Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

Embed Size (px)

Citation preview

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    1/8

    www.moeller.net

    www.eaton.com

    Main and Group Switches in

    Photovoltaic Applications

    Product Information

    N...S1-DC Switch-Disconnectors

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    2/8

    Switch-disconnectors for 1000/1250/1500 V DCContent

    CA01215001Z-en www.eaton.com

    1

    Content

    Ordering

    Switch-disconnectors 2

    Bridge kits 2

    Technical data

    Switch-disconnectors 3

    switch-disconnectors and bridge kits:Reduction of rated operational current 4

    Dimensions

    Switch-disconnectors N2..., N3... 5

    Switch-disconnectors N4... 6

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    3/8

    2 Switch-disconnectorsSwitch-disconnectors for 1000/1250/1500 V DC, 2 pole

    CA01215001Z-en www.eaton.com

    Switch-disconnectors for 1000/1250/1500 VDC,2pole

    Rated opera-tional current= rateduninterruptedcurrent

    Short-circuitprotectivedevice max.fuse gR-characteristic

    Fixed mounted

    Part no.Article no.

    PriceSee PriceList

    EuroDG

    Std. pack Notes

    In = Iu

    A A gR

    Switch-disconnectors for 1000/1250/1500 V DC S = screw connection160 200 N2-4-160-S1-DC

    127732442.00

    431 off S IEC/EN 60947-3

    Main switch characteristics including positive drive toIEC/EN 60204 and VDE 0113.Isolating characteristics to IEC/EN 60947 and VDE 0660.Busbar tag shroud to VDE 0160 Part 100.Switch-disconnectors N can, in addition, be combinedwith voltage releases NZM...-XU, NZM...-XA andauxiliary contactsas well as with remote operator NZM...-XR...Terminal type:For 2 pole switching, series connection of two poleseach is required. See accessories bridge kits.

    N...S1-DC can not be combined with withdrawable unitsand/or connection on rear.N2... : Can not be combined with early-make auxiliary con-

    tacts NZM-...XHIV or box terminal NZM2-4-XKC at Ui >1000V DC.For non-earthed networks > 1000 V DC the installationmust be configured such that the likelihood of a doubleearth fault is negligibly small.1) Will be available approx. in January 2012

    . 200 200 N2-4-200-S1-DC127733

    657.0043

    S

    250 315 N2-4-250-S1-DC 1)

    154940803,00

    43

    S

    320 500 N3-4-320-S1-DC127734

    1,095.0043

    S

    400 500 N3-4-400-S1-DC142267

    1,269.0043

    S

    500 500 N3-4-500-S1-DC142268

    1,483.0043

    S

    800 N4-4-800-S1-DC

    119890

    2,742.00

    43

    S

    1000 N4-4-1000-S1-DC119891

    3,284.0043

    S

    1250 N4-4-1250-S1-DC119886

    3,909.0043

    S

    1400 N4-4-1400-S1-DC119887

    4,797.0043

    S

    1600 N4-4-1600-S1-DC152552

    4,960.0043

    S

    Rated operationalcurrent

    For use with Number ofpoles

    Protec-tion class

    Part no.Article no.

    Priceper itemEurosDG

    Std. pack

    In

    A

    Bridge kitsModel contains parts for upper switch side for 4 pole switches N...-S1-DC that are used as 2 pole switches for DC.The links each connect two contacts in series. Incoming unit and outgoer at bottom or top, user-definable.N4-4-... 1250 A: alternate connection at bottom through module plates NZM4-4-XKM2S-1600.

    Jumper kit with cover 160 at 70 C200 at 65 C

    N2-4-160-S1-DCN2-4-200-S1-DC

    2 pole IP2X NZM2-4-XKV2P131730

    87.0043

    1 off

    Jumper kit with cover 400 at 70 C N3-320(400)-S1-DC 2 pole IP2X NZM3-4-XKV2P131731

    149.0043

    Jumper kit withinsulating plates and

    phase isolator

    400 at 70 C500 at 50 C

    N3-400(500)-S1-DC 2 pole IP00 NZM3-4-XKVI2P142269

    124.0043

    Jumper kit with coverand heat sink

    400 at 70 C500 at 55 C500 at 40 C

    N3-400(500)-S1-DC 2 pole IP1X

    IP2X

    NZM3-4-XKV2P-K142271

    207.0043

    Jumper kit withinsulating plates,phase isolators andheat sinks

    500 at 65 C N3-500-S1-DC 2 pole IP00 NZM3-4-XKVI2P-K142270

    181.0043

    Jumper kit with cover 1250 at 65 C1400 at 40 C

    N4-4-800-S1-DCN4-4-1000-S1-DCN4-4-1250-S1-DCN4-4-1400-S1-DC

    2 pole IP2X NZM4-4-XKV2P119888

    430.0043

    Jumper kit with phaseisolators and heatsinks

    1400 at 65 C1500 at 65 C1600 at 40 C

    N4-4-1400-S1-DCN4-4-1600-S1-DC

    2 pole IP00 NZM4-4-XKV2P-K152553

    900.0043

    N...S1-DC

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    4/8

    Switch-disconnectorsTechnical data

    CA01215001Z-en www.eaton.com

    3

    Circuit-breakers,switch-disconnectors for 1000 V AC/DCTechnical data

    Switch-disconnectors 1000/1250/1500 V DC N2-4...S1-DCmax. 200 A

    N3-4...S1-DCmax. 500 A

    N4-4...S1-DCmax. 1600 A

    Rated operational voltage Ue V DC 1000 (12501)) 1250 (15002)) 1500

    Rated uninterrupted current with terminal jumpers

    at 40 C Iu A 200 (2501)) 500 1600

    at 65 C Iu A 200 (2501)

    ) 500 1500Rated operating current Ie 200 (DC-22A) 500 (DC-22A) 1500 (DC-22A)

    Rated short-time withstand current t =0.1 s Icw kA 3 6 25

    Rated short-time withstand current t =1 s Icw kA 6 25

    Rated conditional short-circuit current Iq kA 15 15

    With back-up fuse up to 1000 V A gR 200 (3151)) 500

    Maximum operating frequency Ops/h 120 60 20

    Lifespan

    mechanical(of which max. 50 % trip by shunt/undervoltagerelease)

    Operations 20000 15000 10000

    Electrical Operations 2500 (DC 22-A) 2000 (DC 22-A) 500 (DC 22-A)

    Rated insulation voltage Ui V DC 1250 1250 (15001)) 1500

    For use in IT electrical power networks V DC 1000 1000 1000

    Notes N...S1-DC can not be combined with withdrawable units and/or connection on rear.N2...: Can not be combined with early-make auxiliary contacts NZM-...XHIV or box terminalNZM2-4-XKC at Ui > 1000 V DC.

    Terminal type N...S1-DC:for 2 pole switches series connection of two poles each is required.See accessories jumper kits NZM...-4-XKV...

    1) Will be available approx. in January 2012.2) Will be available approx. in July 2011.

    N...S1-DC

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    5/8

    4 Switch-disconnectorsTemperature dependency

    CA01215001Z-en www.eaton.com

    Temperature dependency

    Reduction of the rated operational current (derating) under particular ambient conditions

    Basic devices Bridge kits Bus-bar tagshroud

    Mount-ingposi-

    tion

    Temperature compensation coefficient

    20 C 30 C 40 C 50 C 55 C 60 C 65 C 70 C

    Switch-disconnector

    N2-4-160-S1-DC +NZM2-4-XKV2P IP2X s 1 1 1 1 1 1 1 1w 1 1 1 1 1 1 1 1

    N2-4-200-S1-DC +NZM2-4-XKV2P IP2X s 1 1 1 1 1 1 1 0.95

    w 1 1 1 1 1 1 0.95 0.92

    N3-4-320(400)-S1-DC +NZM3-4-XKV2P IP2X s 1 1 1 1 1 1 1 1

    w 1 1 1 1 1 1 1 1

    +NZM3-4-XKVI2P IP00 s 1 1 1 1 1 1 1 1

    w 1 1 1 1 1 1 1 1

    N3-4-500-S1-DC +NZM3-4-XKV2P-K IP2X s 1 1 1 0.95 0.92 0.89 0.86 0.83

    w 1 1 0.98 0.93 0.9 0.87 0.84 0.81

    +NZM3-4-XKV2P-K IP1X s 1 1 1 1 1 0.98 0.95 0.92

    w 1 1 1 1 0.97 0.94 0.91 0.89

    +NZM3-4-XKVI2P IP00 s 1 1 1 1 0.97 0.95 0.92 0.89

    w 1 1 1 0.97 0.95 0.92 0.89 0.87

    +NZM3-4-XKVI2P-K IP00 s 1 1 1 1 1 1 1 0.97

    w 1 1 1 1 1 1 0.97 0.95

    N4-4-800(1000)-S1-DC +NZM4-4-XKV2P IP2X s 1 1 1 1 1 1 1 1

    w 1 1 1 1 1 1 1 1

    N4-4-1250-S1-DC +NZM4-4-XKV2P IP2X s 1 1 1 1 1 1 1 0.97

    w 1 1 1 1 1 1 0.97 0.95

    N4-4-1400-S1-DC +NZM4-4-XKV2P IP2X s 1 1 0.94 0.92 0.9

    w 1 1 0.97 0.91

    +NZM4-4-XKV2P-K IP00 s 1 1 1 1 11) 11) 11) 0.97

    w 1 1 1 1 11) 11) 11) 0.97

    N4-4-1600-S1-DC +NZM4-4-XKV2P-K IP00 s 1 1 1 0.98 0.961) 0.941) 0.931) 0.911)

    w 1 1 1 0.98 0.961) 0.941) 0.931) 0.911)

    Notes Mounting position:v = vertical, h = horizontalIncoming unit and outgoer at bottom or top, user-definable.1) Incoming unit from bottom only.

    N...S1-DC

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    6/8

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    7/8

    6 Switch-disconnectors

    CA01215001Z-en www.eaton.com

    Switch-disconnectors, 4 pole

    N4-4

    Blow out area, minimum clearance to other parts

    690 V : 100 mm1500 V : 200 mm

    Minimum clearance to adjacent parts

    1000 V : 15 mm1500 V : 70 mm

    Jumper kit

    NZM4-4-XKV2P

    NZM4-4-XKV2P-K

    M5 x 110

    70

    280

    140 207

    138

    33 8

    44

    21

    117

    119

    100

    171.

    5

    87.

    5401

    313

    180

    108

    a

    25100

    15

    15

    45

    f

    100

    f 15f 15

    b

    b

    N

    o 10.5

    50

    280

    7070 70 2033

    o 13

    NZM4-4-XKV2P

    32

    56

    16

    466

    280 125.5

    522

    171.

    5

    108.

    5

    SW 16

    M10 x 60

    SW 16

    NZM4-4-XKM2S-1600

    2033

    50

    280

    7070 70

    o 13

    NZM4-4-XKV2P-1400

    32

    56

    16

    613

    647

    201

    240 80.5

    M10 x 65

    SW 16

    M10 x 55

    SW 16

    NZM4-4-XKM2S-1600

    N4

  • 7/29/2019 Eaton ca01215001z Main and Group Switches in Photovoltaic Applications

    8/8

    Addresses worldwide:

    www.moeller.net/address

    E-Mail: [email protected]

    Internet:www.moeller.net

    www.eaton.com

    Publisher:Eaton Electric GmbH

    Hein-Moeller-Strae 7-11

    D-53115 Bonn

    2011 by Eaton Industries GmbH

    Subject to alterationsCA01215001Z-EN/ICD-MTD/SRA 05/11

    Printed in Germany (05/11)Article No.: 156384

    Eaton Corporation

    Eaton is a leading energy

    management company. Eaton

    operates worldwide with products,

    systems and services in the

    electrical, hydraulic, aerospace,

    truck and automotive sectors.

    Eatons Electrical Sector

    Eatons Electrical Sector is the

    worldwide leader in products,

    systems and services for energy

    distribution, safe electricity supply

    and automation in industrial,

    residential and purpose-builtbuildings, public facilities, energy

    providers, commerce and OEMs.

    Eaton Electrical Sector includes the

    brands Cutler-Hammer, Moeller,

    Micro Innovation, Powerware,

    Holec, MEM, Santak and MGE

    Office Protection Systems.

    www.eaton.com4 0 1 5 0 8 1 5 3 0 6 32