Translation of original instructions EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

  • Upload
    others

  • View
    19

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

Translation of original instructions

EB 5757-7 EN

Firmware version 2.04

Edition January 2020

TROVIS 5757-7 Electric Actuator with Process ControllerFor heating and cooling applications

Page 2: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

Note on these mounting and operating instructions

These mounting and operating instructions assist you in mounting and operating the device safely. The instructions are binding for handling SAMSON devices. The images shown in these instructions are for illustration purposes only. The actual product may vary.

Î For the safe and proper use of these instructions, read them carefully and keep them for later reference.

Î If you have any questions about these instructions, contact SAMSON‘s After-sales Service ([email protected]).

The mounting and operating instructions for the devices are included in the scope of delivery. The latest documentation is available on our website at www.samsongroup.com > Service & Support > Downloads > Documentation.

Definition of signal words

Hazardous situations which, if not avoided, will result in death or serious injury

Hazardous situations which, if not avoided, could result in death or serious injury

Property damage message or malfunction

Additional information

Recommended action

DANGER!

WARNING!

NOTICE!

Note

Tip

EB 5757-7 EN

Page 3: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

Contents

EB 5757-7 EN

1 Safety instructions and measures ...................................................................51.1 Notes on possible severe personal injury .........................................................81.2 Notes on possible property damage ................................................................92 Markings on the device ...............................................................................102.1 Actuator nameplate ......................................................................................102.2 Valve nameplate ..........................................................................................103 Design and principle of operation ................................................................113.1 Operating controls .......................................................................................123.1.1 LEDs ...........................................................................................................123.2 LED blinking pattern .....................................................................................123.2.1 Handwheel ..................................................................................................143.2.2 Travel indicator ............................................................................................143.3 Accessories .................................................................................................143.4 Technical data .............................................................................................153.5 Dimensions in mm ........................................................................................164 Measures for preparation ............................................................................184.1 Unpacking ..................................................................................................184.2 Transporting and lifting ................................................................................184.2.1 Transporting ................................................................................................184.2.2 Lifting ..........................................................................................................184.3 Storage .......................................................................................................185 Mounting and start-up .................................................................................195.1 Mounting the actuator onto the valve .............................................................195.2 Installing the control valve into the pipeline ....................................................195.3 Electrical connections ...................................................................................195.4 Configuringtheelectricactuator ....................................................................206 Operation ...................................................................................................236.1 Manually changing the stem position .............................................................237 Servicing.....................................................................................................247.1 Preparation for return shipment .....................................................................24

Page 4: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

Contents

EB 5757-7 EN

8 Malfunctions ...............................................................................................248.1 Emergency action ........................................................................................249 Decommissioning and disassembly ..............................................................249.1 Decommissioning .........................................................................................259.2 Removing the actuator from the valve ............................................................269.3 Disposal ......................................................................................................2610 Annex.........................................................................................................2610.1 After-sales service ........................................................................................2610.2 Configurationlistandcustomersettings .........................................................2710.2.1 Customer setting ..........................................................................................2910.3 Resistance values with Pt 1000 resistors .........................................................3010.4 EU declaration of conformity .........................................................................31

Page 5: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 5

Safety instructions and measures

1 Safety instructions and measuresTheTROVIS 5757-7ElectricActuatorwithProcessControllerisanelectricactuatorwithanintegrated digital controller. It is designed for operating a mounted globe valve. In combina-tionwiththevalve,theactuatorisusedtocontroltheflowofliquidsorvaporsinthepipeline.The electric actuator with process controller is suitable for closed-loop operation in heating and cooling applications.Theactuatorisdesignedtooperateunderexactlydefinedconditions(e.g.thrust,travel).Therefore, operators must ensure that the actuator is only used in applications that meet the specificationsusedforsizingtheactuatorattheorderingstage.Incaseoperatorsintendtousetheactuatorinotherapplicationsorconditionsthanspecified,SAMSONmustbecon-tacted.SAMSON does not assume any liability for damage resulting from the failure to use the de-vice for its intended purpose or for damage caused by external forces or any other external factors.

Î Refertothetechnicaldataforlimitsandfieldsofapplicationaswellaspossibleuses.Seesection 3.4.

Reasonably foreseeable misuseThe actuator is not suitable for the following applications: − Useoutsidethelimitsdefinedduringsizingandinthetechnicaldata

Furthermore, the following activities do not comply with the intended use: − Use of non-original spare parts − Performing service and repair work not described in these instructions

Qualifications of operating personnelThe actuator must be mounted, started up, serviced, and repaired by fully trained and quali-fiedpersonnelonly;theacceptedindustrycodesandpracticesaretobeobserved.Accord-ing to these mounting and operating instructions, trained personnel refers to individuals who areabletojudgetheworktheyareassignedtoandrecognizepossiblehazardsduetotheirspecializedtraining,theirknowledgeandexperienceaswellastheirknowledgeoftheappli-cable standards.

Page 6: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

6 EB 5757-7 EN

Safety instructions and measures

Personal protective equipmentNo personal protective equipment is required for the direct handling of the electric actuator with process controller. Work on the valve on which the electric actuator is mounted may be necessary when mounting or removing the actuator from the valve.

Î Observetherequirementsforpersonalprotectiveequipmentspecifiedinthevalvedocu-mentation.

Î Check with the plant operator for details on further protective equipment.

Revisions and other modificationsRevisions,conversionsorothermodificationstotheproductarenotauthorizedbySAMSON.Theyareperformedattheuser'sownriskandmayleadtosafetyhazards,forexample.Fur-thermore, the product may no longer meet the requirements for its intended use.

Safety featuresNone

Warning against residual hazardsTheelectricactuatorwithprocesscontrollerhasadirectinfluenceonthevalvewhenitismounted on the valve. To avoid personal injury or property damage, plant operators and operatingpersonnelmustpreventhazardsthatcouldbecausedinthecontrolvalvebytheprocess medium, the operating pressure, the signal pressure or by moving parts by taking appropriateprecautions.Theymustobserveallhazardstatements,warningandcautionnotes in these mounting and operating instructions, especially for installation, start-up, and maintenance.

Responsibilities of the operatorThe operator is responsible for proper operation and compliance with the safety regulations. Operators are obliged to provide these mounting and operating instructions as well as the referenced documents to the operating personnel and to instruct them in proper operation. Furthermore, the operator must ensure that operating personnel or third persons are not ex-posed to any danger.

Responsibilities of operating personnel

Operating personnel must read and understand these mounting and operating instructions as wellasthereferenceddocumentsandobservethespecifiedhazardstatements,warningandcaution notes. Furthermore, the operating personnel must be familiar with the applicable health, safety and accident prevention regulations and comply with them.

Page 7: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 7

Safety instructions and measures

Referenced standards and regulationsTheelectricactuatorwithprocesscontrollerfulfillstherequirementsoftheDirectives2014/30/EU and 2014/35/EU. The declaration of conformity includes information about the applied conformity assessment procedure. This declaration of conformity is included in the Annex of these instructions.The electric actuator with process controller is designed for use in low voltage installations.

Î For wiring, maintenance, and repair, observe the relevant safety regulations.

Referenced documentationThe following documents apply in addition to these mounting and operating instructions: − ConfigurationManualu KH 5757-7forTROVIS 5757-7ElectricActuatorwithProcess

Controller (detailed description of all functions and parameters) − Mounting and operating instructions of the valve on which the electric actuator is mount-

ed, e.g. for SAMSON valves:u EB 3135-1forType 2488Pressure-independentControlValve(PICV)u EB 3136forType 2488 NPressure-independentControlValve(PICV)u EB 5861forType 3260Three-wayValveu EB 5863forType 3226Three-wayValveu EB 5866forType 3222GlobeValveu EB 5867forType 3222 NGlobeValveu EB 5868forType 3213GlobeValve

Page 8: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

8 EB 5757-7 EN

Safety instructions and measures

1.1 Notes on possible severe personal injury

DANGER!

Risk of electric shock. Î Beforeconnectingwiring,performinganyworkonthedeviceoropeningthede-vice, disconnect the power supply and protect it against unintentional reconnection.

Î Only use power interruption devices that are protected against unintentional recon-nection of the power supply.

Î Do not open the back housing cover.

The electric actuators with process controllers are protected against dripping water fall-ingatanangle(IP 42).

Î Avoid contact with spray water or water jets.

The switching output L' is live after the power supply has been connected. Î Do not touch the switching output L'.

Risk of bursting in pressure equipment.Control valves and pipelines are pressure equipment. Improper opening can lead to valve components bursting.

Î Beforestartinganyworkonthecontrolvalve,depressurizeallplantsectionscon-cerned as well as the valve.

Î Drain the process medium from all the plant sections concerned and from the valve. Î Wear recommended personal protective equipment. See associated valve docu-mentation.

Page 9: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 9

Safety instructions and measures

1.2 Notes on possible property damage

NOTICE!

Risk of actuator damage due to the power supply exceeding the permissible toler-ances.The electric actuators are designed for use according to regulations for low-voltage in-stallations.

Î Observe the permissible tolerances of the power supply.

Risk of actuator damage due to excessively high tightening torques.The connection of the electric actuator must be tightened with certain torques. Excessive-ly tightened torques lead to parts wearing out quicker.

Î Observethespecifiedtighteningtorques.

Malfunction due to a configuration that does not meet the requirements of the appli-cation.Theelectricactuatorwithprocesscontrollerisconfiguredforthespecificapplicationbysettingconfigurationitemsandparameters.

Î Performtheconfigurationforthespecificapplicationduringstart-upandafterare-set to default settings.

Page 10: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

10 EB 5757-7 EN

Markings on the device

2 Markings on the device

2.1 Actuator nameplate

F: 300 N Firmware: 2.xxVar.-ID xxxxxxx Serial no. xxxx *xxxxxx*

U: 230 V f: 50 Hz P: 3 VA Made in Germanys: 6 mm v: 0.3 mm/s

Electric Actuatorwith Process Controller

TROVIS 5757-7

F Thrusts Rated travelv Stroking speedU Power supplyf Power line frequencyP Power consumption

2.2 Valve nameplateSee associated valve documentation.

Page 11: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 11

Design and principle of operation

3 Design and principle of oper-ation

TheTROVIS 5757-7ElectricActuatorwithProcess Controller is a combination of a lin-ear actuator and an integrated digital con-troller. The combination is especially de-signed for heating applications as well as for fixedsetpointcontrolofheatingsystemsinsmalltomedium-sizedbuildings.Itispartic-ularly suitable for mounting to SAMSON Types 3222,3222 N,2488and3267Valves(DN 15to25)aswellastospecialversionsofType 3226andType 3260Valves.Thedigitalcontrollerisconnectedtoaflowsensor on the input side, which can be op-tionallyupgradedbyareturnflow,outdoororroomsensor.InadditiontothePt 1000input, the digital controller has a potentiome-terinput(1000to1100 Ωor1000to2000 Ω)tomeasuretheflowtemperature.Thisinputinfluencestheheatingcharacteris-tic in the case of outdoor-temperature-con-trolled control and the room temperature set pointinthecaseoffixedsetpointcontrolwithroomtemperatureinfluence.Theheat-ing characteristic and set point can be changedovertheTROVIS-VIEWconfigura-tion software.The output signal of the integrated digital controller acts over the positioner on the syn-chronous motor of the actuator and is trans-ferred over the connected gear to the actua-tor stem (3) and used as the positioning force.

The motor is switched off by torque-depen-dent switches when an end position is reached or in case the motor is overloaded.The actuator is mounted onto the valve using a coupling nut (4).When the actuator stem extends, the valve is closed, opposing the force of the valve spring (7). When the actuator stem retracts, the valve is opened as the plug stem (6) fol-lows the motion of the return spring.

182

4

3

6

7

5

1.1

182

4

3

6

7

5

1.1

5

retractedActuator stem

extended

1 Electric actuator 4 Coupling nut5 Travel indicator

1.1 Connecting cable

6 Plug stem

2 Handwheel (only use when power is dis-connected)

7 Valve spring8 Cover, serial

interface connection, slider switch, and LEDs

3 Actuator stem

Fig. 1: Functional diagram

Page 12: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

12 EB 5757-7 EN

Design and principle of operation

The valve can be moved to any position in the de-energized state by the handwheel (2). Travel and direction of action can be read off the travel indicator (5) on the side of the actuator housing.

Slider switch

Slider switch (red)

Fig. 2: Position of the slider switch

The slider switch allows you to switch be-tweentwodifferentconfigurations#1and#2.Inposition#1,thesliderswitchpointsawayfromthehousingandinposition#2towards the middle of the housing. In both levels#1and#2,thefunctionsdescribedinsection 10.2canbeactivatedandtheasso-ciated parameter settings made. The default settingsisthesameforbothlevels#1and#2,exceptforfunctionblockF13.Changesto functions and parameters can be made over the TROVIS-VIEW software.The position of the slider switch determines which function and parameter settings (level #1or#2)isusedforclosed-loopoperation.

3.1 Operating controls

3.1.1 LEDs

3.2 LED blinking patternThe device has a red and a yellow LED which indicate the operating states of the ac-tuator.The LEDs are located underneath the cover on top of the circuit board.

Blinking pattern of the yellow LED − Actuator switched off or command mode

ON

OFFTime [s]

− Actuator switched on or memory pen ac-tion completed

ON

OFFTime [s]

− Activereturnflowtemperaturelimitationor plausibility error in memory pen

ON

OFFTime [s]

Page 13: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 13

Design and principle of operation

− Preparing to read data from memory pen

ON

OFFTime [s]

− Preparing to write data to memory penON

OFFTime [s]

− Preparing data loggingON

OFFTime [s]

− Data logging in progressON

OFFTime [s]

− EEPROM error in memory penON

OFFTime [s]

Blinking pattern of the red LED − Device switched off, normal operation or

command modeON

OFFTime [s]

− Device start-up or torque-dependent limit switch error

ON

OFFTime [s]

− Exceptional error or sensor line break-age

ON

OFFTime [s]

− EEPROM error in deviceON

OFFTime [s]

− Zero calibrationON

OFFTime [s]

Page 14: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

14 EB 5757-7 EN

Design and principle of operation

− Internal transit time measurementON

OFFTime [s]

− Flow sensor defective

OFF

ON

Time [s]

− Outdoor/room sensor defectiveON

OFFTime [s]

− ReturnflowsensordefectiveON

OFFTime [s]

− Potentiometer defectiveON

OFFTime [s]

3.2.1 HandwheelThe valve can be moved to any position in the de-energized state by the handwheel (2, Fig. 1).

3.2.2 Travel indicatorTravel and direction of action can be read offthetravelindicator(5,Fig. 1)onthesideof the actuator housing.

3.3 AccessoriesAccessories for communicationThe TROVIS-VIEW software is re-quiredfortheTROVIS 5757-7Elec-tric Actuator with Process Controller. The TROVIS-VIEW software can be down-loaded free of charge from our web-site (u www.samson.de > Services > Software > TROVIS-VIEW). The software can also be supplied on a CD-ROM. Further de-tails can be found in Data Sheet u T 6661.

Accessories for heating and cooling appli-cations − Type 5267-2 Contact Sensor (Pt 1000)ConfigurationID:1058683 Permissible temperatures: Medium –20to120 °C Ambient –20to120 °C DegreeofprotectionIP 42

Page 15: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 15

Design and principle of operation

3.4 Technical dataTROVIS 5757-7 Electric Actuator with Process ControllerTemperature sensor Max.3xPt 1000

Operating temperature range –40to150 °CBinaryinputs

BI11) (instead of potentiometer) Floatingcontact,contactload5 V/1 mABI21)(insteadofreturnflowsensor) Floatingcontact,contactload5 V/1 mA

Potentiometer input 1000to1100Ωor1000to2000ΩSwitching output 230 V/50 Hz/1 A

Circulation pump or external demandRated travel 6 mmTransit time for rated travel 20 sThrust 300 NPower supply 230 V(±10 %)/50 HzPower consumption 5 VAClass of protection IIPermissible temperatures 2)

Ambient 0to50 °CStorage –20to70 °C

Degree of protection IP 42Mounting position Any position except suspendedElectromagnetic compatibility AccordingtoEN 61000-6-2,EN 61000-6-3andEN 61326

Compliance ·

Weight Approx.0.7 kg

1) Recommendation: use devices with gold contacts when using relays.2) The permissible medium temperature depends on the valve on which the electric actuator with pro-

cess controller is mounted. The limits in the valve documentation apply.

− Type 5257-7 Room Panel (Pt 1000) with potentiometer and mode selector switchConfigurationID:1180319 Permissible temperatures: Medium –20to60 °C Ambient –20to60 °C DegreeofprotectionIP 30

− Type 5227-2 Outdoor Sensor (Pt 1000)ConfigurationID:1043862 Permissible temperatures: Medium –35to85 °C Ambient –35to85 °C DegreeofprotectionIP 44

Page 16: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

16 EB 5757-7 EN

Design and principle of operation

3.5 Dimensions in mm

Ø 12

5580

11

32 70 eL Stem retracts

aL Stem extends114

2.5 m

70

Fig. 3: TROVIS 5757-7 Electric Actuator with Process Controller

Page 17: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 17

Design and principle of operation

21

Ø4

5036

756022

28

82 32

20

86

Type 5257-7RoomPanel(Pt 1000)ConfigurationID:1180319

Color:CoverandknobsRAL9016·BaseRAL7047 Continuous day mode (rated operation)

Continuous night mode (reduced operation)

Off/frost protection

Type 5227-2OutdoorSensor(Pt 1000)ConfigurationID:1043862

Color: RAL 9016

502 32

30

Type 5267-2ContactSensor(Pt 1000) (flowandreturnflowtemperaturemeasure-

ment)ConfigurationID:1058683

Fig. 4: Accessories for heating applications

Page 18: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

18 EB 5757-7 EN

Measures for preparation

4 Measures for preparationAfter receiving the shipment, proceed as fol-lows:1. Check the scope of delivery. Compare

the shipment received against the deliv-ery note.

2. Check the shipment for transportation damage. Report any damage to SAMSON and the forwarding agent (re-fer to delivery note).

4.1 Unpacking

Do not remove the packaging until immedi-ately before mounting and start-up.

1. Remove the packaging from the electric actuator.

2. Dispose of the packaging in accordance with the valid regulations.

4.2 Transporting and lifting

4.2.1 Transporting − Protect the electric actuator against exter-nalinfluences(e.g.impact).

− Protect the electric actuator against mois-ture and dirt.

− Observe the permissible transportation temperatureof–20to+70 °C.

4.2.2 LiftingDue to the low service weight, lifting equip-ment is not required to lift the electric actua-tor.

4.3 Storage

Risk of actuator damage due to improper storage. − Observe storage instructions. − Avoid long storage times. −Contact SAMSON in case of different stor-age conditions or long storage periods.

We recommend regularly checking the elec-tric actuator and the prevailing storage con-ditions during long storage periods.

Storage instructions − Protect the electric actuator against exter-nalinfluences(e.g.impact).

− Protect the electric actuator against mois-ture and dirt.

− Make sure that the ambient air is free of acids or other corrosive media.

− Observe the permissible storage tem-peraturefrom–20to+70 °C.

− Do not place any objects on the electric actuator.

Information

NOTICE!

Information

Page 19: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 19

Mounting and start-up

5 Mounting and start-up

Risk of malfunction due to incorrectly per-formed start-up.Perform start-up following the described se-quence.

5.1 Mounting the actuator onto the valve

Risk of actuator damage due to excessively high tightening torques.Observe the specified tightening torques.

The actuator has a force-locking connection tothevalveinde-energizedstate.

Î Turnthehandwheel(2,Fig. 1onpage 11)counterclockwisetoretractthe actuator stem as far as it will go.

Î Place the actuator on the valve con-nection and tighten the coupling nut (Fig. 1onpage 11)(tighteningtorque20 Nm).

5.2 Installing the control valve into the pipeline

Degree of protection not achieved due to incorrect mounting position.Do not install the valve with the actuator sus-pended downwards.

Î Install the valve into the pipeline accord-ingthespecificationsinthemountingand operating instructions of the valve.

5.3 Electrical connections

Risk of electric shock. − Upon installation of the electric cables, you are required to observe the regulations concerning low-voltage installations ac-cording to DIN VDE 0100 as well as the regulations of your local power supplier. − Use a suitable power supply which guar-antees that no dangerous voltages reach the device in normal operation or in the event of a fault in the system or any other system parts. − Connect the actuator to the electrical net-work only after the power supply is first switched off. Make sure the power cannot be switched on unintentionally. − The switching output L' is live. Do not touch the switching output L'.

NOTICE!

NOTICE!

NOTICE!

DANGER!

Page 20: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

20 EB 5757-7 EN

Mounting and start-up

TheactuatorrequiresaPt 1000temperaturesensor(e.g.Type 5267-2)tobeconnectedtomeasuretheflowtemperature.Depending on the control task, an outdoor sensor(e.g.Type 5227-2)orroompanel(Type 5257-7only)canbeconnected.Theycanallbecombinedwithareturnflowsen-sor(e.g.Type 5267-2).Additionally, the actuator has a potentiome-terinput1000to1100 Ω(e.g.Type 5257-7)or1000to2000 Ω.Thisinputisusedtocorrecttheroomsetpoint(±5 K)incaseoffixedsetpointcontrolwithroomtemperatureinfluence(u KH 5757-7).Onusinganout-door sensor, it can change the adjusted heat-ing characteristic (u KH 5757-7).Thenon-floatingswitchingoutputcanalterna-tively be used as an output for an external demand for heat.The connected sensors are monitored for line breakages. A fault in the line of a sensor is indicated by the red LED blinking (under-neath the cover on top of the circuit board). Each sensor has its own blinking pattern (see section 3.2).Intheeventthatseveralsensorsare defective, the LED blinks using the se-quence for the sensor with the highest priori-ty:

Highest priority Flow sensor

Outdoor sensor or room sensor

Returnflowsensor

Lowest priority Potentiometer

Example:Intheeventthattheflowsensorand outdoor sensor are defective, the LED initiallyblinkstoindicatethattheflowsensoris defective. When this fault is eliminated, the LED then blinks to indicate that the outdoor sensor is defective.

Î Perform the electrical connection depend-ing on the heating application according to one of the following wiring diagrams (Fig. 5toFig. 7).Assoonastheactuatoris connected to the power supply, the ini-tializationprocedurestarts.

The actuator stem extends and the red and yellow LEDs are illuminated located under the cover on top of the circuit board.As soon as the actuator stem has reached thefinalposition,theredLEDisturnedoff.The yellow LED remains illuminated and indi-cates that the actuator is ready for use.

5.4 Configuring the electric ac-tuator

TheactuatorisconfiguredwiththeTROVIS-VIEW software. All the functions and parametersarelistedinsection 10.2.

The Configuration Manual u KH 5757-7 can be found in the Help menu of the TROVIS-VIEW software. The manual con-tains a detailed description of each function and parameter.

Information

Page 21: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 21

Mounting and start-up

OG YE RD BN BK GN BN BU BK

3 4 6521 L L´N

230 V,VS

Pt 1

000

Pt 1

000

Pt 1

000

ASRüS50 Hz

100/

1000

Ω10

00 Ω

DANGER! Live wires

Application with flow sensor (VS), return flow sensor (RüS) and outdoor sensor (AS) and potentiometer functioning as set point adjuster

OG YE RD BN BK GN BN BU BK

3 4 6521 L L´N

230 V,VS

Pt 1

000

Pt 1

000

AS50 Hz

100/

1000

Ω10

00 Ω

BE2

DANGER! Live wires

Application with flow sensor (VS), outdoor sensor (AS), binary input (BI2) to switch between operat-ing mode and potentiometer for adjusting the set point

OG Orange BN Brown BN BrownYE Yellow BK Black BU BlueRD Red GN Green BK Black

Fig. 5: Electrical connections Note! Terminals at point of installation not included in the scope of delivery.

Page 22: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

22 EB 5757-7 EN

Mounting and start-up

OG YE RD BN BK GB BN BU BK

3 4 6521 L L´N

230 V,VS

Pt 1

000

Pt 1

000

Pt 1

000

AS BE1RüS50 Hz

DANGER! Live wires

Application with flow sensor (VS), return flow sensor (RüS), outdoor sensor (AS) and binary input (BI1) to switch between operating modes

OG YE RD BN BK GN BN BU BK

3 4 6521 L L´N

230 V, 50 HzVS

Pt 1

000

Pt 1

000

ASBE2 BE1

DANGER! Live wires

Application with flow sensor (VS) and outdoor sensor (AS)

OG Orange BN Brown BN BrownYE Yellow BK Black BU BlueRD Red GN Green BK Black

Fig. 6: Electrical connections Note! Terminals at point of installation not included in the scope of delivery.

Page 23: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 23

Operation

OG YE RD BN BK GN BN BU BK

3 4 65

1 432

21 L L´N

230 V,VS

Pt 1

000

Pt 1

000

RüS50 Hz

DANGER! Live wires

Type 5257-7RoomPanel

Application with flow sensor (VS), return flow sensor (RüS) and room sensor with mode selector switch and set point adjuster

Fig. 7: Electrical connections Note! Terminals at point of installation not included in the scope of delivery.

6 OperationImmediately after completing mounting and start-up, the valve with electric actuator is ready for use.

6.1 Manually changing the stem position

The stem must only be manually positioned when the power supply is switched off as the stem position is determined by the process controller in closed-loop operation, meaning any manual adjustment would be automati-cally corrected.

The stem position is changed at the hand-wheel:

Î Switch off the power supply. Î Turn clockwise to extend the actuator stem(approx.4turnsfor1 mmtravel).

Î Turn counterclockwise to retract the actu-atorstem(approx.4turnsfor1 mmtrav-el).

Page 24: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

24 EB 5757-7 EN

Servicing

7 Servicing

The electric actuator with process controller was checked by SAMSON before it left the factory. − The product warranty becomes void if service or repair work not described in these instructions is performed without prior agreement by SAMSON's After-sales Service. −Only use original spare parts by SAMSON, which comply with the original specifications.

7.1 Preparation for return ship-ment

Defective electric actuators can be returned to SAMSON for repair.Proceed as follows to return valves to SAMSON:1. Put the control valve out of operation and

remove it from the pipeline. See associat-ed valve documentation.

2. Remove the electric actuator from the valve.Seesection 9.2.

3. Send the electric actuator to your nearest SAMSON subsidiary. SAMSON subsid-iaries are listed on our website at u www.samson.de>Contact.

8 Malfunctions Î Troubleshooting(seeTable 1).

Contact SAMSON's After-sales Service de-partment for malfunctions not listed in the ta-ble.

8.1 Emergency actionThe plant operator is responsible for emer-gency action to be taken in the plant.

Emergency action in the event of valve fail-ure is described in the associated valve doc-umentation.

9 Decommissioning and disas-sembly

Risk of electric shock. − Before performing any work on the device and before opening the device, disconnect the power supply and protect it against un-intentional reconnection. −Only use power interruption devices that are protected against unintentional recon-nection of the power supply.

InformationInformation

Tip

DANGER! DANGER!

Page 25: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 25

Decommissioning and disassembly

Risk of bursting in control valve compo-nents due to incorrect opening. − Before starting any work on the control valve, depressurize all plant sections con-cerned and the valve. − Drain the process medium from all the plant sections concerned and from the valve. −Wear recommended personal protective equipment. See associated valve documen-tation.

9.1 DecommissioningTo decommission the electric actuator for maintenance work or disassembly, proceed as follows:1. Close the shut-off valves upstream and

downstream of the control valve to stop theprocessmediumfromflowingthrough the valve.

2. Completely drain the pipelines and valve.

3. Disconnect and lock the power supply.4. If necessary, allow the pipeline and valve

components to cool down.5. Remove the valve from the pipeline. See

associated valve documentation.

DANGER! DANGER!

Table 1: Troubleshooting

Error Possible reasons Recommended action

Actuator or plug stem does not move on demand.

Actuator is blocked. Check attachment.Unblock the actuator.

No or incorrect power supply connected.

Check the power supply and connections.

Actuator or plug stem does not move through the whole range.

No or incorrect power supply connected.

Check the power supply and connections.

The electric actuator with process controller does not perform the functions as required.

Theconfigurationoftheelectricactuator does not meet the application requirements.

Checkconfiguration.If necessary, refer to the ConfigurationManualu KH 5757-7.

The electric actuator was reset to its default settings without adaptingtheconfigurationtotheapplication afterwards.

Page 26: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

26 EB 5757-7 EN

Annex

9.2 Removing the actuator from the valve

1. Undo the coupling nut (4) and remove the actuator from the valve connection.

9.3 Disposal Î Observe local, national, and internation-al refuse regulations.

Î Do not dispose of components, lubri-cants,andhazardoussubstancestogeth-er with your other household waste.

10 Annex

10.1 After-sales serviceContact SAMSON's After-sales Service de-partment for support concerning service or repair work or when malfunctions or defects arise.

E-mailYou can reach our After-sales Service at [email protected].

Addresses of SAMSON AG and its subsid-iariesTheaddressesofSAMSONAG,itssubsid-iaries, representatives, and service facilities worldwide can be found on the SAMSON website, in all SAMSON product catalogs or on the back of these Mounting and Operat-ing Instructions.

Required specificationsPlease submit the following details: − Order number and position number in

the order − Type,serialnumber,firmwareversion,

device version

Page 27: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 27

Annex

10.2 Configuration list and customer settingsConfiguration listThereareseparatetwolevels#1and#2.BothlevelscontainthefunctionsF01toF13withthespecifieddefaultsettingsandmeanings.The functions F01 to F13 have the following listed functions.F = Function WE = Default setting 0 = OFF, 1 = ON

F Function WE Meaning01 Control mode 1 0 – Fixed set point control

1 – Control with reference variable02 Selecting the reference variable

(only effective when F01 - 1)0 0 – Outdoor sensor

1 – Room sensor03 Direction of stem action 0 0 – Increasing/increasing >>

1 – Increasing/decreasing <>04 Delayed outdoor temperature

(only effective when F01 - 1 and F02 - 0)

0 0 – Without delay1 – With delay

05 Potentiometer input 0 0 – Not active (binary input)1 – Active

06 Resistance range of potentiome-ter (only effective when F05 - 1)

0 0 – Type 5257-7 Room Panel (1000 to 1100 ohm)1– Remoteadjuster(1000to2000 ohm)

07 Function of potentiometer (only effective when F02 - 0 and F05 - 1)

0 0 – Heating characteristic level shift1 Gradientshift

08 FunctionofbinaryinputBI1(only effective when F05 - 0)

0 0 BI1short-circuited:OFFwithfrostprotection1 BI1short-circuited:Reducedoperation

09 Function of switching output 0 0–BOascirculationpumpcontrol1–BOasheatdemand(ONinratedoperation)

10 Anti-block protection of pumps (only effective when F09 - 0)

1 0 – No anti-block protection1 – When pumps are deactivated: switched on every24 hfor1 min

11 Returnflowtemperaturesensor 1 0 – Inactive, binary input 2 active1–Active,withreturnflowtemperaturelimitation

12 FunctionofbinaryinputBI2(only effective when F11 - 0)

0 0–BI2short-circuited:OFFwithfrostprotection1–BI2short-circuited:Reducedoperation

13 Manual mode 0 1) 0 – Inactive1 – Manual mode (absolute priority)

Page 28: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

28 EB 5757-7 EN

Annex

Parameter listThereareseparatetwoparameterlevels#1and#2.Bothparameterlevelscontainthefunc-tionsP01toP23withthespecifieddefaultsettingsandsettingranges.The parameters have the setting ranges as listed below.P = Parameter WE = Default setting

P Parameters WE Adjustment range

01 Flow temperature set point 70 °C 0to150 °C

02 Flow temperature set-back in reduced operation 15 K 0to50 K

03 Min.flowtemperature 20 °C 0to150 °C

04 Max.flowtemperature 120 °C 0to150 °C

05 Heating characteristic gradient 1.6 0.2 to 3.2

06 Heating characteristic level 0 K –30to30 K

07 Gradientshiftrangeviapotentiometer 1.0 0.0 to 1.5

08 Level shift range via potentiometer 15 K 0to30 K

09 Kpflowtemperaturecontrol 2.0 0.1 to 50.0

10 Tnflowtemperaturecontrol 120 s 0 to 999 s

11 Ty actuator transit time for valve travel 24 s 10 to 240 s

12 Dead band (switching range) 2.0 % 0.5to5.0 %

13 Max.returnflowtemperature 50 °C 10to90 °C

14 Kpreturnflowtemperaturelimitation 1.0 0.1 to 50.0

15 Tnreturnflowtemperaturelimitation 400 s 0 to 999 s

16 Delay time for outdoor temperature 3.0 °C/h 1.0to6.0 °C/h

17 Outdoor temperature limit value at rated operation 22 °C 0to50 °C

18 Outdoor temperature limit value at reduced operation 15 °C 0to50 °C

19 Room temperature set point at rated operation 20 °C 10to40 °C

20 Room temperature set point at reduced operation 15 °C 10to40 °C

21 Max. room temperature boost for switch-off 2 K 1to6 K

22 Timeintervalforflashadaptation 10 min 0 to 100 min

23 Pump lag time 5 min 1 to 999 min

Page 29: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 29

Annex

10.2.1 Customer setting

Station

Operator

SAMSON office

Function blocks Parameters

Performed setting Performed setting

F WE #1 #2 P WE #1 #2 Adjustment range

01 1 01 70 °C 0to150 °C

02 0 02 15 K 0to50 K

03 0 03 20 °C 0to150 °C

04 0 04 120 °C 0to150 °C

05 0 05 1.6 0.2 to 3.2

06 0 06 0 K –30to30 K

07 0 07 1.0 0.0 to 1.5

08 0 08 15 K 0to30 K

09 0 09 2.0 0.1 to 50.0

10 1 10 120 s 0 to 999 s

11 1 11 24 s 10 to 240 s

12 0 12 2.0 % 0.5to5.0 %

13 0 1) 13 50 °C 10to90 °C1) The default setting F13 - 1

appliesforlevel#2.14 1.0 0.1 to 50.0

15 400 s 0 to 999 s

16 3.0 °C/h 1.0to6.0 °C/h

Page 30: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

30 EB 5757-7 EN

Annex

Function blocks Parameters

Performed setting Performed setting

F WE #1 #2 P WE #1 #2 Adjustment range

17 22 °C 0to50 °C

18 15 °C 0to50 °C

19 20 °C 10to40 °C

20 15 °C 10to40 °C

21 2 K 1to6 K

22 10 min 0 to 100 min

23 5 min 1 to 999 min

10.3 Resistance values with Pt 1000 resistors°C –35 –30 –25 –20 –15 –10 –5 0 5 10Ω 862.5 882.2 901.9 921.6 941.2 960.9 980.4 1000.0 1019.5 1039.0

°C 15 20 25 30 35 40 45 50 55 60Ω 1058.5 1077.9 1097.3 1116.7 1136.1 1155.4 1174.7 1194.0 1213.2 1232.4

°C 65 70 75 80 85 90 95 100 105 110Ω 1251.6 1270.7 1289.8 1308.9 1328.0 1347.0 1366.0 1385.0 1403.9 1422.9

°C 115 120 125 130 135 140 145 150Ω 1441.7 1460.6 1479.4 1498.2 1517.0 1535.8 1554.5 1573.1

Page 31: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

EB 5757-7 EN 31

Annex

10.4 EU declaration of conformity

SAMSON AKTIENGESELLSCHAFT Weismüllerstraße 3 60314 Frankfurt am Main

Telefon: 069 4009-0 · Telefax: 069 4009-1507 E-Mail: [email protected]

Revison 05

EU Konformitätserklärung/EU Declaration of Conformity Für das folgende Produkt / For the following product

Kombinierter Regler mit Hubantrieb / Controller with Electric Actuator Typ / Type 5757

wird die Konformität mit den nachfolgenden EU-Richtlinien bestätigt / signifies compliance with the following EU Directives:

EMC 2004/108/EC (bis/to 2016-04-19) EMC 2014/30/EU (ab/from 2016-04-20) EN 61000-6-2:2005, EN 61000-6-3:2010

LVD 2006/95/EC (bis/to 2016-04-19) LVD 2014/35/EU (ab/from 2016-04-20) EN 60730-1:2011, EN 61010-1:2010

Hersteller / Manufacturer:

SAMSON AKTIENGESELLSCHAFT Weismüllerstraße 3

D-60314 Frankfurt am Main Deutschland/Germany

Frankfurt, 2016-04-06

Gert Nahler ppa. Günther Scherer Zentralabteilungsleiter/Head of Department Qualitätssicherung/Quality Managment Entwicklung Automation und Integrationstechnologien/ Development Automation and Integration Technologies ce

_575

7-0_

de_e

n_re

v05.

pdf

Page 32: EB 5757-7 EN - Samson AG · EB 5757-7 EN Firmware version 2.04 Edition January 2020 TROVIS 5757-7 Electric Actuator with Process Controller For heating and cooling applications

2020

-01-

16 ·

Engl

ish

SAMSON AKTIENGESELLSCHAFTWeismüllerstraße 3 · 60314 Frankfurt am Main, GermanyPhone: +49 69 4009-0 · Fax: +49 69 [email protected] · www.samsongroup.com

EB 5757-7 EN