MECHANICAL REQUIREMENTS
SECTION 23 05 29 - HANGERS AND SUPPORT FOR HVAC PIPING AND DUCTWORK
SECTION 23 34 23 - POWER VENTILATORS
SECTION 23 37 00 - AIR INLETS AND OUTLETS
2016 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE CALIFORNIA CODE
OF REGULATIONS (CCR) TITLE 24, PART 1
2016 CALIFORNIA BUILDING CODE (CBC) CALIFORNIA CODE OF REGULATIONS (CCR)
TITLE 24, PART 2
(2015 INTERNATIONAL BUILDING CODE (IBC) W/CALIFORNIA AMENDMENTS)
2016 CALIFORNIA ELECTRICAL CODE (CEC) CALIFORNIA CODE OF REGULATIONS
(CCR) TITLE 24, PART 3
(2014 NATIONAL ELECTRICAL CODE (NEC) W/CALIFORNIA AMENDMENTS)
2016 CALIFORNIA MECHANICAL CODE CALIFORNIA CODE OF REGULATIONS (CCR)
TITLE 24, PART 4
(2015 UNIFORM MECHANICAL CODE (UMC) W/CALIFORNIA AMENDMENTS)
2016 CALIFORNIA PLUMBING CODE CALIFORNIA CODE OF REGULATIONS (CCR) TITLE
24, PART 5
(2015 UNIFORM PLUMBING CODE (UPC) W/CALIFORNIA AMENDMENTS)
2016 CALIFORNIA ENERGY EFFICIENCY STANDARDS CODE CALIFORNIA CODE OF
REGULATIONS (CCR) TITLE 24, PART 6
2016 CALIFORNIA FIRE CODE (CFC) CALIFORNIA CODE OF REGULATIONS (CCR) TITLE
24, PART 9
(2015 INTERNATIONAL FIRE CODE (IFC) W/CALIFORNIA AMENDMENTS)
2016 CALIFORNIA REFERENCED STANDARDS CODE CALIFORNIA CODE OF
REGULATIONS (CCR) TITLE 24, PART 12
AMERICANS WITH DISABILITIES ACT (ADA) TITLE II - ACCESSIBILITY GUIDELINES FOR
BUILDINGS AND FACILITIES (ADAG)
1990 STATE FIRE MARSHAL REGULATIONS AND AMENDMENTS TO-DATE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, CALIFORNIA STATE
ACCESSIBILITY STANDARDS
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 19
STANDARDS:
NFPA 13 AUTOMATIC SPRINKLER SYSTEM (2016)
NFPA 14 STANDPIPE SYSTEMS (2016)
NFPA 17 DRY CHEMICAL EXTINGUISHING SYSTEMS (2016)
NFPA 17a WET CHEMICAL SYSTEMS (2016)
NFPA 20 STATIONARY PUMPS (2016)
NFPA 22 WATER TANKS FOR PRIVATE FIRE PROTECTION (2016)
NFPA 24 PRIVATE FIRE MAINS (2016)
NFPA 72 NATIONAL FIRE CODE (2016)
NFPA 80 FIRE DOORS AND OTHER OPENING PROTECTIVES (2016)
NFPA 92 STANDARD FOR SMOKE CONTROL SYSTEMS (2015)
REFERS TO "SMACNA" HVAC DUCT CONSTRUCTION STANDARDS
EXHAUST AIR
DOWN THRU ROOF
SUPPLY AIR
DTR
EA
SA
E OR EXH.
S OR SUPP.
XXX
TYP TYPICAL
UNLESS NOTED OTHERWISE
UP THRU ROOF
EQUIPMENT NUMBER
UTR
U.N.O.
CUBIC FEET OF AIR PER MINUTE
SUPPLY
EXHAUST
CFM
GI GALVANIZED IRON
STATIC PRESSURES.P.
ABOVE FINISHED FLOOR
GALVANIZED
AFF
GALV.
EXISTING DUCT OR EQUIPMENT TO BE REMOVED
EXIST. EXISTING(E)
MANUFACTURER& MODEL NO.
AIR
CFMQUANTITY IN
W.C.
S.P.
SERVEDFINISH
AREALOCATION REMARKS
MILL FINISH1900WALL
0.01ON
4.63
SIZE
W x H
(IN.)
FREEAREAVEL.
(FPM)
COMPLETE WITH BIRDSCREEN, AND GRAVITY SHUTTERS.
MILL FINISHWALL
ONCOMPLETE WITH BIRDSCREEN, AND GRAVITY SHUTTERS.
INTAKE LOUVER SCHEDULE
1900 0.01 4.6354x30
54x30
BOY'S LOCKERS
GIRL'S LOCKERSRUSKIN
L375D
RUSKIN
L375D
SYMBOL ABBREV. DESCRIPTION
1. ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY.
BEFORE PROCEEDING WITH THE WORK CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, SIZES,
REQUIRED CLEARANCES AND ASSUME FULL RESPONSIBILITY FOR THE FITTING OF ALL EQUIPMENT
AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK AND TO THE WORK OF OTHER
TRADES.
2. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL SPECIAL FITTINGS
AND LOCATIONS ARE NOT EXACTLY LOCATED.
3. THIS CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING OUT HIS WORK
AND EQUIPMENT. HE SHALL COORDINATE THE WORK OF THIS SECTION WITH THE WORK OF OTHER
TRADES AND ALL JOB CONDITIONS.
4. ALL LINE VOLTAGE WIRING, EQUIPMENT AND LINE VOLTAGE CONDUIT SHOWN DASHED SHALL BE BY
THE ELECTRICAL CONTRACTOR. LOW VOLTAGE WIRING AND LOW VOLTAGE CONDUIT SHALL BE BY
THE HVAC CONTRACTOR. VERIFY ELECTRICAL CHARACTERISTICS PRIOR TO BID AND MATERIAL
PURCHASE.
5. WHERE ANCHORAGE DETAILS ARE NOT SHOWN ON THE DRAWINGS, THE FIELD INSTALLATION
SHALL BE SUBJECT TO THE APPROVAL OF THE MECHANICAL AND STRUCTURAL ENGINEER.
6. INSTALL ALL FRESH AIR INTAKES OF MECHANICAL EQUIPMENT AS TO BE 10'-0" FROM ANY AND ALL
SANITARY VENTS OR EXHAUST FAN DISCHARGE. WHEN NECESSARY, EXTEND VENTS OR PROVIDE
ADDITIONAL FRESH AIR INTAKE DUCTWORK AS DIRECTED BY THE ENGINEER.
7. THE SIZES, WEIGHTS AND CAPACITIES OF ALL EQUIPMENT SCHEDULED ON THE PLAN HAVE BEEN
CAREFULLY COMPUTED. SHOULD EQUAL ITEMS BY DIFFERENT MANUFACTURERS (SEE
SPECIFICATIONS) BE SUBMITTED FOR APPROVAL, ALL SUCH SUBMITTALS SHALL INCLUDE 1/4"
SCALE SHOP DRAWINGS SHOWING METHOD OF INSTALLATION.
8. REQUIRED ROUTINE MAINTENANCE ACTION SHALL BE CLEARLY STATED AND INCORPORATED ON A
READILY ACCESSIBLE LABEL, WHICH MAY BE LIMITED TO IDENTIFYING BY TITLE AND/OR
PUBLICATION NUMBER THE OPERATION AND MAINTENANCE MANUAL FOR THAT PARTICULAR MODEL
AND TYPE OF PRODUCT. ONE COPY OF THIS INFORMATION SHALL BE FURNISHED BY THE
CONTRACTOR TO THE OWNER.
9. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES AT THE SITE. ANY COSTS TO
INSTALL WORK TO ACCOMPLISH SAID COORDINATION WHICH DIFFERS FROM THE WORK AS SHOWN
ON THE PLANS SHALL BE INCURRED BY THE CONTRACTOR. ANY DISCREPANCIES, AMBIGUITIES OR
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT DURING BID TIME FOR
CLARIFICATION. ANY SUCH CONFLICTS NOT CLARIFIED PRIOR TO BID SHALL BE SUBJECT TO THE
INTERPRETATION OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER.
10. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DO ALL CORING, SAW CUTTING, PATCHING
AND REFINISHING OF EXISTING WALLS AND SURFACES WHEREVER IT IS NECESSARY FOR HIM TO
PENETRATE FOR HIS WORK. ALL OPENINGS SHALL BE SEALED TO MEET THE FIRE RATING OF THE
PARTICULAR WALL, FLOOR OR CEILING PENETRATED.
11. BEFORE BIDDING THE PROJECT THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY THE
CLEARANCES AVAILABLE TO BRING THE SPECIFIED EQUIPMENT AND MATERIAL TO THE SITE.
1. SUBMITTALS: SUBMIT FOR REVIEW 1 ELECTRONIC COPY OF SHOP DRAWINGS,
BROCHURES (CATALOG DATA), AND LISTS OF PROPOSED MATERIALS GIVING
MANUFACTURERS' NAMES, CATALOG NUMBER, TRADE NAMES, CUTS AND DETAILED
DESCRIPTION. WHEN MORE THAN ONE ITEM OF ITS KIND APPEARS ON SUBMITTAL
DATA, CAREFULLY DESIGNATE PARTICULAR ARTICLE SELECTED BY TYPE AND SIZE.
SUBMITTED DATA SHEETS SHALL CONTAIN ALL INFORMATION AND PRODUCT
CHARACTERISTICS SCHEDULED AND SPECIFIED.
2. THE CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE ON ALL MATERIALS,
EQUIPMENT AND WORKMANSHIP, FOR A PERIOD OF 1 YEAR FROM DATE OF
ACCEPTANCE OF THE WORK BY THE OWNER.
3. SCALE AND FIGURED DIMENSIONS ARE APPROXIMATE AND ARE FOR ESTIMATING
PURPOSE ONLY. BEFORE PROCEEDING WITH THE WORK, THE CONTRACTOR SHALL
ASSUME ALL RESPONSIBILITY FOR THE FITTINGS OF HIS MATERIAL AND EQUIPMENT TO
OTHER PARTS OF THE EQUIPMENT AND STRUCTURE.
4. WHERE APPARATUS AND EQUIPMENT HAVE BEEN INDICATED ON DRAWINGS, THE
DIMENSIONS HAVE BEEN TAKEN FROM THE SPECIFIED MANUFACTURER. THE
CONTRACTOR SHALL MAKE CHANGES IN PIPING, DUCTING AND CONTROLS TO SUIT
ACTUAL INSTALLED TYPES WITHOUT ADDITIONAL COST TO THE OWNER. THE
CONTRACTOR SHALL CHECK THE DRAWINGS TO SEE THAT THE EQUIPMENT HE
CONTEMPLATES INSTALLING WILL FIT THE SPACES PROVIDED.
5. ALL WORK NOT SHOWN IN COMPLETE DETAIL SHALL BE INSTALLED IN CONFORMANCE
WITH ACCEPTED STANDARD PRACTICE.
6. PIPING, DUCTWORK, AND OTHER EQUIPMENT SHOWN AS EXISTING HAVE BEEN TAKEN
FROM OWNER'S DRAWINGS. CONTRACTOR SHALL VERIFY EXACT LOCATION AND SIZES
IN THE FIELD AND NON DESTRUCTIVE FIELD INVESTIGATION.
7. BEFORE BIDDING THE PROJECT THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY
THE CLEARANCES AVAILABLE TO BRING THE SPECIFIED EQUIPMENT AND MATERIAL TO
THE SITE.
8. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL OFFSETS,
BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOT EXACTLY LOCATED. MECHANICAL
TRADES SHALL FOLLOW THESE DRAWINGS IN LAYING OUT THEIR WORK, CONSULT
GENERAL CONSTRUCTION DRAWINGS TO FAMILIARIZE THEMSELVES WITH ALL
CONDITIONS AFFECTING THEIR WORK AND SHALL VERIFY SPACES IN WHICH THEIR
WORK WILL BE INSTALLED. WHERE JOB CONDITIONS REQUIRE CHANGES IN INDICATED
LOCATIONS AND ARRANGEMENT, MAKE SUCH CHANGES AT NO ADDITIONAL COST TO
THE OWNER.
9. THIS CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING HIS
WORK AND EQUIPMENT. HE SHALL COORDINATE THE WORK OF THIS SECTION WITH THE
WORK OF OTHER TRADES AND ALL JOB CONDITIONS.
10. WHERE MATERIAL IS SHOWN ON DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF SAME
TYPE AND QUALITY AS EXISTING MATERIAL. SUBMIT DATA FOR APPROVAL.
11. UPON COMPLETION AND BEFORE FINAL ACCEPTANCE OF THE WORK, ALL DEBRIS,
TEMPORARY PROTECTIVE COVERINGS, RUBBISH, LEFTOVER MATERIALS, TOOLS AND
EQUIPMENT SHALL BE REMOVED FROM THE SITE.
12. FINALLY, THE ENTIRE INSTALLATION SHALL BE LEFT IN A NEAT, CLEAN AND USABLE
CONDITION.
1. MECHANICAL SUPPORTING DEVICES
A. GENERAL: MECHANICAL EQUIPMENT AND MATERIALS ARE NOT TO BE SUSPENDED
OR SUPPORTED FROM PIPE, ELECTRICAL CONDUIT, CEILING SYSTEMS OR ANY
NON-STRUCTURAL MEMBER.
B. FASTEN TO CONCRETE MASONRY UNITS WITH EXPANSION ANCHORS OR
SELF-TAPPING MASONRY SCREWS. FOR EXPANSION ANCHORS INTO HOLLOW
CONCRETE BLOCK, USE SLEEVE-TYPE ANCHORS DESIGNED FOR THE SPECIFIC
APPLICATION. DO NOT FASTEN IN MASONRY JOINTS. DO NOT USE POWDER
ACTUATED FASTENERS, WOODEN PLUGS, OR PLASTIC INSERTS.
1. PROPELLER FANS
A. GENERAL: DIRECT-DRIVEN AS SCHEDULED PROPELLER FANS CONSISTING OF FAN
BLADES, HUB, HOUSING, ORIFICE RING, MOTOR, DRIVE ASSEMBLY, AND
ACCESSORIES.
B. CONSTRUCTION: FAN SHALL BE OF BOLTED AND WELDED CONSTRUCTION
UTILIZING CORROSION RESISTANT FASTENERS. THE MOTOR SHALL BE MOUNTED
ON A 12 GAUGE STEEL WIRE GUARD. WALL PANEL TO BE MINIMUM 14 GAUGE.
C. PROVIDE WITH THE FOLLOWING ACCESSORIES:
C.A. GRAVITY SHUTTERS: ALUMINUM BLADES IN ALUMINUM FRAME; INTERLOCKED
BLADES WITH NYLON BEARINGS.
C.B. WALL SLEEVE.
C.C. VARIABLE-SPEED CONTROLLER.
C.D. BIRDSCREEN.
1. LOUVERS - FIXED - GALVANIZED
A. LOUVERS SHALL BE A MINIMUM 4" DEEP, 18 GAUGE GALVANIZED STEEL FRAME, AND
18 GAUGE GALVANIZED STEEL BLADES.
B. LOUVERS SHALL BE FURNISHED WITH 1/2" MESH X 19 GAUGE GALVANIZED BIRD
SCREEN IN REMOVABLE FRAME.
C. LOUVERS SHALL BE OF THE DRAINABLE BLADE DESIGN WITH WATER COLLECTED
ON THE LEADING EDGE OF THE BLADE AND DIVERTED TO THE JAMB.
D. LOUVERS SHALL BE SEALED AROUND PERIMETER TO AVOID MOISTURE
PENETRATION BETWEEN THE LOUVER FRAME AND WALL.
E. LOUVERS SHALL BE FURNISHED WITH GRAVITY SHUTTERS.
LEGEND
CODES AND STANDARDSGENERAL NOTES
SPECIFICATIONS
ER
ET
SIG
ER
RE
ENI
GN
E
LANOISSEORPD
F
I A
N
OF CA L I FOR
STA
TE
D PM
ER
IC
eS LI
ME
HAN I CAL
C
.
NTE
R
Exp. 12/31/19
38688
REFERENCE SCALE IN INCHES
0 1 2
© 2018 IMEG CORP.
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Job Number
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
"LOCKER ROOMS EF UPGRADE"
EAST WHITTIER CITY
SCHOOL DISTRICT
2/1
/2018 8
:29:1
1 P
M
10931 STAMY ROAD, WHITTIER, CA 90604
HILLVIEWMIDDLE SCHOOL
M001
GENERAL NOTES, LEGEND
AND DRAWING INDEX
ED
ED
CG
18001320.00
02/01/18
BID DOCUMENTS
HIL
LV
IEW
M
IDD
LE
SC
HO
OL
18001320.0
0
901 VIA PIEMONTESUITE 400ONTARIO, CA91764
PH: 909.477.6915FAX: 909.477.6916www.imegcorp.com
DRAWING INDEX
DWG.NO. DESCRIPTION
M001 GENERAL NOTES, LEGEND AND DRAWING INDEX
M101 MECHANICAL FIRST FLOOR DEMOLITION PLAN
M201 MECHANICAL FIRST FLOOR REMODEL PLAN
M301 DETAILS/CONTROLS
EXHAUST FAN SCHEDULE
TYPE MARK I.D. NUMBER LOCATION SERVICECATOLOG DATA FAN DATA MOTOR
OPERATING WEIGHT(LBS)
REMARKSMANUFACTURER MODEL CFM ESP (IN) FAN RPM
WHEELDIAMETER I(N)
INPUT WATTS HP RPM VOLTAGE PHASE HERTZ
EF 1 LOCKERS BOY'S LOCKER ROOM Loren Cook Company 14XP26D102 900 0.10 938 14.75 113 1/6 1080 115 1 60 70 COMPLETE WITH SHUTTER GUARD, BIRDSCREEN, AND FAN SPEED CONTROLLER
EF 2 LOCKERS BOY'S LOCKER ROOM Loren Cook Company 14XP26D102 900 0.10 938 14.75 113 1/6 1080 115 1 60 70 COMPLETE WITH SHUTTER GUARD, BIRDSCREEN, AND FAN SPEED CONTROLLER
EF 3 LOCKERS GIRLS LOCKER ROOM Loren Cook Company 14XP26D102 900 0.10 938 14.75 113 1/6 1080 115 1 60 70 COMPLETE WITH SHUTTER GUARD, BIRDSCREEN, AND FAN SPEED CONTROLLER
EF 4 LOCKERS GIRLS LOCKER ROOM Loren Cook Company 14XP26D102 900 0.10 938 14.75 113 1/6 1080 115 1 60 70 COMPLETE WITH SHUTTER GUARD, BIRDSCREEN, AND FAN SPEED CONTROLLER
F-43
INSTR
F-44
F-47
F-48
EQUIP.
F-49
GIRL'S.
F-32
ENTRY
F-34
LOCKERS
F-36
LOCKERS
F-38
LOCKERS
F-1
INSTR.
F-3F-5
F-6
EQUIP.
F-7
BOY'S
F-9
ENTRY
F-10
JANITOR
F-24
DRYINGROOM
GIRL'SSHOWER
F-27
F-28
F-29
F-30
F-26
F-15
LOCKERS
F-16
LOCKERS
F-17
LOCKERS
F-14
TOWEL RM.
F-13
LOCKERS
F-12
LOCKERS
F-11
LOCKERS
F-18
CORRIDOR
F-51
CORRIDOR
F-25
STORF-41 F-40 F-39
FH
STAMY ROADEXISTING
BUILDINGF
EXISTING
BUILDINGD
EXISTING
BUILDINGE
EXISTING
BUILDINGA
EXISTING
BUILDINGB
EXISTING
BUILDINGG
EXISTINGBUILDING
C
EXISTINGBUILDING
J
EXISTING
BUILDINGH
EXISTING
BUILDINGI
EXISTINGPARKING LOT #2
EXISTING
PARKING LOT #1
(E) EF
(E) EF
(E) EF
(E) EF
PROJECT LOCATION
ER
ET
SIG
ER
RE
ENI
GN
E
LANOISSEORPD
F
I A
N
OF CA L I FOR
STA
TE
D PM
ER
IC
eS LI
ME
HAN I CAL
C
.
NTE
R
Exp. 12/31/19
38688
REFERENCE SCALE IN INCHES
0 1 2
© 2018 IMEG CORP.
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Job Number
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
"LOCKER ROOMS EF UPGRADE"
EAST WHITTIER CITY SCHOOL DISTRICT
As indicated
2/1
/2018 7
:36:3
3 P
M
10931 STAMY ROAD, WHITTIER, CA 90604
HILLVIEWMIDDLE SCHOOL
M101
MECHANICAL FIRST FLOOR
DEMOLITION PLAN
ED
ED
CG
18001320.00
02/01/18
BID DOCUMENTS
HIL
LV
IEW
M
IDD
LE
SC
HO
OL
18001320.0
0
901 VIA PIEMONTESUITE 400ONTARIO, CA91764
PH: 909.477.6915FAX: 909.477.6916www.imegcorp.com
DEMOLITION KEY NOTES
1/8" = 1'-0"1
MECHANICAL FIRST FLOOR DEMOLITION PLAN
KEY PLAN
GENERAL SHEET NOTES
1. REMOVE EXISTING EXHAUST FAN AND ASSOCIATED ACCESSORIES/SUPPORTS.
F-43
INSTR
F-44
F-47
F-48
EQUIP.
F-49
GIRL'S.
F-32
ENTRY
F-34
LOCKERS
F-36
LOCKERS
F-38
LOCKERS
F-1
INSTR.
F-3F-5
F-6
EQUIP.
F-7
BOY'S
F-9
ENTRY
F-10
JANITOR
F-24
DRYINGROOM
GIRL'SSHOWER
F-27
F-28
F-29
F-30
F-26
F-15
LOCKERS
F-16
LOCKERS
F-17
LOCKERS
F-14
TOWEL RM.
F-13
LOCKERS
F-12
LOCKERS
F-11
LOCKERS
F-18
CORRIDOR
F-51
CORRIDOR
F-25
STORF-41 F-40 F-39
FH
STAMY ROADEXISTING
BUILDINGF
EXISTING
BUILDINGD
EXISTINGBUILDING
E
EXISTINGBUILDING
A
EXISTINGBUILDING
B
EXISTINGBUILDING
G
EXISTING
BUILDING
C
EXISTING
BUILDINGJ
EXISTINGBUILDING
H
EXISTING
BUILDINGI
EXISTING
PARKING LOT #2
EXISTINGPARKING LOT #1
1
EF
2
EF
3
EF
4
EF
60"x24" INTAKE LOUVER 60"x24" INTAKE LOUVER
1
11
1
22
PROJECT LOCATION
ER
ET
SIG
ER
RE
ENI
GN
E
LANOISSEORPD
F
I A
N
OF CA L I FOR
STA
TE
D PM
ER
IC
eS LI
ME
HAN I CAL
C
.
NTE
R
Exp. 12/31/19
38688
REFERENCE SCALE IN INCHES
0 1 2
© 2018 IMEG CORP.
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Job Number
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
"LOCKER ROOMS EF UPGRADE"
EAST WHITTIER CITY SCHOOL DISTRICT
As indicated
2/1
/2018 7
:36:3
5 P
M
10931 STAMY ROAD, WHITTIER, CA 90604
HILLVIEWMIDDLE SCHOOL
M201
MECHANICAL FIRST FLOOR
REMODEL PLAN
ED
ED
CG
18001320.00
02/01/18
BID DOCUMENTS
HIL
LV
IEW
M
IDD
LE
SC
HO
OL
18001320.0
0
901 VIA PIEMONTESUITE 400ONTARIO, CA91764
PH: 909.477.6915FAX: 909.477.6916www.imegcorp.com
1/8" = 1'-0"1
MECHANICAL FIRST FLOOR REMODEL PLAN
REMODEL KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
1 FOR EXHAUST FAN MOUNTING DETAIL, REFER TO 1/M301.
2 FOR INTAKE LOUVER MOUNTING DETAIL, REFER TO 2/M301.
1. FOR EXHAUST FAN CONTROLS REFER TO DETAIL 3/M301.
CLIP ANGLE AROUND ENTIRE PERIMETER OF LOUVER.
BIRD SCREEN
(E) CMU WALL
EXTENDED DRIP SILL
CAULK ALLAROUND (TYP.)
FASTEN LOUVER TO CLIP ANGLES ON 18" MINIMUM CENTERS.
MOUNT FACE OFLOUVER FLUSHWITH EXTERIORFINISH UNLESSOTHERWISE NOTED.
1.
2.
NOTES:
SEAL ALL JOING ON BOTTOM INTERIOR SURFACE OF DUCT WITHIN 6'-0" OF THELOUVER WATER TIGHT.
CAULK SHEETMETAL SCREWS WHERE THEY PENETRATE METAL.
#12 S.M.S. @ 18" O.C.
3/8" HILTI KWIK BOLT TZ @ 18" O.C.
EF
-
1
115V-1∅-60HZ
WALL SWITCH
PER ELEC.
DETAIL NOTES:
SEE CONTROL WIRING LEGEND #4 THIS SHEET.
TYPICAL FOR
EF-1 & EF-2
DISC.
WIRING NOTES:
ELECTRICAL CONTRACTOR.
CIRCUIT BREAKER
DISCONNECT SWITCH
CONTRACTOR (DIVISION 23).
C.B.
DISC.
CONTRACTOR (DIVISION 26).
EQUIPMENT FURNISHED AND INSTALLED BY ELECTRICAL
EQUIPMENT FURNISHED AND INSTALLED BY MECHANICAL
LINE VOLTAGE WIRING AND CONDUIT FURNISHED AND INSTALLED BY
LOW VOLTAGE WIRING AND CONDUIT FURNISHED AND INSTALLED BY MECHANICALCONTRACTOR. SEE SPECIFICATION SECTIONS 26 05 19 AND 26 05 33 FOR CONDUIT ANDWIRING REQUIREMENTS. ALL LOW VOLTAGE WIRING TO BE IN CONDUIT.
NTS 3
NTS 2
NTS 1
NTS 6
NTS 5
NTS 4
NTS 9
NTS 8
NTS 7
INTAKE LOUVER MOUNTING DETAIL
EXHAUST FAN MOUNTING DETAIL
EXHAUST FAN WIRING DIAGRAM
CONTROL LEGEND
WINDOW
WINDOW
WINDOW
WINDOW
SUPPORT BRACKET
1/4" PLYWOOD BLANK-OFF
2x4 BLKG. (TYP.)
CAULK AND SEALWATER TIGHT ALL SIDES
3/8" HILTI KWIK BOLT TZ @16" O.C. MIN 3 TOP &BOTTOM
#10 x 1-1/4" LAG
SCREW @ 5" O.C.
#10 S.M.S.
3"x3"x1/4" ANGLE IRON
SUPPORT BRACKET
3/8" HILTI KWIK BOLT TZ
MIN. 1-1/2" EMB.
(E) CONCRETE WALL
BIRD SCREEN
PLYWOOD BLANK-OFF
FIELD PAINT EXTERIOR AND
INTERIOR BLACK
BIRD SCREEN
SHUTTER GUARD
CAULK AND SEAL WATER
TIGHT ALL SIDES
#10 x 1-1/2" LAG
SCREW @ 6" O.C.
3/8" HILTI KWIK BOLT TZ
@ 16" O.C.
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
ER
ET
SIG
ER
RE
ENI
GN
E
LANOISSEORPD
F
I A
N
OF CA L I FOR
STA
TE
D PM
ER
IC
eS LI
ME
HAN I CAL
C
.
NTE
R
Exp. 12/31/19
38688
REFERENCE SCALE IN INCHES
0 1 2
© 2018 IMEG CORP.
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Job Number
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
"LOCKER ROOMS EF UPGRADE"
EAST WHITTIER CITY
SCHOOL DISTRICT
2/1
/2018 7
:36:3
6 P
M
10931 STAMY ROAD, WHITTIER, CA 90604
HILLVIEWMIDDLE SCHOOL
M301
DETAILS/CONTROLS
ED
ED
CG
18001320.00
02/01/18
BID DOCUMENTS
HIL
LV
IEW
M
IDD
LE
SC
HO
OL
18001320.0
0
901 VIA PIEMONTESUITE 400ONTARIO, CA91764
PH: 909.477.6915FAX: 909.477.6916www.imegcorp.com
DUPLEX GROUND FAULT INTERRUPTING TYPE RECEPTACLE,
20 AMP, 125 VOLT, 2 POLE, 3 WIRE.
CONDUIT RUN, CONCEALED IN CEILING OR WALLS.
MOUNT AT +18 INCHES TO CENTER UNLESS NOTED OTHERWISE.
PANEL DESIGNATION.
SURFACE MOUNTED BRANCH CIRCUIT PANELBOARD.
P1
WEATHERPROOF
NOTE INDICATOR
WP
- -
VANDAL PROOF TYPE MOTOR RATED SWITCH.SM
PIPING, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE.1.
PIPING, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO
COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE
7-05 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.8, 13.6.7,
13.6.5.6, AND 2016 CBC, SECTIONS 1616A.1.23, 1616A.1.24, 1616A.1.25. AND
1616A.1.26.
THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL BE
DETAILED ON THE APPROVED DRAWINGS OR THEY SHALL COMPLY WITH
ONE OF THE OSHPD PRE-APPROVALS (OPM #) AS MODIFIED TO SATISFY
ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D.
COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO
THE START OF HANGING AND BRACING OF THE PIPE, AND ELECTRICAL
DISTRIBUTION SYSTEMS.
THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY
OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
INCLUDED IN THE CONTRACTOR'S BID.
DAYS PRIOR TO THE OUTAGE. ANY OVERTIME PAY SHALL BE
SHUTDOWN MUST BE COORDINATED WITH THE OWNER AND ENGINEER 14
MINIMUM. HOWEVER, WHEN AN INTERRUPTION IS NECESSARY, THE
4. ALL INTERRUPTION OF ELECTRICAL POWER SHALL BE KEPT TO A
THE MOST STRINGENT RULE SHALL APPLY.
WHERE THE CODES HAVE DIFFERENT LEVELS OF REQUIREMENTS,
ALL LOCAL CODES HAVING JURISDICTION.
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS
CALIFORNIA CODE OF REGULATIONS TITLE 24 (CCR)
AMERICAN NATIONAL STANDARD INSTITUTE (ANSI)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
AMERICAN STANDARD ASSOCIATION (ASA)
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
INSULATED POWER CABLE ENGINEERS ASSOCIATION
AMERICAN SOCIETY OF TESTING MATERIALS (ASTM)
CALIFORNIA ELECTRICAL CODE (CEC) - 2016 EDITION
(NEMA)
(IPCEA)
(IEEE)
SHALL COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING:
IN ADDITION, THE MATERIALS, EQUIPMENT, AND INSTALLATION
DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY.
LISTING. CUSTOM MADE EQUIPMENT SHALL HAVE COMPLETE TEST
RECOGNIZED TESTING AUTHORITY WHERE UL DOES NOT HAVE A
THEIR LABEL, OR LISTED AND CERTIFIED BY A NATIONALLY
SHALL BE LISTED BY UNDERWRITER'S LABORATORIES (UL) AND BEAR
3. ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE NEW AND
AND ANCHOR THE EQUIPMENT TO THE SUPPORTING STRUCTURE.
RESIST A LOAD WHICH EXCEEDS THE FORCE LEVEL USED TO RESTRAIN
THE EQUIPMENT AS A WHOLE INCLUDING ITS ATTACHMENTS, WILL
ELEMENTS, SUB-ASSEMBLIES AND/OR PARTS OF SAID EQUIPMENT, AND
DESIGNED AND CONSTRUCTED IN SUCH A MANNER THAT ALL PORTIONS,
2. ALL ELECTRICAL PREFABRICATED EQUIPMENT SHALL BE
ALL DAMAGES CAUSED BY HIM OR HIS WORK.
RESPONSIBLE FOR THE PROPER AND APPROVED REPAIR OF ANY AND
WHEN TRENCHING FOR HIS WORK. THE CONTRACTOR SHALL BE
UTILITY LINES. THE CONTRACTOR SHALL USE EXTREME CAUTION
CALLED TO THE FACT THAT THERE ARE EXISTING UNDERGROUND
AND ASPHALT AS REQUIRED TO PERFORM HIS WORK. ATTENTION IS
TRENCHING, BACKFILLING, COMPACTION AND PATCHING OF CONCRETE
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAWCUTTING,
CONCEALED IN WALLS, OR BELOW SLAB ON GRADE UNLESS NOTED
CONDUIT SHALL BE INSTALLED CONCEALED IN THE CEILING SPACE,
11. CONDUIT SHALL NOT BE INSTALLED IN ANY FLOOR SLAB.
OTHERWISE.
TO ROUGHING IN ALL CONDUIT TO THIS EQUIPMENT.
RESPONSIBLE FOR OBTAINING MANUFACTURER'S SHOP DRAWINGS PRIOR
OPERATIONS SHALL BE PROVIDED. THE CONTRACTOR SHALL BE
WIRING, CONTROLS, AND CONDUIT FOR MECHANICAL AND PLUMBING
LOCATION OF EQUIPMENT. DISCONNECT SWITCHES, STARTERS,
THE DRAWINGS OF OTHER TRADES FOR CONTROL DIAGRAMS, SIZE AND
ELECTRICAL DRAWINGS, AND DRAWINGS OF OTHER TRADES. REVIEW
CONNECTIONS AS INDICATED ON THE SINGLE LINE DIAGRAM,
CONNECTION TO MOTORS AND EQUIPMENT REQUIRING ELECTRICAL
OF THEIR RESPECTIVE EQUIPMENT. SUPPLY POWER AND MAKE
9. COORDINATE WITH OTHER TRADES AS TO THE EXACT LOCATION
SHALL BE MADE BY THE CONTRACTOR.
8. ALL FINAL CONNECTIONS TO OWNER FURNISHED EQUIPMENT
FOR EQUIPMENT.
REVIEW AND TO COORDINATE WITH THE PLUMBING DRAWINGS
NOTED AND SHALL BE COORDINATED WITH OTHER SECTIONS. DO NOT
ELECTRICAL, ARCHITECTURAL, AND PLUMBING ITEMS OR FEATURES.
SCALE THE ELECTRICAL DRAWINGS FOR LOCATIONS OF ANY
SHALL BE AT THE OPTION OF THE CONTRACTOR UNLESS OTHERWISE
13. DRAWINGS ARE DIAGRAMMATIC ONLY. ROUTING OF RACEWAYS
7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
GUARANTEE OF MATERIALS AND WORKMANSHIP FROM THE DATE OF
6. THE CONTRACTOR SHALL FURNISH A ONE YEAR WRITTEN
FROM EACH REPRESENTATIVE].
AFTER RECEIPT OF APPROVAL AND RECOMMENDATION OF ACCEPTANCE
FINAL ACCEPTANCE OF THE WORK WILL BE MADE BY THE OWNER
ITEM OR SYSTEM [TO THE FULL SATISFACTION OF EACH REPRESENTATIVE.
COMPETENT PERSONNEL TO DEMONSTRATE THE OPERATION OF ANY
OWNER WILL INSPECT THE WORK. THE CONTRACTOR SHALL PROVIDE
DRAWINGS HAVE BEEN FULLY COMPLETED, REPRESENTATIVES OF THE
5. AFTER ALL REQUIREMENTS OF THE SPECIFICATIONS AND/OR THE
SUBSTANTIAL COMPLETION.
10. EXACT METHOD AND LOCATION OF CONDUIT PENETRATION AND
OPENINGS IN CONCRETE WALLS OR FLOORS OR STRUCTURAL STEEL
MEMBERS SHALL BE AS DIRECTED BY THE ARCHITECT AND REVIEWED AND
APPROVED BY DSA. PERFORM CORING, SAW CUTTING, PATCHING, AND
REFINISHING OF EXISTING WALLS AND SURFACES WHEREVER IT IS
NECESSARY TO PENETRATE. NO STRUCTURAL MEMBER, FLOOR OR WALL
SHALL BE CUT, NOTCHED OR BORED UNLESS SPECIFICALLY DETAILED ON
THE APPROVED PLANS OR REVIEWED AND APPROVED BY THE ARCHITECT
OF RECORD AND DSA PRIOR TO BEGINNING SUCH WORK. OPENINGS
SHALL BE SEALED IN AN APPROVED METHOD TO MEET THE FIRE RATING
OF THE PARTICULAR WALL, FLOOR OR CEILING. EXACT METHOD AND
LOCATIONS OF CONDUIT PENETRATIONS AND OPENINGS IN CONCRETE
WALLS OR FLOORS SHALL BE UL APPROVED.2016 CALIFORNIA BUILDING CODE (CBC)
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 2
(2015 INTERNATIONAL BUILDING CODE (IBC) W/ 2016 CALIFORNIA AMENDMENTS)
2016 CALIFORNIA ELECTRICAL CODE (CEC)
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 3
(2015 NATIONAL ELECTRICAL CODE (NEC) W/ 2016 CALIFORNIA AMENDMENTS)
2016 CALIFORNIA ENERGY CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 6
2016 CALIFORNIA FIRE CODE (CFC)
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 9
(2015 INTERNATIONAL FIRE CODE (IFC) W/ 2016 CALIFORNIA AMENDMENTS)
2016 CALIFORNIA GREEN BUILDING STANDARDS CODE
2016 CALIFORNIA EXISTING BUILDING CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART10
(2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC))
2016 CALIFORNIA REFERENCED STANDARDS CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 12
AMERICANS WITH DISABILITIES ACT (ADA)
TITLE II - ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADAG)
1990 STATE FIRE MARSHAL REGULATIONS AND AMENDMENTS TO-DATE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, CALIFORNIA STATE
ACCESSIBILITY STANDARDS
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 19
2016 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE
CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 1
(CAL GREEN), PART II, TITLE 24 C.C.R.
2016 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE
SPECIFICATIONS
APPLICABLE CODES AND STANDARDS
SCHOOL EQUIPMENT ANCHORAGE NOTESPART 1 - GENERAL
1.01 SCOPE OF WORK
A. WORK COVERED BY THIS SECTION CONSISTS OF FURNISHING ALL
LABOR, EQUIPMENT, SUPPLIES, AND MATERIALS, UNLESS OTHERWISE
SPECIFIED, AND IN PERFORMING ALL OPERATIONS NECESSARY FOR
THE INSTALLATION OF A COMPLETE AND OPERABLE ELECTRICAL
SYSTEM AS REQUIRED BY THESE SPECIFICATIONS AND AS INDICATED
ON THE DRAWINGS.
B. THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS AND
SPECIFICATIONS IN A MANNER TO BE FULLY COGNIZANT OF ALL
WORK REQUIRED UNDER THIS SECTION.
C. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED
PERMITS UNLESS OTHERWISE ARRANGED AND SCHEDULE ALL
REQUIRED INSPECTIONS FOR THE EXECUTION OF THE WORK UNDER
THIS CONTRACT.
1.02 GENERAL REQUIREMENTS
A. WORK DONE UNDER THIS SECTION SHALL COMPLY WITH THE LATEST
EDITION OF THE CALIFORNIA ELECTRICAL CODE, CEC (NATIONAL
ELECTRICAL CODE NEC), THE STATE OF CALIFORNIA TITLE 24, THE
STATE BUILDING STANDARDS, (OSHA) OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION, AND TO ANY APPLICABLE LOCAL
JURISDICTIONAL REQUIREMENTS. IN CASE OF CONFLICT BETWEEN
REQUIREMENTS, THE MOST RESTRICTIVE SHALL APPLY.
1.03 ELECTRICAL CONTRACTOR'S RESPONSIBILITY
A. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN A
COMPLETE SET OF DRAWINGS AND SPECIFICATIONS. CONTRACTOR
SHALL CHECK THE DRAWINGS OF THE OTHER TRADES AND SHALL
CAREFULLY READ THE ENTIRE SPECIFICATIONS AND DETERMINE HIS
RESPONSIBILITIES.
B. BEFORE SUBMITTING THE BID, THE ELECTRICAL CONTRACTOR SHALL
VISIT THE JOB SITE AND FULLY ACQUAINT HIMSELF WITH EXISTING
CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
INSTALL THE EQUIPMENT AND ASSOCIATED WIRING IN SUCH A
MANNER AS TO CONFORM TO THE EXISTING STRUCTURE OF THE
BUILDING, AVOID OBSTRUCTIONS, AND MEET APPLICABLE CODE
REQUIREMENTS.
C. THE INTENT OF THESE DRAWINGS IS TO DESCRIBE A COMPLETE AND
OPERABLE SYSTEM. WHERE EXISTING CONDITIONS DIFFER FROM
DRAWINGS, ADJUSTMENT SHALL BE MADE AND ALLOWANCES
INCLUDED FOR ALL NECESSARY EQUIPMENT TO COMPLETE ALL
PARTS OF THE DRAWINGS AND SPECIFICATIONS. BRING ANY
QUESTIONS TO THE ARCHITECT OR ENGINEER'S ATTENTION PRIOR TO
BIDDING.
D. WHEREVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE,
EQUIPMENT, DEVICES, CIRCUIT BREAKERS, ETC., ARISES ON THE
DRAWING AND/OR SPECIFICATION, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND
SERVICES REQUIRED BY THE STRICTEST CONDITION NOTED ON
DRAWINGS AND/OR IN SPECIFICATIONS TO ENSURE COMPLETE AND
OPERABLE SYSTEMS AS REQUIRED BY THE OWNER AND ENGINEER.
1.04 WORK NOT INCLUDED
A. CERTAIN LABOR, MATERIALS, OR EQUIPMENT MAY BE FURNISHED
UNDER OTHER CONTRACTS BY THE OWNER. WHEN SUCH IS THE
CASE, THE EXTENT, SOURCE, AND DESCRIPTION OF THESE ITEMS
WILL BE INDICATED ON THE DRAWINGS OR DESCRIBED IN THE
SPECIFICATIONS. UNLESS OTHERWISE NOTED, ALL LABOR, MATERIALS
AND EQUIPMENT FOR THE COMPLETE INSTALLATION OF THE
ELECTRICAL WORK SHALL BE PROVIDED UNDER THIS SECTION OF
THESE SPECIFICATIONS.
1.05 SUBMITTALS
A. AFTER AWARD OF THE CONTRACT AND BEFORE ANY MATERIALS ARE
DELIVERED TO THE JOB SITE, A COMPLETE LIST OF ALL MATERIALS
PROPOSED TO BE FURNISHED AND INSTALLED UNDER THIS SECTION
MUST BE PROVIDED.
1.06 STANDARDS AND MATERIALS
A. ALL MATERIALS SHALL CONFORM TO THE CURRENT APPLICABLE
INDUSTRY STANDARDS, NEMA (NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION), ANSI (AMERICAN NATIONAL
STANDARDS INSTITUTE), IPCEA (INSULATED POWER CABLE ENGINEERS
ASSOCIATION), IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONIC
ENGINEERS), NATIONAL ELECTRICAL SAFETY CODE.
B. UNLESS OTHERWISE INDICATED, ALL MATERIALS SHALL BE
UNDERWRITERS LABORATORIES LISTED AND LABELED, OR CERTIFIED
BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
C. WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT
AS THE ELECTRICAL MECHANICAL EFFICIENCY. DEFECTIVE AND
DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO
FINAL APPROVAL AND ACCEPTANCE. THE DRAWINGS AND
SPECIFICATIONS TAKE PRECEDENCE WHEN THEY ARE MORE
STRINGENT THAN CODES, STATUTES, OR ORDINANCES IN EFFECT.
APPLICABLE CODES, STANDARDS, ORDINANCES, AND STATUTES TAKE
PRECEDENCE WHEN THEY ARE MORE STRINGENT OR CONFLICT WITH
THE DRAWINGS OR SPECIFICATIONS.
1.07 DELIVERY AND STORAGE OF MATERIALS
A. THE CONTRACTOR SHALL INVESTIGATE EACH SPACE IN THE BUILDING
THROUGH WHICH EQUIPMENT MUST PASS TO REACH ITS FINAL
LOCATIONS. IF NECESSARY, THE MANUFACTURER SHALL BE
REQUIRED TO SHIP HIS MATERIAL IN SECTIONS, SIZED TO PERMIT
PASSING THROUGH SUCH RESTRICTED AREAS IN THE BUILDING.
B. THE CONTRACTOR SHALL RETAIN IN HIS POSSESSION AND SHALL BE
RESPONSIBLE FOR ALL PORTABLE AND DETACHABLE PARTS OF
PORTIONS OF INSTALLATIONS SUCH AS FUSES, KEY LOCKS,
ADAPTORS, BLOCKING CLIPS, AND INSERTS UNTIL FINAL COMPLETION
OF WORK. THESE PARTS SHALL BE DELIVERED TO THE OWNER UPON
COMPLETION OF THE WORK.
PART 2 - PRODUCTS
2.01 EQUIPMENT AND MATERIALS
A. ALL MATERIALS FURNISHED AND INSTALLED UNDER THIS CONTRACT
SHALL BE NEW, FREE FROM DEFECTS, AND SHALL BE GUARANTEED
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE OF
THE WORK. SHOULD ANY TROUBLE DEVELOP DURING THEIR PERIOD
DUE TO DEFECTIVE MATERIALS OR FAULTY WORKMANSHIP, THE
CONTRACTOR SHALL FURNISH ALL NECESSARY MATERIALS AND
LABOR TO CORRECT THE TROUBLE WITHOUT ANY COST TO THE
OWNER. ANY DEFECTIVE MATERIAL OR INFERIOR WORKMANSHIP
NOTED AT THE TIME OF INSTALLATION SHALL BE CORRECTED
IMMEDIATELY TO THE SATISFACTION OF THE OWNER.
2.02 CONDUIT
A. PROVIDE RACEWAYS AS INDICATED ON THE DRAWINGS AND AS
B. ALL CONDUITS CONCEALED (CO) SHALL BE SCHEDULE EMT UNLESS
OTHERWISE INDICATED ON THE DRAWING. ALL EMPTY CONDUIT SHALL BE
PROVIDED WITH A at" POLYPROPYLENE PULL STRING.
C. WHERE CONDUIT CROSSES AN EXPANSION JOINT, PROVIDE APPROVED
FITTINGS WHICH ALLOW DEFLECTIONS EQUIVALENT TO TWICE THE
MOVEMENT ALLOWED BY THE DESIGN.
D. PVC SCHEDULE 40 CONDUITS SHALL BE USED ONLY IN
UNDERGROUND APPLICATION, CONDUIT RISERS THOUGHT SLAB SHALL
BE "GRC".
2.03 CONDUCTORS
A. PROVIDE A COMPLETE SYSTEM OF CONDUCTORS IN RACEWAY
SYSTEMS AS SHOWN ON THE DRAWINGS AND THEN HEREIN
SPECIFIED. ALL WIRE SHALL BE ROUTED THROUGH AN APPROVED
RACEWAY REGARDLESS OF VOLTAGE APPLICATION.
2.04 FITTINGS
A. CONNECTOR, COUPLING, LOCKNUT, BUSHINGS AND CAPS USED WITH
RIGID CONDUIT SHALL BE STEEL, THREADED AND GALVANIZED.
BUSHINGS SHALL BE INSULATED.
B. EMT FITTINGS, CONNECTORS AND COUPLINGS SHALL BE STEEL, ZINC,
OR CADMIUM PLATED, COMPRESSION TYPE, WITH INSULATED THROAT.
C. FLEXIBLE STEEL CONDUIT CONNECTORS SHALL BE TWIST-IN-TYPE
WITH INSULATED THROAT. THE FINISH SHALL BE ZINC OR CADMIUM
PLATING.
D. EMT CONDUIT FITTINGS SHALL BE THE COMPRESSION TYPE; SET
SCREW FITTINGS SHALL NOT BE USED.
2.05 JUNCTION AND PULL BOXES
A. FOR INTERIOR DRY LOCATIONS, BOXES SHALL BE GALVANIZED
ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE WITH REMOVABLE,
MACHINE SCREW SECURED COVERS.
B. ALL BOXES SHALL BE SIZED FOR THE NUMBER AND SIZES OF
CONDUCTORS AND CONDUITS ENTERING THE BOX AND EQUIPPED
WITH PLASTER RINGS WHERE REQUIRED.
2.06 OUTLET BOXES
A. FOR FIXTURES, BOXES SHALL BE GALVANIZED, ONE-PIECE DRAWN
STEEL, KNOCKOUT TYPE EQUIPPED WITH 3/8" FIXTURE STUDS AND
PLASTER RINGS WHERE REQUIRED.
B. FOR CONVENIENCE OUTLETS, WALL SWITCHES, OR OTHER DEVICES,
OUTLET BOXES SHALL BE GALVANIZED ONE-PIECE DRAWN STEEL,
KNOCKOUT TYPE 4"X4"X1-1/2" MINIMUM.
C. FOR LOCATIONS WHERE STANDARD BOXES ARE NOT SUITABLE,
SPECIAL BOXES SHALL BE DESIGNED TO FIT SPACE OR MEET OTHER
REQUIREMENTS AND SUBMITTED FOR APPROVAL.
2.07 RECEPTACLES
A. ALL DEVICES SHALL CONFIRM TO THE NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION (NEMA) STANDARDS AND SHALL BE
UNDERWRITERS' LABORATORIES, INC. (UL) LISTED AND LABELED AND
SHALL BE "SPECIFICATIONS GRADE," MEETING THE REQUIREMENTS OF
THE FEDERAL SPECIFICATIONS FOR RECEPTACLE OUTLETS.
B. SINGLE AND DUPLEX RECEPTACLES SHALL BE SPECIFICATION GRADE,
CONVENIENCE RECEPTACLES SHALL BE U-GRPUNDED TYPE, 125
VOLTS, RATED 20 AMPERES, SIDE AND BACK WIRED WITH BINDING
SCREWS ONLY WITH DOUBLE WIPE CONTACTS AND SPRING STEEL
BACK UP CLIPS. HUBBELL MODEL #5362, ARROW HART OR PASS &
SEYMOUR. SEE ITEM C. BELOW FOR RECEPTACLE COLOR.
C. THE GROUND CONTACT SHALL BE ONE PIECE AND INTERNALLY
CONNECTED TO THE FRAME WITH GROUND TERMINAL FOR EXTERNAL
GROUND.
D. GROUND FAULT RECEPTACLES SHALL BE 20 AMPERES, 125 VOLTS
DUPLEX, THREE WIRE GROUND WITH PILOT LIGHT AND TEST AND
RESET BUTTONS. SUITABLE FOR FEED THROUGH WIRING, COLOR TO
BE SELECTED, HUBBELL #5362GF SERIES, OR PASS & SEYMOUR
2091 SIL SERIES.
E. EACH RECEPTACLE OUTLET INSTALLED WITHIN 72" OF SINK OR WET
OR DAMP LOCATION ON ROOF, OUTDOOR BELOW GRADE (PIT),
JANITORS, CLOSETS, AND BATHROOMS, SHALL HAVE AND AUTOMATIC
5 MA., INDIVIDUAL GROUND FAULT (GFI) PROTECTION.
F. ALL RECEPTACLES OUTLETS SHALL BE OF THE SAME MANUFACTURE.
C. PLASTIC COVER PLATES SHALL HIGH IMPACT THERMOPLASTIC, HIGH
STRENGTH, SCRATCH- RESISTANT, SMOOTH AND
SELF-EXTINGUISHING, HUBBELL "PI" SERIES OR PASS & SEYMOUR
RP SERIES.
D. WHERE OUTLETS ARE TO BE WEATHERPROOF, PROVIDE AN AISI TYPE
302 STAINLESS WITH DOUBLE HINGED COVER PASS & SEYMOUR
#WDP-8.
E. PROVIDE PLASTIC COVER PLATES UNLESS NOTED OTHERWISE.
2.09 SUPPORTING DEVICES
A. ALL EQUIPMENT CONDUITS SHALL BE SUPPORTED, ANCHORED AND
BRACED IN ACCORDANCE WITH THE
B. MOST STRINGENT CODES AND REQUIREMENTS. COMPLY WITH
CHAPTER 23 OF THE LATEST CBC (CALIFORNIA BUILDING CODE).
3.05 INSTALLATION
A. WORKMANSHIP IS TO BE NEAT, BY EXPERIENCED WORKMEN WITH ADEQUATE
SUPERVISION, AND IN LINE WITH NORMAL INDUSTRY WORK PRACTICES.
B. VERIFY LOCATION OF EACH OUTLET FOR POWER, SIGNAL,
TELEPHONE/DATA, AND EACH LIGHTING FIXTURE WITH ARCHITECT
PRIOR TO ROUGH-IN. INCLUDE IN BID COST OF RELOCATING EACH
ITEM WITHIN TEN-FEET RADIUS OF ITS INDICATED LOCATION.
C. ALL CONDUIT TO BE RUN CONCEALED UNLESS OTHERWISE NOTED.
ALL CONDUITS SHALL BE ROUTED OVERHEAD IN CEILING SPACES. NO
CONDUITS SHALL BE PERMITTED IN CONCRETE SLAB, MASONRY
WALLS UNLESS SPECIFICALLY SO INDICATED. CONDUIT SHALL BE RUN
SO AS NOT TO INTERFERE WITH OTHER PIPING FIXTURES OR
EQUIPMENT.
D. WHERE ALLOWED, EXPOSED CONDUIT RUNS SHALL BE INSTALLED
PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS,
OR INTERSECTION OF VERTICAL PLANES AND CEILINGS.
E. ALL ELECTRICAL CONDUITS AND OTHER ELECTRICAL RACEWAYS
PASSING THROUGH FIRE RATED CEILINGS, SLABS, WALLS AND
PARTITIONS SHALL BE SEALED TO PREVENT THE SPREAD OF FIRE,
SMOKE, AND GASSES. USE A UL LISTED AND APPROVED FIRE-STOP
MATERIAL EQUAL TO RATING OF A WALL OR A FLOOR SLAB
PENETRATED; INSTALLATION OF FIRE-STOP MATERIAL SHALL BE IN
ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
F. UNLESS WRITTEN PERMISSION IS GRANTED BY THE ARCHITECT, NO
MATERIAL SHALL BE MOUNTED ON THE EXTERIOR WALLS OR
PARAPET TOP OF THE BUILDING.
G. ALL POWER WIRING SHALL BE INSTALLED IN CONDUIT.
H. ALL WIRES FOR ALL SYSTEMS SHALL BE CONTINUOUS FROM SWITCH
TO TERMINAL OR FURTHEST OUTLET. NO JOINTS SHALL BE MADE
EXCEPT IN PULL, JUNCTION OR OUTLET BOXES, OR IN PANEL OR
SWITCHBOARD GUTTERS.
3.06 GROUNDING
A. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AS INDICATED ON
DRAWINGS AND AS REQUIRED BY THE LATEST EDITION OF
APPLICABLE CODES.
B. FURNISH AND INSTALL ALL GROUNDING CONDUCTORS, CONDUIT AND
CLAMPS. THE SIZE OF THE GROUNDING CONDUCTORS SHALL BE NOT
LESS THAN THAT SPECIFIED IN THE CEC AND NEC.
C. EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH CODE SIZE GREEN
GROUND, EQUIPMENT WIRE (PER NEC 250-95) (NOT INDICATED ON
DRAWINGS) WITHIN THE SAME CONDUIT FOR ALL CIRCUITS OF
PANELBOARDS.
3.07 BRANCH CIRCUITS
A. NO MORE THAN THREE BRANCH CIRCUITS PERMITTED IN ONE
CONDUIT UNLESS INDICATED OTHERWISE.
3.08 PROTECTION
A. USE ALL MEANS NECESSARY TO PROTECT THE WORK AND
MATERIALS FROM LOSS DURING AND AFTER INSTALLATION, AND
PROVIDE ADEQUATE AND PROPER STORAGE FACILITIES DURING THE
PROGRESS OF THE WORK. PROVIDE FOR THE SAFETY AND GOOD
CONDITION OF ALL WORK UNTIL FINAL ACCEPTANCE OF THE WORK
BY THE OWNER. REPLACE ALL DAMAGE OR DEFECTIVE WORK,
MATERIAL, AND EQUIPMENT AT NO EXPENSE TO THE OWNER BEFORE
REQUESTING FINAL ACCEPTANCE.
3.09 CLEANING OF EQUIPMENT, MATERIAL, AND PREMISES
A. SITE SHALL BE LEFT BROOM CLEAN AFTER COMPLETION OF WORK
EACH DAY. UPON COMPLETION OF THE WORK, LEAVE THE PREMISES
CLEAN OF ALL DIRT AND DEBRIS.
B. ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT
SHALL BE INSTALLED COMPLETE, THOROUGHLY CLEANED, AND ALL
RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF
ALL MATERIAL AND EQUIPMENT SHALL BE CLEANED AND DELIVERED
IN A PERFECT, UNBLEMISHED CONDITION.
3.10 HANDLING OF WIRE AND CABLE
A. HANDLE WIRE AND CABLE SO AS TO AVOID DAMAGE TO
CONDUCTORS AND TAKE EVERY PRECAUTION TO AVOID SHARP
BENDING OR SCORING OF THE CABLE. CABLE SHALL NOT BE LAID
NOR DRAGGED UPON THE GROUND.
B. THE CONTRACTOR SHALL BE REQUIRED TO REMOVE AND REPLACE
AT HIS OWN EXPENSE ALL WIRE AND CABLE DAMAGED DUE TO
IMPROPER HANDLING, AND SHALL PAY FOR THE NEW WIRE OR
CABLE.
3.11 TESTING AND INSPECTIONS
A. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED
PERMITS AND ARRANGE ALL REQUIRED INSPECTIONS FOR THE
EXECUTION OF THE WORK UNDER THIS CONTRACT.
B. THE CONTRACTOR SHALL REPLACE ALL DAMAGED OR DEFECTIVE
EQUIPMENT OR WORK.
C. ALL CIRCUITS SHALL BE TESTED FOR CONTINUITY AND CIRCUIT
INTEGRITY BY THE CONTRACTOR. ADJUSTMENTS SHALL BE MADE FOR
CIRCUITS NOT COMPLYING WITH TESTING CRITERIA.
D. THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERFORM
ANY ADDITIONAL TESTS REQUIRED BY THE AUTHORITY HAVING
JURISDICTION. HE SHALL ALSO CORRECT ALL FAILURES AND
REPLACE ANY DAMAGED PORTIONS OF THE WORK RESULTING FROM
THOSE TESTS. THE COST OF THE FOREGOING ITEMS SHALL BE PAID
BY THE CONTRACTOR.
E. THE CONTRACTOR SHALL FURNISH THE OWNER CERTIFICATES OF
INSPECTION AND APPROVAL BY THE ELECTRICAL INSPECTION
AUTHORITY ON ALL WORK COMPETED AS REQUIRED.
2.08 DEVICE PLATES
A. PROVIDE PLATE FOR ALL SWITCHES, RECEPTACLES, JUNCTION BOXES,
TELEPHONE, DATA AND OTHER OUTLETS.
B. STAINLESS STEEL PLATE SHALL BE AMERICAN IRON AND STEEL
INSTITUTE (AISI) TYPE 302, WITH BEVELED EDGES, 0.040" THICK
WITH A SATIN SMOOTH FINISH. SMOOTHIE. HUBBELL #97071 SERIES.
PART 3 - EXECUTION
3.01 WORKMANSHIP AND COMPLETION OF INSTALLATION
A. THE CONTRACTOR SHALL MAINTAIN ON JOB SITE A SET OF THE
WORKING DRAWINGS WHICH SHALL BE UPDATED DAILY IN DETAIL FOR
WORK ACCOMPLISHED. UPON COMPLETION OF THE WORK, A SET OF
REPRODUCIBLE CONTRACT DRAWINGS SHALL BE OBTAINED FROM THE
GENERAL CONTRACTOR AND ALL CHANGES AS NOTED ON THE
RECORD SET OF PRINTS SHALL BE INCORPORATED THEREON WITH
RED INK IN A NEAT, LEGIBLE, UNDERSTANDABLE AND PROFESSIONAL
MANNER.
B. ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT
SHALL BE INSTALLED COMPLETE, THOROUGHLY CLEANED, AND ALL
RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF
ALL MATERIAL AND EQUIPMENT SHALL BE CLEANED AND DELIVERED
IN A PERFECT, UNBLEMISHED CONDITION.
D. PERFORM ALL WORK IN A MANNER WHICH WILL NOT CAUSE
UNNECESSARY INCONVENIENCE OR DANGER TO THE OCCUPANTS,
NOR INTERFERE WITH THE ACTIVITIES IN THE BUILDING.
E. UPON COMPLETION OF THE INSTALLATION AND AS A CONDITION OF
ITS ACCEPTANCE FURNISH ONE COPY OF THE FINAL INSPECTION
CERTIFICATE TO THE OWNER.
F. THE CONTRACTOR SHALL COORDINATE AND SCHEDULE EACH POWER
INTERRUPTION WITH OWNER, AND SHALL PROVIDE AT LEAST ONE
WEEKS NOTICE OF PROPOSED INTERRUPTION AND WORK TO BE
ACCOMPLISHED.
3.02 PREPARATION COORDINATION.
A. THE CONTRACTOR SHALL COORDINATE THIS WORK WITH ALL OTHER
CONTRACTORS FURNISHING LABOR, MATERIALS AND WORK, SO THAT
THE WORK AS WHOLE SHALL BE EXECUTED AND COMPLETED
WITHOUT CONFLICT OR DELAY.
3.03 TRENCHING AND BACK FILLING
A. PERFORM ALL SUCH TRENCHING AND BACKFILLING IN ACCORDANCE
WITH DRAWING DETAILS.
B. EXAMINE THE DRAWINGS AND SPECIFICATIONS AND DETERMINE THE
WORK TO BE PERFORMED BY THE ELECTRICAL, PLUMBING AND
3.04 CORE CUTTING, DRILLING, AND PATCHING
A. NO HOLES WILL BE ALLOWED IN ANY STRUCTURAL MEMBERS
WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT OR
STRUCTURAL ENGINEER AND GENERAL CONTRACTOR.
HEREIN SPECIFIED. CONDUITS SHALL BE RIGID STEEL "GRC" (THICK
WALL) GALVANIZED; ELECTRICAL METALLIC TUBING "EMT" (THIN
WALL); FLEXIBLE STEEL, GALVANIZED; LIQUID-TIGHT, FLEXIBLE
STEEL CONDUIT WITH GROUND BOND; OR SCHEDULE 40 PVC.
GENERAL NOTES
OTHER TRADES. PROVIDE THE TYPE AND AMOUNT OF ELECTRICAL
MATERIALS AND EQUIPMENT NECESSARY TO PLACE THIS WORK IN
PROPER OPERATION, COMPLETELY WIRED TESTED AND READY FOR
USE. THIS SHALL INCLUDE ALL CONDUIT, WIRE, DISCONNECTS,
RELAYS, AND OTHER DEVICES FOR THE REQUIRED OPERATION
SEQUENCE OF ALL ELECTRICAL, AND OTHER SYSTEMS OREQUIPMENT.
SYMBOL DESCRIPTION
LEGEND
Exp. 6-30-2019
ELACIRTC
LE
Lic. E16934
ET
AT
S
ROFILACFO
N
AI
F
DPRO ESS IONA
L
ENG
I NE
ER
RE
GIS
TERE
NE
STO
RC. IGNACIO
,JR
.
REFERENCE SCALE IN INCHES
0 1 2
© 2018 IMEG CORP.
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Job Number
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
"LOCKER ROOMS EF UPGRADE"
EAST WHITTIER CITY SCHOOL DISTRICT
2/1
/2018 7
:31:0
3 P
M
10931 STAMY ROAD, WHITTIER, CA 90604
HILLVIEWMIDDLE SCHOOL
E001
GENERAL NOTES,SPECIFICATIONS, LEGENDAND DRAWING LIST
Approver
Checker
Author
18001320.00
02/01/18
BID DOCUMENTS
HIL
LV
IEW
M
IDD
LE
SC
HO
OL
18001320.0
0
901 VIA PIEMONTESUITE 400ONTARIO, CA91764
PH: 909.477.6915FAX: 909.477.6916www.imegcorp.com
DRAWING LIST
DWG.NO. DESCRIPTION
E001 GENERAL NOTES, SPECIFICATIONS, LEGEND AND DRAWING LIST
E201 FIRST FLOOR POWER PLAN
F-43
INSTR
F-44
F-47
F-48
EQUIP.
F-49
GIRL'S.
F-32
ENTRY
F-34
LOCKERS
F-36
LOCKERS
F-38
LOCKERS
F-1
INSTR.
F-3F-5
F-6
EQUIP.
F-7
BOY'S
F-9
ENTRY
F-10
JANITOR
F-24
DRYINGROOM
GIRL'SSHOWER
F-27
F-28
F-29
F-30
F-26
F-15
LOCKERS
F-16
LOCKERS
F-17
LOCKERS
F-14
TOWEL RM.
F-13
LOCKERS
F-12
LOCKERS
F-11
LOCKERS
F-18
CORRIDOR
F-51
CORRIDOR
F-25
STORF-41 F-40 F-39
S S
S
S
S S
FH
STAMY ROADEXISTING
BUILDINGF
EXISTING
BUILDINGD
EXISTING
BUILDINGE
EXISTINGBUILDING
A
EXISTINGBUILDING
B
EXISTINGBUILDING
G
EXISTING
BUILDING
C
EXISTING
BUILDINGJ
EXISTINGBUILDING
H
EXISTING
BUILDINGI
EXISTING
PARKING LOT #2
EXISTING
PARKING LOT #1
M(E)
N(E)
EF-1
EF-3
EF-2EF-4
MM
MM
22
2
2
1
1
1
1
22
2
2
1
1
1
1
PROJECT LOCATION
Exp. 6-30-2019
ELACIRTC
LE
Lic. E16934
ET
AT
S
ROFILACFO
N
AI
F
DPRO ESS IONA
L
ENG
I NE
ER
RE
GIS
TERE
NE
STO
RC. IGNACIO
,JR
.
REFERENCE SCALE IN INCHES
0 1 2
© 2018 IMEG CORP.
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP.
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Job Number
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
"LOCKER ROOMS EF UPGRADE"
EAST WHITTIER CITY SCHOOL DISTRICT
As indicated
2/1
/2018 7
:31:0
4 P
M
10931 STAMY ROAD, WHITTIER, CA 90604
HILLVIEWMIDDLE SCHOOL
E201
FIRST FLOOR POWER PLAN
ED
ED
CG
18001320.00
02/01/18
BID DOCUMENTS
HIL
LV
IEW
M
IDD
LE
SC
HO
OL
18001320.0
0
901 VIA PIEMONTESUITE 400ONTARIO, CA91764
PH: 909.477.6915FAX: 909.477.6916www.imegcorp.com
1/8" = 1'-0"1
FIRST FLOOR POWER PLAN
KEY PLAN
REMODEL KEY NOTES
DEMO KEY NOTES
GENERAL NOTES
1. REFER TO SPECIFICATIONS ON SHEET E0.1 FOR ANY CONDUIT PENETRATION, FIRE AND WEATHERPROOF CAULKING THROUGH EXISTING WALL.
2. PANELBOARD CIRCUITS WERE BASED ON PANEL DIRECTORY FIELD VERIFICATION. PANEL FRONTS WERE NOT REMOVED. CONTRACTOR SHALL VERIFY.
3. FOR EXACT LOCATIONS AND MOUNTING FOR EXHAUST FANS, REFER TO MECHANICAL SHEETS AND DETAILS.
4. CONTRACTOR SHALL ATTEND A MANDATORY JOB WALK WHERE THE OWNER AND REPRESENTATIVES WILL INDICATE WHAT IS EXPECTED ON HOW CONDUITS ARE ROUTED IN CONCEALED MANNER. EXPOSED INSTALLATION OF CONDUIT IS ONLY ALLOWED WHERE PASSING OR RUNNING THROUGH CONCRETE OR BLOCK WALLS.
5. PAINT ALL NEW EXPOSED CONDUITS AND BOXES TO MATCH ADJACENT FINISH.
6. COORDINATE TERMINATION OF CONDUITS WITH MECHANICAL CONTRACTOR OR INSTALLERS.
7. EXACT LOCATION OF PANEL TO BE FIELD VERIFIED.
8. ANY AND ALL PENETRATION FOR ELECTRICAL FEED THROUGH THE RATED WALLS MUST BE FIRE CAULKED WITH AN ACCEPTABLE/APPROVED PRODUCT/MATERIAL BY THE DESIGN TEAM.
9. UPDATE PANEL DIRECTORY AFTER CONSTRUCTION.
1 CONNECT NEW EXHAUST FAN TO EXISTING CIRCUIT. EXTEND CONDUIT AS REQUIRED.
VERIFY EXACT LOCATION FOR EXHAUST FAN CONTROLS WITH OWNER. REFER TO MECHANICAL SHEETS.
2
DISCONNECT AND REMOVE EXISTING EXHAUST FAN FROM CIRCUIT. REFER TO MECHANICAL SHEETS.
EXISTING CIRCUIT TO REMAIN AND TO BE REUSED. CUT PORTION OF EXISTING EXPOSED CONDUIT AND WIRES. LEAVE 12" WIRE SLACK.
1
2